Fluke Fluke FEV100/TY1 KIT2 Manual

Page 1
Test Equipment Depot - 800.517.8431
TECHNICAL DATA
- 5 Commonwealth Ave, MA 01801 - TestEquipmentDepot.com
Fluke eMobility Tools Kit with FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Key features
Test charging states of EVSE with CP state simulation with the 12B ScopeMeter®. Verify charging voltage and maximum available current using the 87V multimeter and TL224 test leads. Check protective earth for correct wiring and functioning with the PE pre-test feature. Perform GFCI troubleshooting of EVSE and verify operation within safety standards.
Product overview: Fluke eMobility Tools Kit with FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Test the safety and performance of a type 1, level 1 or level 2 electric vehicle ac charging stations (EVSEs) with the Fluke FEV100, 87V + 125B ScopeMeter® kit. This kit includes the FEV100 test adapter to simulates the presence of an electrical vehicle. When connected to the test adapter, the 87V multimeter will allow you to monitor the output voltage and maximum charging current of the station. Verify EVSE charging states (vehicle simulation) by connecting the 125B ScopeMeter® to measure the control pilot signal output. With this kit, it's easy to verify an EV charging station is working properly after install and during periodic maintenance, or troubleshoot an EVSE if it is not delivering the appropriate charge. SAE J1772 compliant to North American standards.
EVSE installation safety and performance checks
PE PRE-TEST: Grounding system pre-test verifies that there is no presence of dangerous voltage at the ground terminal󰾬. GFCI TEST: Ground fault circuit interrupter test verifies the breaker of the EVSE is connected by detecting ground faults󰾬.
Page 2
PE ERROR: Ground fault simulation indicates an interruption of the ground conductor; the pending charging process is aborted, and new charging processes are prevented. CP ERROR “E”: The standard J1772 defines Error “E” as a state when charging station is disconnected from vehicle, disconnected from utility, there is a loss of utility power or control pilot is short to control pilot reference (ground).
Specifications: Fluke eMobility Tools Kit with FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Fluke FEV100 Electric Vehicle Charging Station Test Adapter specifications
UL1/N = 120 V, UL2/N = 120 V, UL1/L2 = 208 V, 60 Hz (three-phase system) or
Input voltage
EV connector (EVC-13) SAE J1772 socket, 16 A (type 1, 5P single-phase)
Internal power consumption 2 W max.
Operating temperature -4 °F to 104 °F (-20 °C to 40 °C)
Storage temperature -4 °F to 122 °F (-20 °C to 50 °C)
Operating humidity range 10 % to 85 % relative humidity non-condensing
Storage relative humidity 0 % to 85 % non-condensing
Operating altitude 6561 ft (2000 m) max.
Dimensions (H × W × D) Approx. 8.66 x 4.33 x 1.77 in (220 x 110 × 45 mm) without cable assembly
Weight Approx. 4.4 lb (2 kg)
UL1/N = 120 V, UL2/N = 120 V, UL1/L2 = 240 V, 60 Hz (single-phase system), ±10% voltage fluctuations from nominal
2 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 3
Page 4
Frequency response - ac coupled (lf roll off)
Without probes and test leads <10 Hz (-3 dB)
With STL120-IV 1:1 shielded test leads <10 Hz (-3 dB)
With VP41 10:1 Probe <10 Hz (-3 dB)
