FloAire INDIRECT FIRED BENT TUBE MODULE User Manual

FOR YOUR SAFETY
Modular
In-Direct Fired
Heater
s and Inserts
Installation, Operation, and Maintenance Manual
Modular
In-
Direct
Fired
Heater
In-
Direct Fired Module
Save these inst
ructions
R
ECEIVING AND INSPECTION
WARNING!!
FOR YOUR SAFETY
In-Direct Fired Furnace
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open flames.
4. Immediately call your gas supplier.
Upon receiving unit, check for any interior and exterior damage, and if found, report it immediately to the carrier. Also check that all accessory items are accounted for and are damage free. Turn the blower wheel by hand to verify free rotation and check the damper (if supplied) for free operation.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment. ALWAYS disconnect power and gas prior to working on heater.
. This document is the property of the owner of this equipment and is required for future maintenance. Leave this document with the owner when installation or service is complete.
A0016988
January, 2014 Rev. 21
TABLE OF CONTENTS
WARRANTY ...................................................................................................................................................................................... 3
INSTALLATION ................................................................................................................................................................................. 4
Mechanical ................................................................................................................................................................................... 4
Site Preparation ...................................................................................................................................................................... 4
Assembly ................................................................................................................................................................................ 4
Curb and Ductwork ................................................................................................................................................................. 4
Recommended Supply Ductwork Sizes ................................................................................................................................... 5
Condensation Drain ................................................................................................................................................................ 5
Roof Mount Installation............................................................................................................................................................ 6
Installation with Exhaust Fan ................................................................................................................................................... 6
Indirect Fired Module Installation ............................................................................................................................................. 7
Indoor (INLINE) Installation ..................................................................................................................................................... 7
Indoor Flue Venting ................................................................................................................................................................. 8
Gas ............................................................................................................................................................................................ 11
Electrical .................................................................................................................................................................................... 12
PSC (Permanent Split Capacitor) Motor Speed Control ......................................................................................................... 13
ECM (Electronically Controlled Motor) Speed Control ........................................................................................................... 13
Electric Cabinet Heater ......................................................................................................................................................... 14
Motorized Intake Damper ...................................................................................................................................................... 14
Remote Control Panel ........................................................................................................................................................... 14
Fan to Building Wiring Connection ........................................................................................................................................ 15
OPERATION ................................................................................................................................................................................... 15
Start Up ...................................................................................................................................................................................... 15
Special Tools Required ......................................................................................................................................................... 15
Start Up Procedure ............................................................................................................................................................... 15
Forced High Fire Light-Off (Modulating Stages) .................................................................................................................... 16
High-Fire and Low-Fire Burner Adjustment............................................................................................................................ 16
Gas Pressure Adjustment Reference Information (Natural Gas) ............................................................................................ 18
Furnace Start-Up Summary................................................................................................................................................... 19
Final Start-Up Procedure ....................................................................................................................................................... 20
Pulley Adjustment ................................................................................................................................................................. 21
Pulley Alignment/Proper Belt Tension ................................................................................................................................... 21
Pulley Combination Chart ...................................................................................................................................................... 22
Sequence of Operation ............................................................................................................................................................... 23
Modulating Gas System ........................................................................................................................................................ 23
Flame Safety Control ............................................................................................................................................................ 24
Modulating Stage Sequence ................................................................................................................................................. 24
FVFAB and High Fire Start .................................................................................................................................................... 25
Re-Circulating Control Options ................................................................................................................................................... 25
