Fisher C1P, C1B, C1D Instruction Manual

Page 1
Instruction Manual
D103292X012 September 2009
C1 Controllers and Transmitters
FisherR C1 Series Pneumatic Controllers and Transmitters
Contents
Introduction 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scope of Manual 2. . . . . . . . . . . . . . . . . . . . . . . . . .
Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Educational Services 2. . . . . . . . . . . . . . . . . . . . . .
Installation 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Standard Installation 2. . . . . . . . . . . . . . . . . . . . . .
Panel Mounting 6. . . . . . . . . . . . . . . . . . . . . . . . . . .
Wall Mounting 6. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pipestand Mounting 6. . . . . . . . . . . . . . . . . . . . . . .
Actuator Mounting 6. . . . . . . . . . . . . . . . . . . . . . . .
Pressure Connections 6. . . . . . . . . . . . . . . . . . . . .
Supply Pressure 6. . . . . . . . . . . . . . . . . . . . . . . . .
Process Pressure 8. . . . . . . . . . . . . . . . . . . . . . . .
Vent Assembly 8. . . . . . . . . . . . . . . . . . . . . . . . . . .
Controller Operation 9. . . . . . . . . . . . . . . . . . . . . . . .
ProportionalOnly Controllers 9. . . . . . . . . . . . . .
Adjustments 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment: Set Point 9. . . . . . . . . . . . . . . . . .
Adjustment: Proportional Band 9. . . . . . . . . .
Calibration: Proportional−Only Controllers 10. .
Startup: Proportional−Only Controllers 12. . . . .
ProportionalPlusReset Controller 13. . . . . . . .
Adjustments 13. . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment: Set Point 13. . . . . . . . . . . . . . . . .
Adjustment: Proportional Band 13. . . . . . . . .
Adjustment: Reset 13. . . . . . . . . . . . . . . . . . . .
Adjustment: AntiReset Windup 14. . . . . . . .
Calibration 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration: Proportional−Plus−Reset
Controllers 14. . . . . . . . . . . . . . . . . . . . . . . . . .
Calibration: AntiReset Windup 16. . . . . . . . .
Startup: Proportional−Plus−Reset
Controllers 16. . . . . . . . . . . . . . . . . . . . . . . . . .
Differential Gap Controllers 16. . . . . . . . . . . . . . .
Adjustments 16. . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment: Set Point 16. . . . . . . . . . . . . . . . .
Adjustment: Proportional Band 17. . . . . . . . .
Calibration: Differential Gap Controllers 17. . . .
Startup: Differential Gap Controllers 19. . . . . . .
Transmitter Operation 19. . . . . . . . . . . . . . . . . . . . .
Adjustments 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Adjustment: Zero 19. . . . . . . . . . . . . . . . . . . . . . .
Adjustment: Span 19. . . . . . . . . . . . . . . . . . . . . . .
W92631
Figure 1. Fisher C1 Controller YokeMounted on Control
Valve Actuator
Calibration: Transmitters 19. . . . . . . . . . . . . . . . . .
Startup: Transmitters 20. . . . . . . . . . . . . . . . . . . . .
Principle of Operation 21. . . . . . . . . . . . . . . . . . . . . .
ProportionalOnly Controllers 21. . . . . . . . . . . . .
ProportionalPlusReset Controllers 22. . . . . . .
Controllers with AntiReset Windup 22. . . . . . . .
Differential Gap Controllers 23. . . . . . . . . . . . . . .
Transmitters 23. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing Gauges 24. . . . . . . . . . . . . . . . . . . . . . .
Replacing Bourdon Tube 24. . . . . . . . . . . . . . . . .
Replacing Bellows Sensing Element 26. . . . . . . .
Changing Proportional or Reset Valve 27. . . . . .
Changing Anti−Reset Windup Differential
Relief Valve 27. . . . . . . . . . . . . . . . . . . . . . . . . .
Changing Action 27. . . . . . . . . . . . . . . . . . . . . . . . .
ProportionalOnly to a Differential
Gap Controller 27. . . . . . . . . . . . . . . . . . . . . . .
Reverse to Direct Action 28. . . . . . . . . . . . . . . . .
Relay Replacement 29. . . . . . . . . . . . . . . . . . . . . .
Changing Output Signal Range 30. . . . . . . . . . . .
Parts Ordering 31. . . . . . . . . . . . . . . . . . . . . . . . . . . .
www.Fisher.com
Page 2
Instruction Manual
C1 Controllers and Transmitters
Contents (Continued)
Parts Kits 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Parts List 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Common Parts 31. . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting Parts for Panel, Wall, Pipestand
or Actuator Mounting 39. . . . . . . . . . . . . . . . . . .

Introduction

Scope of Manual

This instruction manual provides installation, operating, maintenance, and parts information for the Fisher C1 Series pressure controllers and transmitters shown in figure 1. Refer to separate instruction manuals for information regarding the control valve, actuator, and accessories.
Do not install, operate, or maintain C1 Series pressure controllers and transmitters without first being fully trained and qualified in valve, actuator, and accessory installation, operation, and maintenance. To avoid personal injury and property damage, it is important to carefully read, understand, and follow all the contents of this manual, including all safety cautions and warnings. If you have any questions about these instructions, contact your Emerson Process Management sales office before proceeding.

Description

The C1 Series pneumatic pressure controllers and transmitters use a bellows or Bourdon tube sensing element to sense the gauge pressure, vacuum, compound pressure, or differential pressure of a liquid or gas. The controller or transmitter output is a pneumatic pressure signal that can be used to operate a final control element, indicating device, or recording device.
Unless otherwise noted, all NACE references are to NACE MR01752002.
September 2009

Educational Services

For information on available courses for C1 Series controllers and transmitters, as well as a variety of other products, contact:
Emerson Process Management Educational Services, Registration P.O. Box 190; 301 S. 1st Ave. Marshalltown, IA 501582823 Phone: 8003388158 or Phone: 6417543771 FAX: 6417543431 email: education@emersonprocess.com

Installation

WARNING
To avoid personal injury or property
damage resulting from the sudden
release of pressure:
D Always wear protective clothing, gloves, and eyewear when performing any installation operations.
D Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and appropriate preventive measures are not taken. Preventive measures may include, but are not limited to, one or more of the following; remote venting of the unit, reevaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any ignition sources. For information on remote venting of this controller/ transmitter, refer to page 8.
D If installing into an existing application, also refer to the WARNING at the beginning of the Maintenance section in this instruction manual.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process media.

Specifications

Specifications for the C1 Series controllers and transmitters are listed in table 1. Table 2 explains available configurations and options.
2

Standard Installation

The instruments are normally mounted vertical with the case/cover as shown in figure 1. If installing the instrument in any other position, be sure that the vent opening shown in figure 2 is facing downward.
Page 3
Instruction Manual
September 2009
Available Configurations
See table 2
Input Signal
Type: J Gauge pressure, J vacuum,
J compound pressure, or J differential pressure of a liquid or gas
Limits: See table 3 or 4
Output Signal
ProportionalOnly or ProportionalPlusReset Controllers and Transmitters:
J 0.2 to 1.0 bar (3 to 15 psig) or J 0.4 to 2.0 bar (6 to 30 psig) pneumatic
pressure signal
Differential Gap Controllers:
J 0 and 1.4 bar (0 and 20 psig) or J 0 and 2.4 bar (0 and 35 psig) pneumatic
pressure signal Action: Control action is field reversible between J direct (increasing sensed pressure produces increasing output signal) and J reverse (increasing sensed pressure produces decreasing output signal).
Supply Pressure Requirements
(1)
See table 5
C1 Controllers and Transmitters
Table 1. Specifications
Supply and Output Connections
1/4 NPT internal
Common Signal Pressure Conversions
See table 6
Proportional Band Adjustment
For ProportionalOnly Controllers: Full output
pressure change adjustable from J 2% to 100% of the sensing element range for 0.2 to 1.0 bar (3 to 15 psig) or J 4% to 100% of the sensing element range for 0.4 to 2.0 bar (6 to 30 psig)
For ProportionalPlusReset Controllers: Full output pressure change adjustable from J 3% to 100% of the sensing element range for 0.2 to 1.0 bar (3 to 15 psig), or J 6% to 100% of the sensing element range for 0.4 to 2.0 bar (6 to 30 psig)
Differential Gap Adjustment
For Differential Gap Controllers:
Full output pressure change adjustable from 15% to 100% of sensing element range
Reset Adjustment
For ProportionalPlusReset Controllers:
Adjustable from 0.01 to 74 minutes per repeat (100 to 0.01 repeats per minute)
Supply Pressure Medium
Air or natural gas Air Quality: Supply pressure must be clean, dry air
that meets the requirements of ISA Standard
7.0.01. A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized
Natural Gas: Natural gas must be clean, dry, oilfree, and noncorrosive. H2S content should not exceed 20 ppm.
SteadyState Air Consumption
(2,3)
0.2 to 1.0 bar (3 to 15 psig): 0.08 normal m3/hour (3 scfh)
0.4 to 2.0 bar (6 to 30 psig): 0.12 normal m3/hour (4.5 scfh)
continued
Zero Adjustment (Transmitters Only)
Continuously adjustable to position span of less than 100% anywhere within the sensing element range
Span Adjustment (Transmitters Only)
Full output pressure change adjustable from 6 to 100% of sensing element range
Performance
Repeatability: 0.5% of sensing element range Deadband (Except Differential Gap Controllers)
(4)
: 0.1% of process sensing element
span
Typical Frequency Response at 100% Proportional Band
Output to Actuator: 0.7 Hz and 110 degree phase shift with 1850 cm3 (113 inches3) volume, actuator at midstroke Output to Positioner Bellows: 9 Hz and 130 degree phase shift with 0.2 to 1.0 bar (3 to 15 psig) output to 33 cm3 (2 inches3) bellows
3
Page 4
Instruction Manual
C1 Controllers and Transmitters
Table 1. Specifications (continued)
Ambient Operating Temperature Limits
J Standard Construction: 40 to 71_C (−40 to 160_F) J High Temperature Construction: 18 to 104_C (0 to 220_F)
Antireset windup (differential pressure relief) and process pressure gauge options are only available in the standard construction
If the process temperature is outside the ambient operating range of the controller, the length of the capillary tube run from the sensor point to the controller process input may be adjusted to protect the controller from the process temperature
Typical Ambient Temperature Operating Influence
Proportional Control only:
Output pressure changes $3.0% of sensing element range for each 28_C (50_F) change in temperature between 40 and 71_C (40 and 160_F) for a controller set at 100% proportional band
ProportionalPlusReset Control:
Output pressure changes $2.0% of sensing element range for each 28_C (50_F) change in temperature between 40 and 71_C (40 and 160_F) for a controller set at 100% proportional band
(1)
September 2009
Transmitters only:
Output pressure changes $3.0% of sensing element range for each 28_C (50_F) change in temperature between 40 and 71_C (40 and 160_F) for a transmitter set at 100% span
Hazardous Area Classification
Complies with the requirements of ATEX Group II Category 2 Gas and Dust
Refer to figure 25 for location of ATEX marking
Approximate Weight
8.2 kg (18 pounds)
Options
Case pressure tested to 0.14 bar (2 psig)
Declaration of SEP
Fisher Controls International LLC declares this product to be in compliance with Article 3 paragraph 3 of the Pressure Equipment Directive (PED) 97 / 23 / EC. It was designed and manufactured in accordance with Sound Engineering Practice (SEP) and cannot bear the CE marking related to PED compliance.
However, the product may bear the CE marking to indicate compliance with other applicable European Community Directives.
1. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded.
2. Normal m3/hr: normal cubic meters per hour (m3/hr, 0_C and 1.01325 bar, absolute). Scfh: standard cubic feet per hour (ft3/hr, 60_F and 14.7 psig).
3. To convert from air flow rate to natural gas flow rate multiply by 1.29.
4. An adjustable differential gap (differential gap controllers) is equivalent to an adjustable deadband.
Table 2. Available Configurations
TYPE NUMBER
DESCRIPTION
Proportionalonly controller
Proportionalplusreset controller
Differential gap controller − − −
Transmitter C1D
4
Bourdon Tube Sensing
Element (Gauge Pressure Only)
Without anti−reset windup
With antireset windup − − −
C1P C1B
Bellows Sensing Element
Gauge Pressure Differential Pressure
C1D
Page 5
Instruction Manual
September 2009
C1 Controllers and Transmitters
Table 3. Bourdon Tube Pressure Range and Materials
PRESSURE RANGES
(1,2)
MAXIMUM ALLOWABLE STATIC PRESSURE LIMITS
Standard With Optional Travel Stop
Bar Psig Bar Psig Bar Psig
0 to 2.0 0 to 4.0 0 to 7.0
0 to 14 0 to 20 0 to 40 0 to 70
0 to 100 0 to 200 0 to 350
0 to 550 0 to 700
1. If the process can trip to a pressure outside of the operating range of the sensing element, a commercially available device, such as an overpressure protector, may be used to protect against pressure surges and pulsations.
2. Range marked on Bourdon tube may be in kPa (1 bar = 100 kPa)
3. Bourdon tube may be pressurized to limit shown without permanent zero shift.
4. With travel stop set at 110% of the range.
5. Bourdon tubes are also available in NACE compliant material. Contact your Emerson Process Management sales office for additional information.
0 to 30 0 to 60 0 to 100
0 to 200 0 to 300 0 to 600 0 to 1000
0 to 1500 0 to 3000 0 to 5000
0 to 8000 0 to 10.000
2.0
4.0
7.0 14
20 40 70
100 200 350
550 700
30 60
100 200
300 600
1000 1500
3000 5000
8000
10,000
3.3
6.6 11
19 29 50 83
115 230 380
550 700
(3)
48 96
160 280
420 720
1200 1650
3300 5500
8000
10,000
(4)
MATERIAL
(5)
316 stainless steel
Table 4. Bellows Pressure Ranges and Materials
PRESSURE RANGES
(1)
0 to 150 mbar (0 to 60 inch wc)
Vacuum
0 to 340 mbar (0 to 10 inch Hg) 0 to 1.0 bar (0 to 30 inch Hg)
75 mbar vac. to 75 mbar (30 inch wc vac. to 30 inch wc)
Compound Pressure
500 mbar vac. to 500 mbar (15 inch Hg vac. to 7.5 psig)
1.0 bar vac. to 1.0 bar (30 inch Hg vac. to 15 psig)
Gauge Pressure
0 to 150 mbar (0 to 60 inch wc) 0 to 250 mbar 0 to 350 mbar
(3)
(0 to 100 inch wc)
(4)
(0 to 140 inch wc)
0 to 0.35 bar (0 to 5 psig)
Positive pressure
0 to 0.5 bar (0 to 7.5 psig) 0 to 0.7 bar (0 to 10 psig)
0 to 1.0 bar (0 to 15 psig) 0 to 1.4 bar (0 to 20 psig) 0 to 2.0 bar (0 to 30 psig)
0 to 300 mbar (0 to 80 inch wc)
Differential Pressure
(5)
0 to 0.7 bar (0 to 10 psi) 0 to 1.4 bar (0 to 20 psi) 0 to 2.0 bar (0 to 30 psi)
1. If the process can trip to a pressure outside of the operating range of the sensing element, a commercially available device, such as an overpressure protector, may be used to protect against pressure surges and pulsations.
2. Bellows may be pressured to limit shown without permanent zero shift.
3. Transmitter only.
4. Except transmitter.
5. The overrange limit for these sensing elements is a differential pressure equal to the maximum allowable static pressure limit.
MAXIMUM ALLOWABLE STATIC
PRESSURE LIMITS
Brass
Construction
(2)
Stainless Steel
Construction
Bar Psig Bar Psig
1.4
2.8
2.8
1.4
2.8
2.8
1.4
1.4
2.8
2.8
2.8
2.8
2.8
2.8
2.8
1.4
2.8
2.8
−−−
20 40 40
20 40 40
20 20 40 40 40
40 40 40 40
20 40 40
−−−
−−−
−−−
6.9
−−−
6.9
6.9
−−−
−−−
−−−
−−−
−−−
−−−
6.9
−−−
6.9
−−−
−−−
−−−
6.9
−−−
−−−
100
−−−
100 100
−−−
−−−
−−−
−−−
−−−
−−−
100
−−−
100
−−−
−−−
−−−
100
OUTPUT SIGNAL RANGE
Bar
Psig
1. If this pressure is exceeded, control may be impaired.
0.2 to 1.0 or 0 and 1.4 (differential gap) 1.4 2.8
0.4 to 2.0 or 0 and 2.4 (differential gap) 2.4 2.8 3 to 15 or 0 and 20 (differential gap) 20 40 6 to 30 or 0 and 35 (differential gap) 35 40
Table 5. Supply Pressure Requirements
NORMAL OPERATING SUPPLY
PRESSURE
(1)
MAXIMUM ALLOWABLE SUPPLY PRESSURE
TO PREVENT INTERNAL PART DAMAGE
5
Page 6
Instruction Manual
C1 Controllers and Transmitters

