D-Series with AS-I Installation, Operation & Maintenance
502.969.8000
Installation on Actuator
Orientations, Normal and Reverse Acting
Normal acting is full CW when the process valve is closed and CCW when the process valve is open. Reverse acting
is full CW when the process valve is open and CCW when the process valve is closed.
90° indicator dome assemblies are design to accommodate any mounting arrangement and can be adjusted up to
9° off axis if needed. 45° indicator dome assemblies can only accommodate normal acting applications that are
mounted parallel ±9°. Consult your local distributor or factory representative for 45° reverse acting or mounted
perpendicular applications.
The image to the left shows a TopWorx™ unit mounted
parallel to the process valve in the closed position.
The green arrow at the top shows the “normal acting”
direction of travel to open the valve. This is the standard
orientation and your unit unless otherwise specified will
be factory set to operate in this fashion.
Illustration #2
The image to the right shows a TopWorx™ mounted
perpendicular to the process valve in the closed
position. The green arrow at the top shows the
“normal acting” direction of travel to open the valve.
Notice that the indicator dome has been rotated 90°
compared to the unit above.
Illustration #1
2
www.topworx.com
Installation on Actuator (continued)
Mounting
TopWorx™ has numerous mounting bracket kits available to meet your specific application, whether rotary or linear.
Consult your local distributor or factory representative for ordering information. The illustration shows a direct Namur
mount on a quarter turn valve. Refer to your mounting kit documentation for specific mounting instructions.
Storage
Until conduit, conduit plugs, and any applicable spool valve port connections are properly installed, the TopWorx™
unit will not support its IP/NEMA rating as the unit ships with temporary covers. Ensure that it is stored in a dry
environment with a relative humidity range between 10%-95% and a temperature ranging from -40ºF (-40ºC) to
160ºF (71ºC). Once properly installed, the temperature range listed on the nameplate will supersede this storage
temperature range.
Illustration #3: Mounting Assembly
Installation Notes
1. Use caution not to allow undue axial (thrust) load on the shaft.
2. Cycle the valve a couple of times prior to final tightening of the
mounting kit hardware. This allows the shaft to self-center in the
pinion slot, or coupler. Refer to the dimensions and materials section of this document for appropriate tightening torque.
3. Always use sound mechanical practices when torqueing down any
hardware or making pneumatic connections. Refer to the Integrated
Pneumatic Control Valves section for detailed information on
pneumatic connections.
4. This product comes shipped with plastic plugs in the conduit entri es
in an effort to protect the internal components from debris during
shipment and handling. It is the responsibility of the
receiving and/or installing personnel to provide
appropriate permanent sealing devices to prevent
he intrusion of debris, or moisture, when stored
outdoors or when installed.
5. It is the responsibility of the installer, or end user, to
install this product in accordance with the National
Electrical Code (NFPA 70) or any other national or
regional code defining proper practices.
TM
3
D-Series with AS-I Installation, Operation & Maintenance
Dimensions and Materials: TopWorx™ DXP
502.969.8000
Illustration #4
SHAFT TYPE OPTIONAL
SEE SHAFT DETAIL
SECTION
IN ORDER TO DISINGAGE THE SHAFT FROM THE ID BUSHING
MINIMUM 2.5" REQUIRED CLEARANCE
AND REMOVE LID WHERE OPTIMUM CONDITIONS APPLY
4.52
.85
2.10
MOUNTING SURFACE
OPTIONAL CONDUIT ENTRIES
2.13
6.65
USED ONLY WHEN 4 ENTRIES
ARE SPECIFIED
OPTIONAL CONDUIT ENTRIES
6.21
MATERIALS OF CONSTRUCTION
Cast A360 aluminum with dichro-
Enclosure
Fasteners
Shaft
Shaft
Bushing
Indicator
Dome
Seals
mate conversion coating inside &
out, epoxy coated exterior rated for
250 hrs salt spray per ASTM B117
304 Stainless Steel standard
316 Stainless Steel optional
304 Stainless Steel standard
316 Stainless Steel optional
Oilite Bronze
Polycarbonate, UV F1 rated
O-ring seals available in: Buna &
D-Series with AS-I Installation, Operation & Maintenance
Dimensions and Materials: Shafts
Illustration #8
: Shaft Detail
502.969.8000
8
www.topworx.com
Illustration #9: Enclosure Assembly
TM
Screws are
captive
Pilot Device Options:
See Illustration
#5
#12
O-ring Seal
Sensor
Options:
See
Illustration
pg. 10
#6
Inter nal Ground
Lug
Indicator As semb ly
See Illustration#2
Shaft Assembly
See Illustration#7
#10
Valve Options:
See Illustration #4
#11
Indicator / Dome Replacement Kits
AV-GB002 90º, Green/Open, Red/Closed, Buna O-Ring
AV-YB002 90º, Yellow/Open, Black/Closed, Buna O-Ring
AV-TB002 90º, Green/Thru, Red/Divert, Buna O-Ring
AV-4B002 90º, Green/Open, Red/Closed, Buna O-Ring
Conduit Entry
External Ground Lug
Illustration #10: Indicator Assembly
Indicator Dome,
O
+
5 adjustable
Polycarbonate
with keyed mask.
