Flint & Walling Constant Pressure Pumping Stations User Manual

Operating Instructions & Parts Manual
!
!
!
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
FW1442
0313
Supersedes
0411
Pump Station Add-on Kit
KEY FEATURES OF THE ARTESIAN DRIVE PUMP STATION ADD-ON KIT:
The duplex kit is designed as an add on to the Single pump Artesian Drive pump station to increase the capacity of the pumping station without adding an additional drive. The duplex kit, must match the HP of the pump station that it is to be added to for proper operation. When added to the pump station, the single phase pump will turn on when the drive is running the three phase pump at full speed and still cannot reach the system pressure set point. When the single phase pump is running, depending upon demand, the drive may shut off the 3-phase pump. After the single phase pump has started and demand decreases, when the pressure increase to 5 PSI above the set point the drive will start up the three phase pump again and then shut down the single phase pump. To reduce the chance of damage to the single phase pump and motor that can occur with short cycling, the single phase motor will remain running for a minimum of 1 minute even if the system pressure rises above the set point. Once the single phase motor turns off, it will also remain off for one minute before it will turn back on even if the pres­sure drops below the system set point.
If plumbing cannot withstand maximum pump pressure plus incoming pressure, a pressure control valve shuld be installed after the check valve on the single phase pump and set 10 psi above the system pressure set point on the drive. This will prevent any damage to the system plumbing in the event a sudden drop in water demand creates maximum deadhead pressure.
Only shaded areas included in package
Figure 1
General Safety Information
Carefully read and follow all safety instructions in this manual and on pump. Keep safety labels in
good condition. Replace missing or damaged safety labels.
This is a SAFETY ALERT SYMBOL. When you see this symbol on the pump or in the manual, look for one of the following signal words and be alert to the potential for personal injury or property damage.
Warns of hazards that WILL cause serious personal injury, death or major property damage if ignored.
Warns of hazards that CAN cause
serious personal injury or death, if ignored.
Warns of hazards that MAY cause minor personal injury, product or property damage if ignored.
IMPORTANT: Indicates factors concerned with operation, installation, assembly or maintenance which could result in damage to the machine or equipment if ignored.
NOTE: Indicates special instructions which are important but are not related to hazards.
Read these warnings and instructions carefully. Failure to follow could result in serious bodily injury and/or property damage.
Electrical installations shall be in accordance with National Electric Code (NEC) and all applicable local codes and ordinances. A licensed electrician should
1 (FW1442)
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
023507 B
perform installation.
!
!
!
!
!
!
!
!
Be sure system is connected to a circuit equipped with a fuse or circuit breaker of the correct rating.
Always disconnect power source before performing any work on or near the controller, motor or its connected load. If the power disconnect point is out-of-sight, lock it
in the open position and/or tag it to prevent unexpected application of power. Failure to do so could result in fatal electrical shock or bodily injury.
DO NOT handle pump with wet hands or when standing in water as fatal electrical shock could occur. Disconnect main power supply before handling system for any reason.
Protect the power cable from coming in contact with sharp objects, oil, grease, hot surfaces or chemicals. DO NOT kink the power cable. If damaged replace immediately.
NEVER leave the control box, fused disconnect switch, or covers open (either partially or completely) when not being worked on by a competent electrician or repairman.
Always use caution when operating electrical controls in damp areas. If possible, avoid all contact with electrical equipment during thunderstorms or extreme damp conditions.
Install all electrical equipment in protected area to prevent mechanical damage which could produce serious electrical shock and/or equipment failure.
Single Phase Motor Data: Chart A
MODEL HP
C22231H 3
C22251H 5 230V 230V - 27.4 H
C22271H 7-½ 230V 230V - 34.5 H
Minimum Wire Size Charge (Gauge): Chart B
HP Volts Phase
3 115/230 1 8/12 8/12 4/10 4/10 2/8 40/20
5 230 1 8 8 8 8 6 40
7.5 230 1 6 6 6 6 4 50
IMPORTANT: Wire charts are for reference only. Consult local and state codes for approved wire sizes.
MOTOR
VOLTAGE
115/208-
230V
Distance in Feet From Motor To Service Panel
0-50ft 50-100ft 100-150ft 150-200ft 200-300ft
Connected Motor
DO NOT use this system to pump flammable liquids such as gasoline, fuel oil, kerosene, etc. Failure to follow the above warning could result in property damage and/or personal injury.
This product contains chemicals known to the State of California to cause
cancer and birth defects or other reproductive harm.
Do not pump water above 140 degrees Fahrenheit.
This unit not tested for use in
swimming pool areas.
