Flomatic 89598PO Installation Manual

UNLEADED BACKFLOW PREVENTERS
OPERATION & MAINTENANCE MANUAL
LEAD
High Quality Valves Built to Last...
Table of Contents
Features and Operating Procedures.....1
Installation Guidelines & Procedures.....3
Trouble Shooting Procedures & Guide.....4
Trouble Shooting Solutions.....5
General Service Procedures RPZE/DCVE.....6
Check Valve Service Procedures.....7
Relief Valve Service Procedures.....8
Pressure Vacuum Breaker Service Instructions.....9
Repair Kits for PVB.....10
Repair Kits for RPZE & DCVE.....11
How to Contact & Warranty.....12
OPERATING AND MAINTENANCE PROCEDURES
Reduced Pressure Backflow Preventer
Flomatic has a consistent backflow design that ranges from 1/2"-10", (15mm-250mm). The Flomatic Model RPZE II design is a more compact/economical model and is used when space is limited. The Flomatic Model RPZE is available in size 3/4"-2", (19mm-50mm) with a unleaded bronze body and cover as standard. The 2 1/2"-10", (64mm-250mm) are manufactured with epoxy coated ductile iron for strength.
The Flomatic backflow preventer includes tightly closing resilient seated shut-off valves on each end of the body. The assembly has two independent and internally loaded check valves with a pressure differential relief valve between them.
The pressure drop across the first check valve is approximately 6.0 PSID (41 kPa). The relief valve consists of a hydraulically balanced diaphragm. The high-pressure side of the first check valve is connected to the top of the diaphragm through an access hole in the body of the casting. The low-pressure side is connected to the reduced pressure zone keeping the relief valve closed during normal operation. This is spring loaded to force the relief valve open when the pressure drop across the first check reduces to approximately 2.5 PSID (17 kPa).
NORMAL FLOW CONDITION
High Quality Valves Built to Last...
Flow Direction
LEGEND
Inlet Pressure
Outlet Pressure
Intermediate Zone Pressure
1
SPECIFICATION SHEET RPZE (1/2"-2") (12mm-50mm)
Features
•Unleaded body, test cocks and ball valves
•Ultimate mechanical protection of potable water, against hazards of cross connection contamination.
•Meets all specifications of
AWWA,ASSE and USC Foundation for Cross Connection Control and Hydraulic Research.
•Non-Interchangeable check valve assembly
•Replaceable check valve and removable 316 stainless steel relief valve seats
•Top entry single access cover
•Vertical test cocks
•Low Head loss
•Simple construction, fewer parts
Operation
The backflow preventer shall be a Reduced Pressure Principle and shall include a tightly closing resilient seated shut-off valve on each end of the body. The assembly shall be fitted with four (4) properly located resilient seated test cocks.
The assembly shall have two (2) independent and internally loaded check valve with a pressure differential relief valve located between the check valves.
The backflow preventer shall meet the requirements of the following standards:USC’s FCCC& Hr Manual,
Sec. 10, ASSE 1013 and CSA B64.4. Australia & New Zealand AS/NZS 2845-1
FLOMATIC SPECIFICATIONS
The Reduced Pressure Principle backflow preventer shall protect against backflow by either backpressure or backsiphonage from a cross-connection between potable water systems and substances that are considered to have health hazards.
It shall consist of two (2) mechanically independent, spring loaded, center guided check valves. It shall also have a hydraulically dependent differential pressure relief valve, set in an integral cast unleaded bronze body, with a single access cover. The assembly shall have four (4) vertical test cocks and two shut off valves which are quarter-turn, full-port, resilient seated and ball type.
The seat of each check valve and the relief valve shall be replaceable. The check valves shall be held into place by stainless steel clips and the check valve assemblies shall be non-interchangeable with silicone discs.
The backflow preventer shall be suitable for supply
pressure up to 175 psi (1205kPa) and water tem­peratures from 33 to 180 F.
2
INSTALLATION GUIDELINES & PROCEDURES
Proper installation of the assembly is essential to the correct function of the assembly.
The following instructions are important characteristics of a proper installation.
1. Before installing any of Flomatic's backflow
assemblies, flush the lines thoroughly to remove all debris, chips and other foreign objects. Failure to do so may make any of these assemblies inoperable.
2. Allow sufficient clearance around the installed assembly to conduct testing (minimum 18" (450mm) around). The assembly should be installed in a horizontal position with a minimal clearance of 12" (300mm) between the relief valve discharge port and the flood level. The maximum height should be 30" (762mm) to allow for testing at a reasonable height.
3. Flomatic's RPZE assemblies are approved by
national approval agencies and are to be installed in a horizontal position. Approval agencies do not recommend installation of a RPZE in a pit. Flooding of the pit can result in a cross connection contamination. If local codes permit installation of a RPZE in a pit, adequate drainage must be provided to prevent the pit from flooding.
4. Placement of the assembly should be planned
where water discharge from the relief valve will not be objectionable or cause property damage.
5. Insure that the water supply pressure does not
exceed the manufacturer’s maximum water pressure or temperature. The unit should also be protected against thermal water expansion, extreme backpressure and/or water hammer.
6. The most common cause of field problems for RPZE’s is dirt or debris in the system. At the time of installation dirt or debris will become trapped in the first check seating area, resulting in a continuous discharge from the relief valve in a static or backflow condition.
THEREFORE THE SYSTEM SHOULD ALWAYS BE FLUSHED BEFORE THE ASSEMBLY IS INSTALLED.
7. To effectively flush the systems after the assembly has been installed, remove the internal components and open the inlet shutoff valve to flush all debris from the line and assembly. If debris in the water continues to cause problems, a strainer should be installed upstream of the assembly.
3
Loading...
+ 11 hidden pages