Table 1 lists the International Electrical Symbols. Some or all of these symbols
may be used on the instrument or in this manual.
Tabl e 1 International Electrical Symbols
SymbolDescription
AC (Alternating Current)
AC-DC
Battery
CE Complies with European Union Directives
1 Before You Start
Symbols Used
DC
Double Insulated
Electric Shock
Fuse
PE Ground
Hot Surface (Burn Hazard)
Read the User’s Manual (Important Information)
Off
On
1
9150 Portable Furnace
User’s Guide
SymbolDescription
Canadian Standards Association
OVERVOLTAGE (Installation) CATEGORY II, Pollution Degree 2 per IEC1010-1 re
fers to the level of Impulse Withstand Voltage protection provided. Equipment of
OVERVOLTAGE CATEGORY II is energy-consuming equipment to be supplied from
the fixed installation. Examples include household, office, and laboratory appliances.
C-TIC Australian EMC Mark
The European Waste Electrical and Electronic Equipment (WEEE) Directive
(2002/96/EC) mark.
1.2Safety Information
Use this instrument only as specified in this manual. Otherwise, the protection
provided by the instrument may be impaired.
The following definitions apply to the terms “Warning” and “Caution”.
• “Warning” identifies conditions and actions that may pose hazards to the
user.
• “Caution” identifies conditions and actions that may damage the instrument being used.
1.2.1
WARNINGS
To avoid personal injury, follow these guidelines.
BURN HAZARD - DO NOT touch the well access surface of the unit.
The temperature of the well access is the same as the actual temperature shown
on the display. If the unit is set at 600°C and the display reads 600°C, the well
is at 600°C.
The top sheet metal of the furnace may exhibit extreme temperatures for areas
close to the well access.
The air over the well can reach temperatures greater than 200°C. Probes should
only be inserted and removed from the unit when the unit is set at temperatures
less than 200°C.
-
DO NOT turn off the unit at temperatures higher than 100°C. This could create
a hazardous situation. Select a set-point less than 100°C and allow the unit to
cool before turning it off.
DO NOT remove inserts and insulators at high temperatures. Inserts and insu
-
lators are the same temperature as the display temperature.
2
1 Before You Start
Safety Information
DO NOT operate this unit without a properly grounded, properly polarized
power cord.
DO NOT connect this unit to a non-grounded, non-polarized outlet.
HIGH VOLTAGE is used in the operation of this equipment. SEVERE IN
-
JURY OR DEATH may result if personnel fail to observe safety precautions.
Before working inside the equipment, turn the power off and disconnect the
power cord.
Always replace the fuse with one of the same rating, voltage, and type.
Overhead clearance is required. DO NOT place this instrument under a cabinet
or other structure.
DO NOT use this unit for any application other than calibration work.
DO NOT use this unit in environments other than those listed in the user’s
guide.
DO NOT turn the unit upside down with the inserts in place; the inserts will
fall out of the unit.
DO NOT operate near flammable materials.
Use of this instrument at HIGH TEMPERATURES for extended periods of
time requires caution.
Completely unattended high temperature operation is not recommended for
safety reasons.
Before initial use, after transport, and anytime the furnace has not been energized for more than 10 days, the calibrator must be energized for a dry-out period of 1 to 2 hours before it can be assumed to meet all of the safety
requirements of the IEC1010-1.
Materials used in this furnace may be irritating to skin, eyes, and respiratory
tract. Consult the material manufacturer’s MSDS (Material Safety Data Sheet).
Proper ventilation and safety precautions must be observed.
Follow all safety guidelines listed in the user’s guide.
Calibration Equipment should only be used by Trained Personnel.
1.2.2
CAUTIONS
To avoid possible damage to the instrument, follow these guidelines.
DO NOT plug the unit into 230 V if the heater switches and fuse holder read
115 V. This action will cause the fuses to blow and may damage the instrument.
Components and heater lifetime can be shortened by continuous high tempera
ture operation.
Most probes have handle temperature limits. Be sure that the probe hand tem
perature limit is not exceeded in the air above the unit.
-
-
3
9150 Portable Furnace
User’s Guide
Allow for test probe expansion inside the well as the furnace heats.
DO NOT use fluids to clean out the well.
Never introduce foreign material into the probe hole of the insert. Fluids, etc.
can leak into the calibrator causing damage.
DO NOT change the values of the calibration constants from the factory set
values. The correct setting of these parameters is important to the safety and
proper operation of the calibrator.
DO NOT drop or force the probe stems into the well. This type of action can
cause a shock to the sensor and affect the calibration.
DO use a ground fault interrupt device.
1.3Authorized Service Centers
Please contact one of the following authorized Service Centers to coordinate
service on your Hart product:
Fluke Corporation, Hart Scientific Division
799 E. Utah Valley Drive
American Fork, UT 84003-9775
USA
Phone: +1.801.763.1600
Telefax: +1.801.763.1010
E-mail: support@hartscientific.com
Fluke Nederland B.V.
Customer Support Services
Science Park Eindhoven 5108
5692 EC Son
NETHERLANDS
Phone: +31-402-675300
Telefax: +31-402-675321
E-mail: ServiceDesk@fluke.nl
Fluke Int'l Corporation
Service Center - Instrimpex
Room 2301 Sciteck Tower
22 Jianguomenwai Dajie
4
1 Before You Start
Authorized Service Centers
Chao Yang District
Beijing 100004, PRC
CHINA
Phone: +86-10-6-512-3436
Telefax: +86-10-6-512-3437
E-mail: xingye.han@fluke.com.cn
Fluke South East Asia Pte Ltd.
Fluke ASEAN Regional Office
Service Center
60 Alexandra Terrace #03-16
The Comtech (Lobby D)
118502
SINGAPORE
Phone: +65 6799-5588
Telefax: +65 6799-5588
E-mail: antng@singa.fluke.com
When contacting these Service Centers for support, please have the following
information available:
• Model Number
•
Serial Number
•
Voltage
•
Complete description of the problem
5
2Introduction
2 Introduction
The Hart Scientific 9150 thermocouple furnace can be used for calibrating ther
mocouple and RTD temperature probes. Calibrations may be done over a range
of 150°C to 1200°C (302°F to 2192°F). Temperature display of the 9150 is 0.1
degrees below 1000°and 1 degrees above 1000°.
The furnace features:
Rapid heating and cooling
•
Interchangeable multiple hole probe sleeves
•
Convenient handle
•
RS-232 interface
•
Built in programmable features include:
Temperature scan rate control
•
• Eight set-point memory
• Adjustable readout in °C or °F
The temperature is accurately controlled by Hart’s hybrid analog/digital controller. The controller uses a Type S thermocouple as a sensor and controls the
well temperature with a solid state relay (triac) driven heater. The furnace
should be calibrated yearly by trained personnel at Hart Scientific.
The LED front panel continuously shows the current well temperature. The
temperature may be easily set with the control buttons to any desired temperature within the specified range. The calibrator’s multiple fault protection devices insure user and instrument safety and protection.
The 9150 calibrator furnace was designed for portability, low cost, and ease of
operation. Through proper use, the instrument will provide continued accurate
calibration of temperature sensors and devices. The user should be familiar
with the safety guidelines and operating procedures of the furnace as described
in this manual.
