Flint & Walling AD150145 User Manual

Operating Instructions & Parts Manual
!
Centrifugal Constant Pressure Control
Models AD052045, AD070059, AD096074, AD096096, AD150145
Descriptions and Features
The F&W Artesian Drive is a dependable water system Variable Frequency Drive (VFD) that uses custom program­ming to enhance the performance of standard centrifugal pumps. When applied correctly to three phase motor driven pumps, the Artesian Drive eliminates pressure cycling associat­ed with conventional pressure switch controlled water pump­ing systems and provides a constant output pressure.
KEY FEATURES OF THE ARTESIAN DRIVE INCLUDE:
• Constant water pressure with a wide range of settings (30-80 psi) (Note: The maximum obtainable system pres­sure is limited by the performance of the pump installed)
• Smaller pressure tank can be used
• Fits the pump to the application – pump speed is con-
trolled to provide the optimum performance without overloading the motor
• Flexibility – you can use this unit with standard off-the­shelf pumps and 3-Phase motors
• No in-rush (power-on transient) current
• Low motor start-up current (soft-starting)
• Active Power Factor Correction minimizes input RMS cur-
rent
• Protection features
- Dry run conditions – using intelligent load monitor­ing (see Page 8)
- Bound pump – with auto-reversing torque
- High voltage / lightning surge
- Low line voltage
- Short circuit
Unpacking
When unpacking the unit, inspect carefully for any damage that may have occurred during transit.
Included Items:
A. Controller Unit F. Wiring Enclosure
B. Strain Relief Fittings
* Only one fitting w/
AD150145
C. Pressure Sensor and Boot H. Warranty Card
D. Sensor Adjustment Tools I. Installation Guide
E. Sensor Cable J. Installation Manual
G. Memory Stick & Retainer
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
B
C
E
D
Figure 1
General Safety Information
Carefully read and follow all safety instructions in this manual and on pump. Keep safety labels in good condi-
tion. Replace missing or damaged safety labels.
this symbol on the pump or in the manual, look for one of the following signal words and be alert to the potential for personal injury or property damage.
personal injury, death or major property damage if ignored.
personal injury or death, if ignored.
personal injury, product or property damage if ignored.
IMPORTANT: Indicates factors concerned with operation, installation, assembly or maintenance which could result in damage to the machine or equipment if ignored.
NOTE: Indicates special instructions which are important but are not related to hazards.
1 (FW1086)
This is a SAFETY ALERT SYMBOL. When you see
Warns of hazards that WILL cause serious
Warns of hazards that CAN cause serious
Warns of hazards that MAY cause minor
A
F
FW1086
0411
Supersedes
0809
J
H
I
G
IL0736
022687
!
carefully. Failure to follow could result in serious bodily injury
!
!
!
!
!
!
!
!
IL0729
and/or property damage.
controller can still hold a lethal voltage even after power has been removed. Allow 10 minutes for dangerous internal voltage to discharge before opening the unit.
capacitors with the Artesian Drive. Damage will result to both motor and drive.
perform installation.
Read these warnings and instructions
Capacitors inside the Artesian Drive
Do not use power factor correction
Electrical installations shall be in accordance with National Electric Code (NEC) and all applicable local codes and ordinances. A licensed electrician should
Be sure system is connected to a circuit equipped with a fuse or circuit breaker of the correct rating.
Always disconnect power source before performing any work on or near the controller, motor or its connected load. If the power disconnect point is out-of-sight, lock
it in the open position and/or tag it to prevent unexpected application of power. Failure to do so could result in fatal electrical shock or bodily injury.
DO NOT handle pump with wet hands or when standing in water as fatal electrical shock could occur. Disconnect main power supply before handling system for any reason.
Protect the power cable from coming in contact with sharp objects, oil, grease, hot surfaces or chemicals. DO NOT kink the power cable. If damaged replace immediately.
NEVER leave the control box, fused disconnect switch, or covers open (either partially or completely) when not being worked on by a competent electrician or repairman.
This product contains chemicals known to the State of California to cause
cancer and birth defects or other reproductive harm.
