This instruction manual provides installation, operation, maintenance, and parts ordering information for the Fisher
i2P‐100 transducer (see figure 1).
Refer to separate manuals for instructions covering equipment used with the transducer.
Do not install, operate, or maintain an i2P-100 electro‐pneumatic transducer without being fully
trained and qualified in valve, actuator, and accessory installation, operation and maintenance. To
avoid personal injury or property damage it is important to carefully read, understand, and follow all of
the contents of this manual, including all safety cautions and warnings. If you have any questions about
these instructions, contact your Emerson sales office
www.Fisher.com
.
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
NOTICE
Dropping or rough handling of the transducer can cause damage to the converter module resulting in a shifted output or a
minimum output.
Description
The transducer receives a 4‐20 mA DC input signal and transmits a proportional user field‐configurable pneumatic
output pressure to a final control element. The pneumatic output ranges are typically 0.2 to 1.0 bar (3 to 15 psig),
0.4 to 2.0 bar (6 to 30 psig), and 0.14 to 2.3 bar (2 to 33 psi). A typical application is in electronic control loops where
the final control element is a control valve assembly that is pneumatically operated. The input signal and output
pressure range of the transducer is indicated on the nameplate, attached to the housing.
Specifications
Specifications for the i2P‐100 transducer are listed in table 1.
WARNING
This product is intended for a specific current range, temperature range and other application specifications. Applying
different current, temperature and other service conditions could result in malfunction of the product, property damage or
personal injury.
Scan or click
code to find out
more about the
i2P-100 transducer
Instruction Manual
D103198X012
Table 1. Specifications
i2P-100 Transducer
May 2022
Input Signal
Available as standard with 4‐20 mA.
User configurable by dip switch for split ranging, see
table below.
Output Signal
(1)
Available as standard 0.2 to 1.0 bar (3 to 15 psig), 0.4
to 2.0 bar (6 to 30 psig), or 0.14 to 2.3 bar
(2 to 33 psig). User configurable by dip switch
selection and zero and span potentiometer
adjustment, see table below.
Input Signal
4‐20 mA DC
0.14 to 2.32 to 33
4‐12 mA DC0.2 to 1.03 to 15
12‐20 mA DC0.2 to 1.03 to 15
Output Pressure
Barpsig
0.2 to 1.03 to 15
0.4 to 2.06 to 30
Equivalent Circuit
The i2P‐100 equivalent circuit is a series circuit
consisting of a constant voltage drop (battery) of
approximately 4 VDC and a total resistance of 40
ohms. Input is shunted by two 6.8 V zener diodes (see
figure 9).
Supply Pressure
(2)
Recommended: 0.3 bar (5 psi) higher than upper
range limit of output signal
Maximum: 3.4 bar (50 psig)
Medium: Air or Non-Corrosive Natural Gas
Maximum Steady-State Flow Rate
Refer to tables 3 and 4
Maximum Output Air Capacity
(3)
8.0 m3/hr (300 scfh) at 1.4 bar (20 psig) supply
pressure
Performance
(4)
Reference Accuracy:±1.0% of full scale output span;
includes combined effects of hysteresis, linearity, and
deadband
(continued)
Independent Linearity: ±0.5% of full scale output span
Hysteresis: 0.4% of full scale output span
Frequency Response: Gain is attenuated 3 dB at 3 Hz
with transducer output signal piped to a typical
instrument input
Temperature Effect:±0.14% per degrees Celsius
(±0.075% per degrees Fahrenheit) of span
Supply Pressure Effect: 0.2% of full scale output span
per psi supply pressure change
Vibration Effect: Less than 1% of full scale output span
when tested to ISA S75.13
Electromagnetic Compatibility
Meets EN 61326‐1:2013
Immunity—Industrial locations per Table 2 of
EN 61326‐1 Standard. Performance is shown
in table 2 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Operating Ambient Temperature Limits
(2)
-40 to 85_C (-40 to 185_F)
Electrical Seal
Single sealed device per ANSI/ISA 12.27.01
Electrical Classification
Hazardous Area:
CSA—Intrinsically Safe, Explosion-proof,
Type n, Dust‐Ignition proof
FM—Intrinsically Safe, Explosion-proof,
Type n, Non‐incendive, Dust‐Ignition proof
ATEX—Intrinsically Safe, Flameproof, Type n
IECEx—Intrinsically Safe, Flameproof, Type n
Electrical Housing:
When Remotely VentedNo Remote Venting
CSA—Type 4X Encl.
FM—NEMA 4X
ATEX—IP66
IECEx—IP66
CSA—Type 3 Encl.