-
7
3 Specifications and Environmental Conditions
3Specifications and Environmental
Conditions
3.1Specifications
Temperature Range150–1200°C (302–2192°F)
Display Resolution0.1° to 999.9°, 1° above 1000°
Stability±0.5°C
Display Accuracy±5.0°C
Well Diameter1.25" (32 mm)
Well Depth4" (102 mm)
Heating Time35 minutes to 1200°C
Cooling Time140 minutes with block
Well to Well Uniformity±0.5°C to ±1.0°C (insert “C” at 1200°C)
Size12.4" H x 8.2" W x 12.4"D (315 x 208 x 315 mm)
Weight28 lb. (13 kg)
Fault ProtectionSensor burnout and short protection, over temperature thermal cutout
Specifications
3.2Environmental Conditions
Although the instrument has been designed for optimum durability and trou
ble-free operation, it must be handled with care. The instrument should not be
operated in an excessively dusty or dirty environment. Maintenance and clean
ing recommendations can be found in the Maintenance Section of this manual.
The instrument operates safely under the following conditions:
•
temperature range: 5 - 50°C (41 - 122°F)
•
ambient relative humidity: 15 - 50%
•
pressure: 75kPa - 106kPa
•
mains voltage within ± 10% of nominal
•
vibrations in the calibration environment should be minimized
•
altitude less than 2000 meters
-
-
9
9150 Portable Furnace
User’s Guide
3.3Warranty
Fluke Corporation, Hart Scientific Division (Hart) warrants this product to be
free from defects in material and workmanship under normal use and service
for a period as stated in our current product catalog from the date of shipment.
This warranty extends only to the original purchaser and shall not apply to any
product which, in Hart's sole opinion, has been subject to misuse, alteration,
abuse or abnormal conditions of operation or handling.
Software is warranted to operate in accordance with its programmed instruc
tions on appropriate Hart products. It is not warranted to be error free.
Hart's obligation under this warranty is limited to repair or replacement of a
product which is returned to Hart within the warranty period and is determined,
upon examination by Hart, to be defective. If Hart determines that the defect or
malfunction has been caused by misuse, alteration, abuse or abnormal condi
tions or operation or handling, Hart will repair the product and bill the pur
chaser for the reasonable cost of repair.
To exercise this warranty, the purchaser must forward the product after calling
or writing an Authorized Service Center (see Section 1.3). The service centers
assume NO risk for in-transit damage.
THE FOREGOING WARRANTY IS PURCHASER'S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY
IMPLIED WARRANTY OR MERCHANTABILITY, OR FITNESS FOR ANY
PARTICULAR PURPOSE OR USE. HART SHALL NOT BE LIABLE FOR
ANY SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OR LOSS WHETHER IN CONTRACT, TORT, OR OTHERWISE.
-
-
-
10
4Safety Guidelines
Operate the instrument in room temperatures between 5-50°C (41-122°F).
•
Allow sufficient air circulation by leaving at least 6 inches of space be
tween the instrument and nearby objects. Overhead clearance needs to al
low for safe and easy insertion and removal of probes for calibration.
The furnace is a precision instrument. Although it has been designed for
•
optimum durability and trouble free operation, it must be handled with
care. Always carry the unit in an upright position to prevent the probe
sleeves from dropping out. The convenient fold-up handle allows one
hand carrying. The instrument should not be operated in excessively wet,
oily, dusty, or dirty environments. It is important to keep the well of the
instrument clean and clear of any foreign matter. Do not operate near
flammable materials.
DO NOT use fluids to clean out the well.
•
The instrument can generate extreme temperatures. Precautions must be
•
taken to prevent personal injury or damage to objects. Probes may be extremely hot or cold when removed from the instrument. Cautiously handle
probes to prevent personal injury. Always use the special sleeve tongs that
are supplied with the calibrator to remove the sleeve. Carefully place
probes on a heat/cold resistant surface or rack until they are at room temperature. Never place any objects other than the special probe sleeves supplied with the calibrator into the well.
• Use only a grounded AC mains supply of the appropriate voltage to
power the instrument. Refer to Section 3.1, Specifications, for power details.
•
Before initial use, after transport, and anytime the furnace has not been
energized for more than 10 days, the instrument needs to be energized for
a “dry-out” period of 1-2 hours before it can be assumed to meet all of the
safety requirements of the IEC 1010-1.
•
The instrument is equipped with operator accessible fuses. If a fuse
blows, it may be due to a power surge or failure of a component. Replace
the fuse once. If the fuse blows a second time, it is likely caused by fail
ure of a component part. If this occurs, contact Hart Scientific Customer
Service. Always replace the fuse with one of the same rating, voltage, and
type. Never replace the fuse with one of a higher current rating.
•
If a mains supply power fluctuation occurs, immediately turn off the in
strument. Power bumps from brownouts and blackouts could damage the
instrument. Wait until the power has stabilized before re-energizing the
instrument.
•
Air circulated through the unit keeps the chassis cool. DO NOT SHUT
OFF THE FURNACE WHILE AT HIGH TEMPERATURES.
4 Safety Guidelines
-
-
-
-
11
5Quick Start
5.1Unpacking
5 Quick Start
Unpacking
Unpack the furnace carefully and inspect it for any damage that may have oc
curred during shipment. If there is shipping damage, notify the carrier
immediately.
Verify that the following components are present:
9150 Furnace
•
3150, Insert
•
Insert Insulator
•
Power Cord
•
Manual
•
RS-232 Cable
•
5.2Set-Up
Place the calibrator on a flat surface with at least 6 inches of free space around
the instrument. Plug the power cord into a grounded mains outlet. Observe that
the nominal voltage corresponds to that indicated on the back of the calibrator.
Carefully insert the probe sleeve into the well. (DO NOT drop the sleeve in the
well.) Probe sleeve holes should be of the smallest diameter possible while still
allowing the probe to slide in and out easily. Sleeves with various hole sizes are
available from Hart Scientific. The well must be clear of any foreign objects,
dirt and grit before the sleeve is inserted. The sleeve is inserted with the two
small tong holes positioned upward.
Turn on the power to the calibrator by toggling the switch on the power entry
module. The fan should begin quietly blowing air through the instrument and
the controller display should illuminate after 3 seconds. After a brief self test
the controller should begin normal operation. If the unit fails to operate please
check the power connection.
The display begins to show the well temperature and the well heater starts oper
ating to bring the temperature of the well to the set-point temperature.
-
-
5.3Power
Plug the furnace power cord into a mains outlet of the proper voltage, fre
quency, and current capability. Refer to Section 3.1, Specifications, for power
details. Turn the furnace on using the rear panel “POWER” switch. The furnace
turns on and begins to heat to the previously programmed temperature
set-point. The front panel LED display indicates the actual furnace temperature.
-
13
9150 Portable Furnace
User’s Guide
5.4Setting the Temperature
Section 8 explains in detail how to set the temperature set-point on the calibra
tor using the front panel keys. The procedure is summarized here.
(1) Press “SET” twice to access the set-point value.
(2) Press “SET” to move the cursor to the units that need changing.
(3) Press “UP” or “DOWN” to change the set-point value.
(4) Press “SET” until the display exits to store the new set-point.
(5) Press “EXIT” to return to the temperature display without saving the
new set-point value.
When the set-point temperature is changed the controller switches the well
heater on or off to raise or lower the temperature. The displayed well tempera
ture gradually changes until it reaches the set-point temperature. The well may
require 35 minutes to reach the set-point depending on the span. Another 10 to
20 minutes is required to stabilize within ±0.5°C of the set-point. Ultimate stability may take 15 to 20 minutes more of stabilization time.