Do not pump water above 140 degrees Fahrenheit.
This unit not tested for use
in swimming pool areas.
How it Works
The F&W Artesian Drive is designed to be part of a system that consists of only four major components:
A. Standard Pump and Three Phase Motor.
B. Artesian Drive Controller.
C. Small Pressure Tank (for tank size, see Table 2).
D. Pressure Sensor (provided).
Power Supply from Circuit Breaker
Figure 2a - Constant Pressure Diagram for booster pumps
Power to Motor
Motor
Pump
Outlet
Pressure Relief Valve
Inlet
Constant Pressure Diagram
Pressure Relief Valve
Pump
Outlet
Tank
Tank
Pressure Sensor Leads
Pressure Sensor Leads
Always use caution when operating electrical controls in damp areas. If possible, avoid all contact with electrical equipment during thunderstorms or extreme damp conditions.
Install all electrical equipment in protected area to prevent mechanical damage which could produce serious electrical shock and/ or equipment failure.
DO NOT use this system to pump flammable liquids such as gasoline, fuel oil, kerosene, etc. Failure to follow the above warning could result in property damage and/or personal injury.
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
Power Supply from Circuit Breaker
Figure 2b - Constant Pressure Diagram for centrifugal pumps
Constant Pressure
The F&W Artesian Drive provides consistent pressure regula­tion using custom programming to run a standard motor and pump according to the pressure demands indicated by a heavy duty pressure switch. By adjusting the motor/pump speed, the Artesian Drive can deliver consistent pressure
2 (FW1086)
Power to Motor
Inlet
Motor
IL0783
dependably, even as water demand changes. For example,
!
!
!
!
!
!
a small demand on the system, such as a kitchen faucet, results in the motor/pump running at a relatively low speed. As greater demands are placed on the water system, such as opening additional faucets or using appliances, the motor/ pump speed increases accordingly to maintain the desired sys­tem pressure.
MOTOR SOFT START
Whenever the Artesian Drive detects that water is being used, the controller always “ramps up” the motor speed at the same time as gradually increasing voltage, resulting in a cool­er running motor and lower in-rush current compared to a motor being used on conventional water systems. If the water demand is very low, the system may cycle on and off at very low speeds, but due to the drive’s soft-start feature and pres­sure switch’s dependable design, this will not harm the motor or the pressure sensor.
SYSTEM DIAGNOSTICS
In addition to regulating system pressure and accurately controlling motor operation, the Artesian Drive continuously scans the system and can detect a variety of abnormal condi­tions. If there is elevated risk of damage to a part of the sys­tem, the drive will protect the system and display a code for the fault. If possible, the drive will try to restart itself when the fault condition passes.
PUMP SIZING – ARTESIAN DRIVE (CENTRIFUGAL)
The Artesian Drive is configured at the factory for use with standard 3-phase motors and pumps.
NOTE: The Artesian Drives are factory programmed to F&W pumps to provide optimum performance and motor protec­tion. The Artesian Drive can be used with other pumps, but the maximum motor amperage needs to be compared to the factory programmed current value (refer to the Specifications section under the appropriate model). If the maximum motor current varies more than 5% from the programmed value, the motor current value in the drive needs to be changed for motor protection and optimum performance. For details on how to change this value in the drive, please contact Technical Support at 1-800-345-9422.
The motor rated current must be set correctly to avoid a risk of fire in the
event of a motor overload.
DRIVE CONFIGURATION
When sized correctly, the Artesian Drive systems are ready to go right out of the box and need no configuration. Under certain circumstances there are several programming param­eters that can be changed to accommodate non standard systems. For further information to change these parameters, please call Technical Support at 1-800-345-9422
from contact with internal electrical components. DO NOT, under any circumstances, attempt to modify connections to the drive until power has been removed and 10 minutes have passed for internal voltages to discharge!
