WELCOME TO THE ECHOSWITCH® QUICK START
The EchoSwitch® Quick Start provides basic mounting, setup and use instructions for getting the
EchoSwitch
not addressed here, please refer to the EchoSwitch
®
up and running quickly. If you have a non-standard installation or setup requirement that is
®
Manual or other support documentation located at
flowline.com.
WE DO YOUR LEVEL BEST
Thank you for purchasing EchoSwitch®. The sensor provides integrated LCD and three push-button
configuration. This quick start includes everything you’ll need to get the sensor up and running.
COMPONENTS
Depending on how the sensor part number that was shipped, EchoSwitch® comes with a Viton® gasket for
installation and the Quick Start.
ECHOSWITCH
LU74-5004 & LU74-5064
®
Viton® gasket (2”)
P/N: 200129
LU78-5004 & LU78-5064
ENCLOSURE
While the switch housing is liquid-resistant the EchoSwitch® is not designed to be operational when immersed.
It should be mounted in such a way that the enclosure and transducer do not come into contact with the
application media under normal operational conditions. The enclosure has a flip cover with dual 1/2” NPT
female conduit ports and an internal terminal strip for wiring. Before closing the enclosure, make sure that the
enclosure gasket is properly seated, and that any conduit fittings, cable connectors or plugs are installed
correctly and sealed. Note: If using the Flowline LM90-1001 (liquid tight fitting) on the ½” conduit, the cable
minimum is 0.170” (4.3mm) and the maximum is 0.450” (11.4mm).
| 2QS300282 Rev B
MOUNTING THE ECHOSWITCH®
The sensor should always be mounted perpendicular to the liquid surface using the provided Viton® mounting
gasket. Insure that there are no restrictions or obstacles in the path of the acoustic signal. For further
®
mounting information, please refer to the EchoSwitch
manual at www.flowline.com.
Mounting with a Tank Adapter:
Select a tank adapter fitting, such as the LM52-2890.
Mounting in Riser:
As installations with tall, narrow risers can impede the
acoustic signal. 2" diameter risers should be no taller than
4". Larger diameter risers should be no taller than 12".
For best results, follow a 2:1 Height to Inner Diameter
ratio (example: 8” High to 4” Inner Diameter).
Mounting in Side Mount Bracket:
Use Flowline's LM50-1001 side mount bracket.
LM50-1001 Shown
Note: The Side Mount Bracket (LM50 series) is not designed for use with stand pipes or as a method to
secure stand pipes. There are too few threads to properly hold the sensor and the stand pipe.
QS300282 Rev B 3 |
IMP
O
12345
6
u
A
a
e
u
s
s
a
r
o
h
t
o
b
n
a
a
m
e
s
e
t
e
A
H
C
I
n
e
m
n
s
c
p
o
a
p
)
t
e
s
l
n
w
c
a
d
u
W
e
e
e
a
P
n
e
t
e
n
t
a
h
o
e
p
f
s
d
o
n
a
o
n
e
e
p
a
o
e
t
u
t
e
d
m
e
a
o
a
n
B
n
RTANT MO
UNTING GU
DELINES
) Never m
) Liquid s
) Mount a
) Never m
) Do not o
) Do not i
Mo
nting with
st
nd-pipe m
incr
ase perfor
pipe
is 3”. Larg
red
cer bushing
tank
adapter (S
sen
or (see exa
The
pipe length
to prevent
time
equ
lization hol
sou
ces of subs
unt the se
ould never
least 3” fro
unt the se
struct the
stall in the
Stand-Pi
y be used t
ance in he
r diameter
. Avoid the
x T or S x S
mple below
should run
foam from
within the
antial turbu
sor at an a
nter the de
the side
sor in a va
ensor’s be
enter of a
e:
dampen t
vy vapor.
ipes can b
use of multi
) and conn
.
he measur
ntering the
ensor’s de
ence which
gle.
ad band.
all.
uum.
m width.
ome top ta
rbulence, s
hen moun
used. Th
ple pipe fitti
ct the pipe
ment span
pipe. Cut t
d band. L
might caus
k.
parate sur
ing the sen
pipe shoul
gs when p
o the inside
nd the bott
e bottom e
cate the st
the liquid i
ace foam fr
or in a sta
be attach
ssible. An
slip and us
om of the pi
d of the pi
nd-pipe aw
n the pipe t
m the poin
d-pipe, the
d with a co
ideal moun
a reducer
pe should r
e at 45° an
y from pu
oscillate.