-
-
14
6Parts and Controls
The user should become familiar with the furnace back panel, front panel, and
constant temperature block assembly.
6.1Back Panel
6 Parts and Controls
Back Panel
The back panel (Figure 1) features the Power Entry Module (PEM) that con
tains the power cord socket, the power switch, and the heater voltage switch,
the serial port, and the fan.
Figure 1 Back Panel
-
Power Cord - On the back of the calibrator is the removable power cord inlet
that plugs into an IEC grounded socket.
Power Switch - The power switch is located on the power entry module
(PEM). The PEM also houses the fuses and the dual voltage selector. The PEM
and Heater Voltage Switch allow the unit to be field switchable for 115 VAC
(±10%) or 230 VAC (±10%) operation.
Heater Voltage Switch - To be used only when changing the input voltage.
(See Section 7.2 for instructions.)
Serial Port - A DB-9 male connector is present for interfacing the calibrator to
a computer or terminal with serial RS-232 communications.
15
9150 Portable Furnace
User’s Guide
Fan - The fan inside the calibrator runs continuously when the unit is being op
erated to provide cooling for the instrument. Slots at the top and sides of the
calibrator are provided for airflow. The area around the calibrator must be kept
clear to allow adequate ventilation. The airflow is directed upward and can be
extremely hot.
6.2Front Panel
The front panel consists of the controller display and the controller keypad as
showninFigure2.
Figure 2 Front Panel
-
16
Controller Display - The digital display is an important part of the temperature
controller because it not only displays set and actual temperatures but also dis
plays various calibrator functions, settings, and constants. The display shows
temperatures in units according to the selected scale °C or °F.
Controller Keypad - The four button keypad allows easy setting of the
set-point temperature. The control buttons (SET, DOWN, UP, and EXIT) are
used to set the calibrator temperature set-point, access and set other operating
parameters, and access and set calibration parameters.
Setting the control temperature is done directly in degrees of the current scale.
It can be set to one-tenth of a degree Celsius or Fahrenheit.
The functions of the buttons are as follows:
SET – Used to display the next parameter in the menu and to store parameters
to the displayed value.
DOWN – Used to decrement the displayed value of parameters.
UP –Usedtoincrementthedisplayedvalue.
Constant Temperature Block Assembly
EXIT – Used to exit from a menu. When EXIT is pressed any changes made to
the displayed value are ignored.
6 Parts and Controls
6.3Constant Temperature Block Assembly
The constant temperature block assembly is shown in Figure 3 and consists of
removable inserts.
Figure 3 Removable Inserts
6.3.1Constant Temperature Block
The “Block” is made of aluminum-oxide and provides a relatively constant and
accurate temperature environment for the sensor that is to be calibrated. A
1.25-inch diameter well is provided that may be used for sensors of that size or
may be sleeved down with various sized multi-hole probe sleeves. Heaters sur
round the block assembly and provide even heat to the sensor. A Type S ther
mocouple is used to sense and control the temperature of the block. The entire
assembly is surrounded by a heat reflector to thermally isolate the chassis and
electronics.
6.3.2Probe Sleeves and Tongs
The calibrator is supplied with a multi-hole aluminum-oxide probe sleeve and
insulator sleeve for insertion into the calibrator well and tongs for removing
sleeves. Probe sleeves of various hole sizes are available to allow the user’s
probe to fit snugly into the well whatever the diameter of the probe.
Insert A and an insulator is provided unless otherwise indicated . The inserts
are:
-
-
17
9150 Portable Furnace
User’s Guide
or
Insert A Model 3150-2 (variety block): 1/2”, 1/4”, 3/8”, 3/16”, 1/8”, and
•
1/16” holes
Insert B Model 3150-3 (comparison block): two each 3/8”, 1/4”, and
•
3/16” holes
Insert C Model 3150-4 (1/4” comparison block): six 1/4” holes
•
18
7General Operation
7.1Changing Display Units
The 9150 can display temperature in Celsius or Fahrenheit. The temperature
units are shipped from the factory set to Celsius. To change to Fahrenheit or
back to Celsius there are two ways:
1 - Press the “SET” and “DOWN” simultaneously.
or
1 - Press the “SET” key three times from the temperature display and then
“EXIT” to show the units.
Un= C
2 - Press the “UP” or “DOWN” key to change units.
3 - Press “SET” to store changes and then “EXIT” to display the temperature.
7.2Switching to 230V Operation
7 General Operation
Changing Display Units
The 9150 is switchable from 115 VAC to 230 VAC 50/60 Hz. Switching the
voltage can change the calibration, so the unit should be calibrated after
changing the input voltage.
To change from 115 VAC to 230 VAC
1.Unplug the unit.
2.With a small straight slot screwdriver remove the fuse holder from the
PEM located on the back of the unit.
3.Replace the two 12A F 250V fuses with two 6.3A F 250V fuses.
4.Replace the fuse holder with the “230V” in the display window.
5.Lay the unit on its side and with a small straight slot screwdriver, move
the heater switches located on the bottom of the unit to display “230V”.
Note: If the heater switches and the fuse holder do not all read “230V when
complete, the unit will either not heat or only heat at a fraction of its capacity.
If not done properly, the unit could become damaged and void the calibration
and warranty. Refer to Section 3.1, Specifications, for correct fuse usage.
CAUTION: Do not plug the unit into 230V if the heater switches and fuse
holder read 115V. This will cause the fuses to blow and may damage the
instrument.
19
8Controller Operation
8 Controller Operation
Well Temperature
This section discusses in detail how to operate the furnace temperature control
ler using the front control panel. By using the front panel key-switches and
LED display the user may monitor the well temperature, adjust the set-point
temperature in degrees C or F, monitor the heater output power, adjust the con
troller proportional band, and program the probe calibration parameters, operat
ing parameters, serial interface configuration, and controller calibration
parameters. Operation of the functions and parameters are shown in the
flowchart in Figure 4 on page 22. This chart may be copied for reference.
In the following discussion a button with the word SET, UP, DOWN, or EXIT
inside indicates the panel button while the dotted box indicates the display
reading. Explanation of the button or display reading are to the right of each
button or display value.
8.1Well Temperature
The digital LED display on the front panel allows direct viewing of the actual
well temperature. This temperature value is what is normally shown on the display. The units, C or F, of the temperature value are displayed at the right. For
example,
962.3 CWell temperature in degrees Celsius
The temperature displayed function may be accessed from any other function
by pressing the “EXIT” button.
-
-
-
8.2Temperature Set-point
The temperature set-point can be set to any value within the range and resolu
tion as given in the specifications. Be careful not to exceed the safe upper tem
perature limit of any device inserted into the well.
Setting the temperature involves two steps: (1) select the set-point memory and
(2) adjust the set-point value.
8.2.1Programmable Set-points
The controller stores 8 set-point temperatures in memory. The set-points can be
quickly recalled to conveniently set the calibrator to a previously programmed
temperature set-point.
To set the temperature one must first select the set-point memory. This function
is accessed from the temperature display function by pressing “SET”. The
number of the set-point memory currently being used is shown at the left on the
display followed by the current set-point value.
-
-
21
9150 Portable Furnace
User’s Guide
Figure 4 Controller Operation Flowchart
22
200.0 CWell temperature in degrees Celsius
8 Controller Operation
Temperature Set-point
S
Access set-point memory
1. 200.Set-point memory 1, 200.0°C currently used
To change the set-point memory press “UP” or “DOWN”.