Serious or fatal electrical shock may result
UNDERLOAD SENSITIVITY
The Artesian Drive controller is configured at the factory to ensure detection of Underload faults in a wide variety of pumping applications including dead head and run dry conditions. In very rare cases (as with certain pumps in shal­low wells) this trip level may result in nuisance faults. If the pump is installed in a shallow well, activate the controller and observe system behavior. Once the controller begins to
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
regulate pressure, check operation at several flow rates to make sure the default sensitivity does not induce nuisance Underload trips. If it becomes necessary to desensitize the Underload trip level, please call of Technical Support at 1-800­345-9422 for further details.
from contact with internal electrical components. DO NOT, under any circumstances, attempt to modify connections to the drive until power has been removed and 10 minutes have passed for internal voltages to discharge!
Serious or fatal electrical shock may result
Before Getting Started
from failure to connect the ground terminal to the motor, Artesian Drive controller, metal plumbing, or other metal near the motor or cable, using wire no smaller than motor cable wires. To minimize risk of electrical shock, disconnect power before working on or around the Artesian Drive system. CAPACITORS INSIDE THE ARTESIAN DRIVE CONTROLLER CAN STILL HOLD LETHAL VOLTAGE EVEN AFTER POWER HAS BEEN DISCONNECTED. ALLOW 10 MINUTES FOR DANGEROUS INTERNAL VOLTAGE TO DISCHARGE BEFORE REMOVING ARTESIAN DRIVE COVER.
areas.
IMPORTANT: This equipment should be installed by technically qualified personnel. Failure to install it in compliance with national and local electrical codes and within F&W recommendations may result in electrical shock hazard, fire hazard, unsatisfactory performance, or equipment failure. Installation information is available directly from F&W at our toll-free number 1-800-345-9422.
three phase motors. Use of this unit with improperly sized motors may result in damage to both motor and electronics.
Serious or fatal electrical shock may result
Do not use motor or system in swimming
Use Artesian Drive only with properly sized
Controller Location Selection
The drive’s enclosure is NEMA 1 rated
and is intended for indoor use only. It should be mounted in a location that provides protection from water spray/drips and only be accessed by trained and authorized personnel.
The Artesian Drive controller is intended for operation in ambient temperatures up to 104°F (40°C) at 230 VAC input. The following recommendations will help in selection of the proper location of the Artesian Drive unit:
1. A tank tee is recommended for mounting the tank, pressure
sensor, pressure gauge, and pressure relief valve at one junction. If a tank tee is not used, the pressure sensor should be located within 6 feet (1.8 meters) downstream of the pressure tank to minimize pressure fluctuations.
NOTE: There should be no elbows between the tank and pres­sure sensor and the tank should be between the the pump and pressure sensor.
2. The unit should be mounted on a sturdy supporting
structure such as a wall or supporting post. Please take into account the weight of the unit (refer to the Specifications section under the appropriate model).
3. The electronics inside the Artesian Drive are air-cooled. As a
result, there should be at least 4 inches of clearance on each side and below the unit to allow room for air flow.
3 (FW1086)
clearance on each side and below the unit to allow room for
IL0735
IL0734
air flow.
4” Min
4” Min
Power Supply from Circuit Breaker
Figure 3a - Mounting Clearance - Booster Pumps
4” Min
4” Min
Power Supply from Circuit Breaker
Figure 3a - Mounting Clearance - Centrifiugal Pumps
There should be at least 4 inches of
4” Min
4” Min
Pressure Relief Valve
Inlet
Motor Pump
Outlet
Pressure Tank to
Power to Motor
4” Min
4” Min
Pressure Relief Valve
Outlet
Inlet
Power to Motor
Pressure Sensor
Mounting Clearance
Pump
Motor
Pressure Tank to Pressure Sensor
Tank
Tank
IL0784
Pressure Sensor Leads
6 Ft. or Less
Pressure Sensor Leads
6 Ft. or Less
4. Do not expose a Artesian Drive to rain or water spray. For outdoor installations, place the drive inside a NEMA 3R enclosure. Note: Please reference maxim temperature ratings listed above.
