Installation Guide
D103060X014
English – December 2012
Type 6392
Introduction
This installation guide provides instructions for installation, startup,
and adjustment. To receive a copy of the instruction manual, contact
your local Sales Office or view a copy at www.fisher.com. For further
information refer to: Type 92C Instruction Manual, D100255X012.
PED Categories
This product may be used as a safety accessory with pressure
equipment in the following Pressure Equipment Directive categories. It
may also be used outside of the Pressure Equipment Directive using
sound engineering practice (SEP) per table below. For information on
the current PED revision see Bulletin: D103053X012.
PRODUCT SIZE CATEGORIES FLUID TYPE
1/4 NPT SEP 1
Specifications
Maximum Inlet and Outlet Pressures
Cast Iron Construction: 17.2 bar / 250 psig
Steel Construction: 20.7 bar / 300 psig
Outlet Pressure Ranges
See Table 1
Proof Test Pressure
All Pressure Retaining Components have been proof tested
per Directive.
Temperature Capabilities
Cast Iron Construction: 208°C / 406°F
Steel and Stainless Steel Construction: 260°C / 500°F
Optional High Temperature Steel and Stainless Steel Body:
343°C / 650°F
(1)
(1)
(1)
Installation
WARNING
!
Only qualified personnel should install or service
a regulator. Regulators should be installed,
operated and maintained in accordance with
international and applicable codes and regulations
and Emerson Process Management Regulator
Technologies, Inc. instructions.
If the regulator vents fluid or a leak develops in the
system, it indicates that service is required. Failure
to take the regulator out of service immediately
may create a hazardous condition.
Personal injury, equipment damage or leakage
due to escaping fluid or bursting of pressurecontaining parts may result if this regulator
is overpressured or is installed where service
conditions could exceed the limits given in the
Specifications section, or where conditions
exceed any ratings of the adjacent piping or
piping connections.
Table 1. Outlet Pressure Ranges
SPRING USAGE
Standard use up to 500°F / 260°C
High Pressure and/or High Temperature
over 500°F / 260°C
To avoid such injury or damage, provide pressurerelieving or pressure-limiting devices (as required
by the appropriate code, regulation or standard) to
prevent service conditions from exceeding limits.
Additionally, physical damage to the regulator
could result in personal injury and property
damage due to escaping fluid. To avoid such injury
and damage, install the regulator in a safe location.
Clean out all pipelines before installation of the regulator and check
to be sure the regulator has not been damaged or has collected
foreign material during shipping. For NPT bodies, apply pipe
compound to the external pipe threads. For flanged bodies, use
suitable line gaskets and approved piping and bolting practices.
Install the regulator in any position desired, unless otherwise
specified, but be sure flow through the body is in the direction
indicated by the arrow on the body.
It is important that the regulator be installed
so that the vent hole in the spring case
is unobstructed at all times. For outdoor
installations, the regulator should be located away
from vehicular traffic and positioned so that water,
ice and other foreign materials cannot enter the
spring case through the vent. Avoid placing the
regulator beneath eaves or downspouts, and be
sure it is above the probable snow level.
OUTLET PRESSURE RANGE
bar psig
0.34 to 4.8 5 to 70
1.4 to 10.3 20 to 150
1.0 to 6.9 15 to 100
5.5 to 17.2 80 to 250
Note
Overpressure Protection
The recommended pressure limitations are stamped on the
regulator nameplate. Some type of overpressure protection is
needed if the actual inlet pressure exceeds the maximum operating
outlet pressure rating. Overpressure protection should also be
provided if the regulator inlet pressure is greater than the safe
working pressure of the downstream equipment.
Regulator operation below the maximum pressure limitations does
not preclude the possibility of damage from external sources or
debris in the line. The regulator should be inspected for damage
after any overpressure condition.
Startup
The regulator is factory set at approximately the midpoint of the
spring range or the pressure requested, so an initial adjustment
may be required to give the desired results. With proper installation
completed and relief valves properly adjusted, slowly open the
upstream and downstream shutoff valves.
1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.

Type 6392
Adjustment
To change the outlet pressure, remove the closing cap or loosen
the locknut and turn the adjusting screw clockwise to increase outlet
pressure or counterclockwise to decrease pressure. Monitor the
outlet pressure with a test gauge during the adjustment. Replace the
closing cap or tighten the locknut to maintain the desired setting.
Taking Out of Service (Shutdown)
WARNING
!
To avoid personal injury resulting from sudden
release of pressure, isolate the regulator from all
pressure before attempting disassembly.
Parts List
Type 6392
Key Description
1 Pilot Body
2 Spring Case
3 Orice
4 Valve Plug
5 Valve Plug Guide
6 Stem Assembly
7 Diaphragm
8* Diaphragm Gasket
9 Lower Spring Seat
10 Stem Guide Bushing
11 Valve Plug Spring
12 Strainer Screen
13 Control Spring
14 Upper Spring Seat
15 Jam Nut
16 Adjusting Screw
17 Cap Screw
18 Nameplate
19 Drive Screw
26 Valve Plug Cap
16
2
14
13
17
7
1
10
6
3
12
E0100
16A1520-B
APPLY LUBRICANT/SEALANT:
L = ANTI-SEIZE LUBRICANT
S = ANTI-SEIZE COMPOUND
15
L
18
19
9
8
L
26
4
S
11
5
Figure 1. Type 6392 Assembly
*Recommended spare part.
Webadmin.Regulators@emerson.com
Fisher.com
Emerson Automation Solutions
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574
Europe
Bologna 40013, Italy
T +39 051 419 0611
For further information on the current
PED revision see Bulletin: D103053X012
or scan the QR code.
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
Asia Pacic
Singapore 128461, Singapore
T +65 6777 8211
Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
D103060X014 © 2002, 2018 Emerson Process Management Regulator
Technologies, Inc. All rights reserved. 08/18.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. All other marks are the property of their prospective owners.
Fisher™ is a mark owned by Fisher Controls International LLC, a
business of Emerson Automation Solutions.
The contents of this publication are presented for information purposes
only, and while effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied,
regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which
are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not
assume responsibility for the selection, use or maintenance of any
product. Responsibility for proper selection, use and maintenance of any
Emerson Process Management Regulator Technologies, Inc. product
remains solely with the purchaser.