5. 900.New set-point memory 5, 900.0°C
Press “SET” to accept the new selection and access the set-point value.
S
Accept selected set-point memory
8.2.2Set-point Value
The set-point value may be adjusted after selecting the set-point memory and
pressing “SET”.
0900.0Set-point value in °C
The first digit flashes on and off. If the set-point value is correct, press “EXIT”
to display the temperature scale units.
If the first digit is correct press “SET”.
To adjust the first digit, press “UP” or “DOWN”. Then, press “SET” to go to
the second digit. The second digit of the temperature should now be flashing.
Adjust this digit by pressing “UP” or “DOWN”.
Press “SET” to accept the second digit and repeat until the last digit has been
adjusted.
0962.7New set-point value
Press “SET” to accept the new set-point. If “EXIT” is pressed all changes made
to the set-point are discarded.
S
Accept new set-point value
8.2.3Temperature Scale Units
Temperature Scale Units of the controller are set by the user to degrees Celsius
(°C) or Fahrenheit (°F). The units are used in displaying the well temperature,
set-point, and proportional band.
Press “SET” after adjusting the set-point value to change display units.
Un= C
23
9150 Portable Furnace
User’s Guide
Press “UP” or “DOWN” to change the units.
Press “EXIT” to display the well temperature or press “SET” to access the scan
control.
8.3Scan
The scan rate can be set and enabled so that when the set-point is changed the
furnace heats or cools at a specified rate (degrees per minute) until it reaches
the new set-point. With the scan disabled the furnace heats or cools at the maxi
mum possible rate.
8.3.1Scan Control
The scan is controlled with the scan on/off function that appears in the main
menu after the temperature scale units.
Scale units currently selected
Un= FNew units selected
-
Sc=OFFScan function off
Press “UP” or “DOWN” to toggle the scan on or off.
Sc=OnScan function on
Press “SET” to accept the present setting and access the scan rate.
S
Accept scan setting
8.3.2Scan Rate
The next function in the main menu is the scan rate. The scan rate can be set
from .1 to 99.9°C/minute. The maximum scan rate however is actually limited
by the natural heating or cooling rate of the instrument. This rate is often less
than 100°C/minute, especially when cooling.
The scan rate function appears in the main menu after the scan control function.
The scan rate units are in degrees per minute, degrees C or F depending on the
selected units.
Sr=10.0Scan rate in °C/min.
Press“UP”or“DOWN”tochangethescanrate.
Sr= 5.8New scan rate
24
Press “SET” to accept the new scan rate and continue.
8 Controller Operation
Ramp and Soak Program
S
Accept scan rate
8.4Ramp and Soak Program
The ramp and soak program feature for the 9150 allows the user to program a
number of set-points, cycle the furnace automatically between the temperatures
at a scan rate set by the user, and hold the furnace at each temperature for a pe
riod of time set by the user. The user can select one of four different cycle func
tions. The Ramp and Soak Menu is accessed by pressing “SET” and “UP”
simultaneously.
8.4.1Program Points
The 9150 contains eight “program points”. Each program point contains a
set-point, scan rate, and soak time. When the unit is in program mode the unit
heats or cools to the current program set-point at the current program scan rate.
Once the program set-point is reached the unit waits for the program soak time
before heating or cooling to the next program set-point. To access the Ramp
and Soak Program Menu press “SET” and “UP” simultaneously.
962.4Well temperature
S+U
ProGRamp and Soak Program
Access Ramp and Soak Program Menu
-
-
Press “SET” to access the number of program points.
8.4.2Number of Program Points
The first parameter in the program menu is the number of program points to cy
cle through. Up to 8 set-points can be used in a ramp and soak program.
Pn= 8Number of program points to cycle through
Use the “UP” and “DOWN” buttons to change the program points. The valid
range is from 2 to 8.
Pn= 4New number of program points
Press “SET” to continue. Pressing “EXIT” causes any changes made to the pa
rameter to be discarded.
S
Accept the new number of program points.
-
-
25
9150 Portable Furnace
User’s Guide
8.4.3Program Set-Points
The controller allows the user to adjust up to eight program points. These are
accessed by pressing “SET” after setting the number of program points as de
scribed in Section 8.4.2. Each program point has three associated parameters:
the program set-point, the program scan rate, and the program hold (or soak)
time. After adjusting the number of program points press “SET”.
Use the “UP” or “DOWN” buttons to select any of the program points. The
controller only allows the user to edit program points that are less than or equal
to the number of programs points selected as explained in Section 8.4.2. For
example, if the user has selected 4 program points program points 5, 6, 7, and 8
cannot be edited.
Press “SET” to edit a program point.
-
SP 1Program point 1
SP 4Program point 4
S
The first value to edit is the program set-point.
Edit program point
0962.7Program set-point value in °C
Use “UP”, “DOWN”, and “SET” to adjust the set-point as each digit flashes.
0970.0New program set-point value for program point 4
Press “SET” to save the new set-point value or “EXIT” to discard changes.
S
The next value to edit is the program soak time.
Accept the program point set-point
Pt 4Program point 4 soak time
Press “SET” to edit the program soak time.
S
Edit program point soak time
00001Current program point soak time
Use “UP”, “DOWN”, and “SET” to adjust the program soak time. This value
can be any integer from 0 to 14400. This time is the minutes the program
set-point maintains after the temperature of the furnace has settled and before
proceeding to the next set-point. Each digit flashes individually to indicate that
26
8 Controller Operation
Ramp and Soak Program
it can be adjusted.
00200Program point 4 soak time set for 200 minutes
Press “SET” to save the new soak-time value or “EXIT” to discard changes
S
The next value to edit is the program scan rate. This value is ignored if scan is
not enabled for the unit (See Section 8.3.1).
Accept the program point soak time
Sr 4Program point 4 scan rate
Press “SET” to edit the program scan rate.
S
Edit the program point scan rate
10.0Current program point 4 scan rate
Use “UP” and “DOWN” to adjust the program scan rate.
11.3New program point 4 scan rate
Press “SET” to save the new scan rate value or “EXIT” to discard changes.
S
After “SET” is pressed the controller advances to the next program point or, if
there are no more program points to edit, exits to the Program Function Menu.
Repeat the above steps to edit any program point.
Accept the program point scan rate
8.4.4Program Function Mode
The next parameter is the program function or cycle mode. There are four pos
sible modes which determine whether the program scans up (from set-point 1
to n) only or both up and down (from set-point n to 1), and also whether the
program stops after one cycle or repeats the cycle indefinitely. The table below
shows the action of each of the four program mode settings.
-
FunctionAction
1up-stop
2up-down-stop
3up-repeat
4up-down-repeat
Pf=1
27
9150 Portable Furnace
User’s Guide
Press “SET” to adjust the program mode and the “UP” or “DOWN” buttons to
change the mode.
Program mode
Pf=4
Press “SET” to continue or “EXIT” to continue without saving the new value.
S
Save new setting
New mode
8.4.5Program Control
The final parameter in the program menu is the control parameter. You may
choose between three options to either start the program from the beginning,
continue the program from where it was when it was stopped, or stop the
program.
P=OFF
Use the “UP” or “DOWN” buttons to change the status.
P=Go
Press “SET” to activate the new program control command and return to the
temperature display.
