Fisher DVC6200 Instruction Manual

Instruction Manual
D103605X012
DVC6200 Digital Valve Controller
Fisher™ FIELDVUE™ DVC6200 Digital Valve Controller
This manual applies to
Instrument Level HC, AD, PD, ODV Device Type 1309 Hardware Revision 2 Firmware Revision 7 Device Revision 13 DD Revision 71
Contents
Section 1 Introduction 3.................
Installation, Pneumatic and Electrical Connections,
and Initial Configuration 3.....................
Scope of Manual 3..............................
Conventions Used in this Manual 3................
Description 3..................................
Specifications 5................................
Related Documents 5...........................
Educational Services 8...........................
Section 2 Wiring Practices 9..............
Control System Requirements 9..................
HART Filter 9.................................
Voltage Available 9............................
Compliance Voltage 11........................
Auxiliary Terminal Wiring Length Guidelines 12....
Maximum Cable Capacitance 12.................
Installation in Conjunction with a Rosemountt 333 HART Tri‐Loopt HART‐to‐Analog
Signal Converter 13.........................
Section 3 Configuration 15...............
Guided Setup 15...............................
Manual Setup 15...............................
Mode and Protection 16........................
Instrument Mode 16.......................
Write Protection 16........................
Instrument 16................................
Identification 16...........................
Serial Numbers 17.........................
Units 17..................................
Terminal Box 17...........................
Input Range 17............................
Spec Sheet 18.............................
Edit Instrument Time 18....................
W9713
Travel/Pressure Control 18......................
Travel/Pressure Select 18...................
Cutoffs and Limits 19.......................
Pressure Control 19........................
Pressure Fallback 20........................
Control Mode 20..........................
Characterization 21........................
Dynamic Response 23......................
Tuning 24....................................
Travel Tuning 24...........................
Pressure Tuning 27........................
Travel/Pressure Integral Settings 27..........
Valve and Actuator 28..........................
Partial Stroke Test 30..........................
Outputs 36...................................
Output Terminal Configuration 36............
Switch Configuration 36....................
HART Variable Assignments 37..............
Transmitter Output 37.....................
Alert Setup 38.................................
Change to HART 5 / HART 7 38....................
April 2021
www.Fisher.com
DVC6200 Digital Valve Controller
April 2021
Instruction Manual
D103605X012
Contents (continued)
Section 4 Calibration 39.................
Calibration Overview 39.........................
Travel Calibration 40...........................
Auto Calibration 40........................
Manual Calibration 41......................
Pushbutton Calibration 42..................
Sensor Calibration 43..........................
Pressure Sensors 43........................
Analog Input Calibration 44.................
Relay Adjustment 45...........................
Double‐Acting Relay 45.....................
Single‐Acting Relays 46.....................
PST Calibration 47.............................
Section 5 Device Information, Alerts,
and Diagnostics 48.....................
Overview 48...................................
Status & Primary Purpose Variables 48............
Device Information 48.........................
Service Tools 49................................
Device Status 49..............................
Alert Record 49...............................
Alert Reporting 49.............................
Deadband Principle of Operation 52..............
Diagnostics 54................................
Stroke Valve 54............................
Partial Stroke Test (ODV only) 54.............
Variables 56...................................
Section 6 Maintenance and
Troubleshooting 57.....................
Replacing the Magnetic Feedback Assembly 58......
Module Base Maintenance 58.....................
Tools Required 58.............................
Component Replacement 59....................
Removing the Module Base 59..................
Replacing the Module Base 60...................
Submodule Maintenance 61......................
I/P Converter 61...............................
Printed Wiring Board (PWB) Assembly 63..........
Pneumatic Relay 65............................
Gauges, Pipe Plugs or Tire Valves 65..............
Terminal Box 66................................
Removing the Terminal Box 66..................
Replacing the Terminal Box 67...................
Troubleshooting 67.............................
Checking Voltage Available 67....................
Restart Processor 68............................
DVC6200 Technical Support Checklist 70...........
Section 7 Parts 71......................
Parts Ordering 71...............................
Parts Kits 71...................................
PWB Assembly 71.............................
Parts List 73...................................
Housing 73...................................
Common Parts 73.............................
Module Base 73...............................
I/P Converter Assembly 73......................
Relay 73.....................................
Terminal Box 74...............................
Feedback Connection Terminal Box 74............
Pressure Gauges, Pipe Plugs, or Tire
Valve Assemblies 74.........................
DVC6215 Feedback Unit 74.....................
HART Filters 74...............................
Appendix A Principle of Operation 81......
HART Communication 81........................
DVC6200 Digital Valve Controller 81...............
Appendix B Device Communicator
Menu Tree 85........................
Glossary 95............................
Index 101.............................
2
Instruction Manual
D103605X012
Section 1 Introduction
Installation, Pneumatic and Electrical Connections, and Initial Configuration
Introduction
April 2021
Refer to the DVC6200 Series Quick Start Guide (D103556X012) for DVC6200 installation, connection and initial configuration information. If a copy of this quick start guide is needed scan or click the QR code at the right, contact your Emerson
sales office or visit our website at Fisher.com.
Scan or click to access field support
Scope of Manual
This instruction manual is a supplement to the DVC6200 Series Quick Start Guide (D103556X012) that ships with every instrument. This instruction manual includes product specifications, reference materials, custom setup information, maintenance procedures, and replacement part details.
This instruction manual describes using an Emerson Device can also use Fisher ValveLink instrument. For information on using ValveLink software with the instrument refer to ValveLink software help or documentation.
Do not install, operate, or maintain a DVC6200 digital valve controller without being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal
injury or property damage, it is important to carefully read, understand, and follow all of the contents of this manual, including all safety cautions and warnings. If you have any questions about these
instructions, contact your Emerson sales office before proceeding.
software or ValveLink Mobile software to setup, calibrate, and diagnose the valve and
Communicator to set up and calibrate the instrument. You
Conventions Used in this Manual
Navigation paths and fast‐key sequences are included for procedures and parameters that can be accessed using the Device Communicator.
For example, to access Device Setup:
Device Communicator Configure > Guided Setup > Device Setup (2‐1‐1)
Refer to Appendix B for Device Communicator menu trees.
Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex
Device Communicator.
Description
DVC6200 digital valve controllers (figures 1‐1 and 1‐2) are communicating, microprocessor‐based current‐to‐pneumatic instruments. In addition to the traditional function of converting an input current signal to a pneumatic output pressure, the DVC6200 digital valve controller, using the HARTr communications protocol, gives easy access to information critical to process operation. You can gain information from the principal component of the process, the control valve itself, using the Device Communicator at the valve, or at a field junction box, or by using a
3
Introduction
April 2021
Instruction Manual
D103605X012
Figure 1‐1. FIELDVUE DVC6200 Digital Valve Controller Mounted on a Fisher Sliding-Stem Valve Actuator
X1182-1
Figure 1‐2. FIELDVUE DVC6200 Digital Valve Controller Integrally Mounted to a Fisher GX Control Valve
W9616
personal computer or operator's console within the control room. Additionally, an option is available which provides isolated circuitry for a valve position transmitter (for separate valve position feedback) or an integrated switch that can be set as a limit switch or an alert switch.
Using a personal computer and ValveLink software or AMS Suite: Intelligent Device Manager, or a Device Communicator, you can perform several operations with the DVC6200 digital valve controller. You can obtain general information concerning software revision level, messages, tag, descriptor, and date.
Diagnostic information is available to aid you when troubleshooting. Input and output configuration parameters can be set, and the digital valve controller can be calibrated. Refer to table 1‐1 for details on the capabilities of each diagnostic tier.
Using the HART protocol, information from the field can be integrated into control systems or be received on a single loop basis.
The DVC6200 digital valve controller is designed to directly replace standard pneumatic and electro‐pneumatic valve mounted positioners.