Panel Mounting

Refer to figure 2. Cut a hole in the panel surface according to the
dimensions shown in figure 2. Remove the cap screws (key 252), brackets (key 251), and vent assembly (key 28). Slide the controller or transmitter into the cutout and reattach the brackets. Tighten the cap screw located in the center of each bracket to draw the case snugly and evenly against the panel. Reinstall the vent unless a remote vent will be used.
Wall Mounting
Refer to figure 2. Drill four holes in the wall using the dimensions
shown in figure 2. In the bracket (key 251) are 8.7 mm (0.3438 inch) diameter holes. Back out the cap screw located in the center of each bracket. (The screws are used for panel mounting but are not required for wall mounting.) If tubing runs through the wall, drill holes in the wall to accommodate the tubings. Figure 2 shows the pressure connection locations in the back of the case.
Mount the controller to the bracket using the four cap screws (key 252) provided. Attach the bracket to the wall, using suitable screws or bolts.
Pipestand Mounting
Refer to figure 2. Use a hammer and punch to knock out the blanks in
the two holes indicated in the back view of figure 2. Attach the spacer spools (key 228) and the mounting plate (key 213) to the controller with cap screws, lock washers, and nuts (keys 215, 221, and 216). Attach the controller to a 2inch (nominal) pipe with pipe clamps (key 250).

Actuator Mounting

Refer to figure 3. Controllers specified for mounting on a control valve
actuator are mounted at the factory. If the instrument is ordered separately for installation on a control valve actuator, mount the instrument according to the following instructions.
Mounting parts for the different actuator types and sizes vary. Two typical actuatormounting installations are shown in figure 3; see the parts list for parts required for the specific actuator type and size involved.
September 2009
Use a hammer and punch to knock out the blanks in the two holes indicated in the back view of figure 2. Attach the spacer spools (key 228) and the mounting plate (key 213) to the controller with machine screws, lock washers, and nuts (keys 215, 221, and
216). Attach the mounting bracket to the actuator yoke
with cap screws (key 222) and, if needed, spacer spools. On some designs, the mounting bracket is attached to the actuator diaphragm casing rather than to the yoke.

Pressure Connections

WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure, do not install any system component where service conditions could exceed the limits given in this manual. Use pressurerelieving devices as required by government or accepted industry codes and good engineering practices.
All pressure connections on C1 Series instruments are 1/4 NPT internal. Use 6 mm (1/4inch) or 10 mm (3/8inch) pipe or tubing for supply and output piping. The pressure connection locations are shown in figure 2.

Supply Pressure

WARNING
Severe personal injury or property damage may occur from an uncontrolled process if the instrument supply medium is not clean, dry, oilfree and noncorrosive. While use and regular maintenance of a filter that removes particles larger than 40 micrometers in diameter will suffice in most applications, check with an Emerson Process Management field office and industry instrument supply medium quality standards for use with hazardous gas or if you are unsure about the proper amount or method of air filtration or filter maintenance.
6
Page 7
Instruction Manual
September 2009
180.8 (7.12)
VENT ASSEMBLY (KEY 28)
PIPESTAND MOUNTING
2 INCH (NOMINAL) PIPE
C1 Controllers and Transmitters
142.7
(5.62)
65.8
(2.59)
23.1
(0.91)
KNOCKOUT
63.5
(2.50)
63.5
(2.50)
69.1
(2.72)
BACK VIEW
KNOCKOUT
244.3 (9.62)
215.9 (8.50)
8.7
(11/32)
MOUNTING HOLES
PANEL MOUNTING WALL MOUNTING
NOTES:
1. ALL CONNECTIONS ARE 1/4 NPT INTERNAL. 2
HIGHPRESSURE CONNECTION FOR DIFFERENTIALPRESSURE UNITS.
3
LOWPRESSURE CONNECTION FOR DIFFERENTIALPRESSURE UNITS.
E1052
Figure 2. Panel, Wall, and Pipestand Mounting
Supply pressure must be clean, dry air that meets the requirements of ISA Standard 7.0.01. A maximum 40 micrometer particle size in the air system is acceptable. Further filtration down to 5 micrometer particle size is recommended. Lubricant content is not to exceed 1 ppm weight (w/w) or volume (v/v) basis. Condensation in the air supply should be minimized. Alternatively, natural gas may be used as the supply pressure medium. Gas must be clean, dry, oilfree, and noncorrosive. H2S content should not exceed 20 ppm.
Use a suitable supply pressure regulator to reduce the supply pressure source to the normal operating
218.9 (8.62)
CUTOUT FOR PANEL MOUNTING
14.3
(0.56) R
FOUR HOLES FOR WALL MOUNTING
101.6 (4.00)
mm (INCH)
supply pressure shown in table 5. Connect supply pressure to the SUPPLY connection at the back of the case.
WARNING
To avoid personal injury or property damage resulting from the sudden release of process pressure, use a high pressure regulator system when operating the controller or transmitter from a high pressure source.
7
Page 8
Instruction Manual
C1 Controllers and Transmitters
If operating the controller or transmitter from a high pressure source [up to 138 bar (2000 psig)], use a high pressure regulator system, such as the Fisher 1367 High Pressure Instrument Supply System. For 1367 system installation, adjustment, and maintenance information, refer to the 1367 HighPressure Instrument Supply System with Overpressure Protection instruction manual, D100343X012.

Process Pressure

WARNING
To avoid personal injury or property damage resulting from the sudden release of pressure when using corrosive media, make sure the tubing and instrument components that contact the corrosive medium are of suitable noncorrosive material.
Also refer to the Installation Warning at the beginning of this section.
The pressure connections to the controller depend upon the type of pressure sensing, gauge or differential. Gauge pressure controllers use either a
Bourdon tube or bellows as the sensing element, as indicated in table 2. Differential pressure controllers use two bellows to sense differential pressure.
For gauge pressure instruments: The control pressure block (key 10 in figure 21) has two connections. Process pressure can be connected either to the CONTROL connection on the back of the case, or to the connection on the left side of the case, shown in figure 2, depending on the instrument application. Plug the unused connection.
For differential pressure instruments: Connect the low pressure line to the CONTROL connection on the side of the case and the high pressure line to the CONTROL connection on the back of the case as shown in figure 2.
When installing process piping, follow accepted practices to ensure accurate transmission of the process pressure to the controller or transmitter. Install shutoff valves, vents, drains, or seal systems as needed in the process pressure lines. If the instrument is located such that the adjacent process pressure lines will be approximately horizontal, the lines should slope downward to the instrument for liquidfilled lines and upward to instruments for gasfilled lines. This will minimize the possibility of
September 2009
Table 6. Common Signal Pressure Conversions
Mps kg/cm
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.14
0.15
0.17
0.18
0.20
0.22
0.23
0.24
0.34
0.55
0.69
1.03
1. Values as listed in ANSI/S7.4.
2. Values as listed in IEC Standard 382.
3. Values rounded to correspond with kPa values.
0.2
0.3
0.4
0.5
0.6
0.8
0.8
1.0
1.0
1.3
1.4
1.5
1.8
1.9
2.0
2.2
2.3
2.5
3.5
5.6
7.0
10.5
2
(3)
bar kPa Psi
0.2
0.3
0.4
0.5
0.6
0.8
0.8
1.0
1.0
1.2
1.4
1.5
1.7
1.9
2.0
2.2
2.3
2.4
3.4
5.5
6.9
10.3
(2)
(2)
(3)
20
35
40
50 60
75 80 95
100
125 140
150 170 185
200
220 230 240 345 550
690
1035
(1)
(1)
(1)
(1)
3 5 6 7 9
11 12 14 15 18
20 22 25 27 30
32 33 35 50 80
100 150
air becoming trapped in the sensor with liquid−filled lines or of condensation becoming trapped with gasfilled lines. The recommended slope is 83 mm per meter (1 inch per foot).
If a controller is being used in conjunction with a control valve to control pipeline pressure, connect the process pressure line in a straight section of pipe approximately 10 pipe diameters from the valve but away from bends, elbows, and areas of abnormal fluid velocities. For pressurereducing service, the process line must be connected downstream of the valve. For pressurerelief service, the process pressure line must be connected upstream of the control valve. Install a needle valve in the process pressure line to dampen pulsations.

Vent Assembly

WARNING
Personal injury or property damage could result from fire or explosion of accumulated gas, or from contact with hazardous gas, if a flammable or hazardous gas is used as the supply pressure medium. Because the instrument case and cover assembly do not form a gastight seal when the assembly is enclosed, a remote vent
8
Page 9
Instruction Manual
September 2009
line, adequate ventilation, and necessary safety measures should be used to prevent the accumulation of flammable or hazardous gas. However, a remote vent pipe alone cannot be relied upon to remove all flammable and hazardous gas. Vent line piping should comply with local and regional codes, and should be be as short as possible with adequate inside diameter and few bends to reduce case pressure buildup.
CAUTION
When installing a remote vent pipe, take care not to overtighten the pipe in the vent connection. Excessive torque will damage the threads in the connection.
The vent assembly (key 28, figure 2) or the end of a remote vent pipe must be protected against the entrance of all foreign matter that could plug the vent. Use 13 mm (1/2inch) pipe for the remote vent pipe, if one is required. Check the vent periodically to be certain it has not become plugged.
C1 Controllers and Transmitters
SUPPLY PRESSURE REGULATOR
GE33946A
TYPICAL ROTARY ACTUATOR

Controller Operation

ProportionalOnly Controllers
This section describes the adjustments and procedures for calibration and startup. Adjustment locations are shown in figure 4 unless otherwise specified. All adjustments must be made with the cover open. When the adjustments and calibration procedures are complete, close and latch the cover.
To better understand the adjustments and overall operation of the controller, refer to the Principle of Operation section in this manual for proportionalonly controllers. Refer also to the schematic diagram in figure 13.