Several rotation and
form options.
Available in Buna-N,
Silicone, EPDM, Viton
O-ring
Color-coded Indicator is
available in several
coordinating rotations and
forms for various valve
types, such as 90 , 180
and Thru-divert applications.
10-32 Captive screws,
Stainless (x4)
00
9
D-Series with AS-I Installation, Operation & Maintenance
502.969.8000
Illustration #11: SCM-ASI
Sensor Communication Module
Calibration
Switch
CLOSE ASI OPEN
-
AS-i
Terminals
Solenoid
Terminals
Solenoid Note: Internal mount pilot in the DXP/DXS is 0.6W. For any externally mounted, or customer supplied, solenoid valve 4 watt maximum
power consumption is allowed. A 170 mA max surge current limitation is required to prevent activation of the short circuit protection.
I
S
A
+
LEDs
Open
Outputs
TopWorx
SCM-ASi 2.1
Close
AUX Input
Inputs
Terminals
- D2 + - D3 +
Illustration #12: SCM-ASI
Wiring Diagram
D-Series with ASi Wiring
Step 1
For internally-mounted or external pilot device(s), wire the ‘+’
and ‘-’ leads to the terminals marked D0 (open) and D1
(closed). The internally-mounted pilot has an LED indicator
for power verification. Note: For an externally mounted
solenoid valve, 4 watt maximum power consumption
is allowed. A 160 mA surge current limit is required to
prevent activation of the short circuit protection circuit.
Step 2
Connect the AS-i communication wires to the terminals
marked AS-i ‘+’ and AS-i ‘-’ . (See Illustration 12 for wiring
diagram) Note:For calibration of the switches, a 24 VDC
power supply may be used instead of an ASI Controller.
If an ASI Controller is not available, wire +24 VDC to
ASI+, and GND to ASI-. The calibration switch will still be
able to actuate the valve.
Additional Instruction for wiring an external switch input.
For externally mounted auxiliary input limit switches, wire
switches to the terminals marked -D2+ for the open switch
and -D3+ for the closed limit switch.
Profile S-B.A.0
Device ID
Device I/O
Inputs
D2 Open Limit Switch
D3 Closed Limit Switch
new TopWorx AS-i 2.1 module, make sure the input and
output data bit positions are updated as indicated above.
AS-i Specifications
A Free Profile
B 2 Inputs / 2 Outputs
0 Switch Open
1 Switch Closed
0 De-energize Solenoid
1 Energize Solenoid
closed solenoid current
Max solenoid current = 160mA
per outputMax power = 4 watts per output)
Calibrating Limit Switches inside the SCM-ASi Module
Never perform the switch calibration procedure where area is known to be hazardous.
Step 1
Once pneumatic hookup and wiring has been completed
close the valve using the SCM-ASI on-board calibration
switch, as seen in Illustration 11. If no AS-i network connection is available, you may connect a 24VDC power supply to
the + ASI - terminals as previously described.
Step 2
With the valve in the CLOSED position, disengage the
BOTTOM Cam from the splined Hub and rotate Clockwise
until the Red LED lights. Release the Cam to re-engage the
splined Hub.
Step 3
Open the valve by sliding the calibration switch to the OPEN
position.
Step 4
Once the valve is in the OPEN position, disengage the TOP
cam from the splined hub and rotate Counter-clockwise until
the Green LED lights. Release the Cam to re-engage the
splined Hub.
Step 5
Cycle the valve CLOSED and OPEN several times using the
calibration switch to verify both limit switches are
maintaining their set points.
Step 6
Finally, slide the calibration switch to the ASI position. The AS-i
network will now have full control of the valve once the SCMASI has been addressed.
10
www.topworx.com
TM
Pneumatic Hookup Procedures
Prior to connecting the supply air to the spool valve, flush the
system to remove any debris or contaminates. Galvanized
pipe can easily flake and contaminate the system and therefore is not recommended. A 40 micron point of use filter at
every device is recommended.
4-Way Spool Valves
The TopWorx spool valve is a 5 port, 4-way valve driven by
an internally mounted pilot valve. The spool valve supply port
and work ports are marked as follows:
***Never Plug, Block or Restrict Port 5***
5
4
DOUBLE ACTI NG ACT UATORSSPRING RETURN A CTUATORS
Supply
1
Always install vents
or speed controls
3
2
Port to OpenPort to Cl o se
Highly Recommended
TopWorx highly recommends Locktite 567 brand thread sealant. Do not use a hard setting pipe compound. If Teflon
thread seal tape is used, start the wrap on the second thread
from the leading thread of the fitting. This will prevent tape
shreds from contaminating the spool valve seals.
