Fisher IM Supplement: Module Definitions, IO Bytes, and Data Length for FIELDVUE DVC6200p PROFIBUS PA Digital Valve Controller Manuals & Guides

Instruction Manual Supplement
D104019X012
DVC6200p
November 2017
Module Definitions, IO Bytes, and Data Length
for FIELDVUE
DVC6200p PROFIBUS PA Digital
Valve Controller
Contents
AO Module 3..................................
DO Module 9..................................
DI Module 10..................................
A GSD file contains information about the device capabilities.
Modules are defined within the GSD. Each module represents a distinct sub set of parameter values for a specific function block in the DVC6200p; each function block can have one or more modules defined.
Slots originate in the Class 1 Master (Configuration Host) and represent an address range of bytes. Typically, slots will define address ranges for Input values (I) and other address ranges for Output values (Q).
If a Slot is not used it must NOT be null or blank. It must be assigned as an Empty Module.
Modules are assigned to specific Slots. For example any of the AO modules must be assigned to Slot 1. If a DO module is required it must be assigned to Slot 3. The slot assignments are defined in the device GSD file FC051037.gsd.
Slot Definition Slot (1) = AO 21 1,2,3,4,5,6,7,8,9,10,11,12,13,14,15 Slot (2) = AI 16 1,16,17 Slot (3) = DO 18 1,18,19,20,21,22,23,24 Slot (4) = DI 1 1 25 1,25 Slot (5) = DI 2 2 25 1,25
Note
The AO module is always assigned to the first slot. In some systems the first slot is defined as 0; consequently the AO module will be defined as Slot 0, the AI module will be defined as Slot 1, etc.
Module
www.Fisher.com
DVC6200p
November 2017
Instruction Manual Supplement
D104019X012
The example below shows an AO Module, number 5, assigned to Slot 1. The slots that are not used have been assigned as an EMPTY_MODULE. Different Class 1 Masters will present different views and may have a different number of configurable slot locations.
The below example is from a Siemens PCS7. On the right pane the DVC6200p is selected. All of the modules available for the device are listed. In this example Module 9 has been selected.
With the graphic image of the DVC6200p highlighted slot assignments are made in the table for the DVC6200p.
The AO module 9 has been assigned to Slot 0 (the first slot) in this example. Unused slots must be defined as EMPTY_MODULE as shown below and not as Blank or Null. Most control systems define the Inputs (I) and Output (Q) address ranges automatically.
2
Instruction Manual Supplement
D104019X012
AO Module
Slot 1 Assignment
Module Module Name Input Bytes Output Bytes
1 EMPTY_MODULE 0 0
2 AO_SP(S) 0 5
3 AO_SP(L) 0 5
4 AO_SP_RDBK_POSD(S) 7 5
5 AO_SP_RDBK_POSD(L) 7 5
6 AO_SP_CKBK(S) 3 5
7 AO_SP_CKBK(L) 3 5
8 AO_SP_RDBK_POSD_CKBK(S) 10 5
9 AO_SP_RDBK_POSD_CKBK(L) 10 5
10 AO_RIN_ROUT(S) 5 5
11 AO_RIN_ROUT(L) 5 5
12 AO_RIN_ROUT_CKBK(S) 8 5
13 AO_RIN_ROUT_CKBK(L) 8 5
14 AO_SP_RDBK_RIN_ROUT_POSD(S) 15 10
15 AO_SP_RDBK_RIN_ROUT_POSD(L) 15 10
DVC6200p
November 2017
Module 2
AO_SP(S)
Module Definition AO_SP(S)
Input data length 0
Output data length 5
Parameter data length 0
Identifiers 0xA4
Module 3
AO_SP(L)
Module Definition AO_SP(L)
Input data length 0
Output data length 5
Parameter data length 0
Identifiers 0x82, 0x84, 0x8, 0x5
AO_SP(S) AO_SP(L)