FM—NEMA 3
ATEX—IP64
IECEx—IP64
3
i2P-100 Transducer
May 2022
Table 1. Specifications (continued)
Instruction Manual
D103198X012
Other Classifications/Certifications
CUTR— Customs Union Technical Regulations
(Russia, Kazakhstan, Belarus, and Armenia)
Mounting Position
J Actuator J pipestand or J surface
INMETRO— National Institute of Metrology, Quality,
and Technology (Brazil)
KTL—Korea Testing Laboratory (South Korea)
NEPSI— National Supervision and Inspection Centre
Approximate Weight (Transducer Only)
2.5 kg (5.5 lbs)
for Explosion Protection and Safety of
Instrumentation (China)
Contact your Emerson sales office
classification/certification specific information
for
Actuator Stroking Time
See figure 2
Connections
Supply and Output Pressure: 1/4 NPT internal
connection
Vent: 1/4 NPT internal
Electrical: Standard 1/2 NPT
Wire Size: 18 to 22 AWG
Adjustments
(1)
Zero and Span: Trim potentiometers (20 turn) for
zero and span adjustments are located under the
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 4 paragraph
3 of the PED Directive 2014/68/EU. It was designed
and manufactured in accordance with Sound
Engineering Practice (SEP) and cannot bear the CE
marking related to PED compliance.
housing cap (see figure 10).
Switch: Allows input signal split range and
user‐configurable 0.14 to 2.3 bar (2 to 33 psig)
output.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology
1. For other ranges, zero and span adjustments are needed.
2. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded.
3. Normal m
4. Performance values are obtained using a transducer with a 4 to 20 mA DC input signal and a 0.2 to 1.0 bar (3 to 15 psig) output signal at an ambient temperature of 24_C (75_F).
3
/hr—Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60_F and 14.7 psia).
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
Table 2. EMC Summary Results—Immunity
PortPhenomenonBasic StandardTest Level
Electrostatic discharge (ESD)IEC 61000‐4‐2
Enclosure
I/O signal/control
Specification limit = ±1% of span
1. A=No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
4
Radiated EM fieldIEC 61000‐4‐3
Burst (fast transients)IEC 61000‐4‐4
SurgeIEC 61000‐4‐5
Conducted RFIEC 61000‐4‐6150 kHz to 80 MHz at 3 VrmsA
4kV Contact
8kV Air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
1 kV
1 kV (line to ground only, each)
Performance
(1)
Criteria
A
A
A
A
Instruction Manual
D103198X012
Table 4. Maximum Steady-State Flow Rate
Table 3. Maximum Steady-State Flow Rate (Air)
SUPPLY PRESSUREOUTPUT PRESSURE
BarPsiBarPsim3/hrScfh
0.2 - 1.03 - 15
1.420
0.230.041.5
0.6290.062.0
1.0150.072.6
0.4 - 2.06 - 30
2.435
0.460.051.7
1.2180.082.9
2300.124.1
0.1 - 2.32 - 33
2.638
1. Normal m3/hour - Normal cubic meters per hour (0C and 1.0135 bar, absolute).
Scfh - Standard cubic feet per hour (60F and 14.7psig).
0.120.041.5
1.217.50.082.9
2.3330.124.3
STEADY STATE
FLOW RATE
(1)
Figure 2. Output‐Time Relationships for Fisher i2P‐100 Transducer
(Natural Gas)
i2P-100 Transducer
May 2022
SUPPLY PRESSUREOUTPUT PRESSURE
BarPsiBarPsim3/hrScfh
0.2 - 1.03 - 15
1.420
0.230.061.95
0.6290.072.6
1.0150.13.38
0.4 - 2.06 - 30
2.435
0.460.62.21
1.2180.113.77
2300.155.33
0.1 - 2.32 - 33
2.638
1. Normal m3/hour - Normal cubic meters per hour (0C and 1.0135 bar, absolute).
Scfh - Standard cubic feet per hour (60F and 14.7psig).
2. Natural gas steady state flow based on natural gas specific gravity of 0.6.
Flow decreases as specific gravity increases.
0.120.061.94
1.217.50.113.74
2.3330.185.55
STEADY STATE
FLOW RATE
(1,2)
100
90
80
70
60
50
OUTPUT
40
30
20
10
(% OF i2P‐100 OUTPUT SPAN)
0
0 102030405060708090
A6815
LOADING
EXHAUSTING
100
TIME (%)
Installation
The i2P‐100 transducer has been designed and approved for use with either air or natural gas as the supply medium. If
using natural gas as the pneumatic supply medium, natural gas will be used in the pneumatic output connections of
the transducer to any connected equipment. In normal operation the unit will vent the supply medium into the
surrounding atmosphere unless it is remotely vented. When using natural gas as the supply medium, in a
non‐hazardous location in a confined area, remote venting of the unit is required. Failure to do so could result in
personal injury, property damage, and area re‐classification. For hazardous locations remote venting of the unit may
be required, depending upon the area classification, and as specified by the requirements of local, regional, and
federal codes, rules and regulations. Failure to do so when necessary could result in personal injury, property damage,
and area re‐classification.
