DVC6200 or DVC2000
Mounting Instructions
D103537X012
January 2011
Use these instructions to mount a Fisher FIELDVUE
DVC6200 or DVC2000 digital valve controller on
Fisher 1066 size 75 actuators.
All other information regarding the instrument,
including safety cautions and warnings, can be
found in the quick start guide that shipped with your
instrument.
1066 Size 75 Actuator (End Mount)
WARNING
Avoid personal injury or property
damage from sudden release of
process pressure or bursting of parts.
Before performing any maintenance
operations:
D Always wear protective clothing,
gloves, and eyewear.
Digital Valve Controller on
D Use bypass valves or completely
shut off the process to isolate the
control valve from process pressure.
Relieve process pressure from both
sides of the control valve.
D Vent the pneumatic actuator
loading pressure and relieve any
actuator spring precompression.
D Use lock-out procedures to be
sure that the above measures stay in
effect while you work on the
equipment.
D Check with your process or safety
engineer for any additional measures
that must be taken to protect against
process media.
D Do not remove the actuator from
the valve while the valve is still
pressurized.
D Disconnect any operating lines
providing air pressure, electric power,
or a control signal to the actuator. Be
sure the actuator cannot suddenly
open or close the control valve.
Step 1. Attach the coupler (key 1) to the actuator
shaft using the pan head screws (key 2).
2
1
www.Fisher.com

DVC6200 or DVC2000
Digital Valve Controller on
1066 Size 75 Actuator (End Mount)
Step 2. Place the pointer (key 3) before attaching
the magnet assembly (key 4) to the coupler, using
pan head screws (key 5) to tighten in place.
Mounting Instructions
D103537X012
January 2011
4
5
3
7
Step 3. Attach the digital valve controller to the
mounting bracket (key 6) using hex head cap screws
(key 7).
6
2

DVC6200 or DVC2000
Mounting Instructions
D103537X012
January 2011
Step 4. While mounting the bracket with digital
valve controller to the actuator, hold the bracket
approximately one inch above the mounting surface
and move towards coupler until the center hole on
bracket locates magnet assembly approximately at
the center and then move down the bracket. Attach
the bracket to the actuator housing, using hex head
cap screws (key 8) and plain washers (key 9) but do
not tighten. Visually adjust the digital valve controller
assembly so that the magnet assembly
is centered in the housing channel and then
tighten the fasteners.
1066 Size 75 Actuator (End Mount)
Digital Valve Controller on
9
Note:
Select the appropriate screws (key 8) and washers (key 9)
as per actuator thread standard.
8
13
12
11
Step 5. Attach the post mountings (key 10) to the
mounting bracket and then attach travel indicator
scale (key 11) to the post mountings using pan head
screws (key 12) and washers (key 13).
10
3

DVC6200 or DVC2000
Digital Valve Controller on
1066 Size 75 Actuator (End Mount)
Completed digital valve controller mounting kit
assembly will look as shown.
Refer to the Parts List for mounting parts
identification.
PART LIST
KEY QTY DESCRIPTION
1 1 COUPLER
2 2 8−32UNCX0.50” PAN HD SCREW
3 1 POINTER
4 1 MAGNET ASSEMBLY
5 2 M3X0.5X14 PAN HD SCREW
6 1 MOUNTING BRACKET
7 4 M6X1X14 HEX HD CAP SCREW
8 4 5/16”−18UNCX0.88” OR 3/8”−16UNCX0.88”
HEX HD CAP SCREW
9 4 5/16” OR 3/8” PLAIN WASHER
10 2 POST MOUNTING
11 1 TRAVEL INDICATOR SCALE
12 2 M4X0.7X8 PAN HD SCREW
13 2 M4 PLAIN WASHER
Mounting Instructions
D103537X012
January 2011
COMPLETED DIGITAL VALVE
CONTROLLER MOUNTING KIT ASSEMBLY
Fisher is a mark owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. Emerson
Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property
of their respective owners.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they
are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the
designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated
entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of
any product remains solely with the purchaser and end user.
Emerson Process Management
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Chatham, Kent ME4 4QZ UK
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
4
EFisher Controls International LLC 2011; All Rights Reserved