Pressure Sensor Leads
Correct
Power to
Power Supply from Circuit Breaker
Figure 4 - Mounting Orientation
Motor
Mounting Orientation
Pressure Sensor Leads
Power to Motor
Power Supply from Circuit Breaker
Incorrect
5. The Artesian Drive should only be mounted with the wiring end oriented downward. The controller should not be placed in direct sunlight or other locations subject to extreme temperatures or humidity (mounting location should not be subjected to freezing conditions or condensation).
6. The mounting location should have access to 230 VAC electrical supply and to the pump motor wiring. To avoid possible interference with other appliances, please refer to the enclosed Installation Guide and observe all precautions regarding power cable routing.
CIRCUIT BREAKER AND WIRE SIZING
The minimum circuit breaker size and maximum allowable wire lengths for connection of motor to the Artesian Drive are given in the following table:
TABLE 1: MINIMUM BREAKER SIZE AND MAXIMUM CABLE LENGTH (IN FEET)
Drive
Recommended
Model
AD052045 12 16 325 20 5.2 AD070059 12 16 325 25 7.0 AD096074 10 14 325 30 9.6 AD096096 10 14 325 30 9.6 AD150145 8 12 325 30 15.0
Input Cable
Recommended
Motor Cable
Maximum
Cable
Length to
Motor (Ft.)
Recommended
Breaker
Maximum
Continuous
Current
A 10-foot section of cable is provided with the Artesian Drive to connect the pressure sensor.
NOTE:
• Maximum allowable wire lengths are measured between
the controller and motor.
• Aluminum wires should not be used with the Artesian
Drive.
• Wire sizing between the service entrance and the control-
ler must be sufficient to provide the required maximum input amps to the controller while conforming to local standards and codes.
• Artesian Drive minimum breaker amps may appear to
exceed specifications for the three-phase motor because Artesian Drive controllers are supplied from a single­phase service rather than three-phase.
Pressure Tank
The Artesian Drive needs only a small pressure tank to main­tain constant pressure (see table below for recommended
4 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
tank size). The Artesian Drive can also use a bigger tank with
IL0746
!
!
!
a much larger capacity if available.
TABLE 2: MINIMUM PRESSURE TANK
Rated Pump Flow Pressure Tank Size (Total
Volume)
Pump Capacity less than 12
4 Gallon (AT15)
GPM
Pump Capacity greater than
8 Gallon (AT25)
12 but less than 25 GPM
Pump Capacity greater than
14 Gallon (AT44)
25 GPM
The pressure tank pre-charge setting should be 70% of the system pressure sensor setting as indicated in the following table.
TABLE 3: PRESSURE TANK AIR PRECHARGE (PSI)
System Pressure (at Pressure
Sensor)
Pressure Tank Precharge
Setting (± 2 PSI)
30 21
35 25
40 28
45 32
50 35
55 39
60 42
65 46
70 49
75 53
80* 56
*NOTE: High pressure applications above 80 PSI should be addressed through the Tech Support group at Flint & Walling (1-800-345-9422).
Installation Procedure
1. Disconnect electrical power at the main breaker.
2. Drain the system of water (if applicable).
3. Install the pressure sensor (threaded connection down) at the pressure tank tee downstream of the pressure tank (the pressure tank should be between the pressure sensor and the pump). The pressure sensor has a 1/4-18 National Pipe Thread (NPT) connection.
NOTE: The pressure sensor should not be installed in an inverted orientation (threaded connection up). Make sure the pressure sensor and tank are not located more than 3 feet off the main piping.
4. The unit should be mounted on a sturdy supporting structure such as a wall or supporting post. Please take into account the weight of the unit (refer to the Specifications section under the appropriate model). Install the unit to the wall using six mounting screws (not included) as shown in Figure 5.
H
2-3/8”
W1
W2
Figure 5
TABLE 4: DIMENSIONS
Drive Model H W1 W2
AD052045 7-1/2” 2-3/16” 2-3/16” AD070058 7-1/2” 2-3/16” 2-3/16” AD096096 9-1/2” 2-3/4” 2-3/4” AD150145 12-13/32” 3-13/32” 3-13/32”
Wiring Connections
Serious or fatal electrical shock may result from failure to connect the motor, the Artesian Drive, metal plumbing and all other metal near the motor, or cable to the power supply ground terminal, using wire no smaller than motor cable wires. To reduce risk of electrical shock, disconnect power before working on or around the water system.