5
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
Additional information for installation and safe use in hazardous locations can be found in the related instruction
manual supplements as indicated in Hazardous Area Classifications and Special Instructions for “Safe Use” and
Installation in Hazardous Locations on page 7.
WARNING
To avoid personal injury or property damage from the sudden release of pressure, air, or natural gas:
D Always wear protective clothing, gloves, and eyewear when performing any installation operations.
D If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section of this
instruction manual.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
NOTICE
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed
by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
WARNING
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a non‐hazardous
(non‐classified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a
safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area
re‐classification.
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon
the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations.
Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area
re‐classification.
Vent line piping should comply with local and regional codes and should be as short as possible with adequate inside
diameter and few bends to reduce case pressure buildup.
When received from the factory, the set screws (key 8), which provide a locking feature for the housing caps (key 2),
are backed off approximately one turn. When using the i2P‐100 transducer in explosive atmospheres these set screws
must be fully engaged.
WARNING
When using this unit in explosive atmospheres, the set screws (key 8) must be fully engaged to lock/secure the housing
caps. Failure to fully engage these set screws could result in unauthorized opening of the unit, which may result in personal
injury or property damage caused by fire or explosion.
6
Instruction Manual
D103198X012
i2P-100 Transducer
May 2022
Hazardous Area Classifications and Special Instructions for “Safe Use” and
Installation in Hazardous Locations
Refer to the following instruction manual supplements for approval information.
D CSA Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104192X012
D FM Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104193X012
D ATEX Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104194X012
D IECEx Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104195X012
All documents are available from your Emerson sales office
or at Fisher.com. Contact your Emerson sales office for all
)
)
)
)
other approval/certification information.
Mounting
When a transducer is ordered as part of a control valve assembly, the factory mounts the transducer on the actuator
and connects the necessary tubing, then adjusts the transducer as specified on the order. See figures 3 and 4 for
typical mounting configurations.
Figure 3. Fisheri2P‐100 Electro‐Pneumatic
Transducer Mounted on a Size 30 667 Sliding‐Stem
Actuator
CONDUIT
CONNECTION
Figure 4. Fisher i2P‐100 Electro‐Pneumatic
Transducer Mounted on a 2052 Rotary Actuator
with 3610J Positioner and V300B Rotary Valve
CONDUIT
CONNECTION
FIELD
TERMINATION AND
ELECTRONICS
MODULE CAP
W8723
CONVERTER
MODULE CAP
FIELD TERMINATION
AND ELECTRONICS
MODULE CAP
X1354
CONVERTER
MODULE CAP
Transducers also can be ordered separately for mounting on a control valve assembly already in service, or for
mounting on a 2 inch diameter pipestand, or a flat surface. The transducer may be ordered either with or without
mounting parts.
7
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
Note
Do not mount the vent in a downward position as the vent will not drain properly and may become blocked with ice or debris,
resulting in process instability.
Mounting parts include a mounting plate and bolts and, if ordered for pipestand mounting, a pipe clamp. Tubing is not
included if the transducer is not factory mounted. Use 3/8‐inch diameter tubing for all input and output connections.
The length of tubing between the transducer output and the final control element should be as short as possible.
Transducer overall dimensions are shown in figure 5. If weatherproofing is required, mount the transducer so that the
vent can drain. Do not allow moisture or condensate to collect in the vent.
Pneumatic Connections
NOTICE
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed
by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
As shown in figure 5, all pressure connections on the transducer are 1/4 NPT internal connections. Use 3/8‐inch tubing
for all pressure connections. Refer to the vent subsection below for remote vent connections.