Adjustments

Adjustment: Set Point
Adjust the pressure setting knob by turning the knob clockwise to increase the set point and counterclockwise to decrease the set point. Note that the dial setting and actual process pressure may vary significantly, especially with a wide proportional band setting.
SUPPLY PRESSURE REGULATOR
GE33947A
TYPICAL SLIDING STEM ACTUATOR
Figure 3. Actuator Mounting
Adjustment: Proportional Band
To adjust the proportional band, rotate the proportional band adjustment knob to the desired value.
The proportional band adjustment determines the amount of change in controlled pressure required to cause the control valve to stroke fully. It may be adjusted from 2 to 100 percent for 0.2 to 1.0 bar (3 to 15 psig) or 4 to 100 percent for 0.4 to 2.0 bar (6 to 30 psig) of the nominal sensing element pressure rating.
9
Page 10
Instruction Manual
C1 Controllers and Transmitters
CALIBRATION ADJUSTER (KEY 36)
GE28280B E1059
ADJUSTER SCREWS (KEY 48)
Figure 4. Proportional−Only Controller Adjustment Locations
FLAPPER (KEY 40)
NOZZLE (KEY 54)
September 2009
PRESSURE SETTING KNOB (KEY 58)
PRESSURE SETTING DIAL (KEY 6)
PROPORTIONAL BAND ADJUSTMENT KNOB
Calibration: Proportional−Only Controllers
Unless otherwise indicated, key number locations are shown in figure 4.
Provide a process pressure source capable of simulating the process pressure range of the controller. If an output pressure gauge is not provided, install a suitable pressure gauge for calibration purposes.
Connect a pressure source to the supply pressure regulator and be sure the regulator is delivering the correct supply pressure to the controller. The controller must be connected open loop (Open loop: The controller output pressure changes must be dead ended into a pressure gauge). The following procedures use a 0.2 to 1.0 bar (3 to 15 psig) output pressure range as an example. For a 0.4 to 2.0 bar (6 to 30 psig) output range, adjust the values as appropriate.
1. Complete the above connections and provide a process pressure equal to the sensing element range.
2. Rotate the proportional band adjustment knob, shown in figure 4, to 1.5 (15 percent proportional band).
3. Verify that the calibration adjuster screws (key 48) are at midposition in the calibration adjuster (key 36) slots.
IF OUTPUT IS:
NOZZLE
BELOW 8 TO 10 PSIG (0.6 TO 0.7 BAR)
MOVE ADJUSTER RIGHT
ABOVE 8 TO 10 PSIG (0.6 TO 0.7 BAR)
MOVE ADJUSTER
NOTE: 3 TO 15 PSIG (0.2 TO 1.0 BAR) OUTPUT SHOWN. FOR 6 TO 30 PSIG (0.4 TO 2.0 BAR) OUTPUT, ADJUST VALUES AS APPROPRIATE.
A61551 / IL
LEFT
FLAPPER
Figure 5. Reverse−Acting Controller Span Adjustment —
ProportionalOnly Controllers
Depending upon the controller action, perform one or the other of the following procedures.
For reverseacting controllers:
4. Apply an input pressure equal to the sensing element upper range value.
10
Page 11
Instruction Manual
September 2009
5. Rotate the pressure setting knob to the maximum value.
6. Adjust the nozzle (key 54) until the controller output pressure is between 0.6 and 0.7 bar (8 and 10 psig).
7. Apply an input pressure equal to the sensing element lower range value.
8. Rotate the pressure setting knob to the minimum value.
Note
When performing the span adjustment in step 9, do not watch the output gauge while changing the calibration adjuster. The change in output is not a good indication of the change in span. While moving the calibration adjuster, the output pressure may change in the opposite direction than expected. For example, while moving the calibration adjuster to increase span, the output pressure may decrease. This should be disregarded since even though the output pressure decreases, the span is increasing.
Proper controller response depends on nozzletoflapper alignment.
When performing span adjustments, carefully loosen both calibration adjuster screws while holding the calibration adjuster in place. Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver. Verify proper nozzletoflapper alignment and hold the calibration adjuster in place while tightening both adjustment screws.
9. If the output is not between 0.6 and 0.7 bar (8 and 10 psig), adjust the controller span by loosening the two adjusting screws (key 48) and moving the calibration adjuster (key 36) a small distance as indicated in figure 5.
10. Repeat steps 4 through 9 until no further adjustment is necessary.
11. Proceed to the startup procedure for proportional controllers.
For directacting controllers:
4. Apply an input pressure equal to the sensing element lower range value.
C1 Controllers and Transmitters
IF OUTPUT IS:
BELOW 8 TO 10 PSIG (0.6 TO 0.7 BAR)
MOVE ADJUSTER
NOTE: 3 TO 15 PSIG (0.2 TO 1.0 BAR) OUTPUT SHOWN. FOR 6 TO 30 PSIG (0.4 TO 2.0 BAR) OUTPUT, ADJUST VALUES AS APPROPRIATE.
A6154 / IL
LEFT
FLAPPER
Figure 6. Direct−Acting Controller Span
Adjustment—ProportionalOnly Controllers
5. Rotate the pressure setting knob to the minimum value.
6. Adjust the nozzle (key 54) until the controller output pressure is between 0.6 and 0.7 bar (8 and 10 psig.)
7. Apply an input pressure equal to the sensing element upper range value.
8. Rotate the pressure setting knob to the maximum value.
Note
When performing the span adjustment in step 9, do not watch the output gauge while changing the calibration adjuster. The change in output is not a good indication of the change in span. While moving the calibration adjuster, the output pressure may change in the opposite direction than expected. For example, while moving the calibration adjuster to increase span, the output pressure may decrease. This should be disregarded since even though the output pressure decreases, the span is increasing.
Proper controller response depends on nozzletoflapper alignment.
When performing span adjustments, carefully loosen both calibration
MOVE ADJUSTER RIGHT
NOZZLE
ABOVE 8 TO 10 PSIG (0.6 TO 0.7 BAR)
11
Page 12
Instruction Manual
C1 Controllers and Transmitters
adjuster screws while holding the calibration adjuster in place. Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver. Verify proper nozzletoflapper alignment and hold the calibration adjuster in place while tightening both adjustment screws.
9. If the output is not between 0.6 and 0.7 bar (8 and 10 psig), adjust the controller span by loosening the two adjusting screws (key 48) and moving the calibration adjuster (key 36) a small distance as indicated in figure 6.
10. Repeat steps 4 through 9 until no further adjustment is necessary.
11. Proceed to the startup procedure for proportional controllers.
Startup: Proportional−Only Controllers (General Tuning Guidelines)
Calibrate the controller prior to this procedure.
1. Be sure that the supply pressure regulator is delivering the proper supply pressure to the controller.
2. Rotate the pressure setting knob to the desired set point.
3. Set the proportional band adjustment to 100 percent for fast processes (example: liquid pressure or liquid flow). For slow processes (example: temperature), calculate the percentage from the equation below:
For a slow process, determine the initial proportional band setting in percent from the following equation:
September 2009
2 Allowable Overshoot
Pressure Span
For example:
2 0.14 bar
2.1 bar
2 2 psig
(
30 psig
1.3 proportional band setting
4. Proportional Action Disturb the system by tapping the flapper lightly or
change the set point a small amount and check for system cycling. If the system does not cycle then lower the proportional band (raising the gain) and disturb the system again. Continue this procedure until the system cycles. At that point, double the proportional band setting.
Proportional band adjustment affects the set point. Proportionalonly controllers will show some offset from set point depending upon proportional band setting and process demand. After adjusting the proportional band, rezero by carefully rotating the nozzle (key 54) until the steadystate process pressure equals the pressure setting dial reading.
This tuning procedure may be too conservative for some systems. The recommended proportional band setting should be checked for stability by introducing a disturbance and monitoring the process.
100% ^ 13%
100% ^ 13%
100% + P.B.
)
Note
12
Page 13
Instruction Manual
September 2009
CALIBRATION ADJUSTER (KEY 36)
GE28281B E1060
C1 Controllers and Transmitters
RESET ADJUSTMENT KNOB
FLAPPER (KEY 40)
ADJUSTER SCREWS (KEY 48)
Figure 7. Proportional−Plus−Reset Controller Adjustment Locations
NOZZLE (KEY 54)
PRESSURE SETTING KNOB (KEY 58)
PRESSURE SETTING DIAL (KEY 6)
PROPORTIONAL BAND ADJUSTMENT KNOB
ProportionalPlusReset Controllers
This section describes the adjustments and procedures for calibration and startup. The adjustment locations are shown in figure 7 unless otherwise specified. All adjustments must be made with the cover open. When the adjustments and calibration procedures are complete, close and latch the cover. To better understand the adjustments and overall operation of the controller, refer to the Principle of Operation section in this manual for proportionalplusreset controllers. Refer also to the schematic diagram in figure 13.

Adjustments

Adjustment: Set Point
Adjust the pressure setting knob by turning the knob clockwise to increase the set point and counterclockwise to decrease the set point.
Rotate the knob until the indicator points to the desired set point pressure value. The pressure setting dial will reflect the desired set point if the controller is accurately calibrated.
Adjustment: Proportional Band
To adjust the proportional band, rotate the proportional band adjustment knob to the desired value.
The proportional band adjustment determines the amount of change in controlled pressure required to cause the control valve to stroke fully. It may be adjusted from 3 to 100 percent for 0.2 to 1.0 bar (3 to 15 psig) or 6 to 100 percent for 0.4 to 2.0 bar (6 to 30 psig) of the nominal sensing element pressure rating.
Adjustment: Reset
To adjust reset action turn the knob clockwise to decrease the minutes per repeat. Turn the knob counterclockwise to increase the minutes per repeat. Increasing the minutes per repeat provides a slower reset action.
The reset adjustment dial is calibrated in minutes per repeat. By definition, this is the time in minutes required for the reset action to produce an output change which is equal to the change produced by proportional control action. This is in effect, the time in minutes required for the controller to increase (or decrease) its output pressure by an amount equal to a proportional increase (or decrease) caused by a change in set point or process pressure.
13
Page 14
Instruction Manual
C1 Controllers and Transmitters
Adjustment: AntiReset Windup
The externally mounted differential relief valve can be mounted to relieve on increasing or decreasing output pressure.