Table 1‐1. Instrument Level Capabilities
CAPABILITY
Auto Calibration X X X X
Custom Characterization X X X X
Burst Communication X X X X
Alerts X X X X
Step Response, Drive Signal Test & Dynamic Error Band X X X
Advanced Diagnostics (Valve Signature) X X X
Performance Tuner
Travel Control ‐ Pressure Fallback X X X
Supply Pressure Sensor X
Performance Diagnostics X X
Solenoid Valve Testing X X
Lead/Lag Set Point Filter
1. Refer to brochure part # D351146X012 for information on Fisher optimized digital valves for compressor antisurge applications.
2. HC = HART Communicating ; AD = Advanced Diagnostics ; PD = Performance Diagnostics ; ODV = Optimized Digital Valve.
3. Performance Tuner is only available in ValveLink software.
4. Supply Pressure Sensor available starting with Firmware 7.
(3)
(1)
HC AD PD ODV
(4)
DIAGNOSTIC LEVEL
X X X
X X X
(2)
X
4
Instruction Manual
D103605X012
Introduction
April 2021
Specifications
WARNING
Refer to table 1‐2 for specifications. Incorrect configuration of a positioning instrument could result in the malfunction of the product, property damage or personal injury.
Specifications for DVC6200 digital valve controllers are shown in table 1‐2. Specifications for the Device Communicator can be found in the Device Communicator quick start guide
.
Related Documents
This section lists other documents containing information related to the DVC6200 digital valve controller. These documents include:
D Bulletin 62.1:DVC6200 - Fisher FIELDVUE DVC6200 Digital Valve Controller (D103415X012
D Bulletin 62.1:DVC6200(S1) Fisher FIELDUVE DVC6200 Digital Valve Controller Dimensions (D103543X012
D Bulletin 62.1:Digital Valve Controller - Fisher FIELDVUE Digital Valve Controller Product Selection (D104363X012
D Fisher FIELDVUE DVC6200 Series Digital Valve Controller Quick Start Guide (D103556X012
D FIELDVUE Digital Valve Controller Split Ranging (D103262X012
D Using FIELDVUE Instruments with the Smart HART Loop Interface and Monitor (HIM) (D103263X012
D Using FIELDVUE Instruments with the Smart Wireless THUM Adapter and a HART Interface Module (HIM)
(D103469X012
D Audio Monitor for HART Communications (D103265X012
D HART Field Device Specification - Supplement to Fisher FIELDVUE DVC6200 Digital Valve Controller (D103639X012
D Using the HART Tri‐Loop HART‐to‐Analog Signal Converter with FIELDVUE Digital Valve Controllers (D103267X012
D Implementation of Lock‐in‐Last Strategy (D103261X012
D Fisher HF340 Filter Instruction Manual (D102796X012
D AMS Trex Device Communicator User Guide
)
)
)
)
)
)
)
)
)
)
)
)
D ValveLink Software Help or Documentation
All documents are available from your Emerson sale office or at Fisher.com.
5
Introduction
April 2021
Table 1‐2. Specifications
Instruction Manual
D103605X012
Available Mounting
DVC6200 digital valve controller or DVC6215 feedback unit:
657/667 or GX actuators Fisher rotary actuators applications
J Integral mounting to Fisher
J Window mounting to
J Sliding‐stem linear
J Quarter‐turn rotary applications
DVC6205 base unit for 2 inch pipestand or wall mounting (for remote‐mount)
The DVC6200 digital valve controller or DVC6215 feedback unit can also be mounted on other actuators that comply with IEC 60534‐6-1, IEC 60534-6-2, VDI/VDE 3845 and NAMUR mounting standards.
Communication Protocol
J HART 5 or J HART 7
Input Signal
Point-to-Point
Analog Input Signal: 4-20 mA DC, nominal; split ranging available Minimum Voltage Available at Instrument Terminals must be 9.5 VDC for analog control, 10 VDC for HART communication
Minimum Control Current: 4.0 mA Minimum Current w/o Microprocessor Restart: 3.5 mA Maximum Voltage: 30 VDC
Overcurrent protected Reverse Polarity protected
Multi-drop
Instrument Power: 11 to 30 VDC at 10 mA Reverse Polarity protected
Supply Pressure
(1)
Minimum Recommended: 0.3 bar (5 psig) higher than maximum actuator requirements Maximum: 10.0 bar (145 psig) or maximum pressure rating of the actuator, whichever is lower
Medium: Air or Natural Gas
Supply medium must be clean, dry and noncorrosive.
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized.
Per ISO 8573-1
Maximum particle density size: Class 7 Oil content: Class 3 Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Output Signal
Pneumatic signal, up to full supply pressure
Minimum Span: 0.4 bar (6 psig) Maximum Span: 9.5 bar (140 psig) Action:
Steady‐State Air Consumption
J Double, J Single Direct or J Reverse
(2)(3)
Standard Relay At 1.4 bar (20 psig) supply pressure:
Less than 0.38 normal m At 5.5 bar (80 psig) supply pressure: Less than 1.3 normal m
3
/hr (14 scfh)
3
/hr (49 scfh)
Low Bleed Relay
At 1.4 bar (20 psig) supply pressure:
Average value 0.056 normal m At 5.5 bar (80 psig) supply pressure: Average value 0.184 normal m
Maximum Output Capacity
At 1.4 bar (20 psig) supply pressure:
10.0 normal m
At 5.5 bar (80 psig) supply pressure:
29.5 normal m
3
/hr (375 scfh)
3
/hr (1100 scfh)
Operating Ambient Temperature Limits
3
/hr (2.1 scfh)
3
/hr (6.9 scfh)
(2)(3)
(1)(4)
-40 to 85_C (-40 to 185_F)
-52 to 85_C (-62 to 185_F) for instruments utilizing the Extreme Temperature option (fluorosilicone elastomers)
-52 to 125_C (-62 to 257_F) for remote‐mount feedback unit
Independent Linearity
(5)
Typical Value: ±0.50% of output span
Electromagnetic Compatibility
Meets EN 61326-1:2013 Immunity—Industrial locations per Table 2 of the EN 61326-1 standard. Performance is shown in table 1‐3 below. Emissions—Class A ISM equipment rating: Group 1, Class A
-continued-
6
Instruction Manual
D103605X012
Table 1‐2. Specifications (continued)
Introduction
April 2021
Lightning and Surge Protection—The degree of immunity to lightning is specified as Surge immunity in table 1‐3. For additional surge protection commercially available transient protection devices can be used.
Vibration Testing Method
Tested per ANSI/ISA-S75.13.01 Section 5.3.5. A resonant frequency search is performed on all three axes. The instrument is subjected to the ISA specified 1/2 hour endurance test at each major resonance.
Input Impedance
An equivalent impedance of 500 ohms may be used. This value corresponds to 10V @ 20 mA.
Humidity Testing Method
Tested per IEC 61514‐2
Electrical Classification
Hazardous Area Approvals
CSA— Intrinsically Safe, Explosion‐proof,
Division 2, Dust Ignition-proof FM— Intrinsically Safe, Explosion‐proof,
Dust Ignition-proof, Non-Incendive ATEX— Intrinsically Safe, Flameproof, Type n
Dust by intrinsic safety IECEx— Intrinsically Safe, Flameproof, Type n
Dust by intrinsic safety and enclosure
Electrical Housing
CSA— Type 4X, IP66 FM— Type 4X, IP66 ATEX— IP66 IECEx— IP66
Other Classifications/Certifications
Natural Gas Certified, Single Seal Device— CSA, FM, ATEX, and IECEx
Lloyds Register— Marine Type Approval CCC— China Compulsory Certification CML— Certification Management Limited (Japan) CUTR— Customs Union Technical Regulations
(Russia, Kazakhstan and Belarus)
-continued-
ESMA— Emirates Authority for Standardization and Metrology - ECAS-Ex (UAE)
INMETRO— National Institute of Metrology, Quality, and Technology (Brazil)
KOSHA— Korean Occupational Safety & Health Agency (South Korea)
KTL— Korea Testing Laboratory (South Korea) NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety Organisation - Chief Controller of Explosives (India)
SANS— South Africa National Standards Contact your Emerson sales office
for
classification/certification specific information.
