This instruction manual provides installation, operation, maintenance, and parts ordering information for the Fisher
i2P‐100 transducer (see figure 1).
Refer to separate manuals for instructions covering equipment used with the transducer.
Do not install, operate, or maintain an i2P-100 electro‐pneumatic transducer without being fully
trained and qualified in valve, actuator, and accessory installation, operation and maintenance. To
avoid personal injury or property damage it is important to carefully read, understand, and follow all of
the contents of this manual, including all safety cautions and warnings. If you have any questions about
these instructions, contact your Emerson sales office
www.Fisher.com
.
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
NOTICE
Dropping or rough handling of the transducer can cause damage to the converter module resulting in a shifted output or a
minimum output.
Description
The transducer receives a 4‐20 mA DC input signal and transmits a proportional user field‐configurable pneumatic
output pressure to a final control element. The pneumatic output ranges are typically 0.2 to 1.0 bar (3 to 15 psig),
0.4 to 2.0 bar (6 to 30 psig), and 0.14 to 2.3 bar (2 to 33 psi). A typical application is in electronic control loops where
the final control element is a control valve assembly that is pneumatically operated. The input signal and output
pressure range of the transducer is indicated on the nameplate, attached to the housing.
Specifications
Specifications for the i2P‐100 transducer are listed in table 1.
WARNING
This product is intended for a specific current range, temperature range and other application specifications. Applying
different current, temperature and other service conditions could result in malfunction of the product, property damage or
personal injury.
Scan or click
code to find out
more about the
i2P-100 transducer
Instruction Manual
D103198X012
Table 1. Specifications
i2P-100 Transducer
May 2022
Input Signal
Available as standard with 4‐20 mA.
User configurable by dip switch for split ranging, see
table below.
Output Signal
(1)
Available as standard 0.2 to 1.0 bar (3 to 15 psig), 0.4
to 2.0 bar (6 to 30 psig), or 0.14 to 2.3 bar
(2 to 33 psig). User configurable by dip switch
selection and zero and span potentiometer
adjustment, see table below.
Input Signal
4‐20 mA DC
0.14 to 2.32 to 33
4‐12 mA DC0.2 to 1.03 to 15
12‐20 mA DC0.2 to 1.03 to 15
Output Pressure
Barpsig
0.2 to 1.03 to 15
0.4 to 2.06 to 30
Equivalent Circuit
The i2P‐100 equivalent circuit is a series circuit
consisting of a constant voltage drop (battery) of
approximately 4 VDC and a total resistance of 40
ohms. Input is shunted by two 6.8 V zener diodes (see
figure 9).
Supply Pressure
(2)
Recommended: 0.3 bar (5 psi) higher than upper
range limit of output signal
Maximum: 3.4 bar (50 psig)
Medium: Air or Non-Corrosive Natural Gas
Maximum Steady-State Flow Rate
Refer to tables 3 and 4
Maximum Output Air Capacity
(3)
8.0 m3/hr (300 scfh) at 1.4 bar (20 psig) supply
pressure
Performance
(4)
Reference Accuracy:±1.0% of full scale output span;
includes combined effects of hysteresis, linearity, and
deadband
(continued)
Independent Linearity: ±0.5% of full scale output span
Hysteresis: 0.4% of full scale output span
Frequency Response: Gain is attenuated 3 dB at 3 Hz
with transducer output signal piped to a typical
instrument input
Temperature Effect:±0.14% per degrees Celsius
(±0.075% per degrees Fahrenheit) of span
Supply Pressure Effect: 0.2% of full scale output span
per psi supply pressure change
Vibration Effect: Less than 1% of full scale output span
when tested to ISA S75.13
Electromagnetic Compatibility
Meets EN 61326‐1:2013
Immunity—Industrial locations per Table 2 of
EN 61326‐1 Standard. Performance is shown
in table 2 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Operating Ambient Temperature Limits
(2)
-40 to 85_C (-40 to 185_F)
Electrical Seal
Single sealed device per ANSI/ISA 12.27.01
Electrical Classification
Hazardous Area:
CSA—Intrinsically Safe, Explosion-proof,
Type n, Dust‐Ignition proof
FM—Intrinsically Safe, Explosion-proof,
Type n, Non‐incendive, Dust‐Ignition proof
ATEX—Intrinsically Safe, Flameproof, Type n
IECEx—Intrinsically Safe, Flameproof, Type n
Electrical Housing:
When Remotely VentedNo Remote Venting
CSA—Type 4X Encl.
