ounting Instructions
D103453X012 May 2010
Use these instructions to mount a Fisher® FIELDVUE™ DVC6200 digital valve 30-68 actuator.
Avoid personal injury or property damage from sudden release of process pressure or bursting of parts. Before performing any installation operations:
Always wear protective clothing, gloves, and
eyewear.
Do not remove the actuator from the valve while
the valve is still pressurized.
Disconnect any operating lines providing air
pressure, electric power, or a control signal to the actuator. Be sure the actuator cannot suddenly open or close the control valve.
Use bypass valves or completely shut off the
process to isolate the control valve from process pressure. Relieve process pressure from both sides of the control valve.
Vent the pneumatic actuator loading pressure
and relieve any actuator spring precompression.
Use lock-out procedures to be sure that the
above measures stay in effect while you work on the equipment.
Check with your process or safety engineer for
any additional measures that must be taken to protect against process media.
Refer to figure 2 for mounting parts identification for 1061 Size 30-68. Refer to the DVC6200 digital valve controller instruction manual for parts identification. Refer to the appropriate actuator instruction manual for actuator installation, operation, maintenance, and parts identification.
1. Isolate the control valve from the process line pressure and release pressure from both sides of the valve body. Shut off all pressure lines to the actuator, releasing all pressure from actuator.
Use lock-out procedures to be sure that the above measures stay in effect while you work on the equipment.
_____________________________________________________________________________________________________
wMww.Fisher.com
controller on Fisher 1061, size
on 1061, Size 30-68 Actuator
Window Mount
2. Remove the cover plate screws and cover plate from the actuator, if present.
3. Install the cam (key 1) on to the lever of actuator. It is necessary for use of the arced feedback mechanism. Consult with the appropriate actuator instruction manual for proper actuator disassembly and reassembly.
4. Attach the cam (key 1) to the lever arm of the actuator using hex head cap screws (key 2). Ensure that th
5. Attach the d feedback assembly (key 3) as per the actuator requirement using hex socket cap screws (key 4).
6. Attach the arced feedback assembly (key 3), along with the digital valve controller to the yoke of the actuator using hex socket cap screws (key 5) as shown in figure 2.
7. Ensure that the roller of the arced feedback assembly is centered and resting on the cam surface.
8. Make pneumatic and electrical connections to the digital valve controller as described in the digital valve controller instruction manual.
9. It may be necessary to fine tune the placement of the cam so that the digital valve controller receives the proper feedback.
10. Setup and calibrate the digital valve controller as described in the digital valve controller instruction manual or quick start guide.
For additional information concerning mounting, setup, calibration, and maintenance of the DVC6200 digital valve controller, refer to the appropriate instruction manual.
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for the selection, use and maintenance of any product remains with the purchaser and end user.
e cam is oriented as shown in figure 2.
igital valve controller to the arced
Note
DVC6200 Digital Valve Controller
(
)
r
on 1061, Size 30-68 Actuator
Window Mount
Mounting Instructions
D103453X012
May 2010
GE42132
*NOTE: The DVC6200 uses 4 M8 socket screws (key 4) for mounting onto arced feedback assembly.
Figure 1. Arced Feedback Assembly
for 1061 Size 30-68
DVC6200 Mounting Kit on 1061 Size 30-68 Actuator
PARTS LIST
KEY QTY DESCRIPTION
1 1 CAM 2 2 10-24UNCX0.50” HEX HD SCREWS 3 1 ARCED FEEDBACK ASSEMBLY
* 4 4 M8X1.25X16 SOCKET SCREWS
5 4 5/16-18X0.62 SOCKET SCREWS
GG07386
1061 Size 30-68 Actuator with DVC6200 Digital Valve Controlle
Figure 2. Mounting Parts Identification