Breathers (AL-M31) should be installed in the exhaust ports
to keep debris from falling into the spool valve and damaging
the seals. This must be addressed prior to installation, or
storage.
A flow control may be used in Port 3, but should NEVER BE
USED in Port 5. Any blockage or restriction may cause an
internal pressure build-up inside the encloser and pose a
safety issue.
Supply
1
2
Port to Open
3
/Close
5
4
Plug
Spool Valve Specifications
Medium Dried, filtered air (40 micron)
Max Operating
Pressure
Min. Operating
Pressure
Ambient
Temperature Range
Flow Coefficient 1.2Cv or 3.0Cv
Environment Rating Type 4, 4X, IP67
Port Size 1/2” NPT for 3.0Cv valve
Manual Override Available in Latching/Non-Latching
Valve Body Available in Hardcoat Anodized
Valve Seals Spool Seals: Buna-N
100psi (0.7 MPa) (6.89Bar)
30psi (0.28 MPa) (2.76Bar)
Refer to Product Nameplate Marking
1/4" NPT for 1.2Cv valve
Push Type & Palm Actuator Type
Aluminum, 304, or 316 Stainless Steel
Valve Body Seals available in
Buna & Silicone,
Don’t forget!
TopWorx has a complete line of
breathers, flow controls, regulators
and filters.
Check out www.topworx.com or call
us at 502.969.8000 for more details
11
D-Series with AS-I Installation, Operation & Maintenance
**Orifice only applicable to Explosion Proof units.
All others use standard fitting.
12
4-40x.25 (x2)
4-40x0.25 (x2)
Coil 2
4- 40 x .25"
SEM screw
TORQUE
100 IN-OZ
Bracket
SINGLE PILOT ASSEMBLY
4- 40 x .25"
SEM screw
TORQUE
100 IN-OZ
Bracket
Coil 1
Pilot
Assembly
RED Urethane
Tubing (Supply)
YELLOW Urethane
Tubing (Work)
YELLOW Urethane
Tubing (Work)
10-32 Metal Plug
Barbed
“Y” Fitting
RED Urethane
Tubing (Supply)
Pilot
Assembly
YELLOW Urethane
Tubing (Work)
10-32 Metal Plug
Orifice
Assembly
10-32 Metal
Barb Fitting
TORQUE 60 IN-OZ
Orifice
Assembly
10-32 Metal
Barb Fitting
TORQUE 60 IN-OZ
ORIFICE TO BE USED
IN EXPLOSION PROOF
APPLICATIONS ONLY
www.topworx.com
TM
Safe Use
Special Conditions of Safe Use (All installations)
Clean only with a damp cloth to prevent possibility of electrostatic discharge.
For Explosion Proof installations, the internal ground connection shall be used and the external ground connection, if
supplied in addition, is supplemental bonding allowed where local authorities permit, or is required.
When installing with a third party listed nipple-mount solenoid, it is the responsibility of the installer to provide fittings,
and apparatus, suitable for the area classification in accordance with the National Electrical Code.
All cable entry devices or conduit stopping boxes shall be certified in type of explosion protection ‘d’, suitable for the
conditions of use and correctly installed.
The IIC enclosures are excluded from use in carbon disulphide atmospheres.
The air pressure to the valve block, when fitted, shall not exceed 7bar.
Preventative Maintenance
The TopWorx™ Discrete Valve Controllers are designed to operate for one million cycles without servicing. Call
TopWorx when you are approaching this milestone for a preventative maintenance kit and instructions.
13
D-Series with AS-I Installation, Operation & Maintenance
Certifications & Approvals
502.969.8000
14
www.topworx.com
Warranty
TM
15
GLOBAL SUPPORT OFFICES
North America
3300 Fern Valley Road
Louisville, Kentucky 40213 USA
1 502 969 8000
info.topworx@emerson.com
Middle East
P.O. Box 17033
Jebel Ali Free Zone
Dubai 17033
United Arab Emirates
+971 4 811 8283
info.topworx@emerson.com
24 Angus Crescent
Longmeadow Business Estate East
Modderfontein
Gauteng
South Africa
27 011 451 3700
info.topworx@emerson.com
Visit www.topworx.com for comprehensive information on our company,
capabilities, and products — including model numbers, data sheets,
specifications, dimensions, and certifications.
info.topworx@emerson.com
www.topworx.com
Europe
Horsfield Way
Bredbury Industrial Estate
Stockport
SK6 2SU UK
44 0 161 406 5155
info.topworx@emerson.com