EchoPulse LR25 Pulse Radar Level Transmitter
® ®
Product
Application
The general purpose 6.3 GHz. pulse radar level transmitter
provides continuous level measurement up to 114.8’ (35m) with a
4-20 mA signal output, and is congured via its integral push button
display module. The non-contact liquid level sensor is intended for
chemical and petroleum storage or process applications in above
grade metal or reinforced concrete tanks or below grade tanks of
any material. Select this sensor for harsh application conditions
with corrosive or low dielectric media, heavy surface foam or
agitation, higher pressure, steam, condensation or vapor, and
installation in a ange tting. Due to the wider beam angle, special
attention should be given to ensure that the sensor is located with
unobstructed measurement space.
Features
316 L antenna with PTFE inner shield for corrosive media
LR25-0310-40
Shown
Simple conguration via integral push button display module
6.3 GHz. pulse radar is unaffected by most foam and agitation
12” (30cm) dead band enables utilization of the entire tank
LCD displays level in feet or meters with percent of span bar
Optional display mode indicates the echo signal return curve
Auto-temperature compensation for accurate measurement
Fail-safe diagnostics with selectable signal fail-safe outputs
Recognition, storage and rejection of false echo signal returns
Rugged IP67 aluminum enclosure with polycarbonate window
Success
Based upon the type of inow and
system design, not all wastewater
neutralization processes are the
same. Here, a LR25 is mounted
on a 12’ neutralization tank with
agitation, foam and vapor. Its wide
beam, low frequency, 6 GHz. pulse
radar measurement is unaffected by
most process conditions, and is the
right choice for difcult applications
where other level technologies may
not perform reliably.
© 2014 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS301760 REV A

EchoPulse LR25 Pulse Radar Level Transmitter
® ®
Specications
Range:
Frequency:
Accuracy:
Dead band:
Beam angle:
Conguration:
Memory:
Display type:
Display units:
Display bar:
Display graph:
Supply voltage:
Max. consumption:
Signal output:
Signal invert:
Signal fail-safe:
Process temp.:
Temp. comp.:
Storage temp.:
Pressure:
Enclosure rating:
Encl. material:
Encl. window mat.:
Conduit entrance:
Antenna material:
Process mount:
Classication:
Certication:
Compliance:
12” to 114.8’ (30cm to 35m)
6.3 GHz.
± 10mm
12” (30cm)
20º
Push button
Non-volatile
LCD, dot matrix
Feet and meters
Percent of span
Echo signal curve
16-26 VDC
22.5 mA
4-20 mA, two-wire
4-20 mA, 20-4 mA
3.9 mA, 20.5 mA, 22 mA
F: -40º to 266º
C: -40º to 130º
Automatic
F: -40º to 176º
C: -40º to 80º
-14.5 to 580 psi (-1 to 40 bar)
IP67
Aluminum w/silicone gasket
Polycarbonate
(1) 1/2” NPT connector
(1) M20 x 1.5 plug
316 L w/PTFE inner shield
- 40: 4” ange (ANSI)
- 60: 6” ange (ANSI)
General purpose
cTUVus
FCC
CE, CRN, RoHS
Dimensions
3.865"
(98.2mm)
(138.1mm)
5.44"
1.44"
(36.5mm)
D
B
Indicator & Controller
DataLoop™ Indicator DataView™ Controller
LI25 Series LI55 Series
½"
NPT
(83mm)
3.27"
P/N
A
9.0” (228.6mm)
B
0.57” (14.5mm)
C
5.7” (145mm)
D
Antenna / Flange
- 40
4” ANSI
A
C
- 60
6” ANSI
11.0” (279.4mm)
0.63” (16.1mm)
9.7” (247.7mm)
Ordering
(1
Flange size (1)
4 4” ANSI
6 6” ANSI
LR25-0310-40 Shown
© 2014 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS301760 REV A
Notes
To select a radar sensor for distributor purchase,
1)
please go to www.owline.com/LAQ and submit a
level application questionnaire for review. You will
receive a suggested part number and comments
based on your requirements.