Calibration

Calibration: ProportionalPlusReset Controllers
Unless otherwise indicated, key number locations are shown in figure 7.
Before starting this procedure:
D Provide a process pressure source capable of simulating the process pressure range of the controller.
D If an output pressure gauge is not provided, install a suitable pressure gauge for calibration purposes. The controller must be connected open loop (Open loop: The controller output pressure changes must be dead ended into a pressure gauge).
Note
C1P and C1B controllers with antireset windup are supplied with two Orings (key 81), an antireset windup cover (key 80), and two machine screws (key 82). Use these parts in the next step.
1. For C1P and C1B controllers with antireset windup record the direction of the arrow on the antireset windup assembly (key 190, in figure 22). Remove the assembly and install the two Orings (key 81), and cover (key 80) supplied with the controller. Secure the cover with the two machine screws (key 82) provided.
2. Connect regulated supply pressure to the controller. Do not exceed the normal operating pressure in table 5.
3. Rotate the reset knob to 0.01 minutes per repeat (fastest setting).
4. Rotate the proportional band adjustment knob to 1.5 (15 percent proportional band).
5. Verify that the calibration adjuster screws (key 48) are at midposition in the calibration adjuster (key 36) slots.
Depending upon the controller action, perform one or the other of the following procedures.
September 2009
IF OUTPUT IS:
ABOVE 8 TO 10 PSIG (0.6 TO 0.7 BAR)
MOVE ADJUSTER
NOTE: 3 TO 15 PSIG (0.2 TO 1.0 BAR) OUTPUT SHOWN. FOR 6 TO 30 PSIG (0.4 TO 2.0 BAR) OUTPUT, ADJUST VALUES AS APPROPRIATE.
A61551 / IL
Figure 8. Reverse−Acting Controller Span Adjustment—
LEFT
FLAPPER
ProportionalPlusReset Controllers
BELOW 8 TO 10 PSIG (0.6 TO 0.7 BAR)
MOVE ADJUSTER RIGHT
NOZZLE
For reverseacting controllers:
6. Apply an input pressure equal to the sensing element upper range value.
7. Rotate the pressure setting knob to the maximum value.
8. Adjust the nozzle (key 54) until the controller output pressure is between 0.6 and 0.7 bar (8 and 10 psig).
9. Apply an input pressure equal to the sensing element lower range value.
10. Rotate the pressure setting knob to the minimum value.
Note
When performing the span adjustment in step 11, do not watch the output gauge while changing the calibration adjuster. The change in output is not a good indication of the change in span. While moving the calibration adjuster, the output pressure may change in the opposite direction than expected. For example, while moving the calibration adjuster to increase span, the output pressure may decrease. This should be disregarded since even though the output pressure decreases, the span is increasing.
14
Page 15
Instruction Manual
September 2009
Proper controller response depends on nozzletoflapper alignment.
When performing span adjustments, carefully loosen both calibration adjuster screws while holding the calibration adjuster in place. Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver. Verify proper nozzletoflapper alignment and hold the calibration adjuster in place while tightening both adjustment screws.
11. If the output pressure is not between 0.6 and 0.7 bar (8 and 10 psig), adjust the controller span by loosening the two adjusting screws (key 48) and moving the calibration adjuster (key 36) a small distance as indicated in figure 8.
12. Repeat steps 6 through 11 until no further adjustment is necessary.
13. For C1P and C1B controllers with antireset windup, remove the two machine screws, antireset windup cover, and two Orings installed in step 1 of this procedure. Install the antireset windup assembly (key 190) with the arrow pointing in the direction recorded in step 1.
14. Proceed to the Startup procedures for proportionalplusreset controllers.
For directacting controllers:
6. Apply an input pressure equal to the sensing element lower range value.
7. Rotate the pressure setting knob to the minimum value.
8. Adjust the nozzle (key 54) until the controller output pressure is between 0.6 and 0.7 bar (8 and 10 psig).
9. Apply an input pressure equal to the sensing element upper range value.
10. Rotate the pressure setting knob to the maximum value.
Note
When performing the span adjustment in step 11, do not watch the output gauge while changing the calibration adjuster. The change in output is not a good indication of the change in span. While moving the calibration adjuster,
C1 Controllers and Transmitters
IF OUTPUT IS:
BELOW 8 TO 10 PSIG (0.6 TO 0.7 BAR)
MOVE ADJUSTER
NOTE: 3 TO 15 PSIG (0.2 TO 1.0 BAR) OUTPUT SHOWN. FOR 6 TO 30 PSIG (0.4 TO 2.0 BAR) OUTPUT, ADJUST VALUES AS APPROPRIATE.
A6154 / IL
LEFT
FLAPPER
Figure 9. Direct−Acting Controller Span Adjustment
—ProportionalPlusReset Controllers
the output pressure may change in the opposite direction than expected. For example, while moving the calibration adjuster to increase span, the output pressure may decrease. This should be disregarded since even though the output pressure decreases, the span is increasing.
Proper controller response depends on nozzletoflapper alignment.
When performing span adjustments, carefully loosen both calibration adjuster screws while holding the calibration adjuster in place. Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver. Verify proper nozzletoflapper alignment and hold the calibration adjuster in place while tightening both adjustment screws.
11. If the output pressure is not between 0.6 and 0.7 bar (8 and 10 psig), adjust the controller span by loosening the two adjusting screws (key 48) and moving the calibration adjuster (key 36) a small distance as indicated in figure 9.
12. Repeat steps 6 through 11 until no further adjustment is necessary.
13. For C1P and C1B controllers with antireset windup remove the two machine screws, antireset windup cover, and two Orings installed in step 1 of this procedure. Install the antireset windup assembly (key 190) with the arrow pointing in the direction recorded in step 1.
ABOVE 8 TO 10 PSIG (0.6 TO 0.7 BAR)
MOVE ADJUSTER RIGHT
NOZZLE
15
Page 16
Instruction Manual
C1 Controllers and Transmitters
14. Proceed to the Startup procedures for proportionalplusreset controllers.
Calibration: AntiReset Windup
Controllers with antireset windup have a differential relief valve assembly (figure 22). This relief valve is set at the factory to relieve at a 0.3 bar (5 psi) pressure difference between the reset bellows pressure and the proportional bellows pressure. The valve can be adjusted to relieve from 0.14 to 0.4 bar (2 to 7 psig).
The relief valve can relieve on either rising controller output pressure or falling controller output pressure. If the arrow on the relief valve points toward the bottom of the controller case as shown in figure 22, the valve will relieve on falling output pressure. If the arrow points in the opposite direction, the valve will relieve on rising output pressure. The valve can be removed and reinstalled with the arrow pointing in the opposite direction to change the relief action.
Startup: Proportional−Plus−Reset Controllers (General Tuning Guidelines)
Calibrate the controller prior to this procedure.
1. Be sure that the supply pressure regulator is delivering the proper supply pressure to the controller.
2. Rotate the pressure setting knob to the desired set point.
3. Start with a reset setting of 0.05 minutes per repeat (m/r) for fast processes, and 0.5 m/r for slow processes.
4. Set the proportional band adjustment to 100 percent for fast processes (example: liquid pressure or liquid flow). For a slow process (example: temperature), calculate the percentage from the equation below:
For a slow process, determine the initial proportional band setting in percent from the following equation:
2 Allowable Overshoot
Pressure Span
100% + P.B.
September 2009
5. Proportional Action: Disturb the system by tapping the flapper lightly or
change the set point a small amount and check for system cycling. If the system does not cycle then lower the proportional band (raising the gain) and disturb the system again. Continue this procedure until the system cycles. At that point, double the proportional band setting and begin tuning the reset.
6. Reset Action: Disturb the system. If the system does not cycle then
speed up the reset and disturb the system again. Continue this procedure until the system cycles. When the system cycles multiply the reset time setting by a factor of three (3) and slow the reset down to the new value. The reset is now tuned.
This tuning procedure may be too conservative for some systems. The recommended proportional band and reset setting should be checked for stability by introducing a disturbance and monitoring the process as previously described. For some applications, tighter control may be desirable.

Differential Gap Controllers

This section describes the adjustments and procedures for calibration and startup. The adjustment locations are shown in figure 4 unless otherwise specified. The output of each controller is checked at the factory before the instrument is shipped.
To convert a differential gap controller to a proportionalonly controller or vice versa, refer to the appropriate procedure in the Maintenance section.
If the process pressure can be varied through all or part of the sensing element range or through the two desired switching points, use the process pressure for calibration. If not, provide a pressure source to simulate the process pressure range for calibration procedures.
To better understand the adjustments and overall operation of the controller, refer to the Principle of Operation section in this manual for differential gap controllers and the schematic diagram in figure 13.
For example:
2 0.14 bar
2.1 bar
2 2 psig
()
30 psig
1.3 proportional band setting
16
100% ^ 13%
100% ^ 13%

Adjustments

Adjustment: Set Point
The position of the pressure setting knob determines the location of the differential gap within the range of the pressure sensing element. Move the pointer to the desired pressure where the output of the controller should switch from zero to full supply
Page 17
Instruction Manual
September 2009
PROPORTIONAL BAND KNOB SETTING
A22023 / IL
Figure 10. Differential Gap Adjustment for Differential Gap
DIFFERENTIAL GAP (PERCENT OF ELEMENT RANGE)
Controllers
pressure with rising process pressure (direct−acting controllers) or with falling process pressure (reverseacting controllers).
Adjustment: Proportional Band
C1 Controllers and Transmitters
b. Unscrew the spring adjustor (key 65), removing the bias spring (key 70) and washers (key 62) with it.
c. Unclip the lock spring (key 72). Remove the indicator scale (key 69) and proportional band adjustment knob (key 73).
d. Remove the gain adjustment bar (key 63). Flip it over so it attaches to the opposite side of the cantilever spring (key 8) as shown in figure 16 and screw it back down.
e. Flip over the indicator scale (key 69); install it and the proportional band adjustment knob (key 73) as a unit. Snap in the lock spring (key 72).
f. Tighten down the spring adjustor (key 65) with the bias spring (key 70) and washers (key 62) until it stops against the gain adjustment bar (key 63).
The proportional band adjustment shown in figure 4 determines the width of the differential gap. The width of the gap is the difference between the process pressures at which the controller output will switch from zero to full supply pressure, or from full supply pressure to zero. The relationship between the proportional band dial setting and the differential gap is shown in figure 10.

Calibration: Differential Gap Controllers

The output of each controller is checked at the factory before the unit is shipped. Before placing the controller in control of a process loop, check to verify that the controller is calibrated correctly for the application. The controller must be connected open loop (Open loop: The controller output pressure changes must be dead ended into a pressure gauge).
1. Temporarily convert the differential gap controller to proportionalonly controller by disconnecting the proportional tubing (key 25, figure 16) from the mounting base. Reinstall the tubing into the other connection in the mounting base. Remove the proportional band assembly and invert it as shown in figure 16. Do not invert the reversing block (key 37, figure 16).
2. Temporarily invert the proportional band assembly (refer to figure 18):
a. Turn the proportional band assembly (key 73) to 10.
g. Turn the proportional band adjustment knob to the 10 setting. If it cannot be turned to the 10 setting, loosen the spring adjustor (key 65).
3. Calibrate using the calibration procedure for proportionalonly controllers found on page 10 of this manual.
4. When calibration is complete, return the tubing (key 25) and the proportional band assembly to their original locations and continue on with step 5 of this procedure.
Note
After reinstalling the tubing (key 25) and proportional band assembly a slight offset of the output pressure will be noticed due to a combination of switching from the proportional bellows to the reset bellows and the repositioning of the cantilever spring. Performing step 6b below adjusts for this offset.
5. Refer to figure 10 to determine the proportional band dial setting required for the desired differential gap.
For example, assume that a 0 to 100 psig sensing element is being used and the controller is to switch from zero to full supply pressure at a process
17
Page 18
Instruction Manual
C1 Controllers and Transmitters
ADJUSTER SCREWS (KEY 48)
GE34729B E1061
CALIBRATION ADJUSTER (KEY 36)
Figure 11. Transmitter Adjustment Locations
FLAPPER (KEY 40)
NOZZLE (KEY 54)
September 2009
ZERO ADJUSTMENT KNOB (KEY 58)
PRESSURE SETTING DIAL (KEY 6)
SPAN ADJUSTMENT KNOB
pressure of 80 psig with rising process pressure and from full supply pressure to zero at 20 psig with falling pressure. (This is for a directacting controller.) The differential gap is:
5.5 bar * 1.3 bar
6.9 bar
80 psig * 20 psig
(
100 psig
100% + 60%
100% + 60%
)
From figure 10, the proportional band dial setting should be approximately 4.5; rotate the proportional band adjustment knob to 4.5.
6. Setting the process pressure
For a DirectActing Controller:
a. Rotate the pressure setting knob to the pressure at which the controller output is to switch to the upper switching point (zero to full supply pressure) with rising process pressure. In the above example, this pressure is 5.5 bar (80 psig).
b. Increase pressure to the sensing element while monitoring the output pressure gauge. The controller output pressure should switch from zero to full supply pressure when the upper
switching point is reached with rising input pressure.
Note
If the upper switching point is not correct, adjust the nozzle to correct the error. Repeat step 6b until the input pressure and upper switching point are at the desired setting.
c. With falling input pressure, the output should switch from full supply pressure back to zero when the lower switching point is reached.
Reverseacting controllers produce the opposite response.
7. Vary the process pressure and observe the switching points. Widen or narrow the differential gap by rotating the proportional band adjustment knob, then repeat the above steps.
If the output is within the limits stated, refer to the startup procedures in this section. If the output pressure cannot be adjusted within the limits stated, refer to the maintenance procedures.
18
Page 19
Instruction Manual
September 2009

Startup: Differential Gap Controllers

Calibrate the controller prior to this procedure.
1. Be sure that the supply pressure regulator is delivering the proper supply pressure to the controller.
2. Adjust the proportional band setting for the proper differential gap (see figure 10).
3. If the controller is used in conjunction with a control valve, slowly open the upstream and downstream manual shutoff valves, and close the bypass valves.
4. To change the differential gap, perform steps 1 through 5 of the calibration for differential gap controllers procedure.

Transmitter Operation

This section describes the adjustments and procedures for calibration and startup. Refer to figure 11 for the adjustment locations. All adjustments must be made with the cover open. When the adjustments and calibration procedures are complete, close and latch the cover.
To better understand the adjustments and overall operation of the transmitter, refer to the Principle of Operation section in this manual for transmitters. Refer also to the schematic diagram in figure 13.

Adjustments

Adjustment: Zero

The pressure setting dial is marked ZERO ADJUSTMENT PRESSURE SETTING. Zero is in the center of the dial, and the pressure values increase to the right and left of the center as shown in figure
11. To set the zero, rotate the pointer around the pressure setting dial. Rotate the pointer clockwise to increase or counterclockwise to decrease the output depending on transmitter action and desired setting.
For directacting transmitters, zero adjustment determines the process pressure at which the transmitter output signal will be at its lower range limit.
The dial (key 6) graduations are approximate indications of the transmitter zero setting. When making adjustments, do not rely solely on the dial setting. Monitor the process pressure and output pressure to be sure the desired settings are attained.
C1 Controllers and Transmitters

Adjustment: Span

The span adjustment is graduated from 0 to 10. A setting of 10 represents a span setting of 100 percent of the process sensing element range. The transmitter achieves the highest accuracy when the span is 100 percent.
The transmitter span adjustment shown in figure 11 is the same as the controller proportional band adjustment.

