WARNING
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing any maintenance operations:
D Always wear protective clothing
and eyewear.
D Do not remove the actuator from the valve while the valve is still pressurized.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the actuator cannot suddenly open or close the control valve.
D Use bypass valves or completely shut off the process to isolate the control valve from process pressure. Relieve process pressure from both sides of the control valve.
D Vent the pneumatic actuator loading pressure and relieve any actuator spring precompression.
D Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
Refer to figure 2 and the parts list for mounting parts identification. Refer to the DVC6200 or DVC2000 digital valve controller instruction manual for digital valve controller parts identification. Refer to the appropriate actuator instruction manual for actuator installation,operation, maintenance, and parts identification.
1. Isolate the control valve from the process line pressure, and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from the actuator. Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
Digital Valve Controller on
Old NAMUR Rotary Actuators
2. Attach the coupler (key 3) to the actuator shaft using the hex socket cap screw (key 4) and tighten.
3. Place the pointer (key 8) before attaching the magnet assembly (key 6) to the coupler using the pan head screws (key 7) and tighten. The magnet assembly must be oriented per figure 1, so that the flats are approximately as shown relative to the channel in the instrument housing at the actuator mid-travel position.
4. Attach the digital valve controller to the mounting bracket (key 2) using the hex head cap screws (key 5). Allow for minor adjustments if needed.
5. Attach the mounting bracket (key 2) loosely to the actuator using only two of the hex head cap screws (key 1, select metric or inch fasteners, as appropriate for actuator) on the same side of the bracket. Slide the mounting plate (key 9) under the two hex head cap screws and insert two remaining hex head cap screws. Visually center the magnet assembly and digital valve controller and tighten all fasteners.
6. Attach the travel indicator scale (key 10) to the mounting plate (key 9) using plain washer (key 11) and cap screws (key 12). Refer to figure 2.
7. Connect and calibrate the instrument as described in the appropriate instruction manual.
For additional information concerning the mounting, setup, calibration, and maintenance of the DVC6200 or the DVC6000 digital valve controller refer to the appropriate instruction manual.
Note
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use, or maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and end user.
www.Fisher.com
DVC6200 or DVC2000 Digital Valve Controller on Old NAMUR Rotary Actuators
ORIENTATION AT ONE TRAVEL EXTREME
ORIENTATION AT MID-TRAVEL (FLATS PARALLEL TO INSTRUMENT HOUSING CHANNEL)
Mounting Instructions
D103459X012
November 2010
DVC6200
ORIENTATION AT THE OTHER TRAVEL EXTREME
DVC2000
Figure 1. Magnet Assembly Orientation