Fisher IM Supplement: ATEX/IECEx Hazardous Area Approvals - Fisher LCP200 Local Control Panel Manuals & Guides

Instruction Manual Supplement
D104370X012
LCP200 Local Control Panel
August 2021
ATEX/IECEx Hazardous Area Approvals
Fisher
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the LCP200 instruction manual (D104296X012
Always refer to the nameplate itself to identify the appropriate certification. LCP200 instruments with a IIC rating may have different hardware than IIB rated instruments; be sure to order the appropriately
rated instrument based on your application and wiring practices.
WARNING
LCP200 Local Control Panel
), available from your Emerson sales office or Fisher.com.
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification.
Intrinsically Safe
Specific Conditions of Use
1. Install unit in area of low risk from mechanical hazards. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp cloth.
Notes
Ambient temperature rating: -40°C ≤ Ta ≤ +65°C
1. Install per drawing GG55194, shown in figure 1, 2, 3, and 4, as indicated on the nameplate.
2. Substitution of components may impair intrinsic safety.
3. The enclosure contains non-metallic enclosure parts. To prevent the risk of electrostatic sparking, the non-metallic surface shall be cleaned with a damp cloth.
Refer to table 1 for approval information.
Table 1. Approval Information, ATEX/IECEx
Certificate Certification Obtained Entity Rating Temperature Code
ATEX: FM17ATEX0071X II 1 GD IECEx: IECEx FMG 17.0028X
Intrinsically Safe ATEX IECEx
Gas
Ex ia IIC Ga
Dust
Ex ia IIIC Da
Install Per Drawing GG55194 (shown in figure 1, 2, 3, and 4)
Per Drawing GG55194 (shown in figure 1, 2, 3, and 4)
Gas: T6 Dust: T85_C
www.Fisher.com
LCP200 Local Control Panel
August 2021
Figure 1. Intrinsically Safe, LOOP Power, ATEX/IECEx
Wiring Configuration A (LOOP-Powered only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 3, 4, and 5 in Figure 4
LCP200 FM17ATEX0071X IECEx FMG 17.0028X
Ex ia IIC T6 Ga Ex ia IIIC T85_C Da
NOTE: A - and H ­terminals are internally shorted infallibly
24V+ A+ A-
24V-
TEST TRIP
NO C NC NO C NC
H+ H-
RESET
Instruction Manual Supplement
UP TO 3 GROUPS OF CONTACT OUTPUT FOR EACH GROUP OF NO/NC TO C
Ui = 30 V, Ii = 100 mA OR Ui = 24 V, Ii = 174 mA
Pi = 1 W Ci = 7.4 nF Li = 0 mH
NOTE: Users can either wire to NO or NC terminals. Shown here is wiring to NO terminals.
D104370X012
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
AUX + (A+)
Ui = 30 V Ii = internally protected
Pi = 1.4 W Ci = 5.5 nF Li = 0 mH
HART LOOP (H+)
Ui = 30 V Ii = 100 mA Pi = 1 W Ci = 22.1 nF Li = 0 mH
GG55194 Sheet 3
NOTE: Wire from LOOP- of DVC6000/DVC6200 can be terminated to either A- or H- terminal of LCP200 Shown here is termination to A-
INTRINSICALLY SAFE APPARATUS
(DVC6000/DVC6200)
AUX LOOP
HAZARDOUS
LOCATION
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
NON-HAZARDOUS
LOCATION
2
Instruction Manual Supplement
D104370X012
Figure 2. Intrinsically Safe, External Power 24V, ATEX/IECEx
Wiring Configuration B (External 24V Only) From Barrier to Digital Valve Controller and LCP200 See Notes in figure 3 and Notes 1, 2, 4, and 5 in Figure 4.
LCP200 FM17ATEX0071X IECEx FMG 17.0028X
Ex ia IIC T6 Ga Ex ia IIIC T85_C Da
24V+ A+ A- H+ H-24V-
TEST TRIP
NO C NC NO C NC
RESET
UP TO 3 GROUPS OF CONTACT OUTPUT FOR EACH GROUP OF NO/NC TO C
Ui = 30 V, Ii = 100 mA OR Ui = 24 V, Ii = 174 mA
Pi = 1 W Ci = 7.4 nF Li = 0 mH
NOTE: Users can either wire to NO or NC terminals. Shown here is wiring to NO terminals.
LCP200 Local Control Panel
August 2021
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
AUX + (A+)
Ui = 30 V Ii = internally protected
Pi = 1.4 W Ci = 5.5 nF Li = 0 mH
24V TERMINALS
Ui = 30 V Ii = 100 mA Pi = 1 W Ci = 14.63 nF Li = 0 mH
GG55194 Sheet 4
INTRINSICALLY SAFE APPARATUS
(DVC6000/DVC6200)
AUX LOOP
HAZARDOUS
LOCATION
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
NON-HAZARDOUS
LOCATION
3