To avoid a fire hazard and maintain validity of the UL listing, torque the power terminal screws to 12 lb.-in. (1.4 N-m).
Do not use motor or system in swimming areas.
BEFORE BEGINNING WIRING
1. Verify that the power has been shut off at the main breaker.
2. Verify that the dedicated branch circuit for the Artesian
Drive is equipped with a properly-sized circuit breaker. Refer to Table 2 (Page 8) for minimum breaker size.
3. Insert the provided strain relief into the mounting holes on
the bottom of the enclosure. (Strain relief fittings are not supplied for the motor supply cable and power supply leads on AD150145).
4. Remove the Artesian Drive cover. Line up the alignment
notches and slip the memory stick into the slot on the front of the controller. Note: Do not force the stick into place; it should slip into the slot and protrude about 3/4” from the face of the controller with the cover off when fully seated.
5 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
GND
L1
L2
L3
U
V
W
PEPE
IL0731
!
1
2
IL0732
B2
B5
B4
L1 L2 L3 U V W
PE
PE
GND
Output to Motor
IL0747
Figure 6
5. Feed the motor supply cable and 230 VAC power leads through the bottom right and left strain reliefs respectively. Connect the motor ground and power supply ground wires the terminal block marked GND and PE respectively.
Because of the leakage current produced by the internal filtering, permanent fixed ground connections must be made using two independent conductors each with a cross-section equal to or exceeding that of the supply conduc­tors. The drive is provided with two ground terminals marked PE to facilitate this.
6. Connect motor supply leads to terminal block positions
marked U, V and W (right hand side). Connect power leads to terminals marked L1 and L3 (left hand side).
Note: For correct motor rotation and pump performance on F&W manufactured motors, leads 1-7, 2-8 & 3-9 on the motor should be connected to U, V & W respectively. Three phase motors from other manufactures may require that connection U & V be switched at the drive for proper motor rotation and performance.
Figure 8
9. Press the memory stick guard into the slot in the front cover as shown; do not press fully into position. Replace the front cover. Do not over-tighten the screw.
IL0779
Figure 9
Remove Rubber End Cap to Adjust Pressure with 7/32” Allen Wrench
Pressure Sensor Boot
GND
IL0730
Figure10 - Pressure Sensor
Figure 7
10. Connect the other end of the pressure sensor cable with the
7. Feed the pressure sensor leads through the smaller strain relief on the bottom of the Artesian Drive unit and connect the red and black leads to the terminals marked “B2” and “B5” (interchangeable) with a small screwdriver (provided). Make sure to not disconnect the factory installed jumper wire that is already connected to terminal “B2”.
NOTE: A 10-foot section of pressure sensor cable is provided with the controller, but it is possible to use similar 20 AWG wire for distances up to 100 feet from the pressure sensor.
8. Slide the lower enclosure cover into position and tighten
screw on bottom lip as show.
6 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
two spade terminals to the pressure sensor. The connections are interchangeable.
11. Set the pressure tank pre-charge at 70% of the desired water pressure setting. To check the tank’s pre-charge, de­pressurize the water system by opening a tap. Measure the tank pre-charge with a pressure gauge at its inflation valve and make the necessary adjustments.
12. The pressure sensor communicates the system pressure to the Artesian Drive controller. The sensor is preset at the factory to 50 psi, but can be adjusted by the installer using
the following procedure:
!
a. Remove the rubber end-cap.
b. Using a 7/32” Allen wrench (provided), turn the adjusting
screw clockwise to increase pressure and counter­clockwise to decrease pressure. The adjustment range is between 30 and 80 psi (1/4 turn = approximately 3 psi).
c. Replace the rubber end cap.
d. Reset the pressure tank pre-charge to the appropriate
pressure.
e. Cover the pressure sensor terminals with the rubber boot
provided.
exceed the mechanical stop on the pressure sensor or 80 psi.
When increasing the pressure, do not
The pressure sensor may be damaged.