Figure 5. Dimensions and Connections
75.2
(2.96)
22.3
(0.88)
22.9
(0.90)
33.3
(1.31)
33.3
(1.31)
75.7
(2.98)
1/4 18 NPT
OUTPUT
CONNECTION
103.9
(4.09)
67 (2.62) CAP
REMOVAL
CLEARANCE
mm
(INCH)
74.2
81.6
GE0643
(sheet 1 of 4)
(2.92)
(3.21)
67.8
(2.67)
33.3
(1.31)
(2.19)
58.7
(2.31)
55.7
36.3
(1.43)
34.7
(1.37)
98.7
(3.89)
1/4 18 NPT
SUPPLY
CONNECTION
1/2 14 NPT
CONDUIT
CONNECTION
103.9
1/4 18 NPT VENT
OR PIPE‐A‐WAY
CONNECTION
67 (2.62) CAP
REMOVAL
CLEARANCE
(4.09)
1/4 18 NPT
OUTPUT
CONNECTION
8
Instruction Manual
D103198X012
i2P-100 Transducer
May 2022
Supply Pressure Requirements
WARNING
Severe personal injury or property damage could result from an unstable process if the instrument supply medium is not
clean, dry, oil‐free and noncorrosive. While use and regular maintenance of a filter that removes particles larger than 40
micrometers in diameter will suffice in most applications, check with an Emerson field office and industry instrument air
quality standards for use with corrosive air or if you are unsure about the proper amount or method of air filtration or filter
maintenance.
Supply pressure must be clean, dry air or noncorrosive gas. Use a Fisher 67CFR filter regulator with standard 5
micrometer filter, or equivalent, to filter and regulate supply air. The filter regulator can be mounted on a bracket with
the transducer as shown in figure 6 or mounted on the actuator mounting boss. An output pressure gauge may be
installed on the regulator to indicate the supply pressure to the transducer. Also, as an aid for calibration, a second
gauge may be installed on the transducer to indicate transducer output pressure.
Connect the nearest suitable supply source to the 1/4 NPT IN connection on the filter regulator (if furnished) or to the
1/4 NPT SUPPLY connection on the transducer case (if the filter regulator is not attached).
Figure 6. Typical Fisher i2P‐100 Mounting With 67CFR Filter Regulator
MOUNTING BRACKET
CHAMFER 45_ to 27/64 DIA
1/4‐18 NPT EXTERNAL
2.5 INCH
i2P‐100 TRANSDUCER
REGULATOR
PIPE
NIPPLE
9
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
Diagnostic Connections
To support diagnostic testing of valve/actuator/positioner packages, special connectors and hardware are available.
Typical connector installations are shown in figure 7. The hardware used includes a 1/4 NPT pipe nipple and pipe tee
with a 1/8 NPT pipe bushing for the connector. The connector consists of a 1/8 NPT body and body protector.
Figure 7. Diagnostics Hookup for Fisher i2P‐100 Transducer
STEM
PROVIDED WHEN
GAUGE IS SPECIFIED
BODY PROTECTOR
BODY
PIPE BUSHING
GAUGE
PIPE TEE
GE06439‐A
(sheet 1 of 4)
B2395‐1
Note
If the i2P‐100 transducer is used in a valve assembly with a positioner, no hook‐up for diagnostic testing is required for the i2P‐100.
The hook‐up for diagnostic testing should be installed at the positioner.
PIPE NIPPLE (SEE FIGURE 6)
Install the connectors and hardware between the i2P‐100 transducer and the actuator.
1. Before assembling the pipe nipple, pipe tee, pipe bushings, actuator piping, and connector body, apply sealant to
all threads.
2. Turn the pipe tee to position the connector body and body protector for easy access when doing diagnostic testing.
Vent
When using natural gas as the supply medium ensure that the following warnings are read and understood. Contact
your Emerson sales office
WARNING
if you have any questions regarding the information contained in this section.
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a non‐hazardous
(non‐classified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a
safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area
re‐classification.
10
Instruction Manual
D103198X012
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon
the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations.
Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area
re‐classification.
Vent line piping should comply with local and regional codes and should be as short as possible with adequate inside
diameter and few bends to reduce case pressure buildup.
i2P-100 Transducer
May 2022
If a remote vent is required, the vent line must be as short as possible with a minimum number of bends and elbows.
To connect a remote vent, remove the plastic vent (key 71, figure 13). The vent connection is 1/4 NPT internal. Use
3/8‐inch tubing to provide a remote vent.
Electrical Connections
WARNING
For explosion‐proof applications, or when using natural gas as the supply medium, disconnect power before removing the
housing cap. Personal injury or property damage from fire or explosion may result if power is not disconnected before
removing the cap.
For intrinsically safe installations, refer to the nameplate or to instructions provided by the barrier manufacturer for proper
wiring and installation.
Note
For North American explosion‐proof applications in the Class/Division system, the i2P‐100 has been designed such that a conduit
seal is not required. For all other applications install the product as per local, regional, or national code, rules, and regulations.
WARNING
Select wiring and/or cable glands that are rated for the environment of use (such as hazardous location, ingress protection,
and temperature). Failure to use properly rated wiring and/or cable glands can result in personal injury or property damage
from fire or explosion.
