Flint & Walling CCF Series User Manual

INSTALLATION, OPERATION, AND
MAINTENANCE MANUAL
CBW10, CBW10D, CBW20, CBW20D
CCF10, CCF10D, CCF20, CCF20D
AUTOMATIC WATER
PP0131
0611
Supersedes
0610
FILTERS
SPECIFICATION TABLE
Units
Cont. GPM 3 3 5 5
Service Flow
Pipe Size In/Out - Inches 1” 1” 1” 1”
Operating Pressure Range PSI 30 - 125 30 - 125 30 - 125 30 - 125
Max Operating Temperature Degrees F 110 110 110 110
Mineral Tank Size (Dia. x Ht.)
Shipping Weight Lbs. 47.5 137 57.5 235
Overall Height Inches 52 52 60 60
Drain Flow During Regeneration
NOTE:
(1)
Pressure drop not to exceed 15 psi.
(2)
Product materials and workmanship are protected with a written warranty.
(3)
Untreated water provided during all steps of regeneration.
(1)
Peak GPM 8 8 10 10
(2)
(3)
Inches 10 x 44 10 x 44 12 x 52 12 x 52
GPM 5.3 6.5 7.5 7.5
CBW10,
CBW10D
CCF10,
CCF10D
CBW20,
CBW20D
CCF20,
CCF20D
FILL IN FOR FUTURE REFERENCE
MODEL NO:___________________________________________
DATE INSTALLED:______________________________________
DEALER:______________________________________________
023367
remier
IL1037
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Connection to sanitary sewer line
(optional)
Sanitary sewer line
Maximum drain pipe
Air gap device
elevation above drain
port is 5 ft.
Drain
Automatic Water Filters
Sanitary Drain, Floor Drain or
Laundry Tubs are acceptable.
Do not make a direct connection
to the drain. An air gap must
Drain line 1/2” ID diameter
minimum size
be present.
Drain Trap
Cold filtered water inlet
30 p.s.i. minimum pressure
1” minimum pipe size
High Pressure Warning:
If feedwater pressure is known to be above
125 psi, it is strongly recommended that a
pressure reducing valve be installed at this point.
Manual Bypass Valve
(Normally Closed)
(optional)
Manual Inlet Valve
Drain Port
(optional)
Typical Water CBW Installation
Assembly
Filter Tank
Unfiltered water to Sprinklers and any
dersired unfiltered fixtures
Ground Strap
Filter Water Outlet
Manual Outlet Valve
(optional)
110-125 Volt
Continuous Power Supply
Transformer
2
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Automatic Water Filters
INSTALLATION FITTING ASSEMBLIES
Installation fittings connect to the control valve or the bypass valve using nuts that only require hand tightening. Hand tight nut connections between control valve and installation fittings, control valve and bypass valve, and bypass valve and installation fittings allow for ease serviceability. Do not use a pipe wrench to tighten nuts on installation fittings. Hand tighten only.
Split ring retainer design holds the nut on and allows load to be spread over the entire nut surface area reducing the chance for leakage. The split ring design, incorporated into the installation fittings allows approximately 2 degrees off axis alignment to the plumbing system. The installation fittings are designed to accommodate minor plumbing misalignments but are not designed to support the weight of a system or the plumbing.
When assembling the installation fitting package, connect the fitting to the plumbing system first and then attach the nut, split ring and o-ring. Heat from soldering or solvent cements may damage the nut, split ring or o-ring. Solder joints should be cool and solvent cements should be set before installing the nut, split ring and o-ring. Avoid getting primer and solvent cements on any part of the o-rings or split rings, bypass valve or control valve. Solvent cements and primers should be used in accordance with the manufacturer’s instructions.
Slip the nut onto the fitting first, then the split ring second and the o-ring last. hand tighten the nut. If the fitting is leaking, tightening the nut will not stop the leak. Remove the nut, remove the fitting, and check for damage or misalignment of the o-ring.
Do not use pipe dope or other sealant on threads. Teflon tape must be used on the threads of the 1” connection and on the threads for the drain line connection. Teflon tape is not necessary on the nut connection or caps because of o-ring seals.