Manual Positioning Control (Potentiometer) .......................................................................................................................... 25
Two Position Control ............................................................................................................................................................. 25
Static Pressure Control (Photohelic) ...................................................................................................................................... 26
A306 Outdoor Sensor ........................................................................................................................................................... 27
Building Signal Damper Control ............................................................................................................................................ 27
Operation Summary ................................................................................................................................................................... 27
Optional Remote Panel Circuit .............................................................................................................................................. 28
Components.......................................................................................................................................................................... 29
Remote Panel Option ............................................................................................................................................................ 31
Modulating Furnace Thermostat Dip Switch Settings ............................................................................................................ 32
FVFAB Settings .................................................................................................................................................................... 32
High Altitude Orifice Sizing .................................................................................................................................................... 33
Troubleshooting.......................................................................................................................................................................... 34
Airflow Troubleshooting Chart ............................................................................................................................................... 34
Furnace Troubleshooting Chart ............................................................................................................................................. 35
Remote Panel Troubleshooting Chart ................................................................................................................................... 36
Troubleshooting Flow-charts ................................................................................................................................................. 37
MAINTENANCE .............................................................................................................................................................................. 39
General Maintenance ................................................................................................................................................................. 39
2 weeks after startup .................................................................................................................................................................. 40
Every 3 months .......................................................................................................................................................................... 40
Yearly ......................................................................................................................................................................................... 41
Start-Up and Maintenance Documentation ................................................................................................................................. 42
Job Information ..................................................................................................................................................................... 42
Heater Information ................................................................................................................................................................ 42
Maintenance Record ............................................................................................................................................................. 42
Factory Service Department .................................................................................................................................................. 42
2
WARRANTY
This equipment is warranted to be free from defects in materials and workmanship, under normal use and service, for a period of 12 months from date of shipment. All Heat Exchangers have a standard 10 year Pro-rated manufacturer-backed warranty. This warranty shall not apply if:
1. The equipment is not installed by a qualified installer per the MANUFACTURER’S installation instructions shipped with the product,
2. The equipment is not installed in accordance with federal, state and local codes and regulations,
3. The equipment is misused or neglected,
4. The equipment is not operated within its published capacity,
5. The invoice is not paid within the terms of the sales agreement.
The MANUFACTURER shall not be liable for incidental and consequential losses and damages potentially attributable to malfunctioning equipment. Should any part of the equipment prove to be defective in material or workmanship within the 12-month warranty period, upon examination by the MANUFACTURER, such part will be repaired or replaced by MANUFACTURER at no charge. The BUYER shall pay all labor costs incurred in connection with such repair or replacement. Equipment shall not be returned without MANUFACTURER’S prior authorization and all returned equipment shall be shipped by the BUYER, freight prepaid to a destination determined by the MANUFACTURER.
3
INSTALLATION
CLEARANCES
IMPORTANT
It is imperative that this unit is installed and operated with the designed airflow, gas, and electrical supply in accordance with this manual. If there are any questions about any items, please call the service department at 1-866-784-6900 for warranty and technical support issues.
Mechanical
WARNING: DO NOT RAISE VENTILATOR BY THE INTAKE HOOD, BLOWER OR MOTOR SHAFT, OR BEARINGS – USE LIFTING LUGS PROVIDED OR A SLING
Site Preparation
1. Provide clearance around installation site to safely rig and lift equipment into its final position. Supports must adequately support equipment. Refer to manufacturer’s estimated weights.
2. Consider general service and installation space when locating unit.
3. Locate unit close to the space it will serve to reduce long, twisted duct runs.
4. Do not allow air intake to face prevailing winds. Support unit above ground or at roof level high enough to prevent precipitation from being drawn into its inlet. The inlet must also be located at least 10 feet away from any exhaust vents. The heater inlet shall be located in accordance with the applicable building code provisions for ventilation air.
Assembly
Intakes and curbs are shipped unassembled to heater module. Upon unit arrival, use the following procedure to assemble the intake to the heater.
1. Apply silicone or weather-proof gasket on the back side of the flanges of the intake hood or v-bank intake.
2. Screw the flanges of the intake hood or v-bank to the unit with the supplied sheet metal screws. Place caulk on the outside of the screws to prevent water leaks. If the unit is a modular unit with a v-bank or evaporative cooler section, the v-bank or evaporative cooler will bolt to the heater with the bolts provided.
The top, back, and front surfaces of this heater may not be installed less than 6” from combustible materials. The heater base may be installed on combustible surfaces. Allow 24” minimum service clearance on both sides of this heater.