S
Activate new command.
Program presently off
Start cycle from beginning
8.5Secondary Menu
28
Functions which are used less often are accessed within the secondary menu.
The secondary menu is accessed by pressing “SET” and “EXIT” simulta
neously and then releasing. The first function in the secondary menu is the
heater power display. (See Figure 4 on page 22.)
8.6Heater Power
The temperature controller controls the temperature of the furnace by pulsing
the heater on and off. The total power being applied to the heater is determined
by the duty cycle or the ratio of heater on time to the pulse cycle time. By
knowing the amount of heating the user can tell if the calibrator is heating up to
the set-point, cooling down, or controlling at a constant temperature. Monitor
ing the percent heater power lets the user know how stable the well temperature
is. With good control stability the percent heating power should not fluctuate
more than ±1% within one minute.
The heater power display is accessed in the secondary menu. Press “SET” and
-
-
8 Controller Operation
Set-point Voltage
”EXIT” simultaneously and release. The heater power is displayed as a percent
age of full power.
962.4Well temperature
S+E
Access heater power in secondary menu
100.0 PHeater power in percent
To exit out of the secondary menu press “EXIT”. To continue on to the
set-point voltage setting function press “SET”.
8.7Set-point Voltage
The set-point voltage is displayed for informational purposes and is used to cal
ibrate the instrument.
The value of the set-point voltage changes when the set-point temperature is
changed and also when DC1 and DC2 are adjusted.
S+E
100.0 PHeater power in percent
S
Access heater power in secondary menu
Access set-point voltage
-
-
11.934USet-point voltage in millivolts
To exit out of the secondary menu, press “EXIT”. To continue on to the propor
tional band setting function press “SET”.
8.8Proportional Band
In a proportional controller such a this the heater output power is proportional
to the well temperature over a limited range of temperatures around the
set-point. This range of temperature is called proportional band. At the bottom
of the proportional band the heater output is 100%. At the top of the propor
tional band the heater output is 0. Thus as the temperature rises the heater
power is reduced, which consequently tends to lower the temperature back
down. In this way the temperature is maintained at a fairly constant
temperature.
The temperature stability of the well and response time depend on the width of
the proportional band. If the band is too wide the well temperature deviates ex
cessively from the set-point due to varying external conditions. This deviation
is because the power output changes very little with temperature and the con
-
-
-
-
29
9150 Portable Furnace
User’s Guide
troller cannot respond very well to changing conditions or noise in the system.
If the proportional band is too narrow the temperature may swing back and
forth because the controller overreacts to temperature variations. For best con
trol stability the proportional band must be set for the optimum width.
The proportional band width is set at the factory to about 30.0°C. The propor
tional band width may be altered by the user if he desires to optimize the con
trol characteristics for a particular application.
The proportional band width is easily adjusted from the front panel. The width
may be set to discrete values in degrees C or F depending on the selected units.
The proportional band adjustment can be accessed within the secondary menu.
Press “SET” and “EXIT” to enter the secondary menu and show the heater
power. Then press “SET” twice to access the proportional band.
-
-
-
S+E
Access heater power in secondary menu
100.0 PHeater power in percent
S
Access set-point voltage
11.934 USet-point voltage in millivolts
S
Access proportional band
ProPFlashesand then displays the setting
30.0Proportional band
To change the proportional band, press “UP” or “DOWN.”
30.5New proportional band setting
To store the new setting press “SET”. Press “EXIT” to continue without storing
the new value.
S
Accept the new proportional band setting
30
8.9Controller Configuration
The controller has a number of configuration and operating options and calibra
tion parameters which are programmable via the front panel. These are ac
cessed from the secondary menu after the proportional band function by
pressing “SET”. Pressing “SET” again enters the first of three groups of config
uration parameters—operating parameters, serial interface parameters and cali
-
-
-
-
bration parameters. The groups are selected using the “UP” and “DOWN” keys
andthenpressing“SET”.
8.10Operating Parameters
The operating parameters menu is indicated by:
ParOperating parameters menu
Press “SET” to enter the menu. The operating parameters menu contains the
HL (High Limit) parameter, the Soft Cutout parameter, and the Cutout Reset
Mode parameter.
8.10.1High Limit
The HL parameter adjusts the upper set-point temperature. The factory default
and maximum are set to 1200. For safety, a user can adjust the HL down so the
maximum temperature set-point is restricted.
HLHigh Limit parameter
Press “SET” to enable adjustment of HL.
8 Controller Operation
Operating Parameters
S
Access High Limit
1200Flashes the current value and then displays the value for
1200.0Current HL setting
Adjust the HL parameter digit by digit using “UP”, “DOWN”, and “SET” as
each digit flashes.
1005.9New HL setting
Press “SET” to accept the new temperature limit.
8.10.2Soft Cutout
The Soft Cutout parameter is used by the controller to shut the unit down dur
ing over-temperature conditions.
SoFtCoSoft Cutout parameter
Press “SET” to enable adjustments of the Soft Cutout.
S
Access Soft Cutout
adjustment
-
31
9150 Portable Furnace
User’s Guide
Adjust this parameter by using “UP”, “DOWN”, and “SET” as each digit
flashes.
Press “SET” to accept the new temperature limit.
If the temperature of the unit is ever greater than the Soft Cutout temperature
the controller shuts itself down and displays, alternately, “SCtOut”and“Err8”.
8.10.3Cutout Reset Mode
The cutout reset mode determines whether the cutout resets automatically when
the well temperature drops to a safe value or must be manually reset by the
operator.
The parameter is indicated by,
1225Flashes the current value and then displays the value for
adjustment
1225.0Current Soft Cutout setting
1200.0New Soft Cutout setting
32
CtorStCutout reset mode parameter
Press “SET” to access the parameter setting. Normally the cutout is set for automatic mode.
AutoCutout set for automatic reset
To change to manual reset mode press “UP” or “DOWN” and then “SET”.
rStCutout set for manual reset
8.11Serial Interface Parameters
The serial RS-232 interface parameters menu is indicated by,
SEriALSerial RS-232 interface parameters menu
The serial interface parameters menu contains parameters which determine the
operation of the serial interface. The parameters in the menu are: BAUD rate,
sample period, duplex mode, and linefeed.
8.11.1BAUD Rate
8 Controller Operation
Serial Interface Parameters
The BAUD rate is the first parameter in the menu. The BAUD rate setting de
termines the serial communications transmission rate.
The BAUD rate parameter is indicated by,
bAUdSerial BAUD rate parameter
Press “SET” to choose to set the BAUD rate. The current BAUD rate value is
then be displayed.
2400 bCurrent BAUD rate
The BAUD rate of the serial communications may be programmed to 300 600,
1200, 2400, 4800, or 9600 BAUD. 2400 BAUD is the default setting. Use “UP”
or “DOWN” to change the BAUD rate value.
4800 bNew BAUD rate
Press “SET” to set the BAUD rate to the new value or “EXIT” to abort the operation and skip to the next parameter in the menu.
8.11.2Sample Period
The sample period is the next parameter in the serial interface parameter menu.
The sample period is the time period in seconds between temperature measurements transmitted from the serial interface. If the sample rate is set to 5, the instrument transmits the current measurement over the serial interface
approximately every five seconds. The automatic sampling is disabled with a
sample period of 0. The sample period is indicated by,
-
SPErSerial sample period parameter
Press “SET” to choose to set the sample period. The current sample period
value is displayed.
