Fisher Mounting Instructions: DVC6200 Digital Valve Controller on Fisher 585C and 471, Size 60-130 with 0.56 to 4 Inch Travel Except 585C Size 68 (Linear Roller Cam) Manuals & Guides

DVC6200 Digital Valve Controller on Fisher 585C
_
Mounting Instructions
D103465X012 June 2010
Use these instructions to mount a Fisher® FIELDVUETM DVC6200 digital valve controller on Fisher 585C and 471 Size 60 -130 actuators, with 0.56 to 4 inch travel, except 585C Size 68.
Avoid personal injury or property damage from sudden re of parts. Before performing any installation operations:
lease of process pressure or bursting
Always wear protective clothing, gloves,
and eyewear.
Do not remove the actuator from the valve
while the valve is still pressurized.
Disconnect any operating lines providing
air pressure, electric power, or a control signal to the actuator. Be sure the actuator cannot suddenly open or close the control valve.
Use bypass valves or completely shut off
the process to isolate the control valve from process pressure. Relieve process pressure from both sides of the control valve.
Vent the pneumatic actuator loading
pressure and relieve any actuator spring precompression.
Use lock-out procedures to be sure that
the above measures stay in effect while you work on the equipment.
Check with your process or safety
engineer for any additional measures that must be taken to protect against process media.
Refer to figure 3 and the parts list for mounting parts identification. Refer to the DVC6200 digital valve controller instruction manual for digital valve controller parts identification. Refer to the appropriate actuator instruction manual for actuator installation, operation, maintenance, and parts identification. Figure 1 shows the arced feedback assembly.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from actuator. Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
2. During the attachment of cam (key 2) to the valve stem connector it will be necessary to remove the stem connector cap screws. Consult the appropriate actuator
and 471 Size 60-130 with 0.56 to 4 Inch Travel
Except 585C Size 68 (Linear Roller Cam)
instruction manual for proper actuator disassembly and reassembly.
3. Attach the cam (key 2) to the stem connector using two stud bolts (key 1), four plain washers (key 3) and four hex nuts (key 4). In addition to this, use spacers (key 5) to attach the cam to stem connector, if provided, as shown in figure 4.
4. Attach plate mounting face hex head screws (key 8). Similarly, attach the mounting plate to bottom yoke mounting by using a spacer (key 9), stud (key 10), plain washer (key 11) and hex nut (key 12).
5. Attach the digital valve controller to the arced feedback assembly (key 15) using the four metric hex socket cap screws (key 14).
6. Attach the arced feedback assembly along with the digital valve controller to the mounting plate using the four imperial hex socket cap screws (key 13) as shown in figure 3. Ensure that the roller of arced feedback assembly is centered and resting on the cam surface as shown in figure 2.
7. Ensure that the cam is positioned so that when the actuator stem is fully retracted the roller lines up with the mark on the cam.
8. Make pneumatic and electrical connections to the digital valve controller as described in the digital valve controller instruction manual.
9. It may be necessary to fine tune the placement of the cam so that the digital valve controllers receives the proper feedback, by lining up as shown in figure 2.
10. Setup and described in instruction manual or quick start guide.
For additional information concerning mounting, setup, calibration, and maintenance of the DVC6200 digital valve controller, refer to the appropriate instruction manual.
mounting (key 6) to actuator yoke top
using two lock washers (key 7) and two
calibrate the
digital valve controller as
Note
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end user.
_____________________________________________________________________________________________________
www.Fisher.com
DVC6200 Digital Valve Controller on Fisher 585C
y
and 471 Size 60-130 with 0.56 to 4 Inch Travel Except 585C Size 68 (Linear Roller Cam)
PART LIST
KEY QTY PARTS NAME
1 2 STUD BOLTS, CONT THD 2 1 CAM 3 4 PLAIN WASHER 4 4 HEX NUT 5 2 SPACER 6 1 PLATE MOUNTING 7 2 LOCK WASHER 8 2 HEX HD SCREWS
9 1 SPACER 10 1 STUD BOLTS CONT THD 11 1 PLAIN WASHER 12 1 HEX NUT 13 4 SOCKET SCREWS (IMPERIAL)1 14 4 SOCKET SCREWS (METRIC)2
15
1 ARCED FEEDBACK ASSEMBLY
1. THE IMPERIAL SOCKET SCREWS CAN BE IDENTIFIED BY THE COARSER THREADS.
2. METRIC SOCKET SCREWS HAVE A SLIGHTLY LARGER HEAD THAN THE IMPERIAL SOCKET SCREWS.
Figure 2. Installing Cam and Roller Feedback Assembl
Figure 1.Linear Roller Feedback
Mounting Instructions
D103465X012
June 2010
GE42132