SP Setpoint
Output (master view)
Initial Address 0
1 SP -
2 floating-point number
3
4 SP - status
3
DVC6200p
November 2017
Module 4
AO_SP_RDBK_POSD(S)
Module Definition AO_SP_RDBK_POSD(S)
Input data length 7
Output data length 5
Parameter data length 0
Identifiers 0x96, 0xA4
Module 5
AO_SP_RDBK_POSD(L)
Module Definition AO_SP_RDBK_POSD(L)
Input data length 7
Output data length 5
Parameter data length 0
Identifiers:
0xC6, 0x84, 0x86, 0x8, 0x5, 0x8, 0x5, 0x5, 0x5
Instruction Manual Supplement
AO_SP_RDBK_POSD(S) AO_SP_RDBK_POSD(L)
READBACK, POS_D, SP
Readback, position discrete, setpoint
Input (master view)
Initial Address 0
Output (master view)
Initial Address 0
D104019X012
1 READBACK -
floating-point
2
number 3
4 READBACK - status
5 POS_D
6 POS_D - status
1 SP -
floating-point 2
number 3
4 SP - status
Module 6
AO_SP_CKBK(S)
Module Definition AO_SP_CKBK(S)
Input data length 3
Output data length 5
Parameter data length 0
Identifiers 0x92, 0xA4
Module 7
AO_SP_CKBK(L)
Module Definition AO_SP_CKBK(L)
Input data length 3
Output data length 5
Parameter data length 0
Identifiers 0xC3, 0x84, 0x82, 0x8, 0x5, 0xA
AO_SP_CKBK(S) AO_SP_CKBK(L)
Checkback, SP Checkback, setpoint
Input (master view)
Initial Address 0
Output (master view)
Initial Address 0
1 CHECKBACK
2
1 SP -
floating-point 2
number 3
4 SP - status
4
Instruction Manual Supplement
D104019X012
Module 8
AO_SP_RDBK_POSD_CKBK(S)
Module Definition AO_SP_RDBK_POSD_CKBK(S)
Input data length 10
Output data length 5
Parameter data length 0
Identifiers 0x99, 0xA4
Module 9
AO_SP_RDBK_POSD_CKBK(L)
AO_SP_RDBK_POSD(S) AO_SP_RDBK_POSD(L)
READBACK, POS_D, SP
Readback, position discrete, setpoint
Input (master view)
Initial Address 0
DVC6200p
November 2017
1 READBACK -
2 floating-point number
3
4 READBACK - status
5 POS_D
6 POS_D - status
Module Definition AO_SP_RDBK_POSD_CKBK(L)
Input data length 10
Output data length 5
Parameter data length 0
Identifiers
0xC7, 0x84, 0x89, 0x8, 0x5, 0x8, 0x5, 0x5, 0x5, 0xA
Module 10
AO_RIN_ROUT(S)
Module Definition AO_RIN_ROUTS(S)
Input data length 5
Output data length 5
Parameter data length 0
Identifiers 0xB4
Module 11
AO_RIN_ROUT(L)
Module Definition AO_RIN_ROUT(L)
Input data length 5
Output data length 5
Parameter data length 0
Identifiers
0xC4, 0x84, 0x84, 0x8, 0x5, 0x8, 0x5
Output (master view)
Initial Address 0
AO_RIN_ROUTS(S) AO_RIN_ROUTS(L)
RCAS_OUT RCAS_IN
Remote cascade output, remote cascade input
Input (master view)
Initial Address 0
Output (master view)
Initial Address 0
1 SP -
2 floating-point number
3
4 SP - status
1 RCAS_OUT -
2 floating-point number
3
4 RCAS_OUT - status
1 RCAS_IN -
2 floating-point number
3
4 RCAS_IN - status
5
DVC6200p
November 2017
Module 12
AO_RIN_ROUT_CKBK(S)
Module Definition AO_RIN_ROUT_CKBK(S)
Input data length 8
Output data length 5
Parameter data length 0
Identifiers 0x97, 0xA4
Module 13
AO_RIN_ROUT_CKBK(L)
Instruction Manual Supplement
AO_RIN_ROUT_CKBK(S) AO_RIN_ROUT_CKBK(L)
RCAS_OUT CHECKBACK RCAS_IN
Readback cascade output, checkback, remote cascade input
Input (master view)
Initial Address 0
D104019X012
1 RCAS_OUT -
2 floating-point number
3
4 RCAS_OUT - status 5 6
CHECKBACK
7
Module Definition AO_RIN_ROUT_CKBK(L)
Input data length 8
Output data length 5
Parameter data length 0
Identifiers
0xC5, 0x84, 0x87, 0x8, 0x5, 0x8, 0x5, 0xA
Output (master view)
Initial Address 0