Connections
Supply Pressure: 1/4 NPT internal and integral pad for mounting 67CFR regulator
Output Pressure: 1/4 NPT internal Tubing: 3/8‐inch recommended Vent: 3/8 NPT internal Electrical: 1/2 NPT internal or M20
Actuator Compatibility
Sliding‐Stem Linear
Linear actuators with rated travel between 6.35 mm (0.25 inch) and 606 mm (23.375 inches)
Quarter‐Turn Rotary
Rotary actuators with rated travel between 45 degrees and 180 degrees
(6)
Weight
DVC6200
Aluminum: 3.5 kg (7.7 lbs) Stainless Steel: 8.6 kg (19 lbs)
DVC6205: 4.1 kg (9 lbs) DVC6215: 1.4 kg (3.1 lbs)
Construction Materials
Housing, module base and terminal box: A03600 low copper aluminum alloy (standard) Stainless steel (optional)
Cover: Thermoplastic polyester Elastomers: Nitrile (standard)
Fluorosilicone (extreme temperature)
7
Introduction
April 2021
Table 1‐2. Specifications (continued)
Instruction Manual
D103605X012
Options
J Supply and output pressure gauges or J Tire valves J Integral mounted filter regulator J Low‐Bleed Relay J Remote Mount
J Integral 4‐20 mA Position Transmitter
(7)
J Extreme Temperature
(8)
J Stainless Steel
(9)
:
4‐20 mA output, isolated
Supply Voltage: 8‐30 VDC Reference Accuracy: 1% of travel span
The position transmitter meets the requirements of NAMUR NE43; selectable to show failure high ( > 22.5 mA) or failure low (< 3.6 mA). Fail high only when the positioner is powered.
J Integral Switch
(9)
:
One isolated switch, configurable throughout the calibrated travel range or actuated from a device alert Off State: 0 mA (nominal)
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
2. Normal m
3. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
4. Temperature limits vary based on hazardous area approval. Lower temperature limit for CUTR Ex d approval with fluorosilicone elastomers is -53_C (-63.4_F).
5. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long‐stroke applications.
6. Rotary actuators with 180 degree rated travel require a special mounting kit; contact your Emerson sales office for kit availability
7. The Quad O steady-state consumption requirement of 6 scfh can be met by a DVC6200 with low bleed relay A option, when used with up to 4.8 bar (70 psi) supply of Natural Gas at 16_C (60_F). The 6 scfh requirement can be met by low bleed relay B and C when used with up to 5.2 bar (75 psi) supply of Natural Gas at 16_C (60_F).
8. 4‐conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection between base unit and feedback unit. Pneumatic tubing between base unit output connection and actuator has been tested to 91 meters (300 feet). At 15 meters (50 feet) there was no performance degradation. At 91 meters there was minimal pneumatic lag.
9. The electronic output is available with either the position transmitter or the integral switch.
3
/hour - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60_F and 14.7 psia.
On State: up to 1 A Supply Voltage: 30 VDC maximum Reference Accuracy: 2% of travel span
Contact your Emerson sales office
or go to Fisher.com
for additional information
Declaration of SEP
Fisher Controls International LLC declares this product to be in compliance with Article 4 paragraph 3 of the PED Directive 2014/68/EU. It was designed and manufactured in accordance with Sound Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance.
However, the product may bear the CE marking to indicate compliance with other applicable European Community Directives.
Table 1‐3. EMC Summary Results—Immunity
Port Phenomenon Basic Standard Test Level
Electrostatic discharge (ESD) IEC 61000‐4‐2
Enclosure
I/O signal/control
Performance criteria: +/- 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
Radiated EM field IEC 61000‐4‐3
Rated power frequency magnetic field
Burst IEC 61000‐4‐4 1 kV A Surge IEC 61000‐4‐5 1 kV B Conducted RF IEC 61000‐4‐6 150 kHz to 80 MHz at 3 Vrms A
IEC 61000‐4‐8 30 A/m at 50/60Hz A
4 kV contact 8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80% 1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80% 2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
Performance
Criteria
A
A
Educational Services
For information on available courses for the DVC6200 digital valve controller, as well as a variety of other products, contact:
Emerson Automation Solutions Educational Services - Registration Phone: +1-641‐754‐3771 or +1-800‐338‐8158 e‐mail: education@emerson.com emerson.com/fishervalvetraining
(1)
8
Instruction Manual
D103605X012
Wiring Practices
April 2021
Section 2 Wiring Practices22
Control System Requirements
There are several parameters that should be checked to ensure the control system is compatible with the DVC6200 digital valve controller.
HART Filter
Depending on the control system you are using, a HART filter may be needed to allow HART communication. The HART filter is a passive device that is inserted in field wiring from the HART loop. The filter is normally installed near the field wiring terminals of the control system I/O (see figure 2‐1). Its purpose is to effectively isolate the control system output from modulated HART communication signals and raise the impedance of the control system to allow HART communication. For more information on the description and use of the HART filter, refer to the appropriate HART filter instruction manual.
To determine if your system requires a filter contact your Emerson sales office
Note
A HART filter is typically NOT required for any of the Emerson control systems, including PROVOXt, RS3t, and DeltaVt systems.
.
Figure 2‐1. HART Filter Application
NON‐HART BASED DCS
I/O I/O
HART FILTER
4‐20 mA + HART
DIGITAL VALVE CONTROLLER
Tx Tx
VALVE
A6188‐1
Voltage Available
The voltage available at the DVC6200 digital valve controller must be at least 10 VDC. The voltage available at the instrument is not the actual voltage measured at the instrument when the instrument is connected. The voltage measured at the instrument is limited by the instrument and is typically less than the voltage available.
9
Wiring Practices
April 2021
Instruction Manual
D103605X012
As shown in figure 2‐2, the voltage available at the instrument depends upon:
D the control system compliance voltage
D if a filter, wireless THUM adapter, or intrinsic safety barrier is used, and
D the wire type and length.
The control system compliance voltage is the maximum voltage at the control system output terminals at which the control system can produce maximum loop current.
The voltage available at the instrument may be calculated from the following equation:
Voltage Available = [Control System Compliance Voltage (at maximum current)] - [filter voltage drop (if a HART filter is used)] - [total cable resistance maximum current] - [barrier resistance x maximum current].
The calculated voltage available should be greater than or equal to 10 volts DC.
Table 2‐1 lists the resistance of some typical cables.
The following example shows how to calculate the voltage available for a Honeywellt TDC2000 control system with a HF340 HART filter, and 1000 feet of Beldent 9501 cable:
Voltage available = [18.5 volts (at 21.05 mA)] - [2.3 volts] - [48 ohms 0.02105 amps]
Voltage available = [18.5] - [2.3] - [1.01]
Voltage available = 15.19 volts
Figure 2‐2. Determining Voltage Available at the Instrument
TOTAL LOOP
COMPLIANCE VOLTAGE
CONTROL SYSTEM
+
-
Calculate Voltage Available at the Instrument as follows:
Control system compliance voltage
– Filter voltage drop (if used)
– Intrinsic safety barrier resistance (if used) x maximum loop current – 2.55 volts (121 ohms x 0.02105 amps)
– Smart Wireless THUM adapter voltage drop (if used)
– Total loop cable resistance x maximum loop current – 1.01 volts (48 ohms x 0.02105 amps for
= Voltage available at the instrument
NOTES:
Obtain filter voltage drop. The measured drop will be different than this value. The measured filter voltage drop
1
depends upon control system output voltage, the intrinsic safety barrier (if used), and the instrument. See note 3.
The voltage drop of the THUM adapter is linear from 2.25 volts at 3.5 mA to 1.2 volts at 25 mA.
2
The voltage available at the instrument is not the voltage measured at the instrument terminals. Once the instrument is
3
connected, the instrument limits the measured voltage to approximately 8.0 to 9.5 volts.