Calibration: Transmitters

The output of each transmitter is checked at the factory before the unit is shipped. The transmitter provides an output signal that is proportional to the pressure applied to the sensing element. The output pressure has no direct effect on the process pressure.
The transmitter is calibrated at the factory and should not need additional adjustment. Use the following calibration procedures when the sensing element has been changed or other maintenance procedures have altered the calibration of the transmitter. The following procedures use a 0.2 to
1.0 bar (3 to 15 psig) output pressure range as an example. For other output pressure ranges [such as
0.4 to 2.0 bar (6 to 30 psig)] adjust the values to match the application.
Provide a process pressure source capable of simulating the process pressure range of the transmitter. If an output pressure gauge is not provided, install a suitable pressure gauge for calibration purposes. Connect a pressure source to the supply pressure regulator and be sure the regulator is delivering the correct supply pressure to the transmitter.
Note
For stability, some transmitter applications will require additional volume than just the gauge. Provide a minimum volume of approximately 25 cm3 (1.5 in3) or greater if stability is a problem.
Unless otherwise indicated, key number locations are shown in figure 11.
1. Complete the above connections and provide a process pressure equal to the sensing element range.
2. Rotate the span adjustment knob to the maximum setting on the dial (100 percent span).
19
Page 20
Instruction Manual
C1 Controllers and Transmitters
IF OUTPUT IS:
BELOW 15 PSIG (1.0 BAR)
MOVE ADJUSTER
NOTE: 3 TO 15 PSIG (0.2 TO 1.0 BAR) OUTPUT SHOWN. FOR 6 TO 30 PSIG (0.4 TO 2.0 BAR) OUTPUT, ADJUST VALUES AS APPROPRIATE.
A6156 / IL
LEFT
Figure 12. Transmitter Span Adjustment
3. Verify that the calibration adjuster screws (key 48) are at midposition in the calibration adjuster (key 36) slots.
Depending upon the transmitter action, perform one or the other of the following procedures.
For reverseacting transmitters:
4. Rotate the zero adjustment knob to zero.
5. Apply an input pressure equal to the sensing element upper range limit.
6. Adjust the nozzle (key 57) until the transmitter output pressure is at 0.2 bar (3 psig).
7. Set the input pressure equal to zero.
Note
Proper transmitter response depends on nozzletoflapper alignment.
When performing the span adjustment in step 8, carefully loosen both calibration adjuster screws while holding the calibration adjuster in place. Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver. Verify proper nozzletoflapper alignment and hold the calibration adjuster in place while tightening both adjustment screws.
ABOVE 15 PSIG (1.0 BAR)
MOVE ADJUSTER RIGHT
September 2009
8. If the output pressure is not 15 psig, adjust the span by loosening the two adjusting screws (key 48) and moving the calibration adjuster (key 36) a small distance as indicated in figure 12.
9. Repeat steps 4 through 8 until no further adjustment is necessary.
10. Proceed to the startup procedure for transmitters.
For directacting transmitters:
4. Rotate the zero adjustment knob to zero.
5. Set the input pressure to zero.
6. Adjust the nozzle (key 54) until the transmitter output pressure is at 0.2 bar (3 psig).
7. Apply an input pressure equal to the sensing element upper range value.
Note
Proper transmitter response depends on nozzletoflapper alignment.
When performing the span adjustment in step 8, carefully loosen both calibration adjuster screws while holding the calibration adjuster in place. Then move the calibration adjuster slightly in the required direction by hand or using a screwdriver. Verify proper nozzletoflapper alignment and hold the calibration adjuster in place while tightening both adjustment screws.
8. If the output pressure is not 15 psig, adjust the span by loosening the two adjusting screws (key 48) and moving the calibration adjuster (key 36) a small distance as indicated in figure 12.
9. Repeat steps 4 through 8 until no further adjustment is necessary.
10. Proceed to the startup procedure for transmitters.

Startup: Transmitters

1. Be sure that the supply pressure regulator is delivering the proper supply pressure to the transmitter.
2. Refer to the calibration procedures for the transmitter initial settings.
20
Page 21
Instruction Manual
September 2009
CONSTANT SUPPLY PRESSURE
EXHAUST END OF RELAY
BOURDON TUBE
FIXED PIVOT
TO FINAL CONTROL ELEMENT
BEAM AND FLAPPER
SENSED PRESSURE OUTPUT PRESSURE NOZZLE PRESSURE RESET PRESSURE
GE23696 GE34724A E1062
Figure 13. Schematic of Reverse−Acting Proportional−Only and Proportional−Plus−Reset Controllers
EXHAUST
NOZZLE
SENSED PRESSURE
PROPORTIONAL-ONLY
CONTROLLER
RESET BELLOWS
PROPORTIONAL BELLOWS
C1 Controllers and Transmitters
INLET END OF RELAY VALVE
SMALL DIAPHRAGM
LARGE DIAPHRAGM RESTRICTION
VENT
CANTILEVER SPRING
PRESSURE SETTING KNOB PRESSURE SETTING DIAL
RESET
PROPORTIONAL BAND ADJUSTMENT KNOB
BELLOWS
PROPORTIONAL BELLOWS
PROPORTIONAL-PLUS-RESET
CONTROLLER
RESET VALVE
3. If the transmitter is used in conjunction with a control valve, slowly open the upstream and downstream manual shutoff valves, and close the bypass valves.

Principle of Operation

The following sections describe the operation of a controller or transmitter using a Bourdon tube sensing element. The operation is the same for an instrument using a bellows sensing element (key 71, figure 24) except that movement of the beam is caused by expansion or contraction of the bellows or differential bellows.
ProportionalOnly Controllers
As shown in figure 13, supply pressure enters the relay and bleeds through the fixed orifice before escaping through the nozzle. Nozzle pressure also registers on the large relay diaphragm, and loading pressure (controller output pressure) registers on the small relay diaphragm.
A change in the process pressure moves the beam and flapper with respect to the nozzle by either expanding or contracting the Bourdon tube arc. An
increasing process pressure with direct action (or decreasing pressure with reverse action) produces a nozzleflapper restriction that increases the loading on the large relay diaphragm and opens the relay valve. Additional supply pressure flows through the relay chamber to increase the loading pressure on the control valve actuator. A decreasing process pressure with direct action (or increasing pressure with reverse action) produces a nozzleflapper opening that bleeds off pressure on the large relay diaphragm and opens the relay valve to exhaust controller output pressure from the actuator.
This controller output pressure change feeds back to the proportional bellows, countering the pressure change in the nozzle and equalizes the relay diaphragm pressure differential. The relay valve maintains a new loading pressure according to the change in sensed pressure.
If the proportional band adjustment is at its maximum setting (10), the cantilever spring in the proportional band assembly has a low spring rate, allowing more feedback motion to be transferred from the proportional bellows for a change in output pressure. As the effective length of the cantilever is reduced, its spring rate increases, causing less feedback motion from proportional bellows. Setting the cantilever spring to its maximum length results in a proportional band of 100%. The lower the
21
Page 22
Instruction Manual
C1 Controllers and Transmitters
CONSTANT SUPPLY PRESSURE
EXHAUST
RESET BELLOWS
TO FINAL CONTROL ELEMENT
ARROW UP−RELIEVES
ON INCREASING OUTPUT
(OUTPUT AT ZERO
DURING SHUTDOWN)
RESTRICTION
PRESSURE SETTING KNOB
PRESSURE SETTING DIAL
PROPORTIONAL BAND ADJUSTMENT KNOB
September 2009
ARROW DOWN−RELIEVES ON DECREASING OUTPUT
(OUTPUT AT SUPPLY DURING SHUTDOWN)
DIFFERENTIAL RELIEF VALVE
SENSED PRESSURE
SENSED PRESSURE OUTPUT PRESSURE NOZZLE PRESSURE RESET PRESSURE
GE23697A GE34724A E1063
Figure 14. Schematic of Reverse−Acting Proportional−Plus−Reset Controller with Anti−Reset Windup
proportional band adjustment, the shorter the effective length of the cantilever spring. The spring rate of the cantilever spring increases as its length shortens, allowing less motion to be transferred from the bellows to the beam and flapper for a given change in output pressure.
ProportionalPlusReset Controllers
Action of a proportional−plus−reset controller is similar to that of a proportionalonly controller except that feedback from the controller output pressure is piped to a reset bellows as well as to the proportional bellows as shown at the right in figure 13.
With an increasing controller output pressure, pressure in the reset bellows increases. Increases in
CANTILEVER SPRING
PROPORTIONAL BELLOWS
RESET VALVE
reset bellows pressure moves the beam and flapper closer to the nozzle, starting another increase of pressure throughout the system. Pressure buildup continues until the controlled pressure is brought back to the set point. The reset valve is adjustable to vary the amount of delay in the reset action. Closing the reset valve increases the delay in reset action.
Controllers with Anti−Reset Windup
During a prolonged difference between set point and the controlled variable, such as encountered with intermittent control applications (e.g., batch temperature control or wide open monitors on pressure control), reset ramps the controller output to either zero or full supply pressure; this condition is reset windup. When the controlled variable crosses the set point, there will be a delay before the
22
Page 23
Instruction Manual
September 2009
controller output responds to the change in controlled variable. Antireset windup minimizes this delay and permits returning the controlled variable to set point more quickly with minimal overshoot.
As shown in figure 14 a proportionalplusreset controller with antireset windup includes a differential relief valve. The valve consists of two pressure chambers separated by a spring−loaded diaphragm.
For the controller shown in figure 14, proportional pressure registers rapidly on the spring side of the relief valve diaphragm as well as in the proportional bellows, and reset pressure registers on the opposite side of the relief valve diaphragm. As long as controlled pressure changes are slow enough for normal proportional and reset action, the relief valve spring will keep the relief valve diaphragm from opening. However, a large or rapid decrease in controller pressure will cause the relay to exhaust loading pressure from the control device rapidly, and also from the proportional system and spring side of the relief diaphragm. If this decrease on the spring side of the diaphragm is greater than the relief valve spring setting, the diaphragm will move off the relief valve orifice and permit the proportional pressure on the opposite side of the relief valve diaphragm to bleed rapidly into the reset bellows. The antireset windup action also can be reversed to relieve with an increasing proportional pressure.

Differential Gap Controllers

With a differential gap controller, feedback pressure does not counteract the change in flapper position as it does in a proportionalonly controller. Instead, feedback pressure is piped to the bellows located on the side of the beam and flapper opposite the nozzle (the proportional bellows in figure 13). Then, as controller output pressure increases, feedback pressure moves the flapper closer to the nozzle to again increase controller output pressure. This process continues rapidly until the controller output pressure is at the upper range limit. The action of a differential gap controller is so rapid that output pressure changes from zero to maximum as soon as the switching point is reached. The action is similar with falling output pressure. Lower feedback pressure lowers the bellows pressure, which moves the flapper away from the nozzle. This again reduces the output pressure and continues until the output pressure is zero.
C1 Controllers and Transmitters

Transmitters

Action of a pneumatic transmitter is similar to that of a proportionalonly controller. Since the output pressure of the transmitter has no effect on the process pressure, transmitter output pressure is a proportional measure of the process pressure. The proportional band adjustment determines the span of the transmitter, and the pressure setting mechanism determines the zero of the transmitter.

Maintenance

If the installation includes a Fisher 67 Series filter regulator, periodically open the drain on the filter regulator to drain accumulated moisture. Also, push the springout cleaning wire on the relay orifice. Check the opening of the vent assembly (key 28, figure 2) or the opening of the remote vent pipe, if one is used. If necessary, clean the openings.
Parts are subject to normal wear and must be inspected and replaced as necessary. The frequency of inspection and parts replacement depends upon the severity of the service conditions.
WARNING
The following maintenance procedures require taking the controller out of service. To avoid personal injury and property damage caused by the release of pressure or process fluid, observe the following before starting maintenance:
D Always wear protective clothing,
gloves, and eyewear.
D Provide some temporary means of control for the process before taking the controller out of service.
D Provide a means of containing the process fluid before removing any measurement devices from the process.
D Use lock−out procedures to be sure that the above measures stay in effect while you work on the equipment.
D Personal injury or property damage may result from fire or explosion if natural gas is used as the supply medium and appropriate
23
Page 24
Instruction Manual
C1 Controllers and Transmitters
preventative measures are not taken. Preventative measures may include, but are not limited to, one or more of the following; Remote venting of the unit, reevaluating the hazardous area classification, ensuring adequate ventilation, and the removal of any ignition sources. For information on remote venting of this controller/ transmitter, refer to page 8.
D Check with your process or safety engineer for any additional measures that must be taken to protect against process media.

Replacing Gauges

Refer to figures 21 and 22 for key number locations unless otherwise directed.
Three gauge configurations are available for C1 units.
D Output and supply pressure indications
September 2009
correct range so they are not damaged by overpressure.
Note
Key 2 is used as both a supply gauge and an output gauge on units without a process pressure gauge. A quantity of 2 is required for these units. On units with a process pressure indicator gauge (key 4), key 2 is used for the output gauge. A quantity of 1 is required for these units.
Use key 3 for supply pressure indication when a process pressure gauge is installed. Key 3 installs on the supply pressure regulator.
1. Shut off the supply pressure and process lines to the controller or transmitter.
2. Remove the gauge to be replaced: D Unscrew the output or supply gauge (key 2)
from the relay base.
D Output and process pressure indications
D Output, process, and supply pressure
indications One gauge type (key 2) is used for both output and
supply pressure indications when the gauges are installed inside the controller case. Key 2 features a 1/8inch connecting stem that matches the threaded gauge boss extending from the relay base.
In some cases, a process pressure gauge (key 4) covers the position of the internal supply pressure gauge. The supply pressure gauge has been removed and replaced with a pipe plug (key 15). The pressure control block (key 10) is different to accommodate a different control tubing assembly (key 23) with a pressure connection (key 14) for a process pressure gauge. If a supply pressure gauge is required, a gauge with a 1/4inch connecting stem (key 3) must be mounted on the supply pressure regulator.
CAUTION
Before performing this procedure, be sure the replacement gauges are the
D Unscrew the process pressure gauge (key 4)
from the process connection (key 14).
D Unscrew the supply gauge (key 3) from the
supply pressure regulator.
3. Coat the threads of the replacement gauge with a
sealant.
4. Screw the replacement gauge into the relay base,
process connection, or supply pressure regulator.
5. Check for leaks by applying the correct supply
pressure with the nozzle capped to produce full output pressure.