SP=1Current sample period (seconds)
Adjust the value with “UP” or “DOWN” and then use “SET” to set the sample
rate to the displayed value.
SP=60New sample period
8.11.3Duplex Mode
The next parameter is the duplex mode. The duplex mode may be set to full du
plex or half duplex. With full duplex any commands received by the calibrator
-
33
9150 Portable Furnace
User’s Guide
via the serial interface are immediately echoed or transmitted back to the device
of origin. With half duplex the commands are executed but not echoed. The du
plex mode parameter is indicated by,
Press “SET” to access the mode setting
The mode may be changed using “UP” or DOWN” and pressing “SET”.
8.11.4Linefeed
-
dUPLSerial duplex mode parameter
d=FULLCurrent duplex mode setting
d=HALFNew duplex mode setting
The final parameter in the serial interface menu is the linefeed mode. This pa
rameter enables (on) or disables (off) transmission of a linefeed character (LF,
ASCII 10) after transmission of any carriage-return. The linefeed parameter is
indicated by,
LFSerial linefeed parameter
Press “SET” to access the linefeed parameter.
LF=OnCurrent linefeed setting
The mode may be changed using “UP” or “DOWN” and pressing “SET”.
LF=OFFNew linefeed setting
8.12Calibration Parameters
The operator of the 9150 has access to the furnace calibration constants. These
values are set at the factory and must not be altered. The correct values are im
portant to the accuracy and proper and safe operation of the furnace. Access to
these parameters is available to the user only so that in the event the controller
memory fails, the user may restore these values to the factory settings. The user
should have a list of these constants and their settings with the manual.
CAUTION: DO NOT change the values of the furnace calibration con
stants from the factory set values. The correct settings of these parameters
is important to the safety and proper operation of the furnace.
-
-
-
34
The calibration parameters menu is indicated by,
CALCalibration parameters menu
Press “SET” five times to enter the menu. The calibration parameters menu
contains the parameters Hard Cutout, CT1, CE1, CT2, CE2, CT3, and CE3.
8.12.1Hard Cutout
8 Controller Operation
Calibration Parameters
This parameter is the temperature above which the unit shuts down automati
cally. The parameter is set at the factory to approximately 1260°C and cannot
be changed by the user.
8.12.2CT1, CT2, and CT3
The calibration parameters CT1, CT2, and CT3 are the calibration
temperatures.
8.12.3CE1, CE2, and CE3
The calibration parameters CE1, CE2 and CE3 are the calibration errors corresponding to the calibration temperatures.
-
35
9 Digital Communication Interface
9Digital Communication Interface
The furnace is capable of communicatingwithandbeingcontrolledbyother
equipment through the digital serial interface.
With a digital interface the instrument may be connected to a computer or other
equipment. This allows the user to set the set-point temperature, monitor the
temperature, and access any of the other controller functions, all using remote
communications equipment. Communications commands are summarized in
Table 2 on page 40.
9.1Serial Communications
Serial Communications
The calibrator is installed with an RS-232 serial interface that allows serial dig
ital communications over fairly long distances. With the serial interface the user
may access any of the functions, parameters and settings discussed in Section 8
with the exception of the BAUD rate setting.
9.1.1Wiring
The serial communications cable attaches to the calibrator
through the DB-9 connector at
the back of the instrument. Figure 5 shows the pin-out of this
connector and suggested cable
wiring. The serial cable should
be shielded. If the unit is used
in a heavy industrial setting,
the serial cable must be limited
to ONE meter.
9.1.2Setup
Before operation the serial in
terface must first be set up by
programming the BAUD rate
and other configuration param
eters. These parameters are
programmed within the serial
interface menu. The serial in
terface parameters menu is out
lined in Figure 4 on page 22.
To enter the serial parameter
programming mode first press
“EXIT” while pressing “SET”
and release to enter the second
-
-
-
-
-
Figure 5 Serial Cable Wiring Diagram
-
37
9150 Portable Furnace
User’s Guide
ary menu. Press “SET” repeatedly until the display reads “CAL”. Press “UP”
until the serial interface menu is indicated with “SErIAL”. Finally press “SET”
to enter the serial parameter menu. In the serial interface parameters menu are
the BAUD rate, the sample rate, the duplex mode, and the linefeed parameter.
9.1.2.1BAUD Rate
The BAUD rate is the first parameter in the menu. The display prompts with
the BAUD rate parameter by showing “bAUd”. Press “SET” to choose to set
the BAUD rate. The current BAUD rate value is displayed. The BAUD rate of
the 9150 serial communications may be programmed to 300, 600, 1200, 2400,
4800, or 9600 baud. The BAUD rate is preprogrammed to 2400 BAUD. Use
“UP” or “DOWN” to change the BAUD rate value. Press “SET” to set the
BAUD rate to the new value or “EXIT” to abort the operation and skip to the
next parameter in the menu.
9.1.2.2Sample Period
The sample period is the next parameter in the menu and prompted with
“SPEr”. The sample period is the time period in seconds between temperature
measurements transmitted from the serial interface. If the sample rate is set to
5, the instrument transmits the current measurement over the serial interface approximately every five seconds. The automatic sampling is disabled with a
sample period of 0. Press “SET” to choose to set the sample period. Adjust the
period with “UP” or “DOWN” and then use “SET” to set the sample rate to the
displayed value.
38
9.1.2.3Duplex Mode
The next parameter is the duplex mode indicated with “dUPL”. The duplex
mode may be set to half duplex (“HALF”) or full duplex (“FULL”). With full
duplex any commands received by the thermometer via the serial interface are
immediately echoed or transmitted back to the device of origin. With half du
plex the commands are executed but not echoed. The default setting is full du
plex. The mode may be changed using “UP” or “DOWN” and pressing “SET”.
9.1.2.4Linefeed
The final parameter in the serial interface menu is the linefeed mode. This pa
rameter enables (“On”) or disables (“OFF”) transmission of a linefeed charac
ter (LF, ASCII 10) after transmission of any carriage-return. The default setting
is with linefeed on. The mode may be changed using “UP” or “DOWN” and
pressing “SET”.
9.1.3Serial Operation
Once the cable has been attached and the interface set up properly, the control
ler immediately begins transmitting temperature readings at the programmed
rate. The serial communications uses 8 data bits, one stop bit, and no parity.
The set-point and other commands may be sent via the serial interface to set the
-
-
-
-
-
9 Digital Communication Interface
Interface Commands
temperature set-point and view or program the various parameters. The inter
face commands are discussed in Section 9.2. All commands are ASCII charac
ter strings terminated with a carriage-return character (CR, ASCII 13).
9.2Interface Commands
The various commands for accessing the calibrator functions via the digital in
terfaces are listed in this section (see Table 2). These commands are used with
the RS-232 serial interface. The commands are terminated with a carriage-re
turn character. The interface makes no distinction between upper and lower
case letters, hence either may be used. Commands may be abbreviated to the
minimum number of letters which determines a unique command. A command
may be used to either set a parameter or display a parameter depending on
whether or not a value is sent with the command following a “=” character. For
example “s”<CR> returns the current set-point and “s=150.0”<CR> sets the
set-point to 150.0 degrees.
In the following list of commands, characters or data within brackets, “[” and
“]”, are optional for the command. A slash, “/”, denotes alternate characters or
data. Numeric data, denoted by “n”, may be entered in decimal or exponential
notation. Characters are shown in lower case although upper case may be used.