HART FILTER (if used)
1
3
CABLE RESISTANCE
INTRINSIC SAFETY BARRIER (if used)
2
THUM ADAPTER (IF USED)
R
Example Calculation
18.5 volts (at 21.05 mA)
– 2.3 volts (for HF300 filter)
1000 feet of Belden 9501 cable)
= 15.19 volts, available—if safety barrier (2.55 volts) is not used
VOLTAGE AVAILABLE AT THE
+
INSTRUMENT
-
10
Instruction Manual
D103605X012
Wiring Practices
April 2021
Table 2‐1. Cable Characteristics
pF/Ft
(1)
Capacitance
Cable Type
BS5308/1, 0.5 sq mm 61.0 200 0.022 0.074
BS5308/1, 1.0 sq mm 61.0 200 0.012 0.037
BS5308/1, 1.5 sq mm 61.0 200 0.008 0.025
BS5308/2, 0.5 sq mm 121.9 400 0.022 0.074
BS5308/2, 0.75 sq mm 121.9 400 0.016 0.053
BS5308/2, 1.5 sq mm 121.9 400 0.008 0.025
BELDEN 8303, 22 awg 63.0 206.7 0.030 0.098
BELDEN 8441, 22 awg 83.2 273 0.030 0.098
BELDEN 8767, 22 awg 76.8 252 0.030 0.098
BELDEN 8777, 22 awg 54.9 180 0.030 0.098
BELDEN 9501, 24 awg 50.0 164 0.048 0.157
BELDEN 9680, 24 awg 27.5 90.2 0.048 0.157
BELDEN 9729, 24 awg 22.1 72.5 0.048 0.157
BELDEN 9773, 18 awg 54.9 180 0.012 0.042
BELDEN 9829, 24 awg 27.1 88.9 0.048 0.157
BELDEN 9873, 20 awg 54.9 180 0.020 0.069
1. The capacitance values represent capacitance from one conductor to all other conductors and shield. This is the appropriate value to use in the cable length calculations.
2. The resistance values include both wires of the twisted pair.
Capacitance
pF/m
(1)
Resistance
Ohms/ft
(2)
Resistance
Ohms/m
Compliance Voltage
If the compliance voltage of the control system is not known, perform the following compliance voltage test.
(2)
1. Disconnect the field wiring from the control system and connect equipment as shown in figure 2‐3 to the control system terminals.
Figure 2‐3. Voltage Test Schematic
kW POTENTIOMETER
1
VOLTMETER
CIRCUIT UNDER TEST
A6192‐1
MILLIAMMETER
2. Set the control system to provide maximum output current.
3. Increase the resistance of the 1 kW potentiometer, shown in figure 2‐3, until the current observed on the milliammeter begins to drop quickly.
4. Record the voltage shown on the voltmeter. This is the control system compliance voltage.
For specific parameter information relating to your control system, contact your Emerson sales office
.
11
Wiring Practices
April 2021
Instruction Manual
D103605X012
Auxiliary Terminal Wiring Length Guidelines
The Auxiliary Input Terminals of a DVC6200 with instrument level ODV can be used with a locally‐mounted switch for initiating a partial stroke test. Some applications require that the switch be installed remotely from the DVC6200.
The length for wiring connected to the Auxiliary Input Terminals is limited by capacitance. For proper operation of the Auxiliary Input Terminals capacitance should not exceed 100,000 pF. As with all control signal wiring, good wiring practices should be observed to minimize adverse effect of electrical noise on the Aux Switch function.
Example Calculation: Capacitance per foot or per meter is required to calculate the length of wire that may be connected to the Aux switch input. The wire should not exceed the capacitance limit of 100,000 pF. Typically the wire manufacturer supplies a data sheet which provides all of the electrical properties of the wire. The pertinent parameter is the highest possible capacitance. If shielded wire is used, the appropriate number is the “Conductor to Other Conductor & Shield” value.
Example — 18AWG Unshielded Audio, Control and Instrumentation Cable
Manufacturer's specifications include:
Nom. Capacitance Conductor to Conductor @ 1 KHz: 26 pF/ft Nom. Conductor DC Resistance @ 20 Deg. C: 5.96 Ohms/1000 ft Max. Operating Voltage - UL 200 V RMS (PLTC, CMG),150 V RMS (ITC) Allowable Length with this cable = 100,000pF /(26pF/ft) = 3846 ft
Example — 18AWG Shielded Audio, Control and Instrumentation Cable
Manufacturer's specifications include:
Nom. Characteristic Impedance: 29 Ohms Nom. Inductance: .15 μH/ft Nom. Capacitance Conductor to Conductor @ 1 KHz: 51 pF/ft Nom. Cap. Cond. to other Cond. & Shield @ 1 KHz 97 pF/ft Allowable Length with this cable = 100,000pF /(97pF/ft) = 1030 ft
The AUX switch input passes less than 1 mA through the switch contacts, and uses less than 5V, therefore, neither the resistance nor the voltage rating of the cable are critical. Ensure that switch contact corrosion is prevented. It is generally advisable that the switch have gold‐plated or sealed contacts.
Maximum Cable Capacitance
The maximum cable length for HART communication is limited by the characteristic capacitance of the cable. Maximum length due to capacitance can be calculated using the following formulas:
Length(ft) = [160,000 - C
Length(m) = [160,000 - C
master
master
(pF)] [C
(pF)] [C
where:
160,000 = a constant derived for FIELDVUE instruments to ensure that the HART network RC time constant will be no greater than 65 μs (per the HART specification).
cable
cable
(pF/ft)]
(pF/m)]
C
C
= the capacitance of the control system or HART filter
master
= the capacitance of the cable used (see table 2‐1)
cable
12
Instruction Manual
D103605X012
Wiring Practices
April 2021
The following example shows how to calculate the cable length for a Foxborot I/A control system (1988) with a C
master
of 50, 000 pF and a Belden 9501 cable with characteristic capacitance of 50pF/ft.
Length(ft) = [160,000 - 50,000pF] [50pF/ft]
Length = 2200 ft.
The HART communication cable length is limited by the cable characteristic capacitance. To increase cable length, select a wire with lower capacitance per foot. Contact your Emerson sales office
for specific information relating to
your control system.
Installation in Conjunction with a Rosemount 333 HART Tri‐Loop HART‐to‐Analog Signal Converter
Use the DVC6200 digital valve controller in operation with a Rosemount 333 HART Tri‐Loop HART‐to‐Analog Signal Converter to acquire an independent 4‐20 mA analog output signal for the analog input, travel target, pressure, or travel. The HART Tri‐Loop accepts any three of these digital signals and converts them into three separate 4‐20 mA analog channels.
Refer to figure 2‐4 for basic installation information. Refer to the 333 HART Tri‐Loop HART‐to‐Analog Signal Converter Product Manual (00809-0100-4754
) for complete installation information.
Figure 2‐4. HART Tri‐Loop Installation Flowchart
START HERE
Unpack the HART Tri‐Loop
Review the HART Tri‐Loop Product Manual
Digital valve
Set the digital valve controller Burst Option
Set the digital valve controller Burst Mode
E0365
controller Installed?
Yes
No
Install the digital valve controller.
Install the HART Tri‐ Loop; See HART Tri‐ Loop product manual
Mount the HART Tri‐Loop to the DIN rail
Wire the digital valve controller to the HART Tri‐Loop
Install Channel 1 wires from HART Tri‐Loop to the control room
(Optional) Install Channel 2 and 3 wires from HART Tri‐Loop to the control room
Configure the HART Tri‐Loop to receive digital valve controller burst commands
Pass system
test?
Yes
DONE
No
Check troubleshooting procedures in HART Tri‐Loop product manual
13
Wiring Practices
April 2021
Instruction Manual
D103605X012
Commissioning the Digital Valve Controller for use with the HART Tri‐Loop Signal Converter
To prepare the digital valve controller for use with a 333 HART Tri‐Loop, you must configure the digital valve controller to burst mode, and select Burst Command 3. In burst mode, the digital valve controller provides digital information to the HART Tri‐Loop HART‐to‐Analog Signal Converter. The HART Tri‐Loop converts the digital information to a 4 to 20 mA analog signal. Each burst message contains the latest value of the primary (analog input), secondary (travel target), tertiary (configured output pressure), and quaternary (travel) variables.