Rise time, excluding probes, test leads
123B <17.5 ns 124B and 125B <8.75 ns
Without probes and test leads 1 MΩ//20 pF
With BB120 1 MΩ//24 pF
Input impedance
With STL120-IV 1:1 shielded test leads 1 MΩ//230 pF
With VP41 10:1 Probe 5 MΩ//15.5 pF
Sensitivity 5 mV to 200 V/div
Analog bandwidth limiter 10 kHz
Display modes A, -A, B, -B
Direct, with test leads, or with VP41
Max. input voltage A and B
Probe
With BB120 600 Vrms
Max. floating voltage, from any terminal to ground
600 Vrms Cat IV, 750 Vrms up to 400Hz
Horizontal
Scope modes Normal, Single, Roll
Equivalent sampling
600 Vrms Cat IV, 750 Vrms maximum voltage.
123B: 20 ns to 500 ns/div,
124B and 125B: 10 ns to 500 ns/div
Ranges (normal)
Real time sampling 1 μs to 5 s/div
Single (real time) 1 μs to 5 s/div
Roll (real time) 1s to 60 s/div
Equivalent sampling (repetitive
Sampling rate (for both channels
signals)
simultaneously)
Real time sampling 1 μs to 60 s/div 40 MS/s
Trigger
Screen update Free run, on trigger
Source A, B
@ DC to 5 MHz 0.5 divisions or 5 mV
@ 40 MHz
Sensitivity A and B
@ 60 MHz
Slope Positive, negative
Up to 4 GS/s
123B: 4 divisions
124B and 125B: 1.5 divisions
123B: N/A
124B and 125B: 4 divisions
4 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 5
Advanced scope functions
Normal
Captures up to 25 ns glitches and displays analog-like persistence waveform
Display modes
Smooth Suppresses noise from a waveform
Glitch off
Envelope
Does not capture glitches between samples
Records and displays the minimum and maximum of waveforms over time
Continuous fully automatic adjustments of amplitude, time base, trigger levels,
Auto set (Connect-and-View™)
trigger gap, and hold-off. Manual override by user adjustment of amplitude, time base, or trigger level.
Dual input meter
The accuracy of all measurements is within ±(% of reading + number of counts) from 18 °C to 28 °C.
Add 0.1x (specific accuracy) for each °C below 18 °C or above 28 °C. For voltage measurements with 10:1 probe, add probe uncertainty +1%. More than one waveform period must be visible on the screen.
Input A and input B
DC voltage (VDC)
Ranges 500 mV, 5 V, 50 V, 500 V, 750 V
Accuracy ±(0.5% +5 counts)
Common mode rejection (CMRR) >100 dB @ dc, >60 dB @ 50, 60, or 400 Hz
Full scale reading 5000 counts
True-rms voltages (V ac and V ac+dc)
Ranges 500 mV, 5 V, 50 V, 500 V, 750 V
Accuracy for 5% to 100% of range (DC coupled)
Accuracy for 5% to 100% of range (AC or dc coupled)
DC to 60 Hz (V ac+dc) ±(1% +10 counts)
1 Hz to 60 Hz (V ac) ±(1% +10 counts)
60 Hz to 20 kHz ±(2.5% +15 counts)
DC rejection (only VAC) >50 dB
>100 dB @ dc
Common mode rejection (CMRR)
>60 dB @ 50, 60, or 400 Hz
Full scale reading 5000 counts, reading is independent of any signal crest factor.
Peak
Modes Max peak, Min peak, or pk-to-pk
Ranges 500 mV, 5 V, 50 V, 500 V, 2200 V
Accuracy Max peak or Min peak 5% of full scale
Accuracy
Accuracy Peak-to-Peak 10% of full scale
5 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 6
Full scale reading 500 counts
Frequency (Hz)
123B: 1 Hz, 10 Hz, 100 Hz, 1 kHz, 10 kHz, 100 kHz,1 MHz, 10 MHz, and 50 MHz
Ranges
124B and 125B: 1 Hz, 10 Hz, 100 Hz, 1 kHz, 10 kHz, 100 kHz, 1 MHz, 10 MHz, and 70 MHz
Frequency range 15 Hz (1 Hz) to 50 MHz in continuous autoset
Accuracy @1 Hz to 1 MHz ±(0.5% +2 counts)
Full scale reading 10,000 counts
RPM
Max reading 50.00 kRPM
Accuracy ±(0.5% +2 counts)
Duty cycle (PULSE)
Range 2% to 98%
Frequency range 15 Hz (1 Hz) to 30 MHz in continuous autoset
Pulse width (PULSE)