To prevent premature heat exchanger failure, do not locate any gas fired unit in areas where chlorinated, halogenated, or acid vapors are present in the atmosphere.
Curb and Ductwork
This fan was specified for a specific CFM and static pressure. The ductwork attached to this unit will significantly affect the airflow performance. Flexible ductwork
4
and square elbows should not be used. Also, transitions and turns in ductwork near the fan outlet will cause system effect and will drastically increase the static pressure and reduce airflow. The chart below shows the minimum fan outlet duct sizes and straight lengths recommended for optimal fan performance. Follow SMACNA
guides and recommendations for the remaining duct run. Fans designed for rooftop
installation should be installed on a prefabricated or factory built roof curb. Follow curb manufacturer’s instructions for proper curb installation. The unit should be installed on a curb and/or rail elevated not less than 20” above any surface. Be sure duct connection and fan outlet are properly aligned and sealed. Secure fan to curb through vertical portion of the ventilator base assembly flange using a minimum of eight (8) lug screws, anchor bolts, or other suitable fasteners (not furnished). Shims may be required depending upon curb installation and roofing material. Check all fasteners for tightness. The diagrams below show different mechanical installation configurations.
Recommended Supply Ductwork Sizes
Blower Size Duct Size Straight Duct Length
10 14 x 14 48 in. 12 16 x 16 54 in. 15 20 x 20 72 in. 18 24 x 24 86 in. 20 26 x 26 108 in. 25 32 x 32 168 in.
Condensation Drain
In some applications, condensation can form in the flue collection box, especially when furnaces are located downstream of cooling coils. In the event that condensation occurs in the flue collection boxes, there are barbed fittings in the bottom of the flue collection boxes to drain condensation out of the boxes. Each burner in the unit is provided with a burner drain pan or a condensation drain assembly located underneath this fitting for the condensation to collect. If the drain assembly is installed on the heater, it will have ¼” quick seals located below the front access door for field piping or drainage onto the roof. Consult your local code as to the proper drainage regulations of the condensation. The internal drain piping is heated to prevent freezing. If drains are field piped, ensure that the field piping is piped in a fashion to prevent the condensation from freezing. Do not plug the holes under any circumstance as it will cause the burners to overflow.
In the event the IBT does not have condensation drains and condensation exceeds the pan capacity, IBT condensation drain kits can be ordered for installation in the field.
The part names for the kits are:
“IBT Condensation Kit-1” Single Furnace IBT “IBT Condensation Kit-2” Double Furnace IBT “IBT Condensation Kit-3” Triple Furnace IBT “IBT Condensation Kit-4” Quadruple Furnace IBT
IBT Condensation Drain Assembly ¼” NPT Condensation Drain Connections
5
Roof Mount Installation
Installation with Exhaust Fan
6
Indirect Fired Module Installation
Indoor (INLINE) Installation
7
Indoor Flue Venting
IMPORTANT
fan.
IMPORTANT
fan.
Indoor gas fired heating equipment must be vented. Do not operate un­vented. Gas fired heating equipment which has been improperly vented,
or which experiences a blocked vent condition may emit flue gases into heated spaces.
General Venting Guidelines
1. Installation of venting must conform with local building codes, or in the absence of local codes, follow the National Fuel Gas Code.
2. On Units with multiple furnaces, each furnace must be ducted to the outside using its own isolated duct run. Ducts used on each single furnace must Not be Connected together in any fashion. Failure to adhere to this may result in a build-up of Carbon-Monoxide in the space when the furnace is operating with less than all of its furnaces powered.
3. Do not use a vent pipe smaller than the size of the outlet on the heater.
4. Install with a minimum upward slope from unit of ¼ inch per foot and suspend from overhead structure at points no greater than 3 feet apart. For best venting, put as much vertical vent as close to the unit as possible.