NOTE: Ensure that the system is properly grounded all the way to the service entrance panel. Improper grounding may result in the loss of voltage surge protection and interference filtering.
SPECIAL INSTRUCTIONS FOR OUTDOOR INSTALLATION
To install the Artesian Drive in an outdoor installation, the drive must be placed inside NEMA 3R enclosure (Not Included).
Start-Up and Operation
Apply power to the controller. As long as the display is lit up the system has power. When the display shows  . or
DIAGNOSTIC FAULT CODES
Should an application or system problem occur, built-in diag­nostics will protect the system. The display will change to indicate the nature of the fault. In some cases, the system will shut itself off until corrective action has been taken. Fault
TABLE 5: DIAGNOSTIC FAULT CODES
DISPLAY CODE FAULT POSSIBLE CAUSE CORRECTIVE ACTION
 
 
 . Locked Pump Motor/pump misaligned.
 . Short Circuit When fault is indicated imme-
 . Over Current When fault is indicated while
 .
(Number other than
0.0 & motor is not running)
 .  . Overheated Controller High ambient temperature.
 . Controller Stopped Loose jumper wire Re-insert jumper wire into control
Motor Underload Air-locked pump. Overpumped
Undervoltage Low line voltage. Misconnected
Open Circuit Loose connection. Defective
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
codes and the recommended corrective action for each are listed in the following chart.
supplier for repair.
or dry well. Worn pump. Damaged shaft or coupling. Pump deadhead. Blocked pump or screen.
input leads.
Abrasive/Sand-bound pump.
Dragging pump or motor.
diately after power-up, short circuit due to loose connection, defective cable, splice or motor.
motor is running, over current due to loose debris trapped in pump, or water demand is exceeding pump & motor’s capa­bility.
motor or cable.
Direct sunlight. Obstruction of air-flow.
7 (FW1086)
Do not attempt to carry out internal repairs. Return a faulty drive to the
Wait for well to recover and auto­matic restart timer to time out. If the problem does not correct, check motor and pump. See description of “Intelligent Reset” on Page 18.
Check for loose connections. Check line voltage. Report low voltage to the power company. Unit will start automatically when the proper power is supplied.
Unit will attempt to free a locked pump. If unsuccessful, check the motor and pump.
Check motor wiring. Turn power off till display darkens then apply power again to reset.
Check pump.
With power off, check motor, motor wiring and splices. Make certain all connections are tight. Apply power again to reset.
This fault automatically resets when the temperature returns to a safe level.
terminals B2 & B4.
TABLE 6 SYSTEM TROUBLESHOOTING GUIDE
Symptom Possible Cause Corrective Action
Motor/Pump is running backwards. Reverse connection of motor cable wires at connection
point U & V.
Pump capacity cannot supply the demand. Use pump with higher flow rating (if head requirement is
still satisfied).
Water flow rate is not as high as expected.
Temperature in the controller is too high. If the controller’s heat exchanger becomes too hot, the controller will reduce the switching frequency to the motor to lower the power
Make sure there is at least 4 inches of room around the controller for movement of air. Avoid direct sunlight. Reduce ambient temperature below 104°F (40°C). Increase input voltage if below 230 VAC.
consumption.
Disconnected or broken wire feeding motor. Check motor, motor wiring and splices. Make certain all
connections are tight.
Waterlogged tank. Check tank for bladder damage. Replace if necessary.
Excessive pres­sure fluctuations.
Motor runs con­tinuously with no flow demand.
Pressure tank is too small for flow rating of the pump.
Leak in the household or outdoor plumbing. Check for leaky faucets, valves and/or pipe fittings and
Leak in the pitless adapter. Re-seat the pitless adapter. Replace seal as needed.
Reset the tank pre-charge pressure (should be 70% of pres­sure sensor setting).
Use larger tank (refer to Table 3 on Page 4 for minimum Pressure Tank size).
repair.
flashes PLC as shown, the system is active, but the pump is not running. The display will show  . as shown (where the numbers may be fluctuating) when the pump is running.