Spaces may be added within command strings and are ignored. Backspace (BS,
ASCII 8) may be used to erase the previous character. A terminating CR is implied with all commands.
-
-
-
-
39
9150 Portable Furnace
User’s Guide
Tabl e 2 Communications Command Summary
Command Description
Display Temperature
Read current set-points[etpoint]sset: 9999.99 {C or F}set: 150.0 C
Set current set-point to ns[etpoint]=ns=450Instrument
Set temperature units:u[nits]=c/f
Set temperature units to Celsiusu[nits]=cu=c
Set temperature units to
Fahrenheit
Read scan functionsc[an]scscan: {ON or OFF}scan: ON
Set scan function:sc[an]=on/of[f]
Turn scan function onsc[an]=onsc=on
Turn scan function offsc[an]=of[f]sc=of
Read scan ratesr[ate]srsrat: 999.99 {C or F}/min srat: 10.0 C/min
Setscanrateto
minute
Secondary Menu
Read proportional band settingpr[op-band]prpb: 999.9pb: 15.9
Set proportional band to
Read heater power
(duty cycle)
Ramp and Soak Menu
Read number of programmable
set-points
Set number of programmable
set-points to
Read programmable set-point
number
Set programmable set-point num
ber
nton
Read program set-point soak
time
Set program set-point soak time
to
n
minutes
Read program scan ratepx
Set program scan ratepx
Read program control modepcpcprog: {OFF or ON}prog: OFF
Set program control mode:pc=g[o]/s[top]/c[ont]
Start programpc=g[o]pc=g
n
degrees per
n
n
n
Command
Format
u[nits]=fu=f
sr[ate]=
n
pr[op-band]=npr=8.830.1 to 100
po[wer]popo: 999.9po: 1
pnpnpn: 9pn: 2
pn=
n
ps
n
-
psn=
n
pt
n
n=n
pt
n
n=n
Command
ExampleReturned
sr=5.1 to 99.9
pn=41 to 8
ps3psn: 9999.99 {C or F}ps1: 50.00 C
ps3=501 to 8, Instru
pt3tin: 999ti1: 5
pt3=50 to 14400
px3srn: 99.9sr3: 11.3
px3=10.1 to 99.9
Returned
Example
Acceptable
Values
Range
CorF
ON or OFF
ment Range
GO or STOP or
CONT
-
40
Tabl e 3 Communications Commands Summary continued
9 Digital Communication Interface
Interface Commands
Command Description
Stop programpc=s[top]pc=s
Continue programpc=c[ont]pc=c
Read program functionpfpfpf: 9pf: 3
Set program function to
Configuration Menu
Operating Parameters Menu
Read high limithlhlhl: 9999hl: 925
Set high limithl=nhl=900100–1200
Read soft cutoutcutocutoc: 9999.9c: 1150.0
Set soft cutout setting:cu[tout]=n
Set soft cut-out to
Read cut-out modecm[ode]cmcm:{xxxx}cm: AUTO
Set cut-out modecm[ode]=r[eset]/a[uto]Reset or Auto
Set cut-out to be reset manuallycm[ode]=r[eset]cm=r
Set cut-out to be reset
automatically
Serial Interface Menu
Read serial sample settingsa[mple]sasa: 9sa: 1
Set serial sampling setting to
seconds
Set serial duplex mode:du[plex]=f[ull]/h[alf]
Set serial duplex mode to fulldu[plex]=f[ull]du=f
Set serial duplex mode to halfdu[plex]=h[alf]du=h
Set serial linefeed mode:lf[eed]=on/of[f]
Set serial linefeed mode to onlf[eed]=onlf=on
Set serial linefeed mode to offlf[eed]=of[f]lf=of
Cal Menu
Read CT
n
calibration parameterct
Set CT
n
calibration parameter tonctn=
n
n
degreescu[tout]=ncu=5000.0 to 1150.0
Command
Format
pf=
n
cm[ode]=a[uto]cm=a
n
sa[mple]=
n
n
n
Command
ExampleReturned
pf=21to4
sa=00 to 4000
ct1ctn: 99.9Cct1: –10.0C
ct1=–10.00 to 12.00
Returned
Example
Acceptable
Values
FULL or HALF
ON or OFF
Read CE
n
calibration parameterce
Set CE
n
calibration parameter toncen=
n
n
ce1cen: 99.9Cce1: -10.1C
ce1=–10–99.9 to 99.9
41
9150 Portable Furnace
User’s Guide
Tabl e 4 Communications Commands Summary continued
Command Description
These commands are only used for factory testing.
Miscellaneous (not on menus)
Read firmware version number*ver[sion]*verver.9999,9.99ver.9150,2.20
Read structure of all commandsh[elp]hlist of commands
Legend:[] Optional Command data
Note:When DUPLEX is set to FULL and a command is sent to READ, the command is returned followed by a
Command
Format
{} Returns either information
n Numeric data supplied by user
9 Numeric data returned to user
x Character data returned to user
carriage return and linefeed. Then the value is returned as indicated in the RETURNED column.
Command
ExampleReturned
Returned
Example
Acceptable
Values
42
10Test Probe Calibration
For optimum accuracy and stability, allow the calibrator to warm up for 10
minutes after power-up and then allow adequate stabilization time after reach
ing the set-point temperature. After completing operation of the calibrator, al
low the well to cool by setting the temperature to 150°C or less for one-half
hour before switching the power off.
10.1Calibrating a Single Probe
Insert the probe to be calibrated into the well of the furnace calibrator. The
probe should fit snugly into the calibrator probe sleeve yet should not be so
tight that it cannot be easily removed. Avoid any dirt or grit that may cause the
probe to jam into the sleeve. Best results are obtained with the probe inserted to
the full depth of the well. Once the probe is inserted into the well, allow ade
quate stabilization time to allow the test probe temperature to settle as de
scribed above. Once the probe has settled to the temperature of the well, it may
be compared to the calibrator display temperature. The display temperature
should be stable to within 1°C degree for best results.
CAUTION: Never introduce any foreign material into the probe hole of
the insert. Fluids etc. can leak into the calibrator causing damage to the
calibrator or binding and damage to your probe.
10 Test Probe Calibration
Calibrating a Single Probe
-
-
-
-
10.2Furnace Characteristics
There is a temperature gradient vertically in the test well. The heater has been
applied to the block in such a way as to compensate for nominal heat losses out
of the top of the furnace. However, actual heat losses will vary with design of
the thermometer probes inserted into the calibrator and the temperature. For
best results, insert probe to full depth of well.
CAUTION: Do not remove inserts and insulators at high temperatures.
Inserts and insulators are the same temperature as the display tempera
ture. Use extreme care when removing hot inserts and insulators.
10.2.1Stabilization and Accuracy
The stabilization time of the calibrator depends on the conditions and tempera
tures involved. Typically the test well is stable to 0.5°C within 20 minutes of
reaching the set-point temperature as indicated by the display. Ultimate stability
is achieved 10 to 20 minutes after reaching the set temperature.
Inserting a cold probe into a well requires another period of stabilizing depend
ing on the magnitude of the disturbance and the required accuracy. For exam
ple, inserting a .25 inch diameter room temperature probe into a sleeve at
-
-
-
-
43
9150 Portable Furnace
User’s Guide
1200°C takes 10 minutes to be within 0.5°C of its settled point and takes 15
minutes to achieve maximum stability.