5. Fasten individual lengths of vent together with at least three corrosion resistant sheet metal screws.
6. Vent pipes should be fitted with a tee with a drip leg and clean out tap at the low point in the vent run. This should be inspected and cleaned out periodically during the heating season.
7. Do NOT use dampers or other devices in the vent or combustion air pipes.
8. Use a vent terminal to reduce downdrafts and moisture in the vent line.
9. A vent system that terminates vertically but has a horizontal run that exceeds 75% of the vertical rise is considered horizontal.
10. Pressures in Category III venting systems are positive and therefore care must be taken to prevent flue products from entering the heated space. Use only venting materials and components that are UL listed and approved for Category III venting systems.
11. Vent pipes must all be sealed and gastight.
Furnace Only Modules must be installed in a positive pressure airstream. Do not install in a duct on the suction side of a
Vertically Vented Furnaces
1. Use single wall or double wall (Type B) vent pipe of a diameter listed in the following table for the appropriate model.
2. Maximize the height of the vertical run of vent pipe. A minimum of five (5) feet (1.5m) of vertical pipe is required. The top of the vent pipe must extend at least two (2) feet (0.61m) above the highest point on the roof. Use Listed Type B vent for external runs. An approved weatherproof vent cap must be installed on the vent termination.
3. Horizontal runs should be pitched upward ¼ in. per foot (21mm/m) and should be supported at three (3) foot (1m) maximum intervals.
4. Design vent pipe runs to minimize the use of elbows. Each 90 elbow is equivalent to five (5) feet (1.5m) of straight vent pipe.
5. Vent pipe should not be run through unheated spaces. If such runs cannot be avoided, insulate the vent pipe to prevent condensation. Insulation should be a minimum of ½ in. (12.7mm) thick foil faced fiberglass minimum of 1½ # density.
6. Dampers must not be used in vent piping runs, as spillage of flue gases into the occupied space could result.
7. Vent connectors serving Category 1 heaters must not be connected into any portion of a mechanical draft system operating under positive pressure.
National Fuel Gas Code Venting Pipe requirement
75,000-149,999 Use 5-inch pipe 150,000-400,000 Use 6-inch pipe
8
Furnace Only Modules must be installed in a positive pressure airstream. Do not install in a duct on the suction side of a
Vertical Venting
Horizontally Vented Furnaces – Category III
Horizontal vent systems terminate horizontally (sideways)
WARNING: Do not use Type B vent within a building on horizontally vented units.
1. All vent pipe joints must be sealed to prevent leakage. Follow the instructions provided with the approved venting materials.
2. The total equivalent length of vent pipe must not exceed 50 ft. (15.25m). Equivalent length is the total length of straight sections, plus 5 ft. (1.52m) for each 90 elbow and 2.5 ft. (0.76m) for each 45 elbow.
3. The vent system must also be installed to prevent collection of condensate. Horizontal runs should be pitched upward ¼ in. per foot (21mm/m) and should be supported at three (3) foot (1m) maximum intervals.
4. Insulate vent pipe exposed to cold air or routed through unheated areas. Insulate vent pipe runs longer than 10 ft. (3m). Insulation should be a minimum of ½ in. (12mm) thick foil faced fiberglass of 1 ½ # density. Maintain 6 in. (152mm) clearance between vent pipe and combustible materials.
5. An approved Breidert Type L, Field Starkap or equivalent vent cap must be provided. Vent cap inlet diameter must be the same as the vent pipe diameter.
6. The vent terminal must be at least 12 in. (305mm) from the exterior wall that it passes through to prevent degradation of building material by flue gases.
7. The vent terminal must be located at least 12 in. (305mm) above grade, or in snow areas, at least 3 ft. (1m) above snow line to prevent blockage.
8. The vent terminal must be installed with a minimum horizontal clearance of 4 ft. (1.2m) from electric meters, gas meters, regulators or relief equipment.