Do not use Vaseline, oils or other unacceptable lubricants on o-rings. A silicon lubricant may be used on black o-rings.
BYPASS VALVE
The bypass valve easily connects to the control valve body using nuts that only require hand tightening. Hand tighten nut connections between control valve and fittings, control valve and bypass valve, and bypass valve and installation fittings allow for easy serviceability. The split ring retainer design holds the nut on and allows load to be spread over the entire nut surface area reducing the chance for leakage. The split ring design, incorporated into the bypass, allows approximately 2 degrees off axis alignment to the plumbing system. The bypass is designed to accommodate minor plumbing misalignments but is not designed to support the weight of a system or the plumbing.
Avoid getting primer and solvent cements on any part of the o-rings or split rings, bypass valve or control valve. Do not use pipe dope or other sealant on threads. Teflon tape is not necessary on the caps because of o-ring seals.
Do not use Vaseline, oil or other unacceptable lubricants on o-rings. A silicon lubricant may be used on black o-rings.
A. GENERAL
1. Shut off all water at main supply valve.
2. Shut off the fuel supply to water heater.
3. Open faucets (hot and cold) nearest pump or water meter to relieve pressure and drain system.
4. Move filter into the installation position. Loosely attach all fittings to measure for bypass valve assembly (if used), or manual bypass valve.
5. Level the unit. (Do Not use metal shims.)
6. Cut the cold water supply line as required.
7. Install the bypass valve assembly if used.
B. PLANNING INSTALLATION
1. All installation procedures must conform to local plumbing, electrical and sanitation codes and ordinances.
2. It is recommended that outside faucets for lawn service be on the hard water line, ahead of the filter, to conserve filtered water.
3. If this isn’t practical, use the convenient integral bypass valve assembly.
CAUTION: The inlet water temperature MUST NOT exceed 120° F.
4. Do not locate filter where ambient temperature drops below 40° F.
5. Allow space around the filter for ease of servicing.
6. The filter drain lines must never be solidly connected to the sewer line. (Always provide an air gap at the END of the drain line). Valve drain line must not be elevated over 5’ from the top of the filter on well systems, and not over 8’ on municipal water systems.
7. Move the filter into position and connect to bypass assembly (if used). The integral manual bypass option is a connection which eliminates the need for a 3-valve manifold. This makes installation easier and provides a more convenient method of bypassing.
8. IMPORTANT: Be sure that the water inlet line is connected to the “inlet” side of the bypass valve or to the inlet fitting. (Bypass valve both inlet/outlet fittings are marked.) If water lines are reverse, (inlet/ outlet) filter mineral may be forced from the water filter into the household plumbing system. If this
3
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Automatic Water Filters
occurs, household plumbing system must be flushed clean.
C. CONNECT ALL FITTINGS (refer to previous page)
CAUTION: Care must be used when working with copper tubing. Do not allow the flame from torch to contact any portion of the Valve assembly.
1. Attach 3/4” drain line to drain elbow with insert and nut.
2. Do not elevate the drain line over 5’ above the top of the valve (8’ on municipal systems) or to exceed 25’ in length at either height.
CAUTION: An air gap must be provided upon sewer entry. (Conform to local plumbing and sanitation codes and ordinances).
1. Media was shipped boxed under media tank. Carefully unscrew control valve. Be sure to “plug” the top of the distributor tube using tape or some other means. Do not allow filter media to enter inside of distributor tube. (See Fig. 3)
2. Pour the separately boxed media into media tank.
3. Lubricate o-rings on control valve with silicone lubricant. DO NOT USE PETROLEUM JELLY.
4. Lubricate bypass valve o-rings with silicone lubricant and secure to the control valve using adapter couplings, clips and screws.
5. Cut main supply line as required to fit plumbing to the inlet and outlet of bypass valve. Make certain water flow enters through the Inlet and discharges through the Outlet of the bypass valve.