FM—NEMA 4X
ATEX—IP66
IECEx—IP66
CSA—Type 3 Encl.
FM—NEMA 3
ATEX—IP64
IECEx—IP64
3
i2P-100 Transducer
May 2022
Table 1. Specifications (continued)
Instruction Manual
D103198X012
Other Classifications/Certifications
CUTR— Customs Union Technical Regulations
(Russia, Kazakhstan, Belarus, and Armenia)
Mounting Position
J Actuator J pipestand or J surface
INMETRO— National Institute of Metrology, Quality,
and Technology (Brazil)
KTL—Korea Testing Laboratory (South Korea)
NEPSI— National Supervision and Inspection Centre
Approximate Weight (Transducer Only)
2.5 kg (5.5 lbs)
for Explosion Protection and Safety of
Instrumentation (China)
Contact your Emerson sales office
classification/certification specific information
for
Actuator Stroking Time
See figure 2
Connections
Supply and Output Pressure: 1/4 NPT internal
connection
Vent: 1/4 NPT internal
Electrical: Standard 1/2 NPT
Wire Size: 18 to 22 AWG
Adjustments
(1)
Zero and Span: Trim potentiometers (20 turn) for
zero and span adjustments are located under the
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 4 paragraph
3 of the PED Directive 2014/68/EU. It was designed
and manufactured in accordance with Sound
Engineering Practice (SEP) and cannot bear the CE
marking related to PED compliance.
housing cap (see figure 10).
Switch: Allows input signal split range and
user‐configurable 0.14 to 2.3 bar (2 to 33 psig)
output.
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology
1. For other ranges, zero and span adjustments are needed.
2. The pressure and temperature limits in this document and any applicable standard or code limitation should not be exceeded.
3. Normal m
4. Performance values are obtained using a transducer with a 4 to 20 mA DC input signal and a 0.2 to 1.0 bar (3 to 15 psig) output signal at an ambient temperature of 24_C (75_F).
3
/hr—Normal cubic meters per hour (0_C and 1.01325 bar, absolute). Scfh—Standard cubic feet per hour (60_F and 14.7 psia).
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
Table 2. EMC Summary Results—Immunity
PortPhenomenonBasic StandardTest Level
Electrostatic discharge (ESD)IEC 61000‐4‐2
Enclosure
I/O signal/control
Specification limit = ±1% of span
1. A=No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
4
Radiated EM fieldIEC 61000‐4‐3
Burst (fast transients)IEC 61000‐4‐4
SurgeIEC 61000‐4‐5
Conducted RFIEC 61000‐4‐6150 kHz to 80 MHz at 3 VrmsA
4kV Contact
8kV Air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
1 kV
1 kV (line to ground only, each)
Performance
(1)
Criteria
A
A
A
A
Instruction Manual
D103198X012
Table 4. Maximum Steady-State Flow Rate
Table 3. Maximum Steady-State Flow Rate (Air)
SUPPLY PRESSUREOUTPUT PRESSURE
BarPsiBarPsim3/hrScfh
0.2 - 1.03 - 15
1.420
0.230.041.5
0.6290.062.0
1.0150.072.6
0.4 - 2.06 - 30
2.435
0.460.051.7
1.2180.082.9
2300.124.1
0.1 - 2.32 - 33
2.638
1. Normal m3/hour - Normal cubic meters per hour (0C and 1.0135 bar, absolute).
Scfh - Standard cubic feet per hour (60F and 14.7psig).
0.120.041.5
1.217.50.082.9
2.3330.124.3
STEADY STATE
FLOW RATE
(1)
Figure 2. Output‐Time Relationships for Fisher i2P‐100 Transducer
(Natural Gas)
i2P-100 Transducer
May 2022
SUPPLY PRESSUREOUTPUT PRESSURE
BarPsiBarPsim3/hrScfh
0.2 - 1.03 - 15
1.420
0.230.061.95
0.6290.072.6
1.0150.13.38
0.4 - 2.06 - 30
2.435
0.460.62.21
1.2180.113.77
2300.155.33
0.1 - 2.32 - 33
2.638
1. Normal m3/hour - Normal cubic meters per hour (0C and 1.0135 bar, absolute).
Scfh - Standard cubic feet per hour (60F and 14.7psig).
2. Natural gas steady state flow based on natural gas specific gravity of 0.6.
Flow decreases as specific gravity increases.