Wiring connections must be in accordance with local, regional, and national codes for any given hazardous area approval.
Failure to follow the local, regional, and national codes could result in personal injury or property damage from fire or
explosion.
Use the 1/2 NPT conduit connection, shown in figure 5, for installation of field wiring.
Refer to figures 8, 9, and 10 when connecting field wiring from the control device to the transducer. Connect the
positive wire from the control device to the transducer “+” terminal and, the negative wire from the control device to
the transducer “-” terminal. Do not overtighten the terminal screws. Maximum torque is 0.45 NSm (4 lbfSin.). Connect
the transducer grounding terminal to earth ground.
Grounding terminals are provided both inside and outside the transducer housing.
11
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
Figure 8. Typical Field Wiring Diagram
TERMINAL
BLOCK
CONTROL
DEVICE
+
−
NOTE:
1FOR TROUBLESHOOTING OR MONITORING OPERATION,
AN INDICATING DEVICE CAN BE A VOLTMETER ACROSS
A 250 OHM RESISTOR OR A CURRENT METER.
A3875
FIELD WIRING
−+
1
EARTH
GROUND
TRANSDUCER
HOUSING
Operating Information
Figure 9. Equivalent Circuit
+
4 - 20 mA
−
6.8V6.8V4V
40 Ohm
During normal operation, the output of the i2P‐100 transducer is connected to the final control element.
Calibration
WARNING
On explosion‐proof instruments, or when using natural gas as the supply medium, remove electrical power before
removing either of the housing caps in a hazardous area. Personal injury or property damage may result from fire or
explosion if power is applied to the transducer with the cap removed in a hazardous area.
For intrinsically safe areas, current monitoring during operation must be with a meter approved for use in hazardous areas.
Equipment Required
Choose a current or voltage source that is capable, without switching ranges, of driving the transducer through its
entire input range. Switching ranges on a current or voltage source will produce spikes or mid‐scale reverses in the
input signal presented to the transducer, causing errors. The current source should be capable of delivering 30 mA
with 30 VDC maximum compliance voltage.
Calibration Procedure
WARNING
To avoid personal injury or property damage due to an uncontrolled process provide some temporary means of process
control before beginning the calibration procedure.
12
Instruction Manual
D103198X012
Refer to figure 10 for adjustment locations.
Figure 10. Zero and Span Adjustments and Switch Settings
ZERO
PCB/CUP
ASSEMBLY
SPAN
ADJUSTMENT
FIELD WIRING
CONNECTION
GE03345
- +
{
ADJUSTMENT
SEE
SWITCH
SETTINGS
i2P-100 Transducer
May 2022
SWITCH SETTINGS
SETTING ASETTING B
4‐20 mA 3‐15 psi
NOTES:
THE SWITCH SETTINGS WILL PRODUCE THE PERFORMANCE CHARACTERISTICS AS
INDICATED. FOR EXAMPLE, BOTH SWITCHES PLACED IN THE OFF POSITION WILL
CREATE A 4‐20 mA INPUT WITH A 3‐15 PSIG OUTPUT PERFORMANCE CHARACTERISTIC
1. INPUT SIGNAL SPLIT RANGE IS SELECTABLE VIA DIP‐SWITCH CONFIGURATION.
2. OUTPUT RANGE DIP‐SWITCH SELECTION FOR 0.14 TO 2.0 BAR (2 TO 33 PSIG) USES
SETTING B AND REQUIRES ZERO TO SPAN ADJUSTMENTS. FOR OTHER RANGES, ZERO
AND SPAN ADJUSTMENTS NEEDED.
3. SWITCH 1 SET TO THE ON POSITION AND SWITCH 2 SET TO THE OFF POSITION IS
NOT A VALID SWITCH SETTING.
(3)
4‐12 mA 3‐15 psi
4‐20 mA 6‐30 psi
4‐20 mA 2‐33 psi
(1,2)
SETTING C
12‐20 mA 3‐15 psi
(1)
Note
The following steps are for a 4‐20 mA, 0.2 to 1.0 bar (3 to 15 psig) configured unit. The same procedure is used for other
configurations.
1. Remove electronics module cover (cover adjacent to conduit entry, see figure 3 and 4).
NOTICE
Do not attempt to remove either of the housing caps if the locking set screws (key 8) are engaged. Removing housing caps
without disengaging the set screws can cause damage to the housing caps.
2. Input and output ranges are selectable by dip switch selection. Refer to figure 10 for dip switch settings. Adjust dip
switch settings and zero and span as necessary to achieve the desired input/output range.
3. If a current source other than the control device is used as the input source, disconnect the control device and
connect the current source positive terminal to the transducer “+” terminal and the current source negative
terminal to the transducer “-” terminal.
