Installation Sheet
Form 5879
June 2011
99 Series Gas Regulator Vent Assembly
Parts Kit Part Number R99LX000032
Introduction
99 Series
This parts kit is used to replace the existing vented
closing cap (which was obsoleted) with a new nonvented closing cap.
The parts kit for the Type 99 low-pressure pilot
consists of the following parts:
Key Description Part Number
46 Plastic closing cap T11069X0012
60 Type Y602-12 Vent Assembly 27A5516X012
WARNING
!
Avoid personal injury or damage
to property from sudden release of
pressure or uncontrolled gas or other
process uid. Before starting to
disassemble, isolate the pilot or regulator
from all pressure and cautiously release
trapped pressure from the pilot or
regulator. Use gauges to monitor inlet,
loading, and outlet pressures while
releasing these pressures.
To avoid possible personal injury on
a pressure-loaded low-pressure pilot
without handwheel, carefully release
pressure from the spring case by slowly
removing the closing cap. Otherwise
trapped loading pressure could
forcefully eject the freed closing cap.
For the following key number locations, refer to
Figure 1 on the back of this Installation sheet.
Replace the metal closing cap (key 46) with the new
plastic closing cap. Remove the pipe plug (key 60)
and replace it with the new vent assembly.
To remotely vent a low-pressure pilot, remove the
vent assembly from the spring case and install
obstruction-free tubing or piping into the 1/4 NPT
vent tapping. Provide protection on a remote vent
by installing a screened vent cap into the remote
end of the vent pipe.
www.sherregulators.com
D300913X012

99 Series
152
32
58
57
6
10
56
54
8
53
DJ6642
L.S.
23
1
A.S.
A.S.
13
L.S.
L.S.
47
39
42
43
69
154
71
A.S.
45
44 41
46
4
2
L.S.
60
3
5
7
9
11
2812
M.K.
55
1/4 NPT VENT LOCATION SHOWN 90°
COUNTERCLOCKWISE FROM NORMAL
L.S.
29
75
40
15
34
27
17
A.S.
14
26
18
L.S.
25
16
20
22
23
21
24
19
Figure 1. Type 99 Regulator with Low-Pressure Pilot
Industrial Regulators
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Shanghai 201206, China
Tel: +86 21 2892 9000
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Middle East and Africa
Dubai, United Arab Emirates
Tel: +971 4811 8100
For further information visit www.sherregulators.com
The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher is a mark owned by Fisher Controls, Inc., a
business of Emerson Process Management.
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or
guarantees, express or implied, regarding the products or services described herein or their use or applicability. We reserve the right to modify or improve the designs or specications of such
products at any time without notice.
Emerson Process Management does not assume responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use and maintenance of any Emerson
Process Management product remains solely with the purchaser.
Natural Gas Technologies
Emerson Process Management
Regulator Technologies, Inc.
USA - Headquarters
McKinney, Texas 75069-1872, USA
Tel: +1 800 558 5853
Outside U.S. +1 972 548 3574
Asia-Pacic
Singapore 128461, Singapore
Tel: +65 6770 8337
Europe
Bologna 40013, Italy
Tel: +39 051 419 0611
Gallardon 28320, France
Tel: +33 2 37 33 47 00
TESCOM
Emerson Process Management
Tescom Corporation
USA - Headquarters
Elk River, Minnesota 55330-2445, USA
Tels: +1 763 241 3238
+1 800 447 1250
Europe
Selmsdorf 23923, Germany
Tel: +49 38823 31 287
Asia-Pacic
Shanghai 201206, China
Tel: +86 21 2892 9499
©Emerson Process Management Regulator Technologies, Inc., 1996, 2011; All Rights Reserved