Fisher Fisher VBL Volume Booster Manuals & Guides

Instruction Manual
D103317X012
Fisher™ VBL Volume Booster
VBL Volume Booster
December 2021
Contents
Introduction 1.................................
Scope of Manual 1.............................
Description 1.................................
Educational Services 2.........................
Installation 4..................................
Mounting 4..................................
Pressure Connections 5........................
Supply Pressure 5.............................
Operating Information 6.........................
Principle of Operation 7.........................
Maintenance 8.................................
Introduction
Figure 1. Fisher VBL Volume Booster
X0648
Scope of Manual
This instruction manual provides installation, operation, maintenance, and parts information for the Fisher VBL volume booster (figure 1). Refer to separate instruction manuals for information regarding the valve body, actuator, and other accessories.
Do not install, operate, or maintain a VBL volume booster without being fully trained and qualified in valve, actuator and accessory installation, operation and maintenance. To avoid personal injury or
property damage it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. If you have any questions about these instructions,
contact your Emerson sales office
before proceeding.
Description
The VBL volume booster is used in conjunction with a positioner on a throttling control valve to increase stroking speed. The booster has a fixed deadband (controlled by the seat‐to‐seat dimension of the supply and exhaust plugs) which is factory set during assembly and testing. In addition, the booster incorporates soft‐seat construction and an integral bypass restriction to eliminate positioner saturation problems that can occur with volume boosters that do not have these features. Adjustment of the integral bypass restriction is necessary for system stability. This adjustment does not affect the deadband of the booster, but does permit the control valve to respond to small input signal changes from the positioner without sacrificing steady‐state accuracy.
www.Fisher.com
VBL Volume Booster
December 2021
It also allows the booster to deliver high‐volume output for fast stroking when large, rapid input signal changes occur.
The volume booster is used to improve stroking speed. If precision valve control is required, the use of a positioner is recommended. If you use the volume booster only with an actuator, for on‐off control, the integral bypass restriction on the volume booster must be closed (turned fully clockwise).
To facilitate diagnostic testing, you can install connectors and piping with the VBL volume booster.
The O‐rings and diaphragms in the VBL volume booster are HNBR (Hydrogenated Nitrile). HNBR demonstrates excellent temperature capability and shelf life over standard nitrile.
Instruction Manual
D103317X012
Specifications
Specifications for the VBL volume booster are listed in table 1. Information for an individual unit as it comes from the factory appears on the nameplate.
Educational Services
For information on available courses for the VBL volume booster, as well as a variety of other products, contact:
Emerson Automation Solutions Educational Services - Registration Phone: 1-641-754-3771 or 1-800-338-8158 E-mail: education@emerson.com emerson.com/fishervalvetraining
2
Instruction Manual
D103317X012
Table 1. Specifications
VBL Volume Booster
December 2021
Input Signal
Positioner output
Hazardous Area Classification
Complies with the requirements of ATEX Group II Category 2 Gas and Dust
Maximum Input Signal Pressure
VBL-1 and VBL-3: 5.5 bar (80 psig) VBL-2 and VBL-4: 10.3 bar (150 psig)
Input to Output Pressure Ratio
(1)
Maximum surface temperature (Tx) depends on operating conditions
Gas: T5, T6 Dust: T85…T93
Fixed at 1 to 1
Meets Customs Union technical regulation TP TC
Supply Pressure Ranges
(1)
When used in conjunction with a positioner or other pneumatic accessory, always pipe the positioner and
012/2011 for Groups II/III Category 2 equipment
II Gb c T*X X III Db c T*X X
booster with one common supply through a Fisher 67D, 67DR, or 95H regulator (see figure 4). A high‐capacity filter, such as the Fisher 262K, should be installed in the supply line to the regulator. Supply
Safety Instrumented System Classification
SIL3 capable - certified by exida Consulting LLC
pressure also must not exceed the maximum pressure rating of the actuator.