If an external meter is used, connect the current source positive terminal to the transducer “+” terminal. Connect
the meter positive terminal to the transducer “-” terminal and the meter negative terminal to the current source
negative terminal as shown in figure 8.
4. Check the supply pressure to ensure it is at the recommended pressure. Refer to table 1, the Specifications table,
for supply pressure recommendations.
13
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
5. Adjust the input current to the low mA DC.
6. The output pressure should be 0.2 bar (3 psig). If not, adjust the ZERO potentiometer until the output pressure
is 0.2 bar (3 psig).
7. Adjust the input current to the high mA DC.
8. The output pressure should be 1.0 bar (15 psig). If not, adjust the SPAN potentiometer until the output pressure
is 1.0 bar (15 psig).
9. Repeat steps 5 through 8 until the output pressure is within the referenced accuracy requirements without further
adjustment.
10. If a current source other than the control device was used, disconnect the current source and reconnect the control
device.
Principle of Operation
The converter module receives a standard DC current input signal from a control device to operate coils in a force
balanced beam system which in turn, controls bleed air through an integral nozzle/flapper arrangement. The nozzle
pressure provides the input signal to operate the relay as shown in figure 11. Relay output pressure is applied, through
tubing, directly to the final control element or valve/actuator assembly.
Figure 11. Fisher i2P‐100 Transducer Schematic
FIELD TERMINATOR AND
A3877-2
DIAPHRAGM
EXHAUST
DIAPHRAGM
OUTPUT
PRESSURE
ELECTRONICS CIRCUIT
COIL
ZERO
AND
SPAN
CIRCUIT
{
DC
CURRENT
INPUT SIGNAL
F
-
+
F
CURRENT‐TO‐PRESSURE
CONVERTER ASSEMBLY
MAGNET
BEAM
FLAPPER
NOZZLE
PNEUMATIC RELAY
RESTRICTION
VALVE PLUG
SUPPLY PRESSURE
Maintenance
Due to normal wear or damage from external sources such as debris in the supply medium, periodic maintenance or
repair of the transducer may be necessary. Maintenance of the transducer consists of troubleshooting, removal for
14
Instruction Manual
D103198X012
i2P-100 Transducer
May 2022
inspection, and replacement of component parts, as well as removal and inspection of the external removable
filter/restriction and cleaning or replacing as necessary (see figure 1).
WARNING
To avoid personal injury or property damage from the sudden release of pressure, air or natural gas:
D Always wear protective clothing, gloves, and eyewear when performing any maintenance operations.
D Do not remove the actuator from the valve while the valve is still pressurized.
D Disconnect any operating lines providing air pressure, electric power, or a control signal to the actuator. Be sure the
actuator cannot suddenly open or close the valve.
D Use bypass valves or completely shut off the process to isolate the valve from process pressure. Relieve process pressure
on both sides of the valve.
D Use lock‐out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
WARNING
When using natural gas as the supply medium, or for explosion proof applications, the following warnings also apply:
D Remove electrical power before removing either housing cap. Personal injury or property damage from fire or
explosion may result if power is not disconnected before removing either cap.
D Remove electrical power before disconnecting any of the pneumatic connections or removing the external removable
filter/restriction.
When disconnecting any of the pneumatic connections or the external removable filter/restriction, natural gas will seep
from the unit and any connected equipment into the surrounding atmosphere. Personal injury or property damage may
result from fire or explosion if preventative measures are not taken, such as adequate ventilation and the removal of any
ignition sources.
NOTICE
Do not attempt to remove either of the housing caps if the locking set screws (key 8) are engaged. Removing housing caps
without disengaging the set screws can cause damage to the housing caps.
WARNING
When replacing components, use only components specified by the factory. Always use proper component replacement
techniques, as presented in this manual. Improper techniques or component selection may invalidate the approvals and
the product specifications, as indicated in table 1. It may also impair operations and the intended function of the device and
could cause personal injury and property damage.
The converter module and the electronics module are non‐repairable. If troubleshooting or alignment attempts indicate a
faulty converter or electronics module, replace the module or return the transducer to your Emerson sales office
for repair.
15
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
Troubleshooting
The following procedures require taking the control valve/actuator assembly out of service. Provide some temporary
means of process control before taking the control valve out of service.
Electrical
1. Ensure terminal lug connections from the control device to the transducer are of the correct polarity (refer to the
electrical connection procedures in the Installation section of this manual).
