Fluke eMobility Tools Kit with FEV100 Test Adapter,
125B ScopeMeter®, 87V Multimeter and Test Leads
Key features
Test charging states of EVSE with CP state simulation with the 12B ScopeMeter®.
Verify charging voltage and maximum available current using the 87V multimeter and TL224 test leads.
Check protective earth for correct wiring and functioning with the PE pre-test feature.
Perform GFCI troubleshooting of EVSE and verify operation within safety standards.
Product overview: Fluke eMobility Tools Kit with FEV100 Test
Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Test the safety and performance of a type 1, level 1 or level 2 electric vehicle ac charging stations (EVSEs) with the Fluke
FEV100, 87V + 125B ScopeMeter® kit. This kit includes the FEV100 test adapter to simulates the presence of an electrical
vehicle. When connected to the test adapter, the 87V multimeter will allow you to monitor the output voltage and maximum
charging current of the station. Verify EVSE charging states (vehicle simulation) by connecting the 125B ScopeMeter® to
measure the control pilot signal output. With this kit, it's easy to verify an EV charging station is working properly after install
and during periodic maintenance, or troubleshoot an EVSE if it is not delivering the appropriate charge. SAE J1772 compliant
to North American standards.
EVSE installation safety and performance checks
PE PRE-TEST: Grounding system pre-test verifies that there is no presence of dangerous voltage at the ground terminal.
GFCI TEST: Ground fault circuit interrupter test verifies the breaker of the EVSE is connected by detecting ground faults.
Page 2
PE ERROR: Ground fault simulation indicates an interruption of the ground conductor; the pending charging process is
aborted, and new charging processes are prevented.
CP ERROR “E”: The standard J1772 defines Error “E” as a state when charging station is disconnected from vehicle,
disconnected from utility, there is a loss of utility power or control pilot is short to control pilot reference (ground).
Specifications: Fluke eMobility Tools Kit with FEV100 Test Adapter,
125B ScopeMeter®, 87V Multimeter and Test Leads
Fluke FEV100 Electric Vehicle Charging Station Test Adapter specifications
2 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 3
Page 4
Frequency response - ac coupled (lf
roll off)
Without probes and test leads<10 Hz (-3 dB)
With STL120-IV 1:1 shielded test leads<10 Hz (-3 dB)
With VP41 10:1 Probe<10 Hz (-3 dB)
Rise time, excluding probes,
test leads
123B <17.5 ns
124B and 125B <8.75 ns
Without probes and test leads1 MΩ//20 pF
With BB1201 MΩ//24 pF
Input impedance
With STL120-IV 1:1 shielded test leads1 MΩ//230 pF
With VP41 10:1 Probe5 MΩ//15.5 pF
Sensitivity5 mV to 200 V/div
Analog bandwidth limiter10 kHz
Display modesA, -A, B, -B
Direct, with test leads, or with VP41
Max. input voltage A and B
Probe
With BB120600 Vrms
Max. floating voltage, from any
terminal to ground
600 Vrms Cat IV, 750 Vrms up to 400Hz
Horizontal
Scope modesNormal, Single, Roll
Equivalent sampling
600 Vrms Cat IV, 750 Vrms maximum
voltage.
123B: 20 ns to 500 ns/div,
124B and 125B: 10 ns to 500 ns/div
Ranges (normal)
Real time sampling1 μs to 5 s/div
Single (real time)1 μs to 5 s/div
Roll (real time)1s to 60 s/div
Equivalent sampling (repetitive
Sampling rate (for both channels
signals)
simultaneously)
Real time sampling 1 μs to 60 s/div40 MS/s
Trigger
Screen updateFree run, on trigger
SourceA, B
@ DC to 5 MHz0.5 divisions or 5 mV
@ 40 MHz
Sensitivity A and B
@ 60 MHz
SlopePositive, negative
Up to 4 GS/s
123B: 4 divisions
124B and 125B: 1.5 divisions
123B: N/A
124B and 125B: 4 divisions
4 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 5
Advanced scope functions
Normal
Captures up to 25 ns glitches and
displays analog-like persistence
waveform
Display modes
SmoothSuppresses noise from a waveform
Glitch off
Envelope
Does not capture glitches between
samples
Records and displays the minimum and
maximum of waveforms over time
Continuous fully automatic adjustments of amplitude, time base, trigger levels,
Auto set (Connect-and-View™)
trigger gap, and hold-off. Manual override by user adjustment of amplitude, time
base, or trigger level.