Before Getting Started
may result from failure to connect the ground terminal to the motor, Artesian Drive controller, metal plumbing, or other metal near the motor or cable, using wire no smaller than motor cable wires. To minimize risk of electrical shock, disconnect power before working on or around the Artesian Drive system. CAPACITORS INSIDE THE ARTESIAN DRIVE CONTROLLER CAN STILL HOLD LETHAL VOLTAGE EVEN AFTER POWER HAS BEEN DISCONNECTED. ALLOW 10 MINUTES FOR DANGEROUS INTERNAL VOLTAGE TO DISCHARGE BEFORE REMOVING ARTESIAN DRIVE COVER.
swimming areas.
Factory
Voltage
230V 32.2 16.1 G
Wire Size
Serious or fatal electrical shock
Do not use motor or system in
Service Factor
Motor Amps
115V 230V
Code
Letter
Breaker Size
(Amps)
Instructions:
ACTIVATE DUPLEX OPTION IN DRIVE:
When the Artesian drive pump station leaves the fac­tory, the default setting it to have the Duplex Mode turned off. To change settings:
1. Press & release M button to display flashing num­ber on left hand side of display (i.e. 01). Using v & ^ buttons scroll until you reach 10 flashing on left hand side.
2. Press & release M button and then Press & release & ^ buttons to scroll display to show L3 on right hand side.
3. Press & release M button and use v & ^ buttons to scroll until you reach 70 flashing on left hand side.
4. Press & release M button and CodE flashes on the right hand side. Press & release ^ until Co 3 is dis­played.
5. Press & release M button. Using v & ^ scroll the value between OFF to ON.
6. Press & release M button to return to having 61 on left of screen flashing. Using v & ^ buttons scroll to 10 flashing on left hand side.
7. Press & release M button then press & release ^ but­ton until LoC is displayed. Press & release M button twice to return to standard screen.
8. Turn off power to drive & skid system in prepara­tion for mechanical & electrical installation of the duplex kit.
MECHANICAL INSTALLATION:
• Mount pump support to pump station skid strad­dling existing pump as shown in Figure 1 using ¼” bolts, washers & lock washers.
• Mount starter box to side of the pump support with ¼” bolts, nuts, washers & lock washers.
• With help set single phase pump on top of pump support and secure with 3/8” bolts, nuts, washers & lock washers.
• Using Teflon tape or pipe dope on the threads, install a 2” union on discharge of pump and screw check valve into the union tightening with a wrench 1-2 turns past hand tight to prevent leaks.
• Note: For suction lift applications, a service T with a threaded in priming plug should be installed on the intake pipe of the pump for priming purposes. If possible for suction lift applications, it is recom­mended to use a separate drop pipe (not shown in illustrations) into the water source to allow for easier priming.
• Plumb with desired 2” piping (not supplied) as show in Figure 1 from check vale and “T” into discharge manifold.
Because of the 1 minute minimum
run time of the single phase pump, the system plumbing & fixtures must be able to withstand full deadhead system pressure (maximum pump pressure + incoming PSI). If the plumbing system cannot handle deadhead pressure, a pressure control valve needs to be installed after the check valve installed on the single phase pump and set 6-10 PSI above system pressure set on the drive of the pump station.
• Note: For serviceability, unions & isolation vales should be installed to allow replacement of either pump without disturbing the other.
ELECTRICAL INSTALLATION:
• Install, ground, wire and maintain this installation in accordance with your local electrical code and all other codes and ordinances that apply. Consult your local building inspector for local code information. All electrical work should be performed by qualified personnel.
• Ground the starter permanently using a wire of size and type specified by local or United States National Electrical Code. Do not ground to a gas supply line.
• Connect ground wire first. Connect to ground first and then connect ground wire to motor starter box. Connect starter ground to green grounding terminal located inside of the motor terminal box. Ground connection MUST be made to this terminal. Do not connect motor to electrical power supply until unit is permanently grounded; otherwise seri­ous or fatal electrical shock hazard may be caused.
• IMPORTANT: Check local and/or United States National Electric Codes for proper grounding infor­mation.
• Power should supplied with a correctly fused dis­connect switch to provide protection. Consult Local or National Electrical Codes for proper fuse protec­tion based on motor nameplate.
• Whenever possible, the pump should be powered from a separate branch circuit of adequate capacity to keep voltage drop to a minimum during start­ing and running. For longer runs, increase wire size in accordance with the Wire Selection guide. (See Chart B). IMPORTANT: Wire charts are for reference only. Consult local and state codes for approved wire sizes.
• See Figure 4 for wiring from power circuit to starter and to motor.
• For proper electrical connections to the motor, refer to the connection diagram located on the name­plate or inside the terminal box of the motor. Make sure connections are correct for the voltage being supplied to the motor.
2 (FW1442)
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
3 (FW1442)
• Install provided heaters onto starter. Note: the heat-
To Properly Protected
ers provide over current protection for the motor. This starter with heaters installed does not provide protection from short circuits.
• Connect Starter L1 and Overload relay terminal X2 with wire rated for system power and route enough wire to connect them to Drive terminals T5 & T6 respectively.