of measur
minimum di
pling or tan
would be t
bushing to
main subm
drill a 1/4”
p outlets a
ment or
meter of th
k adapter a
select a 3”
ttach the
erged at all
pressure
d/or other
e
d
3” x 2”
Reduc
(T x T)
r Bushing
3” (S x
Tank
T)
dapter
Vent
ole
3” PV
Pipe
Stand-
ipe Exam
le
Stand-Pip
Mounting
| 4
QS300282 Rev
WIRING THE ECHOSWITCH®
The following wiring diagram can be used when wiring to the EchoSwitch® relays.
Note: All three relays share the COM terminal. Relay 1 has both a NO and NC terminal while Relays 2 and 3
have just a NO terminal.
Note: – Isolate power to instrument from power to load (pumps, etc.) as much as possible by running power to
the sensor directly from main power source.
The following wiring diagrams can be used for the 4-20 mA output of the EchoSwitch
®
.
Notes on Safety
Where personal safety or significant property damage can occur due to a spill, the installation must have a
redundant backup safety system installed.
Wiring should always be completed by a licensed electrician.
The sensor must be chemically compatible with the application.
Design a fail-safe system for possible sensor and/or power failure.
Never use the sensor in classified hazardous environments.
QS300282 Rev B 5 |
CONFIGURE THE SENSOR
EchoSwitch® can be configured before installation. The switch features non-volatile memory, so the set points
configured before installation will not be lost when the switch is powered down. To start, all you need is the
following information:
Basic Tank Information
HEIGHT – Distance from the transducer face to the
bottom of the tank.
FILL-H – Maximum fill height of the liquid from the
bottom of the tank.
Set Points (Relays):
You will need the measured distance from the bottom of
the tank to each set point.
Pump and Valve operations will have two set points,
one for ON and the other for OFF.
These values will all be in the same unit of
measurement (inches, centimeters, feet or meters) and
will all be measured from the bottom of the tank.
Power:
Provide input power to the EchoSwitch
TOP-LEVEL MENU
®
.
Note: The Height and Fill Height settings
also determine the 4 to 20 mA current
span. The Height setting determines the
4mA position and the Fill-H setting
determines the 20 mA position.
The sensor is configured with the three buttons on the sensor face (UP,
DOWN and SELECT) and the sensor’s LCD. To access the sensor’s Top-level
menu, simply hold down the SELECT button for five seconds. The display
menu will automatically begin to scroll through the TOP-LEVEL MENU.
When the menu scrolls to an item you wish to configure, simply press the
SELECT button to choose that item. The TOP-LEVEL MENU will continue to
scroll through the following (UNITS – TANK – RELAY 1 – RELAY 2 – RELAY 3 – SAFE – (MPLEX) - HELP – RUN), so if you miss your selection, it will
appear again shortly.
To return to the TOP-LEVEL MENU, press SELECT when EXIT appears.
To return to Operational Mode of the sensor, press SELECT when RUN appears in the TOP-LEVEL
MENU.
Note: To speed up the scrolling of the values on the display, hold down the SELECT button while holding
down the UP or DOWN buttons.
| 6QS300282 Rev B
SET UNITS
The EchoSwitch® displays information in the following units: inches, feet, centimeters, meters or percentage.
The value shown on the display represents the amount of liquid in the tank.
1) Press & hold SELECT for 5 seconds to enter TOP-LEVEL
MENU.
2) Select UNITS.
3) Select the type of units by pressing SELECT.
4) Select EXIT to return to the TOP-LEVEL MENU.
5) Select RUN to return to Operational Mode.
SET HEIGHT AND FILL HEIGHT
This setting customizes the reading for your installation. Follow these instructions to set the height and fill
height for your tank:
1) Press & hold SELECT for 5 seconds to
enter TOP-LEVEL MENU.
2) Select TANK.
3) Select HEIGHT.
4) Use the UP and DOWN buttons to set the
height of your tank. To enter value, press
and hold SELECT for 2 seconds and
release. SAVED will display.
5) Select FILL-H.
6) Use the UP and DOWN buttons to set the fill height of your tank. To enter value, press and hold SELECT
for 2 seconds and release. SAVED will display.
7) Select EXIT to return to the TOP-LEVEL MENU.
8) Select RUN to return to Operational Mode.