Replacing Bourdon Tube

Refer to figure 23 for key number locations unless otherwise directed.
1. Shut off the supply pressure and process lines to
the controller or transmitter.
2. Unscrew the machine screw (key 56) to
disconnect the link (key 16) and bearing (key 31) from the beam (key 39). Be careful to avoid losing the bearing (key 31). Washer(s) (key 62) for the machine screw (key 56) are at times furnished for insertion at the beam (key 39) connection to ensure alignment of the connecting link (key 16).
24
Page 25
Instruction Manual
September 2009
PROPORTIONAL TUBING
RELAY TUBING
(KEY 24)
FLAPPER/SCREW (KEYS 40 AND 46)
REVERSE
ACTING POSITION
REVERSING BLOCK
GE28263A E1064
(KEY 37)
RESET VALVE
(KEY 256)
(KEY 25)
REVERSE ACTING
C1 Controllers and Transmitters
PROPORTIONAL TUBING
RELAY TUBING
REVERSING BLOCK
PROPORTIONAL BAND ASSY
BELLOWS (KEY 52)
DIRECT ACTING POSITION
FLAPPER/SCREW (KEYS 40 AND 46)
PROPORTIONAL-ONLY CONTROLLER OR TRANSMITTER
(KEY 24)
(KEY 37)
RESET VALVE
(KEY 256)
(KEY 25)
DIRECT ACTING
BELLOWS (KEY 52)
PROPORTIONAL BAND ASSY
RESET TUBING
RELAY TUBING
FLAPPER/SCREW (KEYS 40 AND 46)
REVERSE ACTING
POSITION
REVERSING BLOCK
GE34722A E1065
(KEY 37)
(KEY 24)
REVERSE ACTING
(KEY 27)
PROPORTIONAL TUBING (KEY 27)
PROPORTIONAL BAND ASSY
BELLOWS (KEY 52)
PROPORTIONAL-PLUS-RESET CONTROLLER
Figure 15. Reverse/Direct Acting Tubing Connections for Proportional Controllers or Transmitter
3. Disconnect the control tubing (key 23, figure 22). Unscrew the two screws (key 55) and washers (key 45), and remove the Bourdon tube (key 5).
4. Unscrew the machine screw (key 56), and remove the link and bearing (keys 16 and 31) from the Bourdon tube. Be careful to avoid losing the bearing.
5. Attach the link and bearing to the replacement Bourdon tube.
6. Attach the Bourdon tube with two machine screws and washers (keys 55 and 45).
RELAY TUBING
(KEY 24)
REVERSING BLOCK
(KEY 37)
DIRECT ACTING
POSITION
FLAPPER/SCREW (KEYS 40 AND 46)
RESET TUBING (KEY 27)
PROPORTIONAL TUBING (KEY 27)
BELLOWS (KEY 52)
PROPORTIONAL BAND ASSY
DIRECT ACTING
7. Connect the link and bearing to the beam
(key 39).
8. After connecting the link to the beam, make sure
that the link is parallel to the sensing element (key 5) and the beam (key 39) so that it does not bind against the sensing element of the beam. Figure 17 shows a properly aligned connecting link; the connecting link is not in contact with the Bourdon tube or or washers. When properly configured, the connecting link moves freely when touched. Washers (key 62) are used as shims to set parallelism.
25
Page 26
Instruction Manual
C1 Controllers and Transmitters
PROPORTIONAL TUBING
RELAY TUBING
(KEY 24)
FLAPPER/SCREW (KEYS 40 AND 46)
REVERSE ACTING
POSITION
REVERSING BLOCK
GE34724 A E1066
(KEY 37)
Figure 16. Reverse/Direct Acting Tubing Connection for Differential Gap Controller
9. Check to be sure that the beam is parallel with the bottom of the case and that the link (key 16) is in tension. If the beam is not parallel with the case, loosen the machine screws (key 55), reposition the Bourdon tube to get the beam parallel, and retighten the screws.
10. If a Bourdon tube with a different range was installed, remove the machine screw and washer (keys 61 and 60) and dial (key 6). Install a new dial having an adjustment range corresponding to the range of the Bourdon tube. If an optional process pressure gauge (key 4, figure 21) is being used, install a new gauge with the appropriate measurement capability.
11. Check all tubing connections for leaks and the Bourdon tube machine screws, tighten as necessary. Perform the appropriate calibration procedures.
(KEY 25)
REVERSE ACTING
BELLOWS (KEY 52)
PROPORTIONAL BAND ASSY
DIFFERENTIAL-GAP CONTROLLER
September 2009
RELAY TUBING
(KEY 24)
REVERSING BLOCK
(KEY 37)
DIRECT ACTING POSITION
FLAPPER/SCREW (KEYS 40 AND 46)
PROPORTIONAL TUBING
(KEY 25)
DIRECT ACTING
PROPORTIONAL BAND ASSY
BELLOWS (KEY 52)
block (key 8, figure 21) to the bellows assembly (key 71), at the pressure block end.
3. Unscrew the four machine screws (key 41,
figure 21 or 22), and remove the pressure sensing subassembly from the case.
4. Remove the bellows yoke machine screws and
washers (keys 98 and 99), and move the bellows yoke to the right to permit access to the link screw.
5. Disconnect the link (key 71M) and bearing
(key 71L) from the beam. Be careful to avoid losing the bearing.
6. Loosen the nuts that secure the bellows
assembly (key 71), and remove this assembly from the bellows yoke (key 100).
7. For a gaugepressure sensing element (only one
bellows in the assembly), install the proper bellows spring (key 104) into the bellows assembly if the input signal range is being changed.

Replacing Bellows Sensing Element

Refer to figure 24 for key number locations unless otherwise directed.
1. Shut off the supply pressure and process lines to the controller or transmitter.
2. Disconnect the tubing from the mounting base (key 57) and calibration adjuster (key 36). Disconnect the tubing that connects the pressure
26
8. Install the new bellows assembly into the bellows
yoke.
9. Attach the link and bearing to the bellows
assembly. Position the bellows yoke (key 100) on the mounting base (key 57), and attach the link and bearing to the beam. Start but do not tighten the four machine screws (key 98) with washers (key 99) that attach the yoke to the mounting base. Slide the yoke up or down as necessary to position the beam horizontally, as shown in figure 24. Tighten the machine screws.
Page 27
Instruction Manual
September 2009
BOURDON TUBE (KEY 5)
LINK BEARING (KEY 31)
WASHER (QTY 2) (KEY 62)
BEAM (KEY 39)
CONNECTING LINK (KEY 16)
BINDING CONNECTING LINK
(IMPROPERLY ALIGNED)
GE37119
Figure 17. Connecting Link
10. Replace the subassembly in the case and secure with the four machine screws (key 41, figure 21 or 22). Reconnect all tubing.
11. If a bellows assembly with a different range is installed, remove the machine screw and washer (keys 61 and 60) and dial (key 6), and install a new dial having an adjustment range corresponding to the range of the bellows. If an optional process pressure gauge (key 4, figure 21) is being used, install a new gauge with the appropriate measurement capability.
12. Check all tubing connections for leaks and the bellows yoke machine screws, tighten as necessary. Perform the appropriate calibration procedures.
C1 Controllers and Transmitters
BOURDON TUBE (KEY 5)
WASHER (KEY 62)
LINK BEARING (KEY 31)
WASHER (KEY 62)
BEAM
PROPERLY ALIGNED
CONNECTING LINK
3. Refer to figure 14. Install the replacement relief
valve with the arrow positioned so that the controller output will be as noted in step 1 when the process is shut down.

Changing Action

ProportionalOnly to a Differential Gap Controller
A proportional−only controller may be changed to a differential gap controller, or vice versa, by changing the position of the proportional tubing and inverting the proportional band assembly.
(KEY 39)
CONNECTING LINK (KEY 16)

Changing Reset Valve

1. Disconnect the appropriate tubing and remove the reset restriction valve assembly (key 256, figure 22) by removing the screw (key 22, not shown) from the back of the case. Install the desired replacement assembly.
2. Connect the tubing, check all connections for leaks and perform the appropriate calibration procedures.
Changing Anti−Reset Windup Differential Relief Valve
Refer to figure 23 for key number locations.
1. Note the controller output pressure (zero or supply) when the process is shut down.
2. Remove the differential relief valve assembly.
1. Isolate the controller or transmitter from process,
control, and supply pressure. Vent any trapped pressure from the controller or transmitter before proceeding with the following steps.
2. Disconnect the proportional tubing (key 25,
figure 16) from the mounting base (key 57, figure 23 or 24) and reinstall it in the other connection in the mounting base.
3. Do not invert the reversing block unless also
changing the controller action from direct to reverse (or vice versa).
4. Invert the proportional band assembly (refer to
figure 18):
a. Turn the proportional band adjustment knob (key 73) to 10.
b. Unscrew the spring adjustor (key 65), removing the bias spring (key 70) and washers (key 64) with it.
27
Page 28
Instruction Manual
C1 Controllers and Transmitters
PROPORTIONAL BAND ADJUSTMENT KNOB
CANTILEVER SPRING
SPRING ADJUSTOR
GE34725A E1067
c. Unclip the lock spring (key 72). Remove the indicator scale (key 69) and proportional band adjustment knob (key 73).
d. Remove the gain adjustment bar (key 63). Flip it over so it attaches to the opposite side of the cantilever spring (key 8), as shown in figure 16, and screw it back down.
e. Flip over the indicator scale (key 69); install it and the proportional band adjustment knob (key 73) as a unit. Snap in the lock spring (key 72).
f. Tighten down the spring adjustor (key 65) with the bias spring (key 70) and washers (key 64) until it stops against the gain adjustment bar (key 63).
g. Turn the proportional band adjustment knob to the 10 setting. If it cannot be turned to the 10 setting loosen the spring adjustor (key 63).
5. Check all connections for leaks with a soapandwater solution. Perform the appropriate calibration procedure.
(KEY 73)
LOCK SPRING
(KEY 72)
(KEY 8)
BIAS SPRING
(KEY 70)
WASHER
(KEY 64)
(KEY 65)
Figure 18. Proportional Band Assembly
September 2009
MACHINE SCREW (KEY 56)
INDICATOR SCALE (KEY 69)
MACHINE SCREW (KEY 74)
GAIN ADJUSTMENT BAR (KEY 63)
and 19 for key number locations unless otherwise directed.
1. Isolate the controller or transmitter from process,
control, and supply pressure. Vent any trapped pressure from the controller or transmitter before proceeding with this procedure.
2. As shown in figure 15, locate the new tubing,
proportional band assembly, and reversing block positions for the desired action.
3. Locate the two bellows (key 52), the proportional
band assembly (see figure 15), and the reversing block (key 37).
4. Disconnect the tubing (refer to figure 15):
a. For a proportionalonly controller or for a transmitter, disconnect the proportional tubing (key 25) from the mounting base and reconnect them on the opposite side.
b. For a proportionalplusreset controller, disconnect the proportional tubing (key 27) and reset tubing (key 27) from the mounting base and reconnect them on the opposite side.
5. Invert the proportional band assembly (refer to
figure 18):

Reverse to Direct Action

Use the numbered steps below to change from reverse action (increasing process pressure produces decreasing output pressure) to direct action (increasing process pressure produces increasing output pressure), or vice versa. Changing the action is accomplished by reversing the positions of the reversing block, proportional band assembly, and bellows tubing(s). Refer to figures 15, 16, 18,
28
a. Turn the proportional band adjustment knob (key 73) to 10.
b. Unscrew the spring adjustor (key 65), removing the bias spring (key 70) and washers (key 64) with it.
c. Unclip the lock spring (key 72). Remove the indicator scale (key 69) and proportional band adjustment knob (key 73).
Page 29
Instruction Manual
September 2009
OUTER FLEXURE
(KEY 68)
MACHINE SCREW
(KEY 51)
MACHINE SCREW
(KEY 51)
BEAM
(KEY 39)
GE34726B E1068
Figure 19. Beam/Cantilever Spring Assembly
d. Remove the gain adjustment bar (key 63). Flip it over so it attaches to the opposite side of the cantilever spring (key 8) as shown in figure 15 and reattach.
e. Flip over the indicator scale (key 69, figure
18); install it and the proportional ban knob (key
73) as a unit. Snap in the lock spring (key 72).
f. Tighten down the spring adjustor (key 65) with the bias spring (key 70) and washers (key 64) until it stops against the gain adjustment bar (key 63).
g. Turn the proportional band adjustment knob to the 10 setting. If it cannot be turned, loosen the spring adjustor (key 65).
6. Change the reversing block assembly (figure 15 or 16, key 37):
a. Remove the sealing screw (key 49, figure 23 or 24). Inspect the O−ring (key 77 located in the recessed area under the sealing screw head. Replace the Oring if necessary.
b. Remove the reversing block screw (key 50, figure 23 or 24) and reversing block assembly (key 37). Inspect the Orings (key 77) located in the recessed area under the reversing block screw head and between the reversing block assembly and the calibration adjuster (key 36). Replace these Orings if necessary.
C1 Controllers and Transmitters
BELLOWS SPACER (KEY 34)
c. Position the reversing block assembly, with an Oring, on the calibration adjuster (key 36) so that the nozzle is on the opposite side of the beam (key 39) from which it was removed. Position the reversing block hole in the calibration adjuster. Install the reversing block screw (key
50) with an Oring (key 77). d. Install the sealing screw (key 49) with an
Oring in the hole previously covered by the reversing block assembly.
7. Check all connections for leaks with a
soapandwater solution. Perform the appropriate calibration procedures.