Frequency range 15 Hz (1 Hz) to 30 MHz in continuous autoset
Full scale reading 1000 counts
Amperes (AMP)
Ranges Same as V dc, V ac, V ac+dc, or PEAK
With current clamp
Scale factors
Accuracy
Temperature (TEMP) with optional temperature probe
Range 200 °C/div (200 °F/div)
Scale factor 1 mV/°C and 1 mV/°F
Accuracy As V dc (add temp. probe uncertainty)
Decibel (dB)
0 dBV 1 V
0 dBm (600 Ω /50 Ω) 1 mW referenced to 600 Ω or 50 Ω
dB on V dc, V ac, or Vac+dc
Full scale reading 1000 counts
Crest factor (CREST)
0.1 mV/A, 1 mV/A, 10 mV/A, 100 mV/A, 400 mV/A, 1 V/A, 10 mV/mA
Same as V dc, V ac, V ac+dc, or PEAK (add current clamp uncertainty)
Range 1 to 10
Full scale reading 90 Counts
Phase
Modes A to B, B to A
6 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 7
Range 0 to 359 degrees
Resolution 1 degree
Power (125B only)
Configurations
1 phase / 3 phase 3 conductor balanced loads (3 phase: fundamental component only, AUTOSET mode only)
Power factor (PF) Ratio between watts and VA range - 0.00 to 1.00
RMS reading of multiplying corresponding samples of input A (volts) and input B
Watt
(amperes)
Full scale reading 999 counts
Vrms x Arms
VA
Full scale reading 999 counts
√((VA)2-W2)
VA reactive (var)
Full scale reading 999 counts
Vpwm
Purpose To measure on pulse width modulated signals, like motor drive inverter outputs
Principle
Readings show the effective voltage based on the average value of samples over a whole number of periods of the fundamental frequency
Accuracy As Vrms for sinewave signals
Input A to common
Ohm (Ω)
123B and 124B
500 Ω , 5 kΩ, 50 kΩ, 500 kΩ, 5 MΩ, 30 MΩ
Ranges
125B
50 Ω, 500 Ω , 5 kΩ, 50 kΩ, 500 kΩ, 5 MΩ, 30 MΩ
Accuracy ±(0.6% + 5 counts) 50 Ω ±(2% + 20 counts)
Full scale reading 50 Ω to 5 MΩ - 5000 counts, 30 MΩ - 3000 counts
Measurement current 0.5 mA to 50 nA, decreases with increasing ranges
Open circuit voltage <4 V
Continuity (Cont)
Beep <(30 Ω ±5 Ω) in 50 Ω range
Measurement current 0.5 mA
Detection of shorts of ≥1 ms
Diode
@0.5 mA >2.8 V
Measurement voltage
@open circuit <4 V
Measurement current 0.5 mA
Polarity + on input A, - on COM
7 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 8
Capacitance (CAP)
Ranges 50 nF, 500 nF, 5 μF, 50 μF, 500 μF
Full scale reading 5000 counts
Measurement current 500 nA to 0.5 mA, increases with increasing ranges
Advanced meter functions
Zero Set Set actual value to reference
Captures and freezes a stable measurement result. Beeps when stable.
AutoHold (on A)
AutoHold works on the main meter reading, with thresholds of 1 Vpp for AC signals and 100 mV for DC signals.
Fixed decimal point Activated by using attenuation keys
Cursor Readout (124B and 125B)
Sources A, B
Average, min and max readout
Average, min, max and time from start of readout (in ROLL mode; instrument in HOLD)
Single vertical line
Min, max and time from start of readout (in RECORDER mode; instrument in HOLD)
Harmonics values in POWER QUALITY mode.
Peak-peak, time distance and reciprocal time distance readout
Dual vertical lines
Average, min, max and time distance readout (in ROLL mode; instrument in HOLD)
Dual horizontal lines High, low and peak-peak readout
Transition time, 0%-level and 100%-level readout (manual or auto leveling; auto
Rise or fall time
leveling only possible in single channel mode)
Accuracy As oscilloscope accuracy
Recorder
The recorder captures meter readings in Meter Recorder mode or continuously captures waveform samples in Scope Recorder mode. The information is stored on internal memory or on optional SD card (with the 125B or 124B).