Dual input meter
The accuracy of all measurements is within ±(% of reading + number of counts) from 18 °C to 28 °C.
Add 0.1x (specific accuracy) for each °C below 18 °C or above 28 °C. For voltage measurements with 10:1 probe, add
probe uncertainty +1%. More than one waveform period must be visible on the screen.
Input A and input B
DC voltage (VDC)
Ranges500 mV, 5 V, 50 V, 500 V, 750 V
Accuracy±(0.5% +5 counts)
Common mode rejection (CMRR)>100 dB @ dc, >60 dB @ 50, 60, or 400 Hz
Full scale reading5000 counts
True-rms voltages (V ac and V ac+dc)
Ranges500 mV, 5 V, 50 V, 500 V, 750 V
Accuracy for 5% to 100% of range (DC
coupled)
Accuracy for 5% to 100% of range (AC
or dc coupled)
DC to 60 Hz (V ac+dc)±(1% +10 counts)
1 Hz to 60 Hz (V ac)±(1% +10 counts)
60 Hz to 20 kHz±(2.5% +15 counts)
DC rejection (only VAC)>50 dB
>100 dB @ dc
Common mode rejection (CMRR)
>60 dB @ 50, 60, or 400 Hz
Full scale reading5000 counts, reading is independent of any signal crest factor.
Peak
ModesMax peak, Min peak, or pk-to-pk
Ranges500 mV, 5 V, 50 V, 500 V, 2200 V
Accuracy Max peak or Min peak5% of full scale
Accuracy
Accuracy Peak-to-Peak10% of full scale
5 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Power factor (PF)Ratio between watts and VA range - 0.00 to 1.00
RMS reading of multiplying corresponding samples of input A (volts) and input B
Watt
(amperes)
Full scale reading999 counts
Vrms x Arms
VA
Full scale reading999 counts
√((VA)2-W2)
VA reactive (var)
Full scale reading999 counts
Vpwm
PurposeTo measure on pulse width modulated signals, like motor drive inverter outputs
Principle
Readings show the effective voltage based on the average value of samples over
a whole number of periods of the fundamental frequency
AccuracyAs Vrms for sinewave signals
Input A to common
Ohm (Ω)
123B and 124B
500 Ω , 5 kΩ, 50 kΩ, 500 kΩ, 5 MΩ, 30
MΩ
Ranges
125B
50 Ω, 500 Ω , 5 kΩ, 50 kΩ, 500 kΩ, 5 MΩ,
30 MΩ
Accuracy±(0.6% + 5 counts) 50 Ω ±(2% + 20 counts)
Full scale reading50 Ω to 5 MΩ - 5000 counts, 30 MΩ - 3000 counts
Measurement current0.5 mA to 50 nA, decreases with increasing ranges
Open circuit voltage<4 V
Continuity (Cont)
Beep<(30 Ω ±5 Ω) in 50 Ω range
Measurement current0.5 mA
Detection of shorts of≥1 ms
Diode
@0.5 mA>2.8 V
Measurement voltage
@open circuit<4 V
Measurement current0.5 mA
Polarity+ on input A, - on COM
7 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 8
Capacitance (CAP)
Ranges50 nF, 500 nF, 5 μF, 50 μF, 500 μF
Full scale reading5000 counts
Measurement current500 nA to 0.5 mA, increases with increasing ranges
Advanced meter functions
Zero SetSet actual value to reference
Captures and freezes a stable measurement result. Beeps when stable.
AutoHold (on A)
AutoHold works on the main meter reading, with thresholds of 1 Vpp for AC
signals and 100 mV for DC signals.
Fixed decimal pointActivated by using attenuation keys
Cursor Readout (124B and 125B)
SourcesA, B
Average, min and max readout
Average, min, max and time from start of readout (in ROLL mode; instrument in
HOLD)
Single vertical line
Min, max and time from start of readout (in RECORDER mode; instrument in
HOLD)
Harmonics values in POWER QUALITY mode.