Approximate Weight
Aluminum Body: 1.0 kg (2.2 pounds)
Operative Temperature Limits
-40 to 93_C (-40 to 200_F)
(1)
Declaration of SEP
Fisher Controls International LLC declares this product to be in compliance with Article 4 paragraph
Maximum Flow Coefficients
See table 2
3 of the PED Directive 2014/68/EU. It was designed and manufactured in accordance with Sound Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance.
Connections
Input Signal: 1/4 NPT Supply and Output Signal: 1/2 NPT
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. The pressure/temperature limits in this document, and any applicable code or standard limitation should not be exceeded.
However, the product may bear the CE marking to indicate compliance with other applicable European Community Directives.
Ex h IIC Tx Gb Ex h IIIC Tx Db
Table 2. Maximum Flow Coefficients
Instrument
VBL‐1 volume booster 2.5 1.1
VBL-2 volume booster 2.5 1.1
VBL‐3 volume booster 2.5 1.8
VBL-4 volume booster 2.5 1.8
FIELDVUEt DVC6200, DVC6200 SIS, DVC6200f, DVC6200p, DVC6000, DVC6000 SIS, DVC6000f digital valve controllers
FIELDVUE DVC2000 digital valve controller Low pressure relay High pressure relay
Fisher 3570 valve positioner 0.25 0.25
Fisher 3582 valve positioner 0.17 0.19
Fisher 3610J, 3610JP, 3611JP, 3620J, 3620JP, 3621JP valve positioners 0.37 0.30
Supply Port Coefficients Exhaust Port Coefficients
C
v
0.37 0.31
0.13
0.19
C
0.15
0.20
v
3
VBL Volume Booster
December 2021
Instruction Manual
D103317X012
Installation
WARNING
Always wear protective clothing, gloves, and eyewear when performing any installation procedures to avoid personal injury.
System damage may result if a volume booster is installed in a way that it can be physically damaged.
Personal injury or system damage may result when service conditions exceed booster or other equipment ratings. Exceeding the pressure specifications in table 1 may cause leakage, parts damage, or personal injury due to bursting of pressure‐containing parts or explosion of accumulated gas.
Check with your process or safety engineer for any additional measures that must be taken to protect against process media.
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
Note
Do not use separate pressure supplies for the volume booster and associated positioner.
The volume booster may not exhaust immediately upon loss of a separate pressure supply. However, if the system is in a transient state at the time of pressure supply loss or if changes to the booster's input signal are sufficient to overcome the deadband, the booster will exhaust.
A loss of a pressure supply (either separate or common) to a Fisher 3582 or 3610J positioner will cause the positioners output pressure (booster's input pressure) to decay.
Always pipe the positioner and the volume booster with one common supply. See figure 4 for typical installation examples. A 67D, 67DR, or 95H regulator is required to provide sufficient capacity to supply both components. A high‐capacity filter, such as the 262K, should be installed in the supply line to the regulator.
Mounting
The volume booster is typically nipple‐mounted between the pneumatic supply source and the actuator, and may be used with piston or diaphragm actuators. Many actuators require larger casing or cylinder connections and modifications to allow the booster to deliver the higher volume output.
The booster may also be directly mounted to the actuator by using an actuator yoke mounting bracket (see figure 2) or casing mounting bracket. If a mounting bracket is used, remove the appropriate end cap screws and install the mounting bracket. Install the end cap screws, re‐tightening to a recommended torque value of 12.5 NSm (110 lbfSin).
4
Instruction Manual
D103317X012
Figure 2. Volume Booster with Yoke Mounting Bracket
HEX SCREW (QTY 6)
ATTACH THIS SURFACE TO ACTUATOR YOKE
YOKE MOUNTING BRACKET
GE26237-Bracket
VBL Volume Booster
December 2021
HEX SCREW (QTY 6)
YOKE MOUNTING BRACKET
Pressure Connections
CAUTION
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
The input signal connection is 1/4 NPT. The supply and output connections are 1/2 NPT (minimum pipe size recommended for nipple mounting is 1/2 NPT). Connections to the volume booster should be made as indicated in figure 3. Connections for typical applications are shown in figures 4 and 5. Ensure that the piping is of proper size to meet the capacity demands of the booster and that you equip the actuator with properly sized input connections.