Relay Replacement

Key numbers used in this procedure are shown in figure 21 or 22 except where indicated.
1. Shut off the supply pressure and process
pressure line(s) to the controller or transmitter.
2. Disconnect the tubing (key 24) from the relay.
3. Unscrew the output or supply pressure gauge
(key 2).
4. To remove the relay assembly, unscrew two
Phillipshead machine screws (key 29, not shown) located behind the relay on the back of the case.
5. Remove the relay gasket (key 19, figure 21).
6. A new relay can be installed as a replacement. If
a new relay is being installed, continue with the next step.
INNER FLEXURE (KEY 67)
CANTILEVER SPRING (KEY 8)
29
Page 30
Instruction Manual
C1 Controllers and Transmitters
7. Attach the replacement relay and new relay gasket with machine screws inserted through the back of the case. Reinstall the output or supply gauge.
8. Connect the tubing, and check all connections for leaks. Perform the appropriate calibration procedures.

Changing Output Signal Range

Use the following information and subsequent procedures when changing the output signal range of the controller or transmitter. Use the following procedure:
D For a controller or transmitter, use this procedure to change from a 0.2 to 1.0 bar (3 to 15 psig) to a 0.4 to 2.0 bar (6 to 30 psig) output signal range or vice versa.
D For a differential gap controller, use this procedure to change from a 0 and 1.4 bar (0 and 20 psig) to a 0 and 2.4 bar (0 and 35 psig) output signal range or vice versa.
D When changing the supply pressure source to a new range, refer to table 5 for supply pressure requirements for the output signal range selected.
Also, make appropriate changes to the nameplate of the controller or transmitter, reflecting the new range selections. Refer to figure 23 or 24 for key number locations unless otherwise directed.
1. Shut off the supply pressure and process lines to the controller or transmitter.
2. Disconnect the tubing from the mounting base (key 57) and calibration adjuster (key 36).
Disconnect the tubing that connects the pressure block (key 10, figure 21 or 22) to the Bourdon tube or bellows assembly (key 5 or 52), at the pressure block end.
September 2009
ORING (KEY 77)
A62811 / IL
Figure 20. Bellows Screw Detail
Note
The bellows screws (key 53) have an Oring (key 77, figure 20) installed beneath the bellows screw head. Remove the Oring and obtain a replacement when reassembling the bellows.
6. Unscrew the spring adjustor (key 65). Unclip the lock spring (key 72, figure 18) and remove the indicator scale (key 69) and the proportional band adjustment knob (key 73).
7. Compress the bellows (key 52) so that the end of the bellows, beam (key 39), and cantilever spring (key 8) can be removed from the mounting base (key 57).
8. Unscrew the bellows (key 52) from the bellows/cantilever assembly.
9. Remove the cantilever spring from the spacer (key 34).
a. Remove the beam machine screws (figure 19, step 4).
b. Remove the cantilever machine screws (figure 19, step 3).
3. Unscrew the machine screws (key 41, figure 21 or 22), and remove the subassembly from the case.
4. If the controller or transmitter uses a Bourdon tube sensing element disconnect the Bourdon tube from the beam (key 39) by removing the screw (key 56). Be careful to avoid losing the bearing (key 31). Unscrew the machine screws (key 55) and remove the washers and Bourdon tube (keys 45 and 5).
5. Unscrew the bellows screws (key 53) from each end of the mounting base (key 57).
30
c. Remove the inner flexure (figure 19, step 1) and install it on the new cantilever.
10. Install the new cantilever spring (key 8) and reconnect the beam (key 39) to the bellows spacer (key 34) in reverse sequence of steps 9a. and 9b. and reattach the bellows to the beam/cantilever assembly.
11. Compress the bellows and install them into the mounting base (key 57). Align the cantilever spring with the gain adjustment bar (key 63). Install the indicator scale (key 69) and the proportional band
Page 31
Instruction Manual
September 2009
adjustment knob (key 73) as a unit. Snap the lock spring (key 72) onto the indicator scale.
12. Install the spring adjustor (key 65, figure 18) with washers (key 64, figure 18) on either side of the bias spring (key 70, figure 18). Tighten down the spring adjustor until it stops against the gain adjustment bar (key 63).
13. Turn the proportional band adjustment knob to 10. If it cannot be turned to 10 loosen the spring adjustor (key 65).
14. Secure the bellows (key 52) with the bellows screws (key 53), making sure that the nozzle (key 54) is centered on the flapper (key 40).
15. Unscrew the supply and output gauges (figure 21 or 22, key 2) and install new gauges with correct ranges.
16. Replace the subassembly in the case and secure with machine screws (figure 21 or 22, key 41). Reinstall the Bourdon tube if it was removed; refer to the Replacing the Bourdon Tube section. Reconnect all tubing.
17. Check all tubing connections and the bellows machine screws for leaks; tighten as necessary. Perform the appropriate calibration procedures.
C1 Controllers and Transmitters
WARNING
Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use, or maintenance of any product. Responsibility for the selection, use, and maintenance of any product remains with the purchaser and enduser.

Parts Kits

Description Part Number Controller Repair Kits
Kit includes Gasket, Relay Gasket, Bellows Frame
Gasket, and keys 16, 20, 21, 31, 37, 38, 40, 46, 49,
50, 54, 62, 75, 76, and 77
Note
Keys 71K, 71L, and 71M may also be necessary for repair of C1B and C1D controllers. Refer to the Common Parts section for part numbers.

Parts Ordering

Whenever corresponding with your Emerson Process Management sales office about this equipment, mention the serial number of the unit. The serial number can be found on the nameplate (key 22, figure 21). When ordering replacement parts, also state the complete 11character part number of each part required as found in the following parts list.
WARNING
Use only genuine Fisher replacement parts. Components that are not supplied by Emerson Process Management should not, under any circumstances, be used in any Fisher instrument. Use of components not supplied by Emerson Process Management may void your warranty, might adversely affect the performance of the instrument, and could cause personal injury or property damage.
Standard Temperature RC100X00L12 High Temperature RC100X00H12
Relay Replacement Kits
Kit includes keys 19 and 29, the replacement relay, and
2 Machine Screws
Standard Temperature RRELAYX0L22 High Temperature RRELAYX0H22
Case Assembly Seal Kit
Kit includes 3 Manifold Seals, 1 Manifold Cover,
and 10 Mounting Screws RC100X00012

Parts List

Common Parts (Figures 21, 22, 23, and 24)