To commission a DVC6200 for use with a HART Tri‐Loop, perform the following procedures.
Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.
Enable Burst Operation
With I/O Package
Device Communicator
Configure > Manual Setup > Outputs > Burst Mode (2‐2‐6‐6) HC, AD, PD or (2-2-7-6) ODV
Without I/O Package
Configure > Manual Setup > Outputs > Burst Mode (2‐2‐6‐2) HC, AD, PD or (2-2-7-2) ODV
Select Burst Enable and follow the prompts to enable burst mode. Then select Burst Command and follow the prompts to configure Loop Current/PV/SV/TV/QV.
Select the HART Variable Assignments
With I/O Package
Device Communicator
Configure the HART Variable Assignments. The Primary Variable (PV) is always Analog Input. The Secondary Variable (SV), Tertiary Variable (TV) and Quaternary Variable (QV) can be configured to any of the following variables. The variable assignments in the DVC6200 must correspond to the variable assignments in the Tri-Loop.
D Setpoint D Travel (see note below) D Pressure A D Pressure B D Pressure AB D Supply Pressure D Drive Signal D Analog Input
Note
If the instrument is configured to operate in pressure control mode, or detects an invalid travel sensor reading, the Travel variable will report pressure in percent of bench set range.
Configure > Manual Setup > Outputs > HART Variable Assignments (2-2-6-4) HC, AD, PD or (2-2-7-4) ODV
Without I/O Package
Configure > Manual Setup > Outputs > HART Variable Assignments (2-2-6-1) HC, AD, PD or (2-2-7-1) ODV
14
Instruction Manual
D103605X012
Configuration
April 2021
Section 3 Configuration
Note
Fast-key sequences are only applicable to the 475 Field Communicator. They do not apply to the Trex Device Communicator.
Guided Setup
Device Communicator Configure > Guided Setup (2‐1)
To quickly setup the instrument, the following procedures will guide you through the process.
Device Setup is used to configure the unique parameters for the valve, actuator, instrument and accessory construction. After Device Setup is complete, proceed with Auto Calibration.
Auto Calibration is used to establish the limits of physical travel. During this process, the valve will fully stroke from one travel extreme to the other. There are three calibration options to choose from:
d Autocalibrate – Standard runs the full calibration process (recommended).
d Autocalibrate – Without Biases establishes the travel end points, but does not adjust the Minor Loop Feedback
bias. This is for advanced use when manually setting the biases for large actuators.
dAdvanced Settings allows additional custom configuration of calibration parameters. This is for advanced use
when calibrating large actuators.
Manual Setup33
Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel cutoffs and limits. You can also restart the instrument and set the protection.
Table 3‐1. Default Detailed Setup Parameters
Setup Parameter Default Setting
Control Mode Analog Restart Control Mode Resume Last Analog In Range Low 4 mA Analog In Range High 20 mA
Instrument Configuration
Dynamic Response and Tuning
Analog Input Units mA Local AutoCal Button Disabled Polling Address 0 Burst Mode Enable No Burst Command 3 Cmd 3 (Trending) Pressure A-B Input Characterization Linear Travel Limit High 125% Travel Limit Low -25% Travel/Pressure Cutoff High 99.46% Travel/Pressure Cutoff Low 0.50% Set Point Rate Open 0%/sec Set Point Rate Close 0%/sec Set Point Filter Time (Lag Time) 0 sec Integrator Enable Yes Integral Gain 9.4 repeats/minute Integral Deadzone 0.26%
-continued on next page-
(1)
15
Configuration
April 2021
Instruction Manual
D103605X012
Table 3‐1. Default Detailed Setup Parameters (continued)
Setup Parameter Default Setting
Travel Deviation Alert Enable Yes Travel Deviation Alert Point 5% Travel Deviation Time 9.99 sec
Deviation & Other Alerts
1. The settings listed are for standard factory configuration. DVC6200 instruments can also be ordered with custom configuration settings. Refer to the order requisition for the custom settings.
2. Adjust to bar, kPa, or Kg/cm
Pressure Deviation Alert Enable Yes Pressure Deviation Alert Point 5 psi Pressure Deviation Alert Time 5.0 sec Drive Signal Alert Enable Yes Supply Pressure Alert Enable Yes
2
if necessary
(1)
(2)
Mode and Protection
Device Communicator Configure > Manual Setup > Mode and Protection (2‐2‐1)
Instrument Mode
There are two instrument modes for the DVC6200; In Service or Out of Service. In Service is the normal operating mode such that the instrument follows the 420 mA control signal. Out of Service is required in some cases to modify configuration parameters or to run diagnostics.
Note
Some changes that require the instrument to be taken Out Of Service will not take effect until the instrument is placed back In Service or the instrument is restarted.
Write Protection
There are two Write Protection modes for the DVC6200: Not Protected or Protected. Protected prevents configuration and calibration changes to the instrument. The default setting is Not Protected. Write Protection can be changed to Protected remotely. However, to change Write Protection to Not Protected, you must have physical access to the instrument. The procedure will require you to press a button ( ) on the terminal box as a security measure.
Instrument
Device Communicator Configure > Manual Setup > Instrument (2‐2‐2)
Follow the prompts on the Device Communicator display to configure the following Instrument parameters:
Identification
D HART Tag—A tag name up to 8 characters is available for the instrument. The HART tag is the easiest way to
distinguish between instruments in a multi‐instrument environment. Use the HART tag to label instruments electronically according to the requirements of your application. The tag you assign is automatically displayed when the Device Communicator establishes contact with the digital valve controller at power‐up.
D HART Long Tag (HART Universal Revision 7 only)—A tag name up to 32 characters is available for the instrument.
16
Instruction Manual
D103605X012
DDescription—Enter a description for the application with up to 16 characters. The description provides a longer
user‐defined electronic label to assist with more specific instrument identification than is available with the HART tag.
DMessageEnter any message with up to 32 characters. Message provides the most specific user‐defined means for
identifying individual instruments in multi‐instrument environments.
DPolling Address—If the digital valve controller is used in point‐to‐point operation, the Polling Address is 0. When
several devices are connected in the same loop, such as for split ranging, each device must be assigned a unique polling address. The Polling Address is set to a value between 0 and 63 for HART 7 and 0 and 15 for HART 5. To change the polling address the instrument must be Out Of Service.
For the Device Communicator to be able to communicate with a device whose polling address is not 0, it must be configured to automatically search for all or specific connected devices.
Configuration
April 2021
Serial Numbers
D Instrument Serial Number—Enter the serial number on the instrument nameplate, up to 12 characters.
D Valve Serial Number—Enter the serial number for the valve in the application, up to 12 characters.
Units
D Pressure UnitsDefines the output and supply pressure units in either psi, bar, kPa, or kg/cm2.
D Temperature Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the
digital valve controller's printed wiring board.
D Analog Input Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.
Terminal Box
DCalibration (CAL) Button—This button is near the wiring terminals in the terminal box and provides a quick means to
autocalibrate the instrument. The button must be pressed for 3 to 10 seconds. Autocalibration will move the valve through the full range of travel whether the Instrument Mode is In Service or Out of Service. However, if the Write Protection is Protected, this button will not be active. To abort, press the button again for 1 second. The calibration button is disabled by default.
DAuxiliary Terminal Action—These wire terminals can be configured to initiate a partial stroke test upon detection of
a short across the (+) and (-) terminals. The terminals must be shorted for 3 to 10 seconds.
Note
Auxiliary Terminal Action is only available for instrument level ODV.
Analog Input Range
DInput Range Hi—Permits setting the Input Range High value. Input Range High should correspond to Travel Range
High, if the Zero Power Condition is configured as closed. If the Zero Power Condition is configured as open, Input Range High corresponds to Travel Range Low. See figure 3‐1.
17
Configuration
April 2021
Instruction Manual
D103605X012
DInput Range Lo—Permits setting the Input Range Low value. Input Range Low should correspond to Travel Range
Low, if the Zero Power Condition is configured as closed. If the Zero Power Condition is configured as open, Input Range Low corresponds to Travel Range High. See figure 3‐1.
