Fluke FT140 User Manual

®
Model T100,
T120, T140,
VDE
Voltage/Continuity
Tester
Users Manual
© 2006 Fluke Corporation. All rights reserved.
Printed in China
Fluke T100/120/140
Introduction
References marked on instru­ment or in instruction manual:
Warning of a potential danger, comply with instruction manual. Reference. Please use utmost attention.
Caution! Dangerous voltage. Danger of electrical shock. Continuous double or reinforced insulation complies with category II IEC 61140. Symbol for the marking of electrical and electronic equipment (WEEE Directive 2002/96/EC). Suitable for live working. VDE-approved, built- in compliance with the valid directives. Conformity symbol, the instrument com­plies with the valid directives. It complies with the EMV Directive (89/336/EEC). It also complies with the Low Voltage Directi­ve (73/23/EEC).
Measuring Circuit Category CAT III:
In addition to category II, the measuring circuit category III includes electric equipment subject to special demands with reference to safety and availability. Examples: House installations, protective equipment, outlets, switches...
Measuring Circuit Cate­gory CAT IV:
Electric equipment, for which lightning voltage must also be taken into consideration, belongs to category IV. This includes, e.g. the connecti­on to overhead circuits, underground cables to water pumps...
The instruction manual contains informati­on and references, necessary for safe operation and maintenance of the instru­ment. Prior to using the instrument read the instruction manual and comply with it in all sections. Failure to read the instruction manual or to comply with the warnings and references contained herein can result in serious bo­dily injury or instrument damage.
2
Fluke T100/120/140
Introduction
Introduction / Scope of Supply
The FLUKE T100/T120/T140 instruments are voltage and continuity testers with rotary field indication for universal applications. The volta­ge testers are constructed in accordance with the newest safety prescriptions and guarantee safe and reliable measurement and testing. The risk of injury when transporting the instru­ment in clothing pockets or in the tool box is eli­minated due to the fixed test probe cover, as re­quired by VBG 1 (BG) § 35 (Transporting Tools).
The voltage testers represent a valuable sup­port for all testing and measurement in handi­craft and industrial applications as well as for household uses.
The voltage testers FLUKE T100/ T120/ T140 characterised by the following features:
• Constructed in compliance with DIN EN 61243-3, DIN VDE 0682 Part 401 (previously DIN VDE 0680 Part 5), DIN VDE 0682 Part 401 A1, IEC61010
• Fixed test probe cover eliminates risk of i n ­jury (VBG 1, § 35 Transporting Tools)
• Digital LC-Display (only FLUKE T120/T140 )
• Resistance measurement (only T140 )
• LED (FLUKE T100)
• DC and AC voltage measurement up to 690V
• Single-pole phase test
• Continuity test / diode test
• Double-pole rotary direction determination
• IP 65 (IEC 60529, EN 60529, DIN VDE 0470-1)
After unpacking, verify that the instrument is undamaged. The scope of supply comprises: 1 FLUKE T100, T120 or T140 2 Batteries 1,5V IEC LR03 AAA 1 Users Manual
3
Fluke T100/120/140
Safety Measures
Safety Measures
The instruments FLUKE T100/T120/T140 have been constructed and verified in compliance with the safety measures for voltage testers and have left the factory in safe and perfect condition.
In order to avoid electrical shock, the valid safety and VDE regulations regarding ex­cessive contact voltages must receive ut­most attention, when working with volta­ges exceeding 75V (60V) DC or 50V (25V)rms AC. The values in brackets are valid for spezial ranges (for example medi­cine and agriculture).
The detector shall not be used, if the bat­tery box is open. Prior to each test, ensure the proper con­dition of the measuring line and the mea­suring instrument, e.g. broken cables or leaking batteries.
Prior to measurement ensure that the test leads and the test instrument are in per­fect condition. When using this instrument only the hand­les of the probes may be touched . This instrument may only be used within the ranges specified (see 6.0 Technical Data) and within voltage systems up to 690V
The measuring instrument may be used only in the measuring circuit category it has been de­signed for!
Instrument's faultless functionality must be veri­fied prior to every use.
1) Short-circuit the probes. The Rx/Ohm LED must light up. If not, remove/replace the batteries.
2) Test the voltage tester on a known voltage source.
Prior to usage ensure perfect instrument function (e.g. on known voltage source).
The voltage testers may no longer be used if one or several functions fail or if no functionalityis indicated.
4
Fluke T100/120/140
Safety Measures
Do not measure under damp conditions.
Perfect display is only guaranteed within a temperature range of -10°C up to + 55°C, at relative humidity <85%
If the operator’s safety cannot be guaran­ted, the instrument must be removed from service and protected against use.
Safety is no longer ensured in the following cases:
• Obvious damage
• When the device no longer performs the desi­red tests
• Excessive storage under unfavourable condi­tions
• Strain through transport
• Leaking batteries
For all the work, the accident prevention regula­tions of the commercial and industrial worker's compensation insurance carriers for electric in­stallations and equipment must be heeded.
Appropriate Usage
The instrument may only be used under those conditions and for those purposes for which it was built. For this reason, in particular the safety references , the technical data including environmental conditions and the usage in dry environments must be followed.
When modifying or changing the instru­ment, the operational safety is no longer ensured.
The instrument may only be opened by an authorised service technician, e.g. for fuse replacement.
5