IL0748
Figure 11
LEAKY SYSTEMS
Leaky water systems might keep the controller running due to the accurate pressure sensing capability of the pressure sen­sor. Continuous running or starts and stops do not hurt the controller, pump or motor. However, to reduce the on-time of the controller/pump/motor, a “Bump-Mode” procedure has been programmed into the drive. During very low flow (or leaky) conditions this feature periodically increases the speed of the pump several PSI above the set point and shuts off the pump. This adds some time to bleed off before the system starts up again. This “Bump-Mode” can be turned off if desired. Please call Technical Support at 1-800-345-9422 for further details.
NOTE: Artesian Drive maintains a constant pressure at the pressure sensor. Although the pressure is constant at the pressure sensor, pressure drops may be noticeable in other areas of the system when additional taps are opened. This is due to restrictions in the plumbing and will be more pro­nounced the farther the taps are from the pressure sensor. This would be true of any system, and if observed, should not be interpreted as a failure in the performance of the Artesian Drive.
8 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
Although the pressure sensor can be adjusted up to 80 PSI, the maximum obtainable pressure in the system is dependent upon the full load capability of the pump at a given flow. For example, a pump is only capable of producing a pressure of 60 PSI at the flow demand. Increasing the pressure setting of the pressure sensor to 75PSI would only result in the pump running at full speed and producing a pressure of 60 PSI.
UNDERLOAD INTELLIGENT RESET
(Display showing  )
If a motor Underload fault condition occurs, the most likely cause is an overpumped well (dry well) or loss of incoming feed water to the pump. In a dry well situation to allow the well to recover, the Artesian Drive controller will wait 30 seconds to 5 minutes, determined by the amount of time the motor had been running before sensing the underload, before restarting the motor. For example, the first time the fault occurs and the pump has been running 6 minutes, the controller stops the motor and will wait 30 seconds before attempting to restart the pump. If the system would then run for 2 minutes and an underload fault recurs, the controller will wait 3 minutes before attempting to restart the pump. This schedule allows for the minimum off-time possible based on the recovery time of the well or water feed supply.
If there is an obstruction (such as a closed valve) between the pump and the pressure sensor, the controller will also sense an underload is this “dead head” condition stopping the motor to avoid damaging the pump.
6.0
5.0
4.0
3.0
2.0
Off Time (Min.)
1.0
0.0 0 1 2 3 4 5 6 7 8
Run Time (Min.)
IL0750
Figure 12
OVER-TEMPERATURE
The Artesian Drive controller is designed for full power opera­tion in ambient temperatures up to 104°F (40°C) as long as the input voltage is kept at 230 VAC. Under extreme thermal conditions, the controller will reduce the switching frequency in an attempt to avoid shutdown. If the temperature of the controller is still too hot the controller will shut itself off to
avoid causing damage to itself. Full pump output is restored when the controller temperature cools to a safe level.
NOTE: The Artesian Drives are factory programmed to F&W pumps to provide optimum performance and motor protection. The Artesian Drive can be used with other pumps, but the maximum motor amperage needs to be compared to the factory programmed current value (refer to the Specifications section under the appropriate model). If the maximum motor current varies more than 5% from the programmed value, the motor current value in the drive needs to be changed for motor protection and optimum performance. For details on how to change this value in the drive, please contact Technical Support at 1-800-345-9422.
DRIVE SPECIFICATIONS AND DIMENSIONS
Model Number AD052045 AD070059 AD096074 AD096096 AD150145
Voltage 180 -264 AC (Single or Three Phase)
Input from power source
Output to Motor (Three Phase )
For Use With
Pressure Setting
Operating Conditions
Controller Size NEMA 1 ( indoor ) 10.47” H x 3.35” W x 6.15” D 12.54” H x 3.94” W x 6.90” D 15.60” x 4.48” x 8.05”
Weight 2.9 lbs. 3.1 lbs. 4.6 lbs. 4.6 lbs. 9.9 lbs.
RMS = ROOT MEAN SQUARED
* The electrical characteristics of motors vary slightly. See Amp draw on motor nameplate. If the maximum motor cur­rent value (Amp draw) is more than 5% of the programmed value of the Drive, the Drive will need to be set to the current value of the motor to provide proper protection..