Supply Pressure
Supply pressure must be filtered, clean, dry air or noncorrosive gas.
WARNING
If a flammable or hazardous gas is to be used as the supply pressure medium, personal injury, property damage or equipment damage could result from fire or explosion of accumulated gas or from contact with hazardous gas. The volume booster has no provision for piping away the vented exhaust gas. Therefore, do not use flammable or otherwise hazardous gas as a supply medium unless the unit is in a well‐ventilated area and all ignition sources have been removed.
Exhaust Ports
Exhaust to the atmosphere is through exhaust ports in the side of the unit. Keep the exhaust ports free of any obstructions or foreign materials that might clog them.
5
VBL Volume Booster
December 2021
Instruction Manual
D103317X012
Operating Information
The only operating requirement of the volume booster is the adjustment of the bypass restriction for stable actuator performance. Although systems with different characteristics may require different adjusting techniques, the following adjustment procedure is recommended when using the actuator for throttling control.
Note
When sizing the booster, select the lowest C loop may lead to stability problems, thus requiring the bypass to be opened so far that the booster will never operate.
Prior to operation, turn the bypass restriction adjusting screw (figure 3) four or five turns counterclockwise from the fully closed position. With the actuator in operation, slowly turn the restriction clockwise until the booster operates in response to large changes in the input signal, yet allows small changes to move the actuator without initiating booster operation.
that will meet the stroking speed specifications. Oversizing the booster in a closed
v
Figure 3. Volume Booster Sectional View
SPRING SEAT
HEX NUT
BYPASS RESTRICTION ADJUSTING SCREW
PIN, SLOTTED SPRING
BYPASS VALVE
O‐RING
HOUSING, BOTTOM
SUPPLY
O‐RING
END CAP
GE26237-Section
UPPER SPRING
INPUT SIGNAL
HOUSING, TOP
EXHAUST PORT
HEX SCREW
UPPER DIAPHRAGM
DIAPHRAGM SPACER
DIAPHRAGM PLATE ASSEMBLY (INCLUDES LOWER DIAPHRAGM)
EXHAUST
SUPPLY PORT
OUTPUT TO ACTUATOR
LOWER SPRING
VALVE PLUG ASSEMBLY
LUBRICANT
If the actuator is to be used for on‐off control, the restriction should be closed (turned fully clockwise).
Verify that the capacity of the regulator meets the stroking capacity requirements.
6
Instruction Manual
D103317X012
VBL Volume Booster
December 2021
Principle of Operation
Refer to figures 3, 4, and 5.
Because of the restriction, large input signal changes register on the booster input diaphragm sooner than in the actuator. A large, sudden change in the input signal causes a pressure differential to exist between the input signal and the output of the booster. When this occurs, the diaphragms move to open either the supply port or the exhaust port, whichever action is required to reduce the pressure differential. The port remains open until the difference between the booster input and output pressures returns to within the deadband limits of the booster. With the bypass restriction adjusted for stable operation, signals having small magnitude and rate changes pass through the bypass restriction and into the actuator without initiating booster operation. Both the supply and exhaust ports remain closed, preventing unnecessary air consumption and possible saturation of positioner relays.
Figure 4. Typical Installations with Piston Actuator
VBL VOLUME BOOSTER
E1212
SIGNAL
ACTUATOR
PIPE NIPPLE
TOP CYL
BOTTOM CYL
POSITIONER
SUPPLY
67D, 67DR OR 95H REGULATOR
7
VBL Volume Booster
December 2021
Figure 5. Typical Installations with Diaphragm Actuator
SIGNAL
Instruction Manual
D103317X012
VBL VOLUME BOOSTER
PIPE NIPPLE
SUPPLY
67D, 67DR OR 95H REGULATOR
ACTUATOR
E1213
DVC6200 DIGITAL VALVE CONTROLLER WITH RELAY C OR POSITIONER
Maintenance
There are no repairable or replaceable parts on the VBL volume booster. Contact your Emerson sales office if a replacement VBL volume booster is needed.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Cernay, 68700 France Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
8