Figure 3‐1. Calibrated Travel to Analog Input Relationship
TRAVEL RANGE HIGH
CALIBRATED TRAVEL, %
TRAVEL RANGE LOW
ZPC = OPEN
ZPC = CLOSED
THE SHAPE OF THESE LINES DEPENDS ON THE INPUT CHARACTERISTICS LINEAR CHARACTERISTIC SHOWN
ANALOG INPUT
INPUT RANGE
NOTE: ZPC = ZERO POWER CONDITION
A6531‐1
LOW
mA OR % OF 4‐20 mA
INPUT RANGE
HIGH
Spec Sheet
The Spec Sheet provides a means to store the entire control valve specifications on board the DVC6200.
Edit Instrument Time
Permits setting the instrument clock. When alerts are stored in the alert record, the record includes the time and date. The instrument clock uses a 24‐hour format.
Travel/Pressure Control
Device Communicator Configure > Manual Setup > Travel/Pressure Control (2‐2-3)
Travel/Pressure Select
This defines the operating mode of the instrument as well as the behavior of the instrument should the travel sensor fail. There are four choices.
D Travel ControlThe instrument is controlling to a target travel. Fallback is not enabled.
D Pressure ControlThe instrument is controlling to a target pressure. Fallback is not enabled.
D Fallback-Sensor FailureThe instrument will fallback to pressure control if a travel sensor failure is detected.
18
Instruction Manual
D103605X012
Configuration
April 2021
D Fallback-Sensor/Tvl Deviation—The instrument will fallback to pressure control if a travel sensor failure is detected,
or if the Tvl Dev Press Fallback setting is exceeded for more than the Tvl Dev Press Fallback Time.
Note
Travel / Pressure Select must be set to Travel for double‐acting actuators
Cutoffs and Limits
DHi Limit/Cutoff SelectWhen the Hi Cutoff/Limit Select is configured for Cutoff, the Travel Target is set to 123%
when the Travel exceeds the Hi Cutoff Point. When the Hi Cutoff/Limit Select is configured for Limit, the Travel Target will not exceed the Hi Limit Point.
DHi Limit/Cutoff Point—This is the point within the calibrated travel range above which the Limit or Cutoff is in effect.
When using cutoffs, a Cutoff Hi of 99.5% is recommended to ensure valve goes fully open. The Hi Cutoff/Limit is deactivated by setting it to 125%.
DHi Soft Cutoff Rate—This setting allows the valve to ramp to the high travel extreme when the Cutoff Point is
reached at the configured rate. This provides a controlled ramp into the seat in order to minimize seat damage. When set to 0%/sec, the Soft Cutoff rate is disabled.
DLo Limit/Cutoff Select—When the Lo Cutoff/Limit Select is configured for Cutoff, the Travel Target is set to 23%
when the Travel is below the Lo Cutoff Point. When the Hi Cutoff/Limit Select is configured for Limit, the Travel Target will not fall below the Lo Limit Point.
DLo Limit/Cutoff Point—This is the point within the calibrated travel range below which the Limit or Cutoff is in effect.
When using cutoffs, a Cutoff Lo of 0.5% is recommended to help ensure maximum shutoff seat loading. The Lo Limit/Cutoff is deactivated by setting it to 25%.
DLo Soft Cutoff Rate—This setting allows the valve to ramp to the low travel extreme when the Cutoff Point is reached
at the configured rate. This provides a controlled ramp into the seat in order to minimize seat damage. When set to 0%/sec, the Soft Cutoff rate is disabled.
Pressure Control
DPressure Range High—The high end of output pressure range. Enter the pressure that corresponds with 100% valve
travel when Zero Power Condition is closed, or 0% valve travel when Zero Power Condition is open. This pressure must be greater than the Pressure Range Lo.
DPressure Range Lo—The low end of the output pressure range. Enter the pressure that corresponds to 0% valve
travel when Zero Power Condition is closed, or 100% valve travel when Zero Power Condition is open. This pressure must be less than the Pressure Range Hi.
19
Configuration
April 2021
Instruction Manual
D103605X012
Pressure Fallback
Note
Pressure Fallback is available for instrument level AD, PD, ODV.
DTvl Dev Press FallbackWhen the difference between the travel target and the actual travel exceeds this value for
more than the Tvl Dev Press Fallback Time, the instrument will disregard the travel feedback and control based on output pressure.
DTvl Dev Press Fallback TimeThis is the time, in seconds, that the travel target and the actual travel must be
exceeded before the instrument falls back into pressure control.
DFallback RecoveryIf the instrument has fallen into pressure control and the feedback problem is resolved, recovery
to travel control can occur automatically or with manual intervention. To return to travel control when Manual Recovery is selected, change the Fallback Recovery to Auto Recovery, and then back to Manual Recovery (if desired).
Control Mode
DControl ModeThis displays the current control mode of the instrument. This will show Analog if the instrument is
in PointtoPoint mode and is using a 420 mA signal for its power and set point. This will show Digital if the instrument is in Multidrop mode and is using 24 VDC for power and a digital set point for control.
Note
Another mode, Test, may be displayed. Normally the instrument should not be in the Test mode. The digital valve controller automatically switches to this mode whenever it needs to stroke the valve during calibration or stroke valve, for example. However, if you abort from a procedure where the instrument is in the test mode, it may remain in this mode. To take the instrument out of the Test mode, select Change Control Mode and enter Analog or Digital.
D Change Control ModeThis allows the user to configure the control mode to Analog or Digital.
D Restart Control ModeThis defines the Control Mode of the instrument after a restart (e.g. power cycle). Available
choices are Resume Last, Analog and Digital.
20
Instruction Manual
D103605X012
Configuration
April 2021
Characterization
DInput Characterization
Input Characterization defines the relationship between the travel target and ranged set point. Ranged set point is the input to the characterization function. If the zero power condition equals closed, then a set point of 0% corresponds to a ranged input of 0%. If the zero power condition equals open, a set point of 0% corresponds to a ranged input of 100%. Travel target is the output from the characterization function.
To select an input characterization, select Input Characterization from the Characterization menu. You can select from the three fixed input characteristics shown in figure 3‐2 or you can select a custom characteristic. Figure 3‐2 shows the relationship between the travel target and ranged set point for the fixed input characteristics, assuming the Zero Power Condition is configured as closed.
You can specify 21 points on a custom characteristic curve. Each point defines a travel target, in % of ranged travel, for a corresponding set point, in % of ranged set point. Set point values range from -6.25% to 106.25%. Before modification, the custom characteristic is linear.
DCustom Characterization
To define a custom input character, select Custom Characterization from the Characterization menu. Select the point you wish to define (1 to 21), then enter the desired set point value. Press Enter then enter the desired travel target for the corresponding set point. When finished, select point 0 to return to the Characterization menu.
With input characterization you can modify the overall characteristic of the valve and instrument combination. Selecting an equal percentage, quick opening, or custom (other than the default of linear) input characteristic modifies the overall valve and instrument characteristic. However, if you select the linear input characteristic, the overall valve and instrument characteristic is the characteristic of the valve, which is determined by the valve trim (i.e., the plug or cage).
21
Configuration
April 2021
Instruction Manual
D103605X012
Figure 3‐2. Travel Target Versus Ranged Set Point, for Various Input Characteristics (Zero Power Condition = Closed)
125
100
Travel Target, %
0
-25
-25 0 125100
Ranged Set Point, %
Input Characteristic = Linear
125
100
125
100
Travel Target, %
0
-25
-25 0 125100
Ranged Set Point, %
Input Characteristic = Equal Percentage
22
A6535‐1
Travel Target, %
0
-25
-25 0 125100
Ranged Set Point, %
Input Characteristic = Quick Opening
Instruction Manual
D103605X012
Configuration
April 2021
Dynamic Response
DSP Rate Open—Maximum rate (% of valve travel per second) at which the digital valve controller will move to the
open position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow the valve to stroke open as fast as possible.