The results are displayed as Chart recorder display that plots a graph of min and max values of Meter measurements over time or as a waveform recorder display that plots all the captured samples.
Meter readings
Measurement Speed Maximum 2 measurement/s
Record Size (min, max, average) 2 M readings for 1 channel
Recorded Time Span 2 weeks
Maximum number of events 1024
Waveform record
8 Fluke Corporation Fluke eMobil ty Tools K t with FEV100 Test Adapter, 125B ScopeMeter®, 87V Mu timeter and Test Leads
Page 9
Page 10
Page 11
Page 12
Maximum capacitance
9,999 µF
Capacitance
Frequency
Duty cycle
Temperature measurement
80 BK temperature probe
Conductance
accuracy ±(1% + 2)
Maximum resolution 0.01 nF
Maximum frequency
200 kHz
Accuracy ±(0.005% + 1)
Maximum resolution 0.01 Hz
Maximum duty cycle
99.9%
Accuracy ±(0.2% per kHz + 0.1%)
Maximum resolution 0.1%
–200.0 °C – 1090 °C –328.0 °F – 1994.0 °F excluding probe
–40.0 °C – 260 °C –40.0 °F – 500 °F, 2.2 °C or 2% whichever is greater
Maximum conductance
60.00 nS
Accuracy ±(1.0% + 10)
Maximum resolution 0.01 nS
Range
3 V
Diode
Resolution 1 mV
Accuracy ±(2% + 1)
Duty cycle range
Accuracy
Within ±(0.2% per kHz + 0.1%)
Environmental Specifications
Operating temperature –20 °C to + 55 °C
Storage temperature –40 °C to + 60 °C
Humidity (without condensation)
0% – 90% (0 °C – 35 °C) 0% – 70% (35 °C – 55 °C)
Operating Altitude 2000 m
Safety Specifications
Overvoltage category EN 61010–1 to 1000 V CAT III, 600V CAT IV
Agency approvals CE, CSA, RCM
Mechanical and General Specifications
Size 201 x 98 x 52 mm (with holster)
Weight
Display
355 g 624 g – with holster
Digital
6000 counts updates 4/sec. 19,999 counts in high–resolution mode
Analog 32 segments, updates 40/sec
Frequency 19,999 counts, updates 3/sec at > 10 Hz
12 Fluke Corporation Fluke eMobil ty Tools Kit w th FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Page 13
Warranty Lifetime
Battery Life
Alkaline
~400 hours typical, without backlight
Shock 1 Meter drop per IEC 61010–1:2001
Vibration Per MIL–PRF–28800 for a Class 2 instrument
13 Fluke Corporation Fluke eMobil ty Tools Kit w th FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Page 14
Ordering information
FLK-FEV100/TY1 KIT2
Includes:
FEV100
Fluke FEV100/BASIC Test Adapter Fluke FEV-CON/TY1 Type 1 Connector & Cable Soft Carrying Case User Manual 3-year warranty
125B
Fluke 125B Hand-Held Oscilloscope Shielded Test Leads with Black Ground Leads Test Lead Black (for Grounding) Hook Clips (red, blue) Banana-to-BNC Adapters (black, x1) 10:1 Voltage Probe i400s AC Current Clamp USB Angled Adapter WiFi USB Adapter Switch Mode Power Supply, Adapter/Battery Charger Rechargeable Li-ion Battery Pack
87V
Fluke 87V Industrial Multimeter TL75 Test Leads (TL175 Eur) AC175 Alligator Clips Holster with tilt-leg, test lead storage 80BK Temperature Probe 9V Battery (Installed)
TL224
One pair (red, black) silicone insulated leads with one straight female coupler on one end and right angled on the other
14 Fluke Corporation Fluke eMobil ty Tools Kit w th FEV100 Test Adapter, 125B ScopeMeter®, 87V Multimeter and Test Leads
Test Equipment Depot - 800.517.8431 - 5 Commonwealth Ave, MA 01801 - TestEquipmentDepot.com