Fisher IM Supplement: ATEX Hazardous Area Approvals-Fisher LCP100 Local Control Panel Manuals & Guides

Instruction Manual Supplement
D104237X012
LCP100 Local Control Panel
August 2017
ATEX Hazardous Area Approvals
Fisher
Hazardous Area Classifications and Special Instructions for “Safe Use” and Installations in Hazardous Locations
Certain nameplates may carry more than one approval, and each approval may have unique installation/wiring requirements and/or conditions of “safe use”. These special instructions for “safe use” are in addition to, and may override, the standard installation procedures. Special instructions are listed by approval.
Note
This information supplements the nameplate markings affixed to the product and the LCP100 Local Control Panel instruction manual (D103272X012
Always refer to the nameplate itself to identify the appropriate certification.
LCP100 Local Control Panel
), available from your Emerson sales office, Local Business Partner, or at Fisher.com.
WARNING
Failure to follow these conditions of “safe use” could result in personal injury or property damage from fire or explosion, or area re‐classification.
II 1G Ex ia IIB T4 Ga
II 2G Ex e mb [ib] IIC T4 Gb
II 3G Ex ic IIC T4 Gc
Ta = -40_C to +65_C
IP66
www.Fisher.com
LCP100 Local Control Panel
August 2017
Instruction Manual Supplement
D104237X012
Ex ia IIB
Standards Used for Certification
EN 60079-0:2012 EN 60079-11:2012 EN 60079-26:2015
Entity parameters
Refer to drawing GE75327, shown in figure 1, 2, and 3.
Special Conditions for Safe Use
1. The 24 VDC input terminals shall not be used.
2. Under certain extreme circumstances, the plastic enclosure may store an ignition-capable level electrostatic charge. Precautions shall be taken to prevent the build up of electrostatic charge by charge-generating mechanisms, e.g. do not rub with a solvent, as indicated on the product nameplate.
Ex ic IIC and Ex e mb [ib] IIC
Standards Used for Certification
EN 60079-0:2012: +A11:2013 EN 60079-7:2007 EN 60079-11:2012 EN 60079-18:2015
Entity parameters
Ex ic IIC
Ui = 27 VDC Ci = 1.1 nF Li = 0
Special Conditions for Safe Use
1. For Ex ic installations, it is not permitted to connect separate supplies to the LOOP+/LOOP and AUX+/LOOP terminals.
2. In 24VDC mode, do not connect to LOOP+. In Loop mode, do not connect to 24VDC+/24VDC-.
2
Instruction Manual Supplement
LCP100 Local Control Panel
D104238X012
Figure 1. Wiring Configuration from Barrier to Fisher DVC6200 SIS to LCP100 - Loop-Powered Only (Drawing GE75327) (See Notes in Figure 2)
August 2017
POWER SELECTOR SWITCH MUST BE POSITIONED IN THE “LOOP” POSITION
THESE TERMINALS SHALL NOT BE USED FOR Ex ia APPLICATIONS
FOR USE IN ZONE 0 - Ex ia IIB
LCP100
AUX TERMINALS Ui = 30 VDC Ii = 452 mA Pi = 1.4 W Ci = 0 mF Li = 0 mH
LOOP TERMINALS Ui = 30 VDC Ii = 226 mA Pi = 1.4 W Ci = 0.22 mF Li = 16 mH
HAZARDOUS
LOCATION
INTRINSICALLY SAFE
APPARATUS (DVC6200 SIS)
AUX LOOP
NON-HAZARDOUS
LOCATION
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
GE75327-Sheet 1
Figure 2. Schematic Notes for Figure 1 and Figure 3
NOTES:
1. FOR Ex ia APPLICATIONS THE FOLLOWING INFORMATION SHALL BE OBSERVED. a) THE POWER SELECTOR SWITCH MUST BE POSITIONED IN THE “LOOP” MODE POSITION.
b) NO WIRING CONNECTIONS SHALL BE MADE TO THE 24 VDC POWER TERMINALS.
c) THE OVERALL GAS GROUP RATING OF THE INTRINSICALLY SAFE CIRCUIT WILL BE LOWEST GAS GROUPING OF ALL APPARATUS FORMING  THE CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH IIB AND IIC APPARATUS WILL HAVE AN OVERALL CIRCUIT GAS RATING OF IIB.
d) THE LEVEL OF PROTECTION OF THE INTRINSICALLY SAFE CIRCUIT WILL BE THE LOWEST LEVEL OF ALL APPARATUS FORMING THE  CIRCUIT. FOR EXAMPLE, A CIRCUIT WITH BOTH “ia” AND “ib” WILL HAVE AN OVERALL PROTECTION RATING OF “ib”.
2. THE PERMISSIBLE INPUT VOTAGE Ui, INPUT CURRENT Ii AND INPUT POWER Pi OF EACH APPARATUS SHALL BE GREATER THAN OR EQUAL TO THE
OUTPUT VOLTAGE Uo, OUTPUT CURRENT Io, AND OUTPUT POWER Po OF THE ASSOCIATED APPARATUS (BARRIER).
3. INSTALLATION OF THE LCP100 IS SUCH THAT ITS LOOP TERMINALS WILL BE CONNECTED IN PARALLEL WITH OTHER INTRINSICALLY SAFE
APPARATUS LOOP TERMINALS. THE WIRING COMING FROM THE BARRIER INTO THE HAZARDOUS LOCATION MAY BE TERMINATED AT EITHER THE INTRINSICALLY SAFE APPARATUS, AS SHOWN IN FIGURE 1 OR AT THE LCP100, AS SHOWN IN FIGURE 3.
GE75327-Sheet 1
3
LCP100 Local Control Panel
Instruction Manual Supplement
August 2017
Figure 3. Wiring Configuration from Barrier to Fisher LCP100 to DVC6200 SIS - Loop-Powered Only (Drawing GE75327) (See Notes in Figure 2)
D104237X012
POWER SELECTOR SWITCH MUST BE POSITIONED IN THE “LOOP” POSITION
THESE TERMINALS SHALL NOT BE USED FOR Ex ia APPLICATIONS
INTRINSICALLY SAFE
APPARATUS (DVC6200 SIS)
AUX LOOP
FOR USE IN ZONE 0 - Ex ia IIB
LCP100
AUX TERMINALS Ui = 30 VDC Ii = 452 mA Pi = 1.4 W Ci = 0 mF Li = 0 mH
LOOP TERMINALS Ui = 30 VDC Ii = 226 mA Pi = 1.4 W Ci = 0.22 mF Li = 16 mH
HAZARDOUS
LOCATION
NON-HAZARDOUS
LOCATION
ASSOCIATED INTRINSICALLY SAFE APPARATUS (BARRIER)
GE75327-Sheet 2
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.