0.120.061.94
1.217.50.113.74
2.3330.185.55
STEADY STATE
FLOW RATE
(1,2)
100
90
80
70
60
50
OUTPUT
40
30
20
10
(% OF i2P‐100 OUTPUT SPAN)
0
0 102030405060708090
A6815
LOADING
EXHAUSTING
100
TIME (%)
Installation
The i2P‐100 transducer has been designed and approved for use with either air or natural gas as the supply medium. If
using natural gas as the pneumatic supply medium, natural gas will be used in the pneumatic output connections of
the transducer to any connected equipment. In normal operation the unit will vent the supply medium into the
surrounding atmosphere unless it is remotely vented. When using natural gas as the supply medium, in a
non‐hazardous location in a confined area, remote venting of the unit is required. Failure to do so could result in
personal injury, property damage, and area re‐classification. For hazardous locations remote venting of the unit may
be required, depending upon the area classification, and as specified by the requirements of local, regional, and
federal codes, rules and regulations. Failure to do so when necessary could result in personal injury, property damage,
and area re‐classification.
5
i2P-100 Transducer
May 2022
Instruction Manual
D103198X012
Additional information for installation and safe use in hazardous locations can be found in the related instruction
manual supplements as indicated in Hazardous Area Classifications and Special Instructions for “Safe Use” and
Installation in Hazardous Locations on page 7.
WARNING
To avoid personal injury or property damage from the sudden release of pressure, air, or natural gas:
D Always wear protective clothing, gloves, and eyewear when performing any installation operations.
D If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section of this
instruction manual.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process
media.
NOTICE
Do not use sealing tape on pneumatic connections. This instrument contains small passages that may become obstructed
by detached sealing tape. Thread sealant paste should be used to seal and lubricate pneumatic threaded connections.
WARNING
This unit vents the supply medium into the surrounding atmosphere. When installing this unit in a non‐hazardous
(non‐classified) location in a confined area, with natural gas as the supply medium, you must remotely vent this unit to a
safe location. Failure to do so could result in personal injury or property damage from fire or explosion, and area
re‐classification.
When installing this unit in a hazardous (classified) location remote venting of the unit may be required, depending upon
the area classification, and as specified by the requirements of local, regional, and federal codes, rules and regulations.
Failure to do so when necessary could result in personal injury or property damage from fire or explosion, and area
re‐classification.
Vent line piping should comply with local and regional codes and should be as short as possible with adequate inside
diameter and few bends to reduce case pressure buildup.
When received from the factory, the set screws (key 8), which provide a locking feature for the housing caps (key 2),
are backed off approximately one turn. When using the i2P‐100 transducer in explosive atmospheres these set screws
must be fully engaged.
WARNING
When using this unit in explosive atmospheres, the set screws (key 8) must be fully engaged to lock/secure the housing
caps. Failure to fully engage these set screws could result in unauthorized opening of the unit, which may result in personal
injury or property damage caused by fire or explosion.
6
Instruction Manual
D103198X012
i2P-100 Transducer
May 2022
Hazardous Area Classifications and Special Instructions for “Safe Use” and
Installation in Hazardous Locations
Refer to the following instruction manual supplements for approval information.
D CSA Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104192X012
D FM Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104193X012
D ATEX Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104194X012
D IECEx Approval Information for Fisher i2P-100 Electro-Pneumatic Transducer (D104195X012
All documents are available from your Emerson sales office
or at Fisher.com. Contact your Emerson sales office for all
)
)
)
)
other approval/certification information.
Mounting
When a transducer is ordered as part of a control valve assembly, the factory mounts the transducer on the actuator
and connects the necessary tubing, then adjusts the transducer as specified on the order. See figures 3 and 4 for
typical mounting configurations.
Figure 3. Fisheri2P‐100 Electro‐Pneumatic
Transducer Mounted on a Size 30 667 Sliding‐Stem
Actuator
CONDUIT
CONNECTION
Figure 4. Fisher i2P‐100 Electro‐Pneumatic
Transducer Mounted on a 2052 Rotary Actuator
with 3610J Positioner and V300B Rotary Valve
CONDUIT
CONNECTION
FIELD
TERMINATION AND
ELECTRONICS
MODULE CAP
W8723
CONVERTER
MODULE CAP
FIELD TERMINATION
AND ELECTRONICS
MODULE CAP
X1354
CONVERTER
MODULE CAP
Transducers also can be ordered separately for mounting on a control valve assembly already in service, or for
mounting on a 2 inch diameter pipestand, or a flat surface. The transducer may be ordered either with or without
mounting parts.
7
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.