• IMPORTANT: For priming purposes only, temporarily wire nut the wires together instead of connecting to T5 and T6. After full prime, connect to T5 and T6.
• Connect Starter L2 to Coil terminal W with wire rated for system power.
• Install temperature sensor wire provided onto ¼” quick connect terminals of the temperature sensor located near the pump discharge (Figure 2) to drive terminals B2 & B7 (Figure 3) (Note: The new tem­perature sensor wires will share B2 & B7 drive termi­nals with factory installed wires.)
Figure 2 Temperature Sensor Location
Operation
Unit must be full of fluid before operating. Do not run dry, or against a closed discharge. Do not pump dirty water or abrasive liquids. To do so will cause pump failure and will void the warranty.
VALVES
The suction inlet valve should be in the full open posi­tion and hose bib valve should be partially open, allow­ing some back pressure to be exerted against the pump when starting up. Close hose bib valve after priming up is completed.
PRIMING
IMPORTANT: Before starting the pump it is absolutely necessary that both pumps and the suction pipe be completely filled with water. Before the entire duplex pump system is fully operational, the single phase pump, needs to be completely primed and run before returning power to the variable frequency drive.
IMPORTANT: Before priming, verify control wires are temporarily connected with a wire nut instead of being connected to drive terminals T5 & T6.
PRIMING OF PRESSURE BOOST INSTALLATIONS
Priming is simple when pump is connected to a pressure source such as a city main or above ground tank filled to a level of 4 ft. above pump inlet.
1. Open inlet valves fully on suction and open hose bib on skid system manifold.
2. To relieve trapped air, allow water supply to run a minimum of 2 minutes before starting the pump.
3. Turn on power to the single phase pump and run no longer than two (2) minutes. Unit should build pressure & pump water. If not, repeat the sequence above.
4. Once all air has been evacuated and the pump has been primed, close hose bib and turn off power.
5. IMPORTANT: Once priming has been completed & power has been turned off, remove the wire nut connecting control wires and connected them to drive terminals T5 & T6 (Figure 3).
T6T5T4T3T2T1
Transducer Wire - Black
B1
B4
B3B2
B7B6B5
Transducer Wire - Red
Jumper Wire
Temperature Sensor Wire - Red
Temperature Sensor Wire - Black
1
Transducer Cable
Temperature Sensor Cable
2
Figure 3 Drive Control Circuit Terminals
Starter Control Wires
IL1140
Disconnect Circuit
L1 L2
Motor Starter
Coil Terminals
Line Terminals
L1 L2 L3
Overload Relay Terminals
Drive Terminals
Figure 4 Starter Wiring
T5
T6
NC
T1 T2 T3
X2
Starter Control Wires
Install Heaters
Load Terminals
Pump
Motor
IL1139
PRIMING FOR SUCTION LIFT INSTALLATIONS
On suction lift applications prime the unit as follows:
1. Remove priming plug from service tee and fill pump and suction pipe with water.
2. Jog the pump motor by applying power on and off several times to free air trapped inside the pump.
3. After jogging the pump, refill with water and repeat the priming sequence several times to be sure all air is out of the pump and suction pipe.
4. Open hose bib on skid system manifold, start the pump and run no longer than two (2) minutes. Unit should build pressure & pump water. If not, repeat the sequence above.
NOTE: On first use of pump, it may be necessary to re­prime the unit three (3) or four (4) times before all air is out of the suction pipe.
5. Once all air has been evacuated and the pump has been primed, close hose bib and turn off power.
6. IMPORTANT: Once priming has been completed & power has been turned off, remove the wire nut connecting control wires and connected them to drive terminals T5 & T6 (Figure 3).
START-UP PROCEDURE
Once the preceding instructions have been completed, the entire system can be started:
1. Verify that all values installed on the intake side of the pumps are open & the isolation value is closed if installed on the discharge side of the system.
2. Verify that the 3-phase pump is primed. For gravity fed systems, this can be accomplished by opening hose bib valve installed on the system manifold to allow the water pressure to push out the air from the pump. For suction lift systems, fill the pump and intake piping with external water source until water begins coming out the open hose bib valve.
3. Close hose bib valve.
4. Supply electrical power to Pump Station by turning on the user installed disconnect to the ON position and allow system to pressurize and check for leaks on plumbing installed.
5. Once pressure has been established, partially crack open the station isolation valve (while maintaining pressure) and open valves farthest away from pump station to bleed air out of the system & piping
6. When the whole Main Line has been bled of air, fully open the discharge isolation valve.
7. Supply electrical power to single phase pump by truing on the user installed disconnect to the ON position. When demand exceeds the capacity of the three phase pump, the single phase motor will start up for a minimum of one minute.
8. During the first few hours of operation, inspect the pump, piping and any auxiliary equipment used in connection with the unit.