6. Attach drain line to drain line fitting. Position drain line over drain and secure firmly. To prevent back siphoning, be sure to have adequate air gap of at least 2 inches.
7. Make certain bypass valve is in the “bypass” position. Turn on power to well pump or open main supply valve completely.
8. Plug control valve into a non-switched 115v power source.
9. Manually stage filter to the backwash position (see service manual).
10. Open inlet valve and allow the unit to fill SLOWLY. This will allow air to escape from the media tank. Once water continually flows to drain, open both inlet and outlet valves fully.
11. Check for leaks and allow filter to backwash for at least 10 minutes or until water flowing from drain runs clear.
12. Allow unit to fully regenerate (see service manual).
13. Models CBW10D, CBW20D, CCF10D and CCF20D have a dome hole/plug located in the upper dome of the mineral tank. This is used to replenish mineral as required. DO NOT remove dome hole plug without first depressurizing the tank.
Dome Hole (”D” suffix models only)
Distributor Tube
Media Tank
Filter Media
Gravel - preinstalled
INSPECTION AND HANDLING YOUR FILTER
Be sure to inspect the equipment for shipping damage and notify the transportation company if damage exists. Handle the filter with care, as damage can result if dropped or if the filter is set on a sharp object.
CONDUCT A THOROUGH WATER TEST
Your water should have a thorough analysis prior to the selection of water conditioning equipment. Enter your analysis below:
WATER ANALYSIS
IRON (fe) __________ ppm
Manganese (Mn) __________ ppm
pH __________
Tannins __________ ppm
Hydrogen Sulfide (H2S) __________ ppm
NOTE: Hydrogen Sulfide must be tested at the well site. Failure to conduct an “on site” analysis will result in inaccurate test results.
LOCATING EQUIPMENT CORRECTLY
The location of your filter should be selected carefully. A variety of conditions will contribute to proper location as follows:
1. Locate as close as possible to the source of water supply.
2. Locate as close as possible to drain, i.e. laundry tub or floor drain.
4
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Automatic Water Filters
3. Locate in correct relationship to other water treatment equipment (See Figure 1).
4. Allow sufficient area around the equipment for service.
FACTS TO REMEMBER WHILE PLANNING YOUR INSTALLATION
1. All installation procedures MUST conform to local and state plumbing codes.
2. If lawn sprinkling, a swimming pool or geothermal heating/cooling are to be treated by the Chemical Free filter, a larger model filter MUST be selected to accommodate the higher flow rate demands.
3. IMPORTANT: Always use Teflon tape on threaded plastic fittings. NEVER use pipe dope, as it will deteriorate the plastic fittings.
CHECK WATER PRESSURE
Minimum water pressure required at the inlet of the filter is 20 psi. IF PRESSURE IS OVER 100 PSI, A PRESSURE
REGULATING VALVE MUST BE INSTALLED TO REDUCE WATER PRESSURE.
NOTE: Pressure regulating valve must be installed in water line ahead of the air induction assembly.
CHECK PUMPING RATE OF WELL PUMP
The pumping rate of your well pump must be sufficient to properly backwash the filter. Check backwash flow rate required for specific filter model.
Water Pressure Low _____ psi
High _____ psi
Pumping Rate _________ GPM
FILTERED
SOFT WATER
FILTERED WATER
WATER
SOFTE NER
WATER FILTER
PRESSURE
TANK
PRESSURE
SWITCH
WELL WATE R
FROM PUMP
IL1039
Figure 1 - Standard Installation
5
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Addendum for CCF Series
Automatic Water Filters Only
BEFORE INSTALLING YOUR FILTER
INSPECTION AND HANDLING YOUR FILTER
Be sure to inspect the equipment for shipping damage and notify the transportation company if damage exists. Handle the filter with care, as damage can result if dropped or if the filter is set on a sharp object.
CONDUCT A THOROUGH WATER TEST
Your water should have a thorough analysis prior to the selection of water conditioning equipment. Enter your analysis below:
WATER ANALYSIS
IRON (fe) __________ ppm
Manganese (Mn) __________ ppm
pH __________
Tannins __________ ppm
Hydrogen Sulfide (H2S) __________ ppm
NOTE: Hydrogen Sulfide must be tested at the well site. Failure to conduct an “on site” analysis will result in inaccurate test results.