Key Description Part Number
Note
Part numbers are shown for recommended spares only. For part numbers not shown, contact your Emerson Process Management sales office.
1 Case and Cover Assembly, aluminum
31
Page 32
Instruction Manual
C1 Controllers and Transmitters
Key Description Part Number
Note
Key 2 is used as both a supply gauge and an output gauge on units without a process pressure gauge. A quantity of 2 is required for these units. On units with a process pressure gauge (key 106), key 2 is used for the output gauge. A quantity of 1 is required for these units.
Use key 3 for supply pressure indication when a process pressure gauge is installed. Key 3 installs on the supply pressure regulator.
2* Supply and Output Pressure Gauge, w/o process
pressure gauge (1/8inch connecting stem), (2 req’d)
Dual scale
Brass/Plastic
02.0 kg/cm2 and 030 psig 11B8577X042 04.0 kg/cm2 and 060 psig 11B8577X052
SST
02.0 kg/cm2 and 030 psig 11B8583X032 04.0 kg/cm2 and 060 psig 11B8583X052
Triple scale
Brass/Plastic
02.0 bar, 00.2 MPa, and 030 psig 11B8577X012 04.0 bar, 00.4 MPa, and 060 psig 11B8577X022
SST
02.0 kg/cm2 and 030 psig 11B8583X012 04.0 kg/cm2 and 060 psig 11B8583X022
2* Output Pressure Gauge, w/process pressure
gauge (1/8inch connecting stem), Brass/Plastic
Triple scale
02.0 bar, 00.2 MPa, and 030 psig 11B8577X012 04.0 bar, 00.4 MPa, and 060 psig 11B8577X022
3* Supply Pressure Gauge, w/process pressure
gauge (1/4inch connecting stem), Brass/Plastic
Triple scale
02.0 bar, 00.2 MPa, and 030 psig 11B8579X022 04.0 bar, 00.4 MPa, and 060 psig 11B8579X032
Note
Controllers with bellows sensing element use only the 2.0 bar, 0 to 0.2 MPa, and 0 to 0 to 30 psig triple scale brass and stainless steel process pressure gauges. Differential pressure controllers do not use a process pressure gauge.
4* Process Pressure Indicator Gauge (use only when specified)
Triple scale
Stainless steel
02.0 bar, 00.2 MPa, and 030 psig 11B8584X022 020 bar, 02.0 MPa, and 0300 psig 11B8584X012 069 bar, 06.9 MPa, and 01000 psig 11B8584X032
High Temp, silicone 1N873804142
September 2009
Key Description Part Number
8* Cantilever Spring, S30200
315 psi range GE31702X012 630 psi range GE31701X012
9 Nameplate, aluminum
10 Control Pressure Block
For gauge pressure instruments
w/o process pressure gauge
CF8M FMS 20B58 for standard, NACE and oxygen service
w/process gauge
11 Plug, S31600 (not shown)
12 Machine Screw, steel pl (4 req’d) 13 Lockwasher, steel pl/zn pl (4 req’d)
14 Pressure Connection, S31600
15 Pipe Plug, steel pl (not shown)
16* Connecting Link
16 Connecting Link, Bourdon tube w/optional travel stop,
17 Lockwasher, steel pl (2 req’d)
18 Machine Screw, steel pl (2 req’d)
19* Relay Gasket
20* ORing 21* Gasket
22 Mounting Screw for reset restriction valve
23* Control Tubing Assembly, 304 SST
23 Control Tubing Assembly, SST/vinyl
24* Relay Tubing Assembly, 304 SST GE33948X012
SST
used with gauge pressure only
1 req’d for standard/NACE 2 req’d for oxygen service
Use w/process gauge
Use w/process gauge, not used w/Bourdon tube protector
(1)
Std., 188 SST 1L379641012
188 SST
Use w/optional Bourdon tube travel stop
Use w/optional Bourdon tube travel stop
Std Temp, chloroprene 1C897403012 Hi Temp, silicone 1N873804142
(1)
(1)
1/420 UNC, steel pl (not shown)
For Bourdon tube instruments
w/o process pressure gauge
NACE 1H3011000A2 Oxygen Service 1H3011X0012 w/process pressure gauge 1J2530000A2
used with NACE compliant Bourdon tube
, Bourdon tube instruments only
(1)
, nitrile 1C376206992
, chloroprene, (not shown) 1C328603012
5* Bourdon Tube See following table 6 Dial, aluminum 7 Screw, nylon (transmitters only)
32
25* Compensator Tubing, 304 SST GE28421X012
26* Reset Tubing, 304 SST GE30128X012
*Recommended spare parts
1. This part is included in the Controller Repair Kit.
Page 33
Instruction Manual
September 2009
NOTE: KEYS 11, 21, AND 29 ARE NOT SHOWN
GE34729B GE31719A E1069
TRANSMITTER
C1 Controllers and Transmitters
SPRINGOUT CLEANING WIRE
RELAY ASSEMBLY
OPTIONAL PROCESS PRESSURE INDICATION
SUBASSEMBLY (KEY NOS. SHOWN IN FIGURE 23 OR 24)
Figure 21. Typical Reverse Acting Fisher C1 Assembly
(Refer to figure 25 for the Front View of the Case & Cover Assembly)
Key 5* Bourdon Tube
PRESSURE RANGE MATERIAL
kPa Psig Stainless Steel
0200 0200 0400 0400 0700
0700 01400 01400
02000 02000 04000 04000 07000 07000
010,000 020,000
035,000 055,000 070,000
1. Bourdon tubes are also available in NACE compliant material. Contact your Emerson Process Management sales office for additional information.
2. For oxygen service.
030 030 060
060 0100 0100 0200 0200
0300 0300 0600 0600
01000 01000 01500 03000
05000 08000
010,000
32B1243X012 32B1243X212 32B1243X022 32B1243X172 32B1243X032 32B1243X202 32B1243X042 32B1243X162
32B1244X052 32B1244X152 32B1244X062 32B1244X182 32B1244X072 32B1244X192 32B1245X082 32B1245X092
32B1245X102 32B1245X112 32B1245X122
(1)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
*Recommended spare parts
33
Page 34
Instruction Manual
C1 Controllers and Transmitters
NOTE: KEYS 11, 21, 29 ARE NOT SHOWN
GE28280B
Figure 21. Typical Reverse Acting Fisher C1 Assembly (continued)
(Refer to figure 25 for the Front View of the Case & Cover Assembly)
PROPORTIONAL-ONLY CONTROLLER
SPRINGOUT CLEANING WIRE RELAY ASSEMBLY
SUBASSEMBLY (KEY NOS. SHOWN IN FIGURE 23 OR 24)
September 2009
Key Description Part Number
27* Compensator Tubing, 304 SST (2 req’d) GE29222X012
28 Vent Ass’y 29 Machine Screw
(2)
, 188 SST (not shown) (2 req’d)
30 NPT Adaptor, aluminum
31* Link bearing
(1)
, S41600
Bourdon tube instruments only (2 req’d) 1L379546202
32 Rotary Spring, S30400 33 Bellows Stud, brass (not shown)
34 Spacer, 35 Pressure Set Arm, G10080 carbon steel, zinc pl 36 Calibration Adjuster 37 Reversing Block 38 Sleeve
(1)
39 Beam, G10080 carbon steel, zinc pl 40 Flapper
(1)
, Z33520 zinc die casting
, POM (polyoxymethylene)
(1)
, S30100 SST
41 Machine Screw, steel pl (4 req’d)
Key Description Part Number
42 Flexure Strip, S30200 43 Flexure Strip Washer, G10200 carbon steel (2 req’d)
44 Washer, 18−8 SST (2 req’d) 45 Washer, steel pl (2 req’d) 46 Machine Screw
(1)
, steel pl
47 Machine Screw, steel pl (4 req’d) 48 Machine Screw, 188 SST (2 req’d) 49 Sealing Screw 50 Reversing Block Screw
(1)
, SST
(1)
, SST
51 Cap Screw, 18−8 SST (8 req’d) 52* Reversing Bellows Ass’y, SST (2 req’d) 14A5725X022 53 Bellows Screw, 18−8 SST (2 req’d) 54* Nozzle
(1)
, SST 1U639135132 55 Machine Screw, steel pl (2 req’d) 56 Machine Screw, 188 SST (4 req’d)
57 Mounting Base, aluminum
34
*Recommended spare parts
1. This part is included in the Controller Repair Kit.
2. This part is included in the Relay Replacement Kit.
Page 35
Instruction Manual
September 2009
NOTE: KEYS 11, 21, 22, 29 ARE NOT SHOWN
GE28281B E1071
C1 Controllers and Transmitters
SPRINGOUT CLEANING WIRE
RELAY ASSEMBLY
SUBASSEMBLY (KEY NOS. SHOWN IN FIGURE 23 OR 24)
PROPORTIONAL-PLUS-RESET CONTROLLER
WITHOUT ANTI-RESET WINDUP
Figure 22. Typical Reverse Acting Fisher C1 Proportional−Plus−Reset Assembly
(Refer to figure 25 for the Front View of the Case & Cover Assembly)
Key Description Part Number
58 Knob, PPS (polyphenylene sulfide) 59 Knob Spring, steel/zinc pl
60 Washer, G10100 carbon steel, zinc pl 61 Machine Screw, steel pl 62 Washer
63 Gain Adj Bar, A03600 64 Washer, 18−8 SST (2 req’d)
65 Spring Adjustor, 18−8 SST
66 Travel Stop Assembly, SST
67* Inner Flexure, S30200 GE26663X012
68* Outer Flexure, S30200 GE26664X012 69 Indicator Scale, aluminum 70 Bias Spring, S30200
(1)
, brass/zinc pl (2 req’d)
Use w/optional Bourdon tube travel stop
Key Description Part Number
71* Gauge Pressure Bellows (input)
(3)
Brass
0150 mbar (060 inches wc) positive, 0150 mbar
(660 inches wc) vacuum, and 75−0−75 mbar
(30−0−30 inches wc) compound 1L3780000A2 0250 mbar (0100 inches wc) positive 1L3788000A2 00.35 mbar (05 psig) positive and for
0350 mbar (010 inches Hg) vacuum 1L3781000A2 00.5 bar (07.5 psig) positive 1L3789000A2 00.7 bar (010 psig) positive 1L3782000A2 01.0 bar (015 psig) positive, 01.0 bar
(030 inches Hg) vacuum, and 500−0−500 mbar
(15−0−7.5 psig) compound 1L3783000A2 01.4 bar (020 psig) positive 1L3784000A2 02.0 bar (030 psig) positive and 1.001.0 bar
(30−0−15 psig) compound 1L3785000A2
Stainless steel,
01.0 bar (015 psig) positive, 01.0 bar
(030 inches Hg) vacuum, and 500−0−500 mbar
(15−0−7.5 psig) compound 1L3786000A2 02.0 bar (030 psig) positive, 1.001.0 bar
(30−0−15 psig) compound 1L3787000A2
*Recommended spare parts
1. This part is included in the Controller Repair Kit.
3. If ordering the bellows (key 71) to change the range of a gauge pressure controller, also order the appropriate bellows spring (key 80). Also order keys 101, 102, and 103 if you do not have them.
35
Page 36
Instruction Manual
C1 Controllers and Transmitters
SPRINGOUT CLEANING WIRE
RELAY ASSEMBLY
NOTES:
ARROW DOWN—RELIEVES ON DECREASING OUTPUT (OUTPUT @ SUPPLY DURING SHUTDOWN)
1 2
ARROW UP—RELIEVES ON INCREASING OUTPUT (OUTPUT @ ZERO DURING SHUTDOWN)
KEYS 80, 81, AND 82 ARE NOT SHOWN
GE31718A E1072
PROPORTIONAL-PLUS-RESET CONTROLLER WITH DIFFERENTIAL
RELIEF VALVE ASSEMBLY FOR ANTI-RESET WINDUP
September 2009
2
1
Figure 22. Typical Reverse Acting Fisher C1 Proportional−Plus−Reset Assembly (continued)
(Refer to figure 25 for the Front View of the Case & Cover Assembly)
Key Description Part Number
71* DifferentialPressure Bellows (input)
Brass
0200 mbar (080 inches wc) 2L3790000A2 00.7 bar (010 psi) 2L3791000A2 01.4 bar (020 psi) 2L3792000A2
Stainless steel,
02.0 bar (030 psi) 2L3793000A2
71K Machine Screw
bellows sensing instruments only (2 req’d) 1A331928982
71L* Bearing
bellows sensing instruments only (2 req’d) 1L379546202
71M* Link
(4)
72* Lock Spring, 304L SST GE32298X012 73 Proportional Band Adjustment Knob, steel/PPS 74 Machine Screw
75* Gasket
Std Temp, chloroprene (2 req’d) 1D397003012 High Temp, silicone (2 req’d) 1N873604142
76* Nozzle ORing
Std Temp, nitrile 1E222606992 High Temp, fluorocarbon 1N838706382
(4)
, steel pl
(4)
bellows sensing instruments only 1L379641012
(1)
, 188 SST (2 req’d)
(1)
(1)
,
Key Description Part Number
Note
A total of 5 Orings (key 77) are used. 1 Oring is used under the sealing screw (key
49), 1 Oring is used under the reversing block screw (key 50), 1 Oring is used between the reversing block ass’y (key 52) and the calibration adjuster (key 36), and 1 Oring is used in the recessed area under the head of each of the bellows screws (key 53).
77* ORing,
Std Temp, nitrile (5 req’d) 1D687506992 High Temp, fluorocarbon (5 req’d) 1N430406382
Note
Keys 78 through 82 are used for ProportionalPlusReset controllers only.
78 Tubing Assembly, SST 79 Tubing Assembly, SST 80 AntiReset Windup Cover (not shown) 81* ORing (not shown) (2 req’d) 1C853806992
36
*Recommended spare parts
1. This part is included in the Controller Repair Kit.
3. If ordering the bellows (key 71) to change the range of a gauge pressure controller, also order the appropriate bellows spring (key 104). Also order keys 101, 102, and 103 if you do not have them.
4. This part is part of the bellows assembly, key 71.
Page 37
Instruction Manual
September 2009
A
A
C1 Controllers and Transmitters
C
C
B
B
A
A
NOTE: KEYS 33 AND 74 ARE NOT SHOWN
GE26600A E1073
Figure 23. Controller Subassembly with Bourdon Tube Sensing Element
Key Description
82 Machine screw (not shown) (2 req’d) 98 Machine Screw, steel pl (4 req’d)
Gauge and differential pressure bellow instruments
99 Washer, steel pl
for Bourdon tube instruments (2 req’d) for bellows sensing instruments (4 req’d)
100 Bellows Yoke, zinc
use with gauge and differential pressure bellows
Note
Keys 101 through 105 are used for gauge pressure bellows instruments only.
101 Jam Nut, steel pl
SECTION A-A
SECTION B-B
GE33918A/IL
VIEW A-A
BOURDON TUBE TRAVEL
STOP SUBASSEMBLY
SECTION C-C
Key Description Part Number
102 Washer, steel pl 103 Spring seat, pl brass
104 Spring, steel pl 105 Label, bellows sensing instruments only
190 AntiReset Windup Ass’y
For ProportionalPlusReset Controllers only
256 Reset Restriction Valve
For proportionalplusreset controllers
w/o antireset windup 19A4361X012
For proportionalplusreset controllers
w/ antireset windup 19A4363X012
37
Page 38
Instruction Manual
C1 Controllers and Transmitters
B
B
A
A
September 2009
LINK (KEY 71M)
SCREW (KEY 71K)
BEARING (KEY 71L)
SIDE VIEW OF SUBASSEMBLY
WITH GAUGE-PRESSURE
BELLOWS SENSING ELEMENT
NOTES: KEYS 33, 46 AND 74 ARE NOT SHOWN KEY 52 IS FEEDBACK BELLOWS
1
KEYS 71K, 71L, & 71M ARE PART OF THE BELLOWS ASSEMBLY (KEY 71)
GE35161A GE34734A E1074
SECTION B-B
SECTION A-A
1
1
LINK (KEY 71M)
1
1
BEARING (KEY 71L)
1
1
SCREW (KEY 71K)
SIDE VIEW OF SUBASSEMBLY WITH DIFFERENTIAL
PRESSURE BELLOWS SENSING ELEMENT
Figure 24. Controller Subassembly with Either Gauge−Pressure Bellows or Differential−Pressure Bellows Sensing Element
38
Page 39
Instruction Manual
September 2009
SECTION B-B
SECTION A-A
COMPRESSION PLUGS
2X ROLL PIN
A
A
ATEX MARKING
C1 Controllers and Transmitters
2 PSIG LABEL USE WITH 2 PSIG CASE AND COVER ASSEMBLY (INSIDE COVER)
CHANGE ACTION LABEL (INSIDE COVER)
B
B
COVER ASSEMBLY
CASE ASSEMBLY
GE28278A E1075
Figure 25. Front View of Case and Cover Assembly

Mounting Parts for Panel, Wall, Pipestand, or Fisher Actuator Mounting (figures 2 and 3)

Key Description
Note
Contact your Emerson Process Management sales office for C1 mounting FS number.
213 Mounting Plate, steel
For yoke mounting on
470, 472, 513, 656, 657 and 667
For yoke mounting on 480
Vertical
For yoke mounting on 1051 and 1052
Size 40, positions 1 and 3 w/switch and
Size 60, position 1 w/switch
All others
Key Description
213 Mounting Plate, steel (continued)
For yoke mounting on 1061 Size 30,
positions 1 and 3 w/switch and position 1 w/o
switch, Size 40, position 1 w/switch and
Sizes 80 and 100, position 3 w/o switch
All others
For pipe stand mounting
215 Machine Screw, steel pl (specify quantity req’d)
5/16 UNC X 1 inch 5/16 UNC X 11/2 inches 5/16 UNC X 2 inches
216 Hex Nut, steel pl (specify quantity req’d)
For filter regulator mounting on
1051, 1052 and 1061
All other types and mountings
220 Mounting Bracket, steel pl (not shown)
For casing mounting and casingmounted filter
regulator on 1051 and 1052
221 Lockwasher, steel pl (specify quantity req’d)
39
Page 40
Instruction Manual
C1 Controllers and Transmitters
Key Description
222 Cap Screw, steel pl (specify quantity req’d)
5/16 UNC X 3/4 inch 5/16 UNC X 1 inch 5/16 UNC X 11/8 inches 5/16 UNC X 11/4 inches 5/16 UNC X 13/4 inches 5/16 UNC X 21/2 inches 3/8 UNF X 11/8 inches
223 Cap Screw, steel pl
1051 and 1052 with either case or
yoke mounted regulator and 1061
with yoke mounted regulator (2 req’d)
228 Spacer Spool, steel (specify quantity req’d)
470, 472, 480, 513, 656, 657, 667,
pipe stand 1051, 1052 and 1061
229 Cap Screw, steel pl (not shown) (specify quantity req’d)
1051 and 1052 casingmounted
controller
238 Mounting Plate, steel
For yokemounted filter regulator
1051, 1052 and 1062 sizes 40 and 60 1061 size 30
240 Cap Screw, steel
For yokemounted filter regulator on
1051 and 1052 sizes 40 and
60 (2 req’d)
241 Spacer Spool, steel
For yoke mounted filter regulators on
1051 and 1052 sizes 40 and 60 (2 req’d)
September 2009
Key Description
242 Spacer Spool, steel (not shown)
For yoke mounting on
1051 and 1052 size 40 (2 req’d) 1061 sizes 30, 80 and 100 (2 req’d)
243 Street Elbow, pl galvanized malleable iron (not shown)
For mounting on 470, 472, 480, 513, 656,
657, 667, panel, pipe stand, 1051, 1052 and 1061
w/nipplemounted filter regulator
244 Pipe Nipple, pl galvanized steel (not shown)
For mounting on 470, 472, 480, 513, 656,
657, panel, pipe stand, 1051, 1052 and 1061
w/nipplemounted filter regulator
250 Clamp, Steel
For pipe stand mounting (2 req’d)
251 Bracket Assembly, steel
For panel or wall mounting (2 req’d)
252 Cap Screw, steel pl
For panel or wall mounting (4 req’d)
Note
Specify quantity of fittings.
Connector, Brass
1/4 NPT X 1/4 O.D. tubing 1/4 NPT X 3/8 O.D. tubing
Elbow, Brass
1/4 NPT X 1/4 O.D. tubing 1/4 NPT X 3/8 O.D. tubing
Fisher is a mark owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. Emerson Process Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners. This product may be covered under pending patent applications.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice. Neither Emerson, Emerson Process Management, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end−user.
Emerson Process Management
Marshalltown, Iowa 50158 USA Sorocaba, 18087 Brazil Chatham, Kent ME4 4QZ UK Dubai, United Arab Emirates Singapore 128461 Singapore
www.Fisher.com
40
EFisher Controls International LLC 2008, 2009; All Rights Reserved
Loading...