9
10
Through-the-wall vents shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard. Provide vent termination clearances to building or structure features as follows:
Structure Minimum Clearance
Door, Window or gravity inlet 4 ft. (1.2 m) below
4 ft. (1.2 m) horizontally 1 ft. (305 mm) above
Forced air inlet within 10 ft. (3m) 3 ft. (.91 m) above
Adjoining building or parapet 6 ft. (1.8 m)
Adjacent public walkways 7 ft. (2.1 m) above grade
Horizontal Venting
EACH APPLIANCE MUST HAVE ITS OWN INDIVIDUAL VENT PIPE AND TERMINAL. Do not connect
vent system from horizontally vented units to other vent systems or a chimney
11
Gas
Installation of gas piping must conform with local building codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (NFPA 54) – latest edition. In Canada, installation must be in accordance with CAN/CGA-B149.1 for natural gas units and CAN/CGA-B149.2 for propane units.
WARNING: INLET GAS PRESSURE MUST NOT EXCEED 14 IN. W.C. SEE UNIT RATING PLATE FOR PROPER GAS SUPPLY PRESSURE AND GAS TYPE.
1. Always disconnect power
before working on or near a heater. Lock and tag the disconnect switch or breaker to prevent accidental power up.
2. Piping to the unit should
conform with local and national requirements for type and volume of gas handled, and pressure drop allowed in the line. Refer to the Gas Engineer’s Handbook for gas line capacities.
3. The incoming pipe near the
heater should be sized to match the connection on the outside of the unit. Unit inlet sizes are shown in the table to the right. Avoid multiple taps in the gas supply so the unit has a steady supply of gas at all times.
4. Install a ground joint union with brass seat and a manual shut-off valve external to the unit casing,
as shown below, adjacent to the unit for emergency shut-off and easy servicing of controls.
5. Provide a sediment trap, as shown below, before each unit and where low spots in the pipe line
cannot be avoided.
6. Blow out the gas line to remove debris before making connections. Purge line to remove air
before attempting to start unit. Purging of air from gas lines should be performed as described in ANSI Z223.1-latest edition “National Fuel Gas Code”, or in Canada in CAN/CGA-B149.
7. All field gas piping must be
pressure/leak tested prior to unit operation. Use a non­corrosive bubble forming solution or equivalent for leak testing. The heater and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of ½ psi. The heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi.
Gas Pressure Table
Gas Pressure Type Gas Pressure
Inlet Pressure - Natural Gas 7 in. w.c. – 14 in. w.c.
Inlet Pressure - Propane 11 in. w.c. – 14 in. w.c.
Max. Manifold Pressure - Natural Gas 3.5 in. w.c. maximum
Max. Manifold Pressure - Propane 10 in. w.c. maximum
Min. Manifold Pressure - Natural Gas 0.15 in. w.c. minimum
Min. Manifold Pressure - Propane 0.75 in. w.c. minimum
12
8. This unit requires a constant 7 in. w.c. minimum natural gas supply, (LP should be 11 in. w.c.
WARNING!!
NOTICE
minimum) when the unit is operating at maximum gas flow. If the gas supply exceeds 14 in. w.c. it will damage the internal valve
components, and if it is below 7 in. w.c., the heater may not perform to specifications.
Refer to the heater rating plate for determining the minimum gas supply pressure for obtaining the maximum gas capacity for which this heater is specified.
Gas Connection Diagram
Electrical
Before connecting power to the heater, read and understand this entire section of this document. As-built wiring diagrams are furnished with each fan by the factory, and are attached to the door of the unit.
Electrical wiring and connections should be done in accordance with local ordinances and the National Electric Code, ANSI/NFPA70. Be sure the voltage and phase of the power supply and the wire amperage capacity is in accordance with the motor nameplate. For additional safety information refer to AMCA publication 410-96, Recommended Safety Practices for Users and
Installers of Industrial and Commercial Fans.
Disconnect power before installing or servicing fan. High voltage electrical input is needed for this equipment. This work should be performed by a qualified electrician.
1. Always disconnect power before working on or near a
heater. Lock and tag the disconnect switch or breaker to prevent accidental power up.