Peak-peak, time distance and reciprocal time distance readout
Dual vertical lines
Average, min, max and time distance readout (in ROLL mode; instrument in
HOLD)
Dual horizontal linesHigh, low and peak-peak readout
Transition time, 0%-level and 100%-level readout (manual or auto leveling; auto
Rise or fall time
leveling only
possible in single channel mode)
AccuracyAs oscilloscope accuracy
Recorder
The recorder captures meter readings in Meter Recorder mode or continuously captures waveform samples in Scope
Recorder mode. The information is stored on internal memory or on optional SD card (with the 125B or 124B).
The results are displayed as Chart recorder display that plots a graph of min and max values of Meter measurements over
time or as a waveform recorder display that plots all the captured samples.
Meter readings
Measurement SpeedMaximum 2 measurement/s
Record Size (min, max, average)2 M readings for 1 channel
Recorded Time Span2 weeks
Maximum number of events1024
Waveform record
8 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 9
Page 10
Page 11
Page 12
Maximum capacitance
9,999 µF
Capacitance
Frequency
Duty cycle
Temperature measurement
80 BK temperature probe
Conductance
accuracy±(1% + 2)
Maximum resolution0.01 nF
Maximum frequency
200 kHz
Accuracy±(0.005% + 1)
Maximum resolution0.01 Hz
Maximum duty cycle
99.9%
Accuracy±(0.2% per kHz + 0.1%)
Maximum resolution0.1%
–200.0 °C – 1090 °C
–328.0 °F – 1994.0 °F
excluding probe
–40.0 °C – 260 °C
–40.0 °F – 500 °F, 2.2 °C or 2% whichever is greater
Maximum conductance
60.00 nS
Accuracy±(1.0% + 10)
Maximum resolution0.01 nS
Range
3 V
Diode
Resolution1 mV
Accuracy±(2% + 1)
Duty cycle range
Accuracy
Within ±(0.2% per kHz + 0.1%)
Environmental Specifications
Operating temperature–20 °C to + 55 °C
Storage temperature–40 °C to + 60 °C
Humidity (without condensation)
0% – 90% (0 °C – 35 °C)
0% – 70% (35 °C – 55 °C)
Operating Altitude2000 m
Safety Specifications
Overvoltage categoryEN 61010–1 to 1000 V CAT III, 600V CAT IV
Agency approvalsCE, CSA, RCM
Mechanical and General Specifications
Size201 x 98 x 52 mm (with holster)
Weight
Display
355 g
624 g – with holster
Digital
6000 counts updates 4/sec.
19,999 counts in high–resolution mode
Analog32 segments, updates 40/sec
Frequency19,999 counts, updates 3/sec at > 10 Hz
12 Fluke Corporation Fluke eMobil ty Tools Kit w th FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Page 13
WarrantyLifetime
Battery Life
Alkaline
~400 hours typical, without backlight
Shock1 Meter drop per IEC 61010–1:2001
VibrationPer MIL–PRF–28800 for a Class 2 instrument
13 Fluke Corporation Fluke eMobil ty Tools Kit w th FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Page 14
Ordering information
FLK-FEV100/TY1 KIT2
Includes:
FEV100
Fluke FEV100/BASIC Test Adapter
Fluke FEV-CON/TY1 Type 1 Connector & Cable
Soft Carrying Case
User Manual
3-year warranty
125B
Fluke 125B Hand-Held Oscilloscope
Shielded Test Leads with Black Ground Leads
Test Lead Black (for Grounding)
Hook Clips (red, blue)
Banana-to-BNC Adapters (black, x1)
10:1 Voltage Probe
i400s AC Current Clamp
USB Angled Adapter
WiFi USB Adapter
Switch Mode Power Supply, Adapter/Battery Charger
Rechargeable Li-ion Battery Pack
87V
Fluke 87V Industrial Multimeter
TL75 Test Leads (TL175 Eur)
AC175 Alligator Clips
Holster with tilt-leg, test lead storage
80BK Temperature Probe
9V Battery (Installed)
TL224
One pair (red, black) silicone insulated leads with one straight female coupler on one end and right angled on the other
14 Fluke Corporation Fluke eMobil ty Tools Kit w th FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, MA 01801 - TestEquipmentDepot.com