Speeding up the calibration process can be accomplished by knowing how soon
to make the measurement. It is recommended that typical measurements be
made at the desired temperatures with the desired test probes to establish these
times.
44
11Calibration Procedure
At times the user may want to calibrate the unit to improve the temperature
set-point accuracy. Calibration is done by adjusting the controller probe cali
bration constants CE1, CE2, and CE3 so that the temperature of the unit as
measured with a standard thermocouple agrees more closely with the set-point.
The thermometer used must be able to measure the well temperature with
higher accuracy than the desired accuracy of the unit.
11.1Calibration Points
In calibrating the unit, CE1, CE2, and CE3 are adjusted to minimize the
set-point error at each of three different well temperatures. Any three reason
ably separated temperatures may be used for the calibration. Improved results
can be obtained for shorter ranges when using temperatures that are just within
the most useful operating range of the unit. The farther apart the calibration
temperatures, the larger the calibration range but the calibration error is also
greater over the range. Choosing a range of 150°C to 500°C may allow the calibrator to have a better accuracy of maybe ±2.0°C but outside that range the accuracy may be greater than ±10.0°C.
11 Calibration Procedure
Calibration Points
-
-
11.2Calibration Procedure
1.Choose three set-points to use in the calibration of CE1, CE2, and CE3
parameters. These set-points are generally CT1 = 150°C, CT2 = 675°C
and CT3 = 1200°C but other set-points may be used if desired or necessary. Using these three temperature set-points may result in ±4.0°C
accuracy.
2.If the normal set-points are not used, initialize CT1, CT2, and CT3 to the
desired set points. Where CT1 is the low-set point and CT3 is the high
set-point.
3.Set the unit to the low set-point. When the unit reaches the set-point and
the display is stable, wait 15 minutes or so and take a reading from the
thermometer. Repeat step 3 for the other two set-points recording them
as Tm1, Tm2, and Tm3.
4.Retrieve the original calibration errors from the unit or the Report of
Calibration.
5.Record the previous values for CE1, CE2, and CE3 and calculate new
values for CE1, CE2, and CE3 using the following formula.
Tmn –Tsn +CEn = CEm
Where:
Tmn is the temperature measured, Tsn (CTn) is the set-point tempera
-
45
9150 Portable Furnace
User’s Guide
6.Enter the new CEm value in the calibration parameter menu using either
ture, CEn is the old value for calibration error, and CEm is the new value
for calibration error
the keypad or through the serial port.
46
12Maintenance
The calibration instrument has been designed with the utmost care. Ease
•
of operation and simplicity of maintenance have been a central theme in
the product development. Therefore, with proper care the instrument
should require very little maintenance. Avoid operating the instrument in
an oily, wet, dirty, or dusty environment.
If the outside of the instrument becomes soiled, it may be wiped clean
•
with a damp cloth and mild detergent. Do not use harsh chemicals on the
surface which may damage the paint.
Be sure that the well of the furnace is kept clean and clear of any foreign
•
matter. DO NOT use fluids to clean out the well.
If a hazardous material is split on or inside the equipment, the user is re
•
sponsible for taking the appropriate decontamination steps as outlined by
the national safety council with respect to the material.
• If the mains supply cord becomes damaged, replace it with a cord of the
appropriate gauge wire for the current of the instrument. If there are any
questions, call Hart Scientific Customer Service for more information.
• Before using any cleaning or decontamination method except those recommended by Hart, users should check with Hart Scientific Customer
Service to be sure that the proposed method will not damage the equipment.
• If the instrument is used in a manner not in accordance with the equip ment design, the operation of the furnace may be impaired or safety hazards may arise.
•
The over-temperature cutout should be checked every 6 months to see that
it is working properly.
12 Maintenance
-
47
13 Troubleshooting
13Troubleshooting
This section contains information on troubleshooting, CE Comments, and a
wiring diagram.
13.1Troubleshooting Problems, Possible Causes,
and Solutions
In the event that the instrument appears to function abnormally, this section
may help to find and solve the problem. Several possible problem conditions
are described along with likely causes and solutions. If a problem arises, please
read this section carefully and attempt to understand and solve the problem. If
the problem cannot otherwise be solved, contact Hart Scientific Customer Ser
vice for assistance (1-801-763-1600). Be sure to have the model number and
serial number of your instrument available.
ProblemPossible Causes and Solutions
Incorrect temperature
reading
Incorrect calibration parameters. Find the values for CT1, CT2, CT3, CE1, CE2,
and CE3 on the Report of Calibration that was shipped with the instrument (or
from subsequent calibrations of the instrument). Reprogram the parameters into
the Model 9150 memory (see Section 8.12, Calibration Parameters). Allow the
instrument to stabilize and verify the accuracy of the temperature reading.
-
The instrument heats or
cools too quickly or too
slowly
Memory scrambled. The memory may be scrambled due to a power surge or
other aberration. Initialize the system by performing the Factory Reset
Sequence.
Factory Reset Sequence. Hold the SET and EXIT buttons down at the same
time while powering up the instrument. After the instrument displays
lease the buttons. The display shows
version. After performing the master reset sequence, all of the configuration pa
rameters are reset to their default values. Reprogram the calibration parameters
into the Model 9150 memory (see Section 8.12, Calibration Parameters) and
any other applicable configuration parameters. Allow the instrument to stabilize
and verify the accuracy of the temperature reading.
Incorrect scan and scan rate settings. The scan and scan rate settings may be
set to unwanted values. Check the Scan and Scan Rate settings. The scan may
be off (if the unit seems to be responding too quickly). The scan may be on with
the Scan Rate set low (if unit seems to be responding too slowly).
Incorrect heater switch polarity. The PEM and the heater voltage switch may
not be set for the same voltage. Check both settings and correct as needed.
9150
, and then displays the firmware
-init-
,re
49
-
-
9150 Portable Furnace
User’s Guide
ProblemPossible Causes and Solutions
The display shows any of
the following:
err 2,err 3,err
4
Err 7
Temperature cannot be
set above a certain point
The display flashes
Cut-out
13.2Comments
13.2.1EMC Directive
Equipment manufactured by Hart Scientific has been tested to meet the European Electromagnetic Compatibility Directive (EMC Directive, 89/336/EEC).
The Declaration of Conformity for your instrument lists the specific standards
to which the unit was tested.
err 1
,
Err 5,Err 6
,or
Err 8
Controller problem. The error messages signify the following problems with the
controller.
,
Err 1
,
- a RAM error
Err 2
- a NVRAM error
Err 3
- a RAM error
Err 4
- an ADC setup error
Err 5
- an ADC ready error
Err 6
– a Sensor error
Err 7
– a Heater control error
Err 8
– a Soft cutout error
Initialize the system by performing the Factory Reset Sequence describe
above.
Incorrect High Limit parameter. The High Limit parameter may be set below
1200°C. Check this value as described in Section 8.10, Operating Parameters.
Incorrect Soft Cutout parameter. Wait for the instrument to cool and adjust the
Soft Cutout parameter as described in Section 8.10, Operating Parameters.
50
13.2.2Low Voltage Directive (Safety)
In order to comply with the European Low Voltage Directive (73/23/EEC),
Hart Scientific equipment has been designed to meet the IEC 1010-1 (EN
61010-1) and the IEC 1010-2-010 (EN 61010-2-010) standards.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.