2. At the transducer, ensure that the mA DC signal is applied, and ensure that it is within the 4 to 20 mA range.
3. Check switches and ensure that they are properly set. Refer to figure 10.
4. If the problem has not been resolved, see Electronics Module Replacement in this manual.
Pneumatic
Provide a 4‐30 mA DC current source, supply pressure, and a gauge to monitor the output pressure when checking
transducer operation. Refer to figure 13 for key number locations.
1. Ensure that supply pressure to the transducer meets your requirements [0.3 bar (5 psi) higher than upper range
limit of output signal, with a maximum of 3.4 bar (50 psi)].
2. Ensure that the filter (key 11), gasket (key 106), and restrictor (key 10) are open and clean. Remove the two screws
(key 14), the filter cap (key 13), and the O‐ring (key 12) to access the filter, gasket, and restrictor.
3. If a filter/regulator is used, ensure that it is working correctly. If not, ensure the dripwell is not plugged because of
excessive moisture accumulation. If necessary, drain off any moisture, and clean or replace the filter element.
4. Force the converter module to maximum output pressure with a 30 mA DC signal. Output pressure should build up
to the approximate value of the supply pressure [maximum of 3.4 bar (50 psi)].
5. When the input current is removed, the transducer output pressure should drop to less than 0.14 bar (2 psig). If it
does not, check to ensure the vent and exhaust air passageway is free from foreign material.
6. To inspect the relay assembly, refer to the Relay Maintenance procedures in this manual.
7. If the problem has not been resolved, see Converter Module Replacement in this manual.
Converter Module Replacement
Removal
Refer to figure 13 for key number locations.
1. Disconnect operating lines providing air pressure, electric power, or a control signal to the actuator. If using gas as
the supply medium remove electrical power before removing the housing cap.
2. Remove the housing cap (key 2) (the cap farthest away from the conduit). Note that the set screw associated with
this housing cap (key 8) needs to be loosened to remove the cap.
3. Unscrew the two captive screws (key 52) and remove the converter module from the housing.
4. Inspect the O‐ring (key 55) and replace if necessary.
16
Instruction Manual
D103198X012
i2P-100 Transducer
May 2022
Replacement
1. Lubricate the O‐ring (key 55) with a silicone sealant before replacing the converter module in the housing.
2. Insert the converter module into position in the housing (key 1). Replace the two screws (key 52) and tighten them.
3. Replace the housing cap (key 2), making sure to re‐tighten the set screw (key 8).
4. Electrically calibrate the unit using the procedure in the Calibration section of this manual.
Electronics Module Replacement
Removal
Refer to figure 13 for key number locations.
1. Disconnect operating lines providing air pressure, electric power, or a control signal to the actuator. If using gas as
the supply medium remove electrical power before removing the housing cap.
2. Remove the housing cap (key 2) (the cap closest to the conduit). Note that the set screw (key 8) associated with this
housing cap needs to be loosened to remove the cap.
3. Note the location of the wires, then remove the electrical wiring from the terminal block.
4. Remove the three screws (key 26) and remove the electronics module from the housing.
Replacement
1. Insert the electronics module into position in the housing (key 1). Replace the three screws (key 26) and tighten
them.
2. Replace the electrical wiring removed in step 1 of the removal procedures. Do not overtighten the terminal screws.
Maximum torque is 0.45 NSm (4 lbfSin).
3. Electrically calibrate the unit using the procedure in the Calibration section of this manual.
4. Replace the housing cap (key 2), making sure to re‐tighten the set screw (key 8).
17
i2P-100 Transducer
May 2022
Relay Maintenance
Refer to figures 12 and 14 for key number locations.
Figure 12. Valve Plug, Inner Valve Spring and Body Plug Assembly
VALVE PLUG
(KEY 39)
ONE OF THREE
TABS ON VALVE
PLUG
Instruction Manual
D103198X012
END OF SPRING COIL
BODY PLUG
(KEY 32)
A6057‐1
INNER VALVE
SPRING (KEY 35)
O‐RING
(KEY 42)
Removal
1. Remove the four mounting screws (key 36, shown in figure 14) and remove the relay from the transducer. Be
careful not to lose the bias spring (key 34) and input diaphragm (key 38).
2. Remove the body plug (key 32) that holds the inner valve spring (key 35) and valve plug (key 39) in place from the
relay body assembly.
3. Remove the exhaust port assembly (key 33) from the relay assembly.
4. Inspect the springs, exhaust seat, valve plug, and other parts for wear or damage; replace as necessary. Note: the
valve plug supply seat is an insert in the relay body (key 41). If this insert is bad, replace the relay body.
5. Make sure all parts of the relay are clean and that all passages are clear of foreign matter.
Assembly
Note
The relay will not function properly if the tabs on the body block and the relay body are not aligned as specified with the transducer
housing assembly in the following procedure.