Frequency 50/60 Hz
Current (Max) - RMS
Power Factor 1.0 ( constant )
Voltage Voltage Automatically Adjust with Frequency (0 thru 230 Volts)
Frequency Range 15 - 60 Hz
Current, Factory Programmed* (RMS, Each Phase)
Current (Max)
(RMS, Each Phase)
Motor Standard 60 Hz. Pump & 230 Volt 3 Phase Motor Combination
Reference HP Rating* 1 1.5 2 3 5
Factory preset 50 PSI
Adjustable Range 30 - 80 PSI
Temperature
(@ 230 VAC input)
Relative Humidity Max 95% Non-condensing
14.2 Amps 1ø (6.7 Amps 3ø)
4.5 Amps 5.9 Amps 7.4 Amps 9.6 Amps 14.5 Amps
5.2 Amps 7.0 Amps 9.6 Amps 9.6 Amps 15.0 Amps
17.4 Amps 1ø (8.7 Amps 3ø)
23.2 Amps 1ø
(11.9 Amps 3ø)
10° to 40° C ( 14° to 104° F. )
23.2 Amps 1ø
(11.9 Amps 3ø)
29.5 Amps 1ø
(15.7 Amps 3ø)
9 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
Quick Reference Guide to Controller
!
Installation
(Item not to scale)
of passing full pump flow at 100 psi. Install the pressure relief valve between the pump and pressure tank.
pressure resulting in equipment and property damage as well
Many pumps can develop excessive
as possible injury. Always install a pressure relief valve capable
Mounting Screw Locations
Power Supply Connections
B2
B5B4
Pressure Sensor Lead Connections
L2
L1
L3
Mounting Screw Locations
Power Supply from Circuit Breaker
U
V
W
PEPE
B2
B4
B5
GND
L2
L3
L1
U
V
W
L2
L3
L1
PEPE
U
V
W
PEPE
GND
Motor Lead Connections
GND
Power to Motor
Figure 13a - Quick Reference Guide to Controller Installation ­Booster Pumps
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
Pressure Sensor Leads
10 (FW1086)
TABLE 2: MINIMUM PRESSURE TANK
Rated Pump Flow Pressure Tank Size (Total
Volume)
Pump Capacity less than 12
4 Gallon (AT15)
GPM
Pump Capacity greater than
8 Gallon (AT25)
12 but less than 25 GPM
Pump Capacity greater than
14 Gallon (AT44)
25 GPM
The pressure tank pre-charge setting should be 70% of the system pressure sensor setting as indicated in the following table.
TABLE 3: PRESSURE TANK AIR PRECHARGE (PSI)
System Pressure (at
Pressure Sensor)
Pressure Tank
Precharge Setting (± 2
PSI)
30 21
35 25
40 28
45 32
50 35
55 39
60 42
65 46
70 49
75 53
80 56
*NOTE: High pressure applications above 80 PSI should be addressed through the Tech Support group at Flint & Walling (1-800-345-
9422).
GND
From Municipal
Motor
Pressure Sensor Cable (Included)
Check Valve
Isolation Valves
Check Valve
Inlet
Pump
Tank Precharge Inflation Valve
Pressure Tank
Pressure Gauge
Pressure Relief Valve
Discharge into drain rated for max pump output at relief pressure
Drain Valve
Pressure Sensor
To Service
Outlet
11 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
IL0733
B2B4B5
Pressure Sensor Connections
B5
B4
B2
Power Supply Connections
GND
GND
Figure 13b - Quick Reference Guide to Controller Installation ­Centrifugal Pumps
Motor Lead Connections
12 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
Pressure Sensor Cable (Included)
Tank Precharge Inflation Valve
From Municipal
Isolation Valves
Check Valve
Pump
Inlet
Check Valve
Pressure Gauge
Outlet
Motor
Discharge into drain rated for max pump output at relief pressure
Pressure Tank
Pressure Relief Valve
Drain Valve
Pressure Sensor
To Service
13 (FW1086)
95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422
IL0789
Loading...