DSP Rate Close—Maximum rate (% of valve travel per second) at which the digital valve controller will move to the
close position regardless of the rate of input current change. A value of 0 will deactivate this feature and allow the valve to stroke close as fast as possible.
DSet Point Filter Time (Lag Time)—The Set Point Filter Time (Lag Time) slows the response of the digital valve
controller. A value ranging from 0.2 to 10.0 can be used for noisy or fast processes to improve closed loop process control. Entering a value of 0.0 will deactivate the lag filter.
Note
Set Point Filter Time (Lag Time) is available for instrument level HC, AD, and PD.
DLead/Lag Set Point Filter—ODV devices have access to a lead‐lag set point filter that can be used to improve a valve's
dynamic response. The lead‐lag filter is part of the set point processing routine that reshapes the input signal before it becomes travel set point. Lead‐lag filters are characterized by lead and lag time constants.
Note
Lead/Lag is only available for instrument level ODV.
When the valve is in its active control region (off the seat), the lead‐lag filter improves small amplitude response by momentarily overdriving the travel set point. This is useful when the actuator is large and equipped with accessories. As a result, any volume boosters that are present will be activated. The longer the lag time, the more pronounced the overdrive. Since the lead‐lag input filter is used to enhance the dynamic response of a control valve, filter parameters should be set after the tuning parameters have been established.
When the valve is at its seat, the lead‐lag filter also has a boost function that sets the initial conditions of the filter artificially low so that small amplitude signal changes appear to be large signal changes to the filter. The boost function introduces a large spike that momentarily overdrives the instrument and activates any external volume boosters that may be present. The lead‐lag boost function is normally disabled except for those cases where the valve must respond to small command signals off the seat. By setting the lead/lag ratio in the opening and closing directions to 1.0, the boost function can be enabled without introducing lead‐lag dynamics in the active control region. See table 3‐2 for typical lead‐lag filter settings.
Table 3‐2. Typical Lead/Lag Filter Settings for Instrument Level ODV
Parameter Description Typical Value
Lag Time First order time constant. A value of 0.0 will disable the lead‐lag filter. 0.2 sec
Opening Lead/Lag Ratio Initial response to the filter in the opening direction. 2.0
Closing Lead/Lag Ratio Initial response to the filter in the closing direction. 2.0 Lead‐Lag Boost Initial conditions of the lead‐lag filter when the lower travel cutoff is active. Off
23
Configuration
April 2021
Instruction Manual
D103605X012
Tuning
Device Communicator Configure > Manual Setup > Tuning (2‐2-4)
Travel Tuning
WARNING
Changes to the tuning set may cause the valve/actuator assembly to stroke. To avoid personal injury and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly.
DTravel Tuning Set
There are eleven tuning sets to choose from. Each tuning set provides a preselected value for the digital valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response.
Table 3‐3 lists the proportional gain, velocity gain and minor loop feedback gain values for preselected tuning sets.
Table 3‐3. Gain Values for Preselected Travel Tuning Sets
Tuning Set Proportional Gain Velocity Gain Minor Loop Feedback Gain
C
D
E F
G H
I
J K L
M
X (Expert) User Adjusted User Adjusted User Adjusted
4.4
4.8
5.5
6.2
7.2
8.4
9.7
11.3
13.1
15.5
18.0
3.0
3.0
3.0
3.1
3.6
4.2
4.85
5.65
6.0
6.0
6.0
35 35 35 35 34
31 27 23 18 12 12
In addition, you can specify Expert tuning and individually set the proportional gain, velocity gain, and minor loop feedback gain. Individually setting or changing any tuning parameter or running Stabilize/Optimize will automatically change the tuning set to X (expert).
Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize or Performance Tuner in ValveLink software, may be used to achieve the desired results more rapidly than manual Expert tuning.
Table 3‐4 provides tuning set selection guidelines for Fisher and Baumann actuators. These tuning sets are only recommended starting points. After you finish setting up and calibrating the instrument, you may have to select either a higher or lower tuning set to get the desired response.
24
Instruction Manual
D103605X012
Table 3‐4. Actuator Information for Initial Setup
Actuator
Manufacturer
Fisher
Baumann
NOTE: Refer to figure table 3‐6 for feedback connection (magnet assembly) information.
1. X = Expert Tuning. Proportional Gain = 4.2; Velocity Gain = 3.0; Minor Loop Feedback Gain = 18.0
2. Travel Sensor Motion in this instance refers to the motion of the magnet assembly.
3. Values shown are for Relay A and C. Reverse for Relay B.
Actuator Model Actuator Size Actuator Style
Piston Dbl w/ or w/o
Spring. See actuator
instruction manual and
nameplate.
585C & 585CR
25 50 60
68, 80
100, 130
30, 30i
34, 34i, 40, 40i
657
45, 45i, 50, 50i
Spring & Diaphragm
46, 46i, 60, 60i, 70,
70i, & 80‐100
30, 30i
34, 34i, 40, 40i
667
45, 45i, 50, 50i
Spring & Diaphragm
46, 46i, 60, 60i, 70,
70i, 76, 76i & 80‐100
20, 30
1051 & 1052
33 40
Spring & Diaphragm
(Window‐mount)
60, 70
30
1061
40 60
Piston Dbl w/o Spring
68, 80, 100, 130
1066SR
2052
20
27, 75
1 2 3
Piston Sgl w/Spring
Spring & Diaphragm
(Window‐mount)
30, 30E
3024C
34, 34E, 40, 40E
Spring & Diaphragm
45, 45E
225
GX
750 K
Spring & Diaphragm
1200 M
Air to Extend
Air to Retract Towards the top of the instrument
Rotary
16 32 54
10 25
Spring & Diaphragm
54
Starting
Tuning Set
E
I J
L
M
H
K L
M H
K L
M H
I
K
M
J K L
M
G
L
H
J
M
E
H
K
(1)
X
C E
H
E
H
J
Configuration
April 2021
Travel Sensor Motion
Relay A or C
User Specified
Away from the top of the instrument
Towards the top of the instrument
Away from the top of the instrument
Depends upon pneumatic connections. See
description for Travel Sensor Motion
Mounting Style Travel Sensor Motion
A
B
C
Towards the top of the
Towards the top of the
D
Away from the top of the instrument
For Po operating mode (air opens): Towards the top of the instrument For P
operating mode (air closes):
s
Away from the top of the instrument
Air to Open
Towards the top of
the instrument
Away from the top of the instrument
Specify
(2)
(3)
Away from the top of
the instrument
instrument
instrument
Away from the top of
the instrument
Air to Close
Away from the top of
the instrument
25
Configuration
April 2021
Instruction Manual
D103605X012
DProportional Gain—the proportional gain for the travel control tuning set. Changing this parameter will also change
the tuning set to Expert.
DVelocity Gain—the velocity gain for the travel control tuning set. Changing this parameter will also change the
tuning set to Expert.
DMLFB Gain—the minor loop feedback gain for the travel control tuning set. Changing this parameter will also change
the tuning set to Expert.
DIntegral Enable—Yes or No. Enable the integral setting to improve static performance by correcting for error that
exists between the travel target and actual travel. Travel Integral Control is enabled by default.
DIntegral Gain—Travel Integral Gain is the ratio of the change in output to the change in input, based on the control
action in which the output is proportional to the time integral of the input.
DStabilize/Optimize
WARNING
During Stabilize/Optimize the valve may move, causing process fluid or pressure to be released. To avoid personal injury and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid.
Stabilize/Optimize permits you to adjust valve response by changing the digital valve controller tuning. During this routine the instrument must be out of service, however, the instrument will respond to setpoint changes.
If the valve is unstable, select Decrease Response to stabilize valve operation. This selects the next lower tuning set (e.g., F to E). If the valve response is sluggish, select Increase Response to make the valve more responsive. This selects the next higher tuning set (e.g., F to G).
If after selecting Decrease Response or Increase Response the valve travel overshoot is excessive, select Decrease Damping to select a damping value that allows more overshoot. Select Increase Damping to select a damping value that will decrease the overshoot. When finished, select done.