LOCATING EQUIPMENT CORRECTLY
The location of your filter should be selected carefully. A variety of conditions will contribute to proper location as follows:
1. Locate as close as possible to the source of water supply.
2. Locate as close as possible to drain, i.e. laundry tub or floor drain.
3. Locate in correct relationship to other water treatment equipment (See Figure 1).
4. Allow sufficient area around the equipment for service.
4. IMPORTANT: Always use Teflon tape on threaded plastic fittings. NEVER use pipe dope, as it will deteriorate the plastic fittings.
CHECK WATER PRESSURE
Minimum water pressure required at the inlet of the filter is 30 psi. IF PRESSURE IS OVER 125 PSI, A PRESSURE REGULATING VALVE MUST E INSTALLED TO REDUCE WATER PRESSURE.
NOTE: Pressure regulating valve must be installed in water line ahead of the air induction assembly.
CHECK PUMPING RATE OF WELL PUMP
The pumping rate of your well pump must be sufficient to properly backwash the filter. Check backwash flow rate required for specific filter model.
Water Pressure Low _____ PSI
High _____ PSI
Pumping Rate _________ GPM
INSTALLATION
INSTALLING THE AIR INDUCTION ASSEMBLY
1. Shut off all water at the main supply. On a private well system, turn off power to the pump and drain pressure tank. Make sure pressure is relieved from complete system by opening nearest faucet to drain system. SHUT OFF FUEL SUPPLY TO WATER HEATER.
2. Cut main supply line as required to fit air induction assembly in plumbing between well pump and pressure tank. Air induction assembly may be installed in a vertical or horizontal position. Position air induction assembly so that the flow adjusting screw is accessible for adjustment by screwdriver. Install unions to facilitate air induction assembly removal and inspection. Be certain the Flow Arrow on air induction assembly points toward the pressure tank
FACTS TO REMEMBER WHILE PLANNING YOUR INSTALLATION
1. All installation procedures MUST conform to local and state plumbing codes.
2. All water MUST pass through the air induction assembly, pressure tank and the Chemical-Free Iron Filter (See Figure
1)
3. If lawn sprinkling, a swimming pool or geothermal heating/cooling are to be treated by the Chemical Free filter, a larger model filter MUST be selected to accommodate the higher flow rate demands.
IRON FREE
SOFT WATER
IRON FREE WATER
WATER
SOFTENER
Figure 1 - Standard Installation
WATER FILTER
PRESSURE
TANK
PRESSURE
SWITCH
AIR INDUCTION
ASSEMBLY
WELL WATER
FROM PUMP
IL1040
6
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Addendum for CCF Series
Automatic Water Filters Only
and pressure control switch is located on pressure tank side of the air induction assembly (See Figure
2). Allow 8” of straight pipe on both sides of air induction assembly.
SUCTION
PORT
FLOW A DJUSTIN G SCRE W
WATER FLOW WATER FLOW
IL1041
Figure 2 - Air Induction Assembly
INSTALLING THE FILTER
1. Media was shipped separately. Carefully unscrew the control valve. Be sure to “plug” the top of the distributor tube using tape or some other means. Do not allow filter media to enter inside of distributor tube (See Figure 3).
Dome Hole (”D” suffix models only)
Distributor Tube
Media Tank
Filter Media
Gravel - preinstalled
Figure 3 - Media Tank Cutaway
2. Pour the separately shipped media into media tank.
3. Replace control valve on media tank. Lubricate o-rings on control valve with silicone lubricant. DO NOT USE PETROLEUM JELLY.
4. Lubricate bypass valve o-rings with silicone lubricant and secure to the control valve using adapter couplings, clips and screws.
5. Cut main supply line as required to fit plumbing to the inlet and outlet of bypass valve. Make certain water flow enters through the Inlet and discharges through the Outlet of bypass valve.