2. An electrical drop containing the motor power wiring is
shipped with every fan. The electrical drop should be brought through one of the conduit openings located in the base of the unit, run through the curb, and connected to a junction box inside the building.
3. A dedicated branch circuit should supply the motor
circuit with short circuit protection according to the National Electric Code. This dedicated branch should be run to the junction box mentioned above and connected as shown in a following illustration labeled “Fan to Building Wiring Connection”.
4. Make certain that the power
source is compatible with the requirements of your equipment. The heater nameplate identifies
Copper Wire Ampacity
Wire Size AWG Maximum Amps
14 20 12 25 10 30
8 40 6 55
13
the proper phase and voltage of the motor.
5. Units shipped with an optional remote panel have two electrical circuit drops. It is important to
run the motor wires in a separate conduit from the remote control wiring. The DC wires from the unit temperature controller, located in the control drop, should either be shielded cable or be run in a separate conduit.
6. Before connecting heater to the building power source, verify power line wiring is de-energized.
7. Secure the power cables to prevent contact with sharp objects.
8. Do not kink power cable and never allow the cable to come in contact with oil, grease, hot
surfaces or chemicals.
9. Before powering up the heater, check fan wheel for free rotation and make sure that the interior of
the heater is free of loose debris or shipping materials.
10. If any of the original wire supplied with the heater must be replaced, it must be replaced with type
TW wire or equivalent.
PSC (Permanent Split Capacitor) Motor Speed Control
Some single phase direct drive fans contain speed controls that regulate the amount of voltage going to the motor. Specific PSC motors must be used in conjunction with speed controls. The speed control has a knob with an off position, and high to low range. At high speed, the speed control allows all of the line voltage to pass right to the motor.
A minimum speed adjustment is provided to allow independent control of the minimum speed setting. Minimum speed adjustment ensures motor runs with sufficient torque to prevent stalling. To adjust this:
1) Motor must be in actual operating conditions to achieve proper speed
adjustment. Motor will not slow down unless proper load is applied.
2) Turn main control knob to lowest speed position.
3) Locate and adjust minimum speed setting and adjust with small screw driver. This can be found
under the speed control faceplate. (rotate clockwise to decrease minimum speed; counter­clockwise to increase minimum speed).
4) Motor will now operate from this preset minimum speed to full speed.
The lowest minimum voltage that may be applied to these motors is 65VAC. Running lower voltages to the motor can cause premature failure and overheating problems.
ECM (Electronically Controlled Motor) Speed Control
ECM motors and control allows accurate manual adjustment of fan speed. The benefit of ECM motors is exceptional efficiency, performance, and motor life.
The control used with ECM motors features a 4 digit LED numerical display. The blue knob on the control allows the user to set the flow index with a screwdriver. Twenty seconds later, the display shows the motor RPM. Then, the display periodically alternates between the flow index and motor RPM. The flow index has a range of 0 to 100% and is typically linear with motor RPM.
The ECM control requires a 24 VAC input and can locally turn the motor on and off. The motor can be adjusted between 300 RPM and maximum speed with this control.
NOTE: To adjust the speed of 3 phase direct drive motors, a variable frequency drive is required.
14
Electric Cabinet Heater
On units shipped with an optional electric cabinet heater, ensure that the heater is wired to a separate 120V, 15 amp input, the thermostat sensing bulb is mounted correctly in the control vestibule where the heater is located, and the thermostat set to 0 Degrees Fahrenheit.
Motorized Intake Damper
On units shipped with the optional motorized intake damper, a power transformer is supplied with the unit if the main incoming voltage is greater than 120V. The damper motor is automatically energized when the main disconnect switch is in the ON position. No external wiring to the damper motor is required.
Remote Control Panel
On units shipped with the optional remote control panel, an electrical drop containing the panel wiring is provided with the heater. There is a terminal strip inside the remote panel that matches the terminals in the heater unit. The remote panel should be wired as shown below.
Loading...
+ 30 hidden pages