Note: The Height and Fill Height settings also determine the 4 to 20 mA current span. The Height setting
determines the 4mA position and the Fill-H setting determines the 20 mA position.
QS300282 Rev B 7 |
SET A HIGH ALARM RELAY
A high alarm relay will notify you when the tank level reaches a preset high level:
1) Press and hold SELECT for 5 seconds to enter TOP-LEVEL
MENU.
2) Select RELAY1, RELAY2 or RELAY3.
3) Select ALARM.
4) Select HIGH (SAVED appears).
5) Use the UP and DOWN buttons to set the HIGH (ON) set
point for the relay. To enter value, press and hold SELECT
for 2 seconds and release. SAVED will display.
6) Select HYSTER (Hysteresis).
7) Use the UP and DOWN buttons to set the HYSTER (OFF) set
point. To enter value, press and hold SELECT for 2 seconds
and release. SAVED will display.
8) Select EXIT to return to the TOP-LEVEL MENU.
SET A LOW ALARM RELAY
A low alarm relay will notify you when the tank level reaches a preset low level:
1) Press and hold SELECT for 5 seconds to enter TOP-LEVEL
MENU.
2) Select RELAY1, RELAY2 or RELAY3.
3) Select ALARM.
4) Select LOW (SAVED appears).
5) Use the UP and DOWN buttons to set the LOW (ON) set point
for the relay. To enter value, press and hold SELECT for 2
seconds and release. SAVED will display.
6) Select HYSTER (hysteresis).
7) Use the UP and DOWN buttons to set the HYSTER (OFF) set
point. To enter value, press and hold SELECT for 2 seconds
and release. SAVED will display.
8) Select EXIT to return to the TOP-LEVEL MENU.
| 8QS300282 Rev B
FILL A TANK WITH A PUMP OR VALVE
The relays can also be used to automatically fill a tank when the level inside drops too low. To set the sensor
to automatically fill a tank:
1) Press and hold SELECT for 5 seconds to enter TOPLEVEL MENU.
2) Select RELAY1, RELAY2 or RELAY3.
3) Select PUMP or VALVE (SAVED appears).
4) Select FILL (SAVED appears).
5) Select ON.
6) Use the UP and DOWN buttons to set the ON set point
for the relay. This is the lower of the two set points. To
enter value, press and hold SELECT for 2 seconds and
release. SAVED will display.
7) Select OFF.
8) Use the UP and DOWN buttons to set the OFF set point
for the relay. This is the higher of the two set points. To
enter value, press and hold SELECT for 2 seconds and
release. SAVED will display.
If you wish to add a delay when the pump starts, continue to
step 9. Otherwise, select EXIT to return to the top-level
menu.
9) Select DELAY.
10) Using the UP and DOWN buttons, set the DELAY time in
seconds. This pump delay can range from 0 to 600
seconds. To enter value, press and hold SELECT for 2
seconds and release. SAVED will display.
11) Select EXIT to return to the TOP-LEVEL MENU.
QS300282 Rev B 9 |
EMPTY A TANK WITH A PUMP OR VALVE
The relays can also be used to automatically empty a tank when the level inside gets too high. To set the
sensor to automatically empty a tank:
1) Press and hold SELECT for 5 seconds to enter TOPLEVEL MENU.
2) Select RELAY1, RELAY2 or RELAY3.
3) Select PUMP or VALVE (SAVED appears).
4) Select EMPTY (SAVED appears).
5) Select ON.
6) Use the UP and DOWN buttons to set the ON set point
for the relay. This is the higher of the two set points. To
enter value, press and hold SELECT for 2 seconds and
release. SAVED will display.
7) Select OFF.
8) Use the UP and DOWN buttons to set the OFF set point
for the relay. This is the lower of the two set points. To
enter value, press and hold SELECT for 2 seconds and
release. SAVED will display.
If you wish to add a delay when the pump starts, continue to
step 9. Otherwise, select EXIT to return to the TOP-LEVEL
MENU.
9) Select DELAY.
10) Using the UP and DOWN buttons, set the DELAY time in
seconds. This pump delay can range from 0 to 600
seconds. To enter value, press and hold SELECT for 2
seconds and release. SAVED will display.