6. Attach drain line to drain line fitting. Position drain line over drain and secure firmly. To prevent back siphoning, be sure to have adequate air gap of at least 2 inches.
7. Make certain bypass valve is in the “bypass” position. Turn on power to well pump or open main supply valve completely.
8. Plug control valve into a non-switched 115V power source.
9. Manually stage filter to the backwash position (see service manual).
10. Open inlet valve and allow the unit to fill SLOWLY. This will allow air to escape from the media tank. Once water continually flows to drain, open both inlet and outlet valves fully.
11. Check for leaks and allow filter to backwash for at least 10 minutes, or until water flowing from drain runs clear.
12. Allow unit to fully regenerate (see service manual).
13. Models CCF10D and CCF20D have a dome hole/plug located in the upper dome of the mineral tank. This is used to replenish mineral as required. DO NOT remove dome hole plug without first depressurizing the tank.
ADJUSTING THE AIR INDUCTION ASSEMBLY
1. Open nearest faucet until pump starts, then close faucet.
2. Place finger lightly over SUCTION PORT (See figure 2). A slight suction should be detected for approximately ONE-THIRD of pumping cycle. (Do not confuse with one-third of PRESSURE RANGE).
3. If suction duration is too short, increase by turning FLOW ADJUSTING SCREW CLOCKWISE. To decrease duration, turn COUNTER CLOCKWISE.
4. Repeat steps 1 through 3 until proper setting is obtained.
NOTE: When the duration of the suction is too long, cold water may have a “milky” appearance caused by excess air in the system. Correct this condition by reducing the duration of suction. This condition is commonly associated with bladder type pressure tanks In extreme cases where elimination of excess air prevents system from performing satisfactorily, it may be necessary to install a standard air­to-water type pressure tank with an air relief valve.
SUCTION
PORT
FLOW A DJUSTIN G SCRE W
WATER FLOW WATER FLOW
IL1041
Figure 2
7
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Automatic Water Filters
D. PRESSURE TEST THE INSTALLATION
The plumbing system can now be checked for any possible leaks
1. Open the water supply inlet valve very slowly. Once the mineral tank is full of water, slowly open the outlet on the bypass. Open a faucet down stream from the filter & allow the air to escape. DO NOT INITIATE A BACKWASH UNTIL MEDIA IS SATURATED.
2. Allow water to run until clear. CHECK FOR LEAKS!
3. Plug the unit in.
4. Make sure the power cord is plugged into a properly grounded wall receptacle.
E. PROGRAMMING THE CONTROL VALVE How To Set Time Of Day
The user can set the time of day. Time of day should only need to be set initially, and after extended power outages or when daylight saving time begins or ends and at the time of start-up. If an extended power outage occurs, the time of day will flash on and off which indicates the time of day should be reset.
SET
HOUR
STEP 1U - press
.
STEP 2U - Current Time (hour): Set the hour of the day using
buttons. AM/PM toggles
or after 12.
STEP 3U - press
SET
HOUR
button to complete and return to display mode.
MIN. FILL
MIN. FILL
REGEN
REGEN
HOUR
REGEN
REGEN
HOUR
SET
HOUR
SET
HOUR
3
3
TIME-HOUR
PM
DAY S TO REGEN
IL1075
TIME-HOUR
PM
DAY S TO REGEN
IL1075
How To Change Time of Backwash and Days Between Backwashes
STEP 1 - From normal mode,
press simultaneously for 3 seconds and release.
STEP 1A - Backwash Time:
Set the clock to the hour the backwash should occur by using the buttons. An arrow will point to p.m. after 12 (factory
default is 1 a.m.). Press
SET
HOUR
&
buttons
HOUR
SET
REGEN
MIN. FILL
REGEN
HOUR
SET
HOUR
and
to go to step 1B.
3
OR
TIME-HOUR
PM
DAY S TO REGEN
IL1074
STEP 1B - Setting Days Between Backwash: Use the
backwashes (factory default is 3 days).
Press
and buttons to set the days between
SET
HOUR
to return to Normal mode.