9. Check for leaks, excessive vibration or unusual noises.
MAINTENANCE:
For proper maintenance of the pump, please follow instructions in enclosed End suction centrifugal pumps instructions FW0300/134984.
4 (FW1442)
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
5 (FW1442)
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
Troubleshooting Chart
Symptom Possible Cause(s) Corrective Action
Low or no discharge 1. Incorrect rotation 1. Refer to wiring diagram
2. Insufficient inlet pressure or
suction head (NPSH Required)
3. Total head too high 3. Lower discharge head
4. Leak in suction line 4. Repair or replace
5. Impeller clogged or damaged 5. Clean or replace
6. Wrong size piping 6. Make needed adjustments
7. Casing gasket leaking 7. Replace gasket
8. Suction or discharge line valves closed
9. Mechanical seal leaking 9. Replace
Loss of suction 1. Insufficient inlet ressure or suction
head (NPSH Required)
2. Clogged strainer 2. Clean or replace
Pump vibrates and/ or makes excessive noise
Pump leaks at shaft 1. Damaged or worn mechanical seal 1. Replace
Pump will not start or run
Motor problems 1. Various 1. Consult qualified electrician
Pinholes in the casting. Liquid dripsp around seal area but is not seal
1. Mounting plate or foundation not rigid enough
2. Foreign material in pump 2. Clean
3. Damaged impeller 3. Replace
4. Cavitation present 4. Check suction line for proper size and be sure
2. Corrosion due to character of
liquid pumped
1. Improperly wired 1. Refer to wiring diagram
2. Blown fuse or open circuit breaker 2. Replace fuse or close circuit breaker
3. Loose or broken wiring 3. Tighten connections and replace broken wiring
4. Impeller clogged 4. Clean
5. Motor shorted out 5. Replace
2. Overloading motor. Too much
water delivery
3. Liquid heavier and more viscous than water
4. Seal binding 4. Replace
5. Rotor binding 5. Repair or replace
6. Voltage and frequency lower than rating
7. Defects in motor 7. Repair or replace
1. Cavitation caused by insufficient inlet pressure or suction head (NPSH Required)
2. Increase inlet pressure by adding more fluid to fluid source. (See Spec’s for minimum NPSH Required)
8. Open
1. Increase inlet pressure by adding more fluid to fluid source. (See Spec’s for minimum NPSH Required)
1. Reinforce
valve is open. Remove excessive loops in suction line. (See Spec’s for minimum NPSH Required)
2. Discontinue pumping liquid and consult factory
2. Restrict outlet by closing down valve in discharge
line
3. Consult factory
6. Reconnect to rated voltage and frequency
1. Increase inlet pressure by adding a higher level of fluid to source or increasing inlet pressure. (See Spec’s for minimum NPSH Required)
CONTINGENCY OPTIONS
For some applications, a contingency plan is needed if the system is unable to deliver the required water in the event of a component failure which causes one pump to fail. The contingency plans below will allow the working pump to deliver water until the failed component is repaired/replaced, even if the single pump cannot meet the pressure demands required by the application.
1. Problem: Single phase pump or starter failure. Effect: Single phase pump does not run when demand is reached. Drive continues to run 3-phase pump, but system drops below set pressure when demand is high. User Contingency action: None. Long term user action: Repair/replace failed single phase component.
2. Problem: Three Phase pump failure (drive not tripped on fault). Effect: Three phase pump does not run. Single phase motor is controlled by the drive and runs 1 minute on, 1 minute off on low water demand or continuously with higher demand. User Contingency action: None. Long term user action: Repair/replace failed 3-phase pump.
3. Problem: Drive fails. Effect: Neither pump runs. User Contingency action: With power turned off to both drive and single phase motor, remove control wires from drive terminals T5 & T6 and wire nut together. Hook up a hose to hose bib and route
back to supply tank or drain and open hose bib valve. (This is done to guarantee a minimum flow of water thought the pump when there is no demand for water and prevent damage to the pump that can occur when the pump is run deadhead.) Turn power on to single phase pump – Note: Pump will run continuously. Long term user action: Replace drive.
4. Problem: Transducer Fails (Drive Trips tr cL1). Effect: Neither pump runs. User Contingency action: With power turned off to both drive and single phase motor, remove control wires from drive terminals T5 & T6 and wire nut together. Hook up a hose to hose bib and rout back to supply tank or drain and open hose bib valve. (This is done to guarantee a mini­mum flow of water thought the pump when there is no demand for water and prevent damage to the pump that can occur when the pump is run dead­head.) Turn power on to single phase pump – Note: Pump will run continuously. Long term user action: Replace transducer.
6 (FW1442)
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
7 (FW1442)
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
8 (FW1442)
95 North Oak St. • Kendallville, IN 46755 • 1-800-742-5044
Loading...