Fisher Manuals & Guides: FM Hazardous Area Approvals for Fisher i2P-100 Electro-Pneumatic Transducer Manuals & Guides

Instruction Manual Supplement
D104193X012
i2P-100 Transducer - FM
July 2018
FM Hazardous Area Approvals
Fisher
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installation in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the i2P-100 instruction manual (D103198X012
Always refer to the nameplate itself to identify the appropriate certification.
i2P-100 Electro‐Pneumatic Transducer
), available from your Emerson sales office or Local Business Partner, or at www.Fisher.com.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, and area re‐classification.
Special Conditions of Use
Intrinsically Safe, Explosion-proof, Type n, Non‐incendive, Dust‐Ignition proof
1. When product is used with natural gas as the pneumatic medium, the maximum working pressure of the natural gas supply is limited to 50 psi.
2. When product is used with natural gas as the pneumatic medium the product shall be provided with the proper remote venting, as described in the i2P-100 instruction manual (D103198X012).
3. The apparatus enclosure contains aluminum and is considered to constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.
Refer to table 1 for additional information.
www.Fisher.com
i2P-100 Transducer - FM
July 2018
Instruction Manual Supplement
Table 1. Additional Approval Information
Certification Body Certification Obtained Entity Rating Temperature Code
FM
IS Intrinsically Safe Class I, II, III Division 1 GP A, B,C,D,E,F,G per drawing GE07470 (see figure 1) Class I Zone 0 AEx ia IIC T3/T4/T5 per drawing GE07470 (see figure 1)
XP Explosion Proof Class I, Division 1, GP A,B,C,D T5/T6 Class I Zone 1 AEx d IIC T5/T6 NI Non-incendive Class I, Division 2, GP A,B,C,D T5/T6 Type n Class I, Zone 2 AExnC IIC T5/T6 DIP Dust-ignition proof Class II, III Division 1, GP E,F,G T5/T6 S Suitable for Use Class II, III Division 2, GP F,G T5/T6
Vmax = 30 VDC Imax = 100 mA Pi = 1.0 W Ci = 0 uF Li = 0 uH
- - -
T3 (Tamb 85°C) T4 (Tamb 81°C) T5 (Tamb 46°C)
T5 (Tamb 85°C) T6 (Tamb 75°C)
Figure 1. FM Loop Schematic (Drawing GE07470)
D104193X012
HAZARDOUS LOCATION
INTRINSIC SAFETY CLASS I, II, III, DIV 1, GROUPS A,B,C,D,E,F,G CLASS I, ZONE 0 AEx ia IIC
NON-INCENDIVE CLASS I, DIV 2, GROUPS A,B,C,D
FISHER TYPE: i2P-100
Vmax = 30 Vdc Imax = 100 mA Ci = 0 nF Li = 0 mH Pi = 1.0 W
NOTES:
1. THE INSTALLATION MUST BE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC), NFPA 70, ARTICLE 504 AND ANSI/ISA RP12.6 OR ARTICLE 505.
2. CLASS 1, DIV 2 APPLICATIONS MUST BE INSTALLED AS SPECIFIED IN NEC ARTICLE 501-4(B). EQUIPMENT AND FIELD WIRING IS NON-INCENDIVE WHEN CONNECTED TO APPROVED BARRIERS WITH ENTITY PARAMETERS.
3. LOOPS MUST BE CONNECTED ACCORDING TO THE BARRIER MANUFACTURER'S INSTRUCTIONS.
4. MAXIMUM SAFE AREA VOLTAGE SHOULD NOT EXCEED 250 Vrms.
5. RESISTANCE BETWEEN BARRIER GROUND AND EARTH GROUND MUST BE LESS THAN ONE OHM.
6. NORMAL OPERATINGI CONDITIONS 30 Vdc 20 mADC.
7. FOR ENTITY INSTALLATION (I.S. AND N.I.):      Vmax > Voc, or Vt Ci + Ccable < Ca      Imax > Isc, or It   Li + Lcable < La      Pi > Po, or Pt
GE07470_B
NON-HAZARDOUS LOCATION
FM APPROVED BARRIER
WARNING:
THE APPARATUS ENCLOSURE CONTAINS ALUMINUM AND IS CONSIDERED TO CONSTITUTE A POTENTIAL RISK OF IGNTION BY IMPACT OR FRICTION. AVOID IMPACT AND FRICTION DURING INSTALLATION AND USE TO PREVENT RISK OF IGNITION.
2
Loading...
+ 1 hidden pages