Backwash Mode
Typically a system is set to backwash at a time of low water usage. An example of a time with low water usage is when a household is asleep. If there is a demand for water when the system is backwashing, untreated water will be used.
When the system begins to backwash, the display will change to include information about the step of the backwash process. The system runs through the steps automatically and will reset itself to provide treated water when the backwash has been completed.
Manual Backwash
Sometimes there is a need to backwash the system, sooner than
REGEN
MIN. FILL
REGEN
HOUR
SET
HOUR
when the system calls for it, usually referred to as manual backwash.
To initiate a manual backwash at the preset delayed backwash time, press and release
and
REGEN
MIN. FILL
REGEN
HOUR
SET
HOUR
simultaneously. An arrow point on the display indicates that the system will backwash at the preset delayed backwash time. If you pressed the
and buttons in error, pressing the
buttons again will cancel the request.
To initiate a manual backwash immediately, press and hold the
and buttons simultaneously for four seconds. The system will begin to backwash immediately. The request cannot be cancelled. You can manually step through individual cycles by pressing the
button until
display reaches normal mode.
Power Loss
If the power goes out for less than two hours, the system will automatically reset itself. If an extended power outage occurs, the time of day will flash on and off which indicates the time of day should be reset. The system will retain the other information entered by your plumbing professional.
3
1
TIME-HOUR
PM
DAYS TO REGEN
OR
TIME-HOUR
PM
DAYS TO REGEN
IL1042
8
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Bypass Valve
The bypass valve is typically used to isolate the control valve from the plumbing system’s water pressure in order to perform control valve repairs or maintenance. The bypass valve is particularly unique in the water treatment industry due to its versatility and state of the art design features. The bypass valve incorporates four positions including a diagnostic position that allows service personal to work on a pressurized system while still providing untreated bypass water to the facility or residence. Its completely non-metallic, all plastic, design allows for easy access and serviceability without the need for tools.
Automatic Water Filters
The bypass body and rotors are glass filled Noryl and the nuts and caps are glass filled polypropylene. All seals are self-lubricating EPDM to help prevent valve seizing after long periods of non-use. Internal o-rings can easily be replaced if service is required.
The bypass consists of two interchangeable plug valves that are operated independently by red arrow shaped handles. The handles identify the flow direction of the water. The plug valves enable the bypass valve to operate in four positions.
Figure 1
NORMAL OPERATION
“Treated”
Water Exits
Normal Operation:
The inlet and outlet handles point in the direction of flow indicated by the engraved arrows on the control valve. Water flows through the control valve during normal operation and this position also al­lows the control valve to isolate the media bed during the regenera­tion cycle.
Figure 3
Supply
Water Enters
IL1043
DIAGNOSTIC MODE
Supply
Water Exits
Supply
Water Enters
Figure 2
BYPASS OPERATION
“Untreated”
Water Exits
Bypass:
The inlet and outlet handles point to the center of the bypass, the control valve is isolated from the water pressure contained in the plumbing system. Untreated water is supplied to the plumbing system.
Figure 4
Supply
Water Enters
IL1044
SHUT OFF MODE
No
Water Exits
Supply Water is shut off
from the house and the
valve
IL1045
Diagnostic: The inlet handle points in the direction of flow and the outlet handle points to the center of bypass valve, system water pressure is allowed to the control valve and the plumbing system while not allowing water to exit from the control valve to the plumbing.
Shut Off:
IL1046
The inlet handle points to the center of the bypass valve and the outlet handle points in the direction of flow, the water is shut off to the plumbing system. If water is available on the outlet side of the softener it is an indication of water bypass around the system (i.e. a plumbing connection somewhere in the building bypasses the system).
9
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Automatic Water Filters
6
7
Turn counter-clockwise to remove.
Turn clockwise to install.
IL1049
Funnel
IL1047
Service Tool
8
IL1061
Transformer
Description Qty
No.
Part
No.