1 RCAS_IN -
2 floating-point number
3
4 RCAS_IN - status
6
Instruction Manual Supplement
D104019X012
Module 14
AO_SP_RDBK_RIN_ROUT_POSD_CKBK(S)
Module Definition
Input data length 15
Output data length 10
Parameter data length 0
Identifiers 0x9E, 0XA9
AO_SP_RDBK_RIN_ROUT_POSD_ CKBK(S)
Module 15
AO_SP_RDBK_RIN_ROUT_POSD_CKBK(L)
Module Definition
Input data length 15
Output data length 10
Parameter data length 0
Identifiers
AO_SP_RDBK_RIN_ROUT_POSD_ CKBK(L)
0xCB, 0x89, 0x8E, 0x8, 0x5, 0x8, 0x5, 0x8, 0x5, 0x8, 0x5
November 2017
AO_SP_RDBK_RIN_ROUT_POSD_CKBK(S) AO_SP_RDBK_RIN_ROUT_POSD_CKBK(L)
READBACK, RCAS_OUT, POS_D, CHECKBACK, SP, RCAS_IN
Readback, remote cascade output, position discrete, checkback, setpoint, remote cascade input
Input (master view)
Initial Address 0
1 READBACK -
2 floating-point number
3
4 READBACK - status 5 6
RCAS_OUT ­floating-point number
7 8 9 RCAS_OUT - Status 10 POS_D 11 POS_D - Status 12 13
CHECKBACK
14
DVC6200p
Output (master view)
Initial Address 0
1 SP -
2 floating-point number 3 4 SP - status 5 6
RCAS_IN ­floating-point number
7 8 9 RCAS_IN - Status
7
DVC6200p
November 2017
AI Module
Slot 2 Assignment
Module Module Name Input Bytes Output Bytes
16 AI_OUT(S) 5 0
17 AI_OUT(L) 5 0
Module 16
AI_OUT(S)
Module Definition AI_OUTS(S)
Input data length 5
Output data length 0
Parameter data length 0
Identifiers 0x94
Module 17
Instruction Manual Supplement
D104019X012
AI_OUT(L)
Module Definition AI_OUTS(L)
Input data length 5
Output data length 0
Parameter data length 0
Identifiers 0x42, 0x84, 0x5
8
Instruction Manual Supplement
D104019X012
DO Module
Slot 3 Assignment
Module Module Name Input Bytes Output Bytes
18 DO_SP 0 2
19 DO_SP_RDBK 2 2
20 DO_SP_CKBK 3 2
21 DO_SP_RDBK_CKBK 5 2
22 DO_RIN_ROUT 2 2
23 DO_RIN_ROUT_CKBK 5 2
24 DO_SP_RDBK_RIN_ROUT_CKBK 7 4
DVC6200p
November 2017
Module 18
DO_SP
Module Definition DO_SP
Input data length 0
Output data length 2
Parameter data length 0
Identifiers 0xA1
Module 19
DO_SP_RDBK
Module Definition DO_SP_RDBK
Input data length 2
Output data length 2
Parameter data length 0
Identifiers 0xC1, 0x81, 0x81, 0x83
Module 20
DO_SP_CKBK
Module Definition DO_SP_CKBK
Input data length 3
Output data length 2
Parameter data length 0
Identifiers 0xC1, 0x81, 0x82, 0x92
Module 22
DO_RIN_OUT
Module Definition DO_RIN_ROUT
Input data length 2
Output data length 2
Parameter data length 0
Identifiers 0xC1, 0x81, 0x81, 0x8C
Module 23
DO_RIN_ROUT_CKBK
Module Definition DO_RIN_ROUT_CKBK
Input data length 5
Output data length 2
Parameter data length 0
Identifiers 0xC1, 0x81, 0x84, 0x9C
Module 21
DO_SP_RDBK_CKBK
Module Definition DO_SP_RDBK_CKBK
Input data length 5
Output data length 2
Parameter data length 0
Identifiers 0xC1, 0x81, 0x84, 0x93
Module 24
DO_SP_RDBK_ROUT_CKBK
Module Definition DO_SP_RDBK_RIN_ROUT_CKBK
Input data length 7
Output data length 4
Parameter data length 0
Identifiers 0xC1, 0x83, 0x86, 0x9F
9
DVC6200p
November 2017
DI Module
Slot 4 DI1 Assignment Slot 5 DI2 Assignment
Module Module Name Input Bytes Output Bytes
25 DI_OUT 2 0
Module 25
DI_OUT
Module Definition DI_OUT
Input data length 2
Output data length 0
Parameter data length 0
Identifiers 0x91
Instruction Manual Supplement
D104019X012
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
10
E 2014, 2017 Fisher Controls International LLC. All rights reserved.
Loading...