26
Instruction Manual
D103605X012
Configuration
April 2021
Pressure Tuning
DPressure Tuning Set
There are twelve Pressure Tuning Sets to choose from. Each tuning set provides a preselected value for the digital valve controller gain settings. Tuning set C provides the slowest response and M provides the fastest response.
Tuning set B is appropriate for controlling a pneumatic positioner. Table 3‐5 lists the proportional gain, pressure integrator gain and minor loop feedback gain values for preselected tuning sets.
Table 3‐5. Gain Values for Preselected Pressure Tuning Sets
Tuning Set Proportional Gain Integrator Gain Minor Loop Feedback Gain
B C D E
F
G H
I J
K
L
M
X (Expert) User Adjusted User Adjusted User Adjusted
0.5
2.2
2.4
2.8
3.1
3.6
4.2
4.8
5.6
6.6
7.8
9.0
0.3
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
35 35 35 35 35 34
31 27 23 18 12 12
In addition, you can specify Expert tuning and individually set the pressure proportional gain, pressure integrator gain, and pressure minor loop feedback gain. Individually setting or changing any tuning parameter will automatically change the tuning set to X (expert).
Note
Use Expert tuning only if standard tuning has not achieved the desired results.
Stabilize/Optimize, or Performance Tuner in ValveLink software, may be used to achieve the desired results more rapidly than Expert tuning.
DProportional Gain—the proportional gain for the pressure control tuning set. Changing this parameter will also
change the tuning set to Expert.
DMLFB Gain—the minor loop feedback gain for the pressure control tuning set. Changing this parameter will also
change the tuning set to Expert.
DIntegral Enable—Yes or No. Enable the pressure integral setting to improve static performance by correcting for
error that exists between the pressure target and actual pressure. Pressure Integral Control is enabled by default.
DIntegral Gain—Pressure Integral Gain (also called reset) is the gain factor applied to the time integral of the error
signal between desired and actual pressure.This feature is used during pressure control for greater accuracy during pressure control/fallback. Changing this parameter will also change the tuning set to Expert.
Travel/Pressure Integral Settings
DIntegral Dead Zone—A window around the Primary Setpoint in which integral action is disabled. The Dead Zone is
configurable from 0% to 2%, corresponding to a symmetric window from 0% to +/-2% around the Primary Setpoint.
27
Configuration
April 2021
Instruction Manual
D103605X012
Integral Dead Zone is used to eliminate friction induced limit cycles around the Primary Setpoint when the integrator is active. This dead zone value is used during the Auto Calibration of Travel procedure even if the travel integral is disabled; in the case of Auto Calibration travel failures with piston actuators, this value should be set to 1%. Default value is 0.26%.
DIntegrator Limit—The Integrator Limit provides an upper limit to the integrator output. The high limit is configurable
from 0 to 100% of the I/P drive signal.
Valve and Actuator
Device Communicator Configure > Manual Setup > Valve and Actuator (2‐2‐5)
Valve StyleEnter the valve style, rotary or sliding‐stem
Actuator StyleEnter the actuator style, spring and diaphragm, piston double‐acting without spring, piston
single‐acting with spring, or piston double‐acting with spring.
Feedback Connection—Refer to table 3‐6 for Feedback Connection options. Choose the assembly that matches the actuator travel range.
Note
As a general rule, do not use less than 60% of the magnet assembly travel range for full travel measurement. Performance will decrease as the assembly is increasingly subranged.
The linear magnet assemblies have a valid travel range indicated by arrows molded into the piece. This means that the hall sensor (on the back of the DVC6200 housing) has to remain within this range throughout the entire valve travel. The linear magnet assemblies are symmetrical. Either end may be up.
Table 3‐6. Feedback Connection Options
Magnet Assembly
SStem #7 4.2-7 0.17-0.28 -
SStem #19 8-19 0.32-0.75 -
SStem #25 20-25 0.76-1.00 -
SStem #38 26-38 1.01-1.50 -
SStem #50 39-50 1.51-2.00 -
SStem #110 51-110 2.01-4.125 -
SStem #210 110-210 4.125-8.25
SStem #1 Roller > 210 > 8.25 60-90_
RShaft Window #1 - - 60-90_
RShaft Window #2 - - 60-90_
RShaft End Mount - - 60-90_
mm Inch Degrees
Travel Range
Relay Type—There are three categories of relays that result in combinations from which to select. Relay Type: The relay type is printed on the label affixed to the relay body. A = double‐acting or single‐acting B = single‐acting, reverse C= single‐acting, direct Special App: This is used in single‐acting applications where the “unused” output port is configured to read the pressure downstream of a solenoid valve. Lo Bleed: The label affixed to the relay body indicates whether it is a low bleed version.
28
Instruction Manual
D103605X012
Configuration
April 2021
Zero Power Condition—The position of the valve (open or closed) when the electrical power to the instrument is removed. Zero Power Condition (ZPC) is determined by relay type, as shown in figure 3‐3.
Figure 3‐3. Zero Power Condition
A
Relay Type
Single‐Acting Direct (Relay A or C)
Double‐Acting (Relay A)
B
Single‐Acting Reverse (Relay B)
Loss of Electrical Power
Port A pressure to zero.
Port A pressure to zero. Port B pressure to full supply.
Port B pressure to full supply.
Travel Sensor Motion
WARNING
If you answer YES to the prompt for permission to move the valve when determining travel sensor motion, the instrument will move the valve through a significant portion of its travel range. To avoid personal injury and property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid.
Select Clockwise/Toward Bottom, or Counterclockwise/Toward Top. Travel Sensor Motion establishes the proper travel sensor rotation. For quarter‐turn actuators determine rotation by viewing the rotation of the magnet assembly from the back of the instrument.
Note
Travel Sensor Motion in this instance refers to the motion of the magnet assembly. Note that the magnet assembly may be referred to as a magnetic array in user interface tools.
DFor instruments with Relay A and C: If increasing air pressure at output A causes the magnet assembly to move
down or the rotary shaft to turn clockwise, enter CW/To Bottom Inst. If it causes the magnet assembly to move up, or the rotary shaft to turn counterclockwise, enter CCW/To Top Inst.
DFor instruments with Relay B: If decreasing air pressure at output B causes the magnet assembly to down, or the
rotary shaft to turn clockwise, enter CW/To Bottom Inst. If it causes the magnet assembly to move up, or the rotary shaft to turn counterclockwise, enter CCW/To Top Inst.
Maximum Supply Pressure
Enter the maximum supply pressure that is required to fully stroke the valve.
29
Configuration
April 2021
Instruction Manual
D103605X012
Port A Pressure Limit
In single acting direct only applications, the instrument will limit the output pressure to the actuator from Port A. When this pressure limit is exceeded the device will go to the no air state.
CAUTION
This is a firmware controlled feature that requires loop power to the instrument. If loop power is lost, or there is an electronic or firmware failure, the protection feature will not remain in effect.
Output Pressure Limit Enable enables/disables the Port A Pressure Limit feature.
Note
There is an associated alert available with this feature. See the Port A Overpressurized alert in the Alert Setup section.
Partial Stroke Test (PST)
Device Communicator Configure > Manual Setup > Partial Stroke (2-2-7)
Note
Partial Stroke is only available for instrument level ODV.
Partial Stroke Test Parameters
Test Start Point defines the normal (not tripped) end of valve travel. The valve must be at this end for a PST to be
initiated. Setting this value to Not Configured will disable partial stroke tests.
Travel Hi Hi defines, in percent (%) of calibrated travel, the point above which the valve is considered to have reached the high end.
Travel Lo Lo defines, in percent (%) of calibrated travel, the point below which the valve is considered to have reached the low end.
Pause Time is the time between the outgoing and incoming strokes of the test. The default value is 5 seconds. Pause Time will not be used if Short Duration PST is enabled. The outgoing stroke is from the normal end to the PST target and the incoming stroke is the return stroke to normal. See figure 3‐4.
30
Loading...
+ 78 hidden pages