Item
1 023406 Motor 1
2 023412 PC Board 1
3 023408 Piston Assy. 1
4 023409 Seal Assy. 1
5 023410 O-Ring Kit 1
6 127001 Mineral Fill Funnel 1
7 023362 Service Tool 1
8 023411 Transformer 110V-12V 1
10
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Item Description CBW10 CBW10D CBW20 CBW20D CCF10 CCF10D CCF20 CCF20D
1
2 Mineral tank 023319 023320 023483 023491 023319 023320 023483 023491
3 Mineral * * * * 023358 023358 023358(Qty 2) 023358(Qty 2)
4 Gravel 135523 135523 023529 023529 135523 135523 023529 023529
1
2
Distributor tube / screen
Automatic Water Filters
023360 023360 023488 023488 023360 023360 023488 023488
Qty
Application* Part # Description
Iron Removal 135514 Birm
Acid Neutralizer 023357 Calcite
Sediment 135518 Filter-AG
Taste & Odor 135516 Activated Carbon
CBW10
CBW10D
1 Box
1 CF
CBW20
CBW20D
2 Boxes
2 CF
3
4
Bypass Valve Less Connectors 023328
Connectors 023329 Set of 2
IL1052
Air Inducer CCF10 Only 021708
IL1053
11
remier
remier
P
P
roducts
roducts
®
P
P
WATER TREATMENT
Problem Possible Cause Solution
1. Timer does not display time of day
2. Timer does not display correct time of day
3. Control valve regenerates at wrong time of day
4. E1, E2, or E3
E1 - Unable to recognize start of regeneration
E2 - Unexpected stall
E3 - Motor ran too long, timed out trying to reach the next cycle position or trying to reach home position
5. Control valve stalled in regeneration
7. Control valve does not regenerate automatically when UP and DOWN button is depressed and held
8. Control valve does lnot regenerate automatically but does when UP and DOWN button is depressed and held
Automatic Water Filters
Table 6 - Troubleshooting Procedures
a. AC adapter unplugged a. Connect power b. No electric power at outlet b. Repair outlet or use working outlet c. Defective transformer c. Replace transformer d. Defective PC board d. Replace PC board a. Switched outlet a. Use uninterrupted outlet b. Power outage b. Reset time of day c. Defective PC board c. Replace PC board a. Power outages a. Reset control valve to correct time of day b. Time of day not set correctly b. Reset to correct time of day c. Defective PC board c. Reset regeneration time a. Control valve has just been serviced a. Press SET HOUR and DOWN for 3 seconds or
unplug power source jack (black wire) from the circuit board and plug back in to reset control valve.
b. Foreign matter is lodged in control valve b. Check piston and spacer stack
assembly for foreign matter. c. High drive forces on piston c. Replace piston(s) and spacer stack assembly d. Control valve piston not in home position d. Press SET HOUR and DOWN for 3 seconds or
unplug power source jack (black wire) from
the circuit board and plug back in to reset
control valve e. Motor not inserted fully to engage pinion,
motor wires broken or disconnected, motor failure
f. Drive gear label dirty or damaged, missing
or broken gear
g. Drive bracket incorrectly aligned to back
plate h. PC board is damaged or defective h. Replace PC board i. PC board incorrectly aligned to drive
bracket a. Motor not operating a. Replace motor b. No electric power at outlet b. Repair outlet or use working outlet c. Defective AC adapter c. Replace AC adapter d. Defective PC board d. Replace PC board e. Broken drive gear or drive cap assembly e. Replace piston kit f. Broken piston retainer f. Replace piston kit g. Broken main or regenerant piston g. Replace piston kit a. AC adapter unplugged a. Connect AC adapter b. No electric power at outlet b. Repair outlet or use working outlet c. Broken drive gear or drive cap assembly c. Replace drive gear or drive cap assembly. d. Defective PC board d. Replace PC board
a. Defective PC board a. Replace PC board b. Set-up error b. Check control valve set-up procedure
e. Check motor and wiring. Replace
motor if necessary
f. Clean drive gear
g. Reseat drive bracket properly
i. Ensure PC board is correctly snapped on to
drive bracket
12
Loading...