18
Instruction Manual
D103198X012
i2P-100 Transducer
May 2022
1. Assemble the inner valve spring (key 35) onto the body plug (key 32) and fit the valve plug (key 39) onto the inner
valve spring as shown in figure 12. To assure best alignment between the valve plug, inner valve spring, and body
plug; fit the valve plug onto the inner valve spring so that one of the three tabs at the base of the valve plug sets at
the end of the last coil of the inner valve spring.
2. Lubricate the O‐ring (key 42) with a silicone sealant (key 37). Insert the assembled valve plug, inner valve spring,
and body plug into the relay body (key 41). Compress the spring and thread the body plug (key 5) into place. Then,
tighten the body plug.
3. Insert two of the mounting screws (key 36) into two opposite holes of the relay body (key 41). Hold the screws in
place while assembling the following parts on the relay body. The screws serve as studs to align the parts as they are
being assembled.
4. When replacing the exhaust port assembly (key 33), make sure all passages and screw holes are aligned and that
the hole in the center of the exhaust port assembly fits over the valve plug (key 39). Place the exhaust port assembly
on the relay body (key 41). Hold assembled parts in place.
5. Make sure the tabs on the body block (key 40) align with the tabs on the relay body (key 41) and that the side with 5
holes faces the relay body. Place the body block on the assembled parts. Hold assembled parts in place.
6. When replacing the input diaphragm (key 38), make sure all passages and screw holes are aligned. Place the input
diaphragm on the body block (key 40). Hold assembled parts in place.
7. Install the bias spring (key 34) into the transducer housing assembly (key 1). Make sure the tabs on the body block
and relay body align with the tab on the transducer housing assembly. Place the assembled parts onto the
transducer housing assembly. Thread the two mounting screws (key 36) into the transducer housing assembly.
Install the remaining two mounting screws. Tighten all mounting screws to 2 NSm (20 lbfSin).
8. Perform the procedure in the Calibration section of this manual.
Parts Ordering
A serial number is assigned to each transducer and stamped on the nameplate. Always refer to this serial number when
corresponding with your Emerson sales office
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson should not, under any
circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson may void your warranty,
might adversely affect the performance of the instrument, and could cause personal injury and property damage.
Parts Kits
DescriptionPart Number
Repair Kit for i2P‐100 electro‐pneumatic transducer
Contains O‐rings (key 4, 9, 12, and 55) and
Filter/Gasket/Restrictor assembly
(key 10, 11, and 106)R2P100X0032
Note:
Transducers Ordered Prior to November 2013
If you have not yet updated your PWB/Cup Assembly (key 24) and
require the low bleed 0.14 to 2.3 bar (2 to 33 psig) range you must
update your PWB/Cup Assembly using upgrade kit R2P100X0042.
regarding spare parts or technical information.
DescriptionPart Number
Upgrade Kit for i2P‐100 electro‐pneumatic transducer
w/Electronics Module for PWB/Cup Assembly
Contains O‐rings (key 4, 9, 12, and 55)
Filter/Gasket/Restrictor assembly (key 10, 11, and 106),
and PWB/Cup Assembly (key 24)R2P100X0042
32Body Plug
33Exhaust Port Assembly
34Spring
35Spring
36Machine Screw, fill hd (4 req'd)
37Lubricant, silicone sealant (not furnished with relay)
38* Upper Diaphragm
39* Valve Plug
40Body Block
41Relay / Body Assembly
42* O‐Ring
77Anti‐Seize Sealant (not furnished with relay)
107Thread Locking Adhesive (medium strength)
(not furnished with relay)
I/P Converter Assembly
43I/P Converter Assembly
Gauge/Pipe Plug
23Pipe plug, use when gauge is not specified (not shown)
Diagnostic Connections
KeyDescription
FlowScannert diagnostic system hook‐up
Includes pipe tee, pipe nipple, pipe bushings, connector body,
and body protector. See figure 7 for part identification.
Note
If the i2P‐100 transducer is used in a valve assembly with a positioner, no
hook‐up for diagnostic testing is required for the i2P‐100. The hook‐up
for diagnostic testing should be installed at the positioner.
Side Output
For units with gauges
For units without gauges
23* Gauge, (not shown)
0-30 psig/0-0.2 MPa/0-2 bar
0-60 psig/0-0.4 MPa/0-4 bar
*Recommended spare parts
21
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
KeyDescription
Mounting Parts
Note
Contact your Emerson sales office
following i2P‐100 mounting options.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher and FlowScanner are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson
Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
22
E 2005, 2022 Fisher Controls International LLC. All rights reserved.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.