11) Select EXIT to return to the TOP-LEVEL MENU.
| 10QS300282 Rev B
SELECT RELAY FAIL SAFETY OUTPUT / LOST
In the event the sensor does not receive an echo, the Fail Safety Output or LOST setting can be set to turn
each relay ON, OFF or HOLD (to last state) to achieve the desired fail-safe condition. During fail-safe, the
display will read LOST.
1) Press and hold SELECT for 5 seconds to enter TOP-LEVEL MENU.
4) Select an output option, such as ON, OFF, or HOLD. To enter value, press and hold SELECT for 2
seconds and release. SAVED will display.
5) Select EXIT to return to the TOP-LEVEL MENU.
POWER OUTAGE
If power to the EchoSwitch® is removed (intentionally or accidentally), the relays will return to the normal state.
Thus, in Relay 1, NC terminal will be closed and NO terminal will be open. Also, the NO terminals in relays 2
and 3 will also be open. Make sure that the de-energized state is the safe state in your system design. The
EchoSwitch® does use non-volatile memory so any power loss will not affect the settings or configuration of
the sensor.
Select Fail-Safe Current Output / LOST: In the event the sensor does not receive an echo, the Fail-Safe
Current Output or LOST setting can be set to output a current of 4mA, 21mA or HOLD (last known value).
During fail-safe, the display will read LOST.
1) Press and hold SELECT for 5 seconds to enter TOP-LEVEL MENU.
2) Select SAFE.
3) Select OUTPUT.
4) Select an output option, such as 4mA, 21mA, or HOLD. To enter value, press and hold SELECT for 2
seconds and release. SAVED will display.
5) Select EXIT to return to the TOP-LEVEL MENU.
TROUBLESHOOTING
If you face any issues not addressed in this Quick Start, please refer to the EchoSwitch® Manual located on
Flowline’s website at www.flowline.com.
Information on how to set a LOW or HIGH alarm, as well as how to FILL or EMPTY a tank with a pump, can
also be found in the EchoSwitch® Manual located on Flowline’s website at www.flowline.com.
QS300282 Rev B 11 |
WARRANTY
Flowline warrants to the original purchaser of its products that such products will be free from defects in
material and workmanship under normal use and service in accordance with instructions furnished by Flowline
for a period of two years from the date of manufacture of such products. Flowline's obligation under this
warranty is solely and exclusively limited to the repair or replacement, at Flowline's option, of the products or
components, which Flowline's examination determines to its satisfaction to be defective in material or
workmanship within the warranty period. Flowline must be notified pursuant to the instructions below of any
claim under this warranty within thirty (30) days of any claimed lack of conformity of the product. Any product
repaired under this warranty will be warranted only for the remainder of the original warranty period. Any
product provided as a replacement under this warranty will be warranted for the full two years from the date of
manufacture.
RETURNS
Products cannot be returned to Flowline without Flowline's prior authorization. To return a product that is
thought to be defective, go to flowline.com, and submit a customer return (MRA) request form and follow the
instructions therein. All warranty and non-warranty product returns to Flowline must be shipped prepaid and
insured. Flowline will not be responsible for any products lost or damaged in shipment.
LIMITATIONS
This warranty does not apply to products which: 1) are beyond the warranty period or are products for which
the original purchaser does not follow the warranty procedures outlined above; 2) have been subjected to
electrical, mechanical or chemical damage due to improper, accidental or negligent use; 3) have been modified
or altered; 4) anyone other than service personnel authorized by Flowline have attempted to repair; 5) have
been involved in accidents or natural disasters; or 6) are damaged during return shipment to Flowline. Flowline
reserves the right to unilaterally waive this warranty and dispose of any product returned to Flowline where: 1)
there is evidence of a potentially hazardous material present with the product; or 2) the product has remained
unclaimed at Flowline for more than 30 days after Flowline has dutifully requested disposition. This warranty
contains the sole express warranty made by Flowline in connection with its products. ALL IMPLIED
WARRANTIES, INCLUDING WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. The remedies of repair or
replacement as stated above are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL
FLOWLINE BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND
INCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY PERSON. THIS WARRANTY
CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO
PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR REPRESENTATIONS ON BEHALF
OF FLOWLINE. This warranty will be interpreted pursuant to the laws of the State of California. If any portion
of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other
provision of this warranty.
For complete product documentation, video training, and technical support, go to flowline.com.
For phone support, call 562-598-3015 from 8am to 5pm PST, Mon - Fri.
(Please make sure you have the Part and Serial number available.)
| 12QS300282 Rev B