This installation guide provides instructions for
installation, startup and adjustment. To receive a copy of
the instruction manual, contact your local Sales Ofce or
view a copy at www.sher.com. For further information
refer to: 133 Series Instruction Manual, D100270X012.
P.E.D. Category
This product may be used as a safety accessory with
pressure equipment in the following Pressure Equipment
Directive categories. It may also be used outside of the
Pressure Equipment Directive using sound engineering
practice (SEP) per table below.
For information on the
current PED revision see Bulletin: D103053X012.
PRODUCT SIZECATEGORIESFLUID TYPE
DN 50 / NPS 2I1
Specications
Available Constructions
Type 133H: High pressure construction for
outlet pressure range of 0.10 to 0.69 bar / 1.5 to
10 psig. The Type 133H can also use the 5 mbar
to 0.14 bar / 2 in. w.c. to 2 psig springs of the
Type 133L. The maximum operating inlet pressure
is 4.1 bar / 60 psig with a maximum emergency inlet
pressure of 8.6 bar / 125 psig.
Type 133HP: Extra high pressure construction for
outlet pressure range of 0.14 to 4.1 bar / 2 to 60 psig.
The maximum operating inlet pressure rating of
10.3 bar / 150 psig with a maximum emergency inlet
pressure of 10.3 bar / 150 psig.
Type 133L: Low pressure construction for outlet
pressure range of 5 mbar to 0.14 bar / 2 in. w.c. to
2 psig. The maximum operating inlet pressure is
4.1 bar / 60 psig with a maximum emergency inlet
pressure of 8.6 bar / 125 psig.
Type 133Z: Zero gravity governor construction for
outlet pressure range of -2 to 10 mbar / -1 to 4 in. w.c.
The maximum operating inlet pressure is 1.4 bar /
20 psig with a maximum emergency inlet pressure of
8.6 bar / 125 psig.
Body Size and End Connection Styles
BODY SIZEBODY MATERIAL
DNIn.Cast Iron BodyWCC Steel Body
502NPT or CL125 FF FlangedNPT or CL150 RF Flanged
Outlet Pressure Ranges
See Table 1
Maximum Inlet and Outlet Pressures
See Table 2
Proof Test Pressure
All Pressure Retaining Components have been proof
tested per Directive
(1)
(1)
Temperature Capabilities
(1)
-29 to 66°C / -20 to 150°F
Control Line Connection
Types 133H, 133L and 133Z: 3/4 NPT (internal)
connection will be positioned directly over body
outlet (standard position) or 90 degrees right or left of
standard position if specified
Type 133HP: 1/4 NPT (internal) connection positioned
directly over body outlet
Installation
WARNING
!
Only qualied personnel should install
or service a regulator. Regulators should
be installed, operated and maintained
in accordance with international and
applicable codes and regulations and
Emerson Process Management Regulator
Technologies, Inc. instructions.
If the regulator vents uid or a leak
develops in the system, it indicates that
service is required. Failure to take the
regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage or
leakage due to escaping uid or bursting of
pressure-containing parts may result if this
regulator is overpressured or is installed
where service conditions could exceed the
limits given in the Specications section or
where conditions exceed any ratings of the
adjacent piping or piping connections.
To avoid such injury or damage, provide
pressure-relieving or pressure-limiting
devices (as required by the appropriate
code, regulation or standard) to prevent
service conditions from exceeding limits.
Additionally, physical damage to the
regulator could result in personal injury
and property damage due to escaping
uid. To avoid such injury and damage,
install the regulator in a safe location.
Clean out all pipelines before installation of the
regulator and check to be sure the regulator has not
been damaged or has collected foreign material during
shipping. For NPT bodies, apply pipe compound to the
external pipe threads. For flanged bodies, use suitable
line gaskets and approved piping and bolting practices.
Install the regulator in any position desired, unless
otherwise specified, but be sure flow through the body is
in the direction indicated by the arrow on the body.
1. The pressure/temperature limits in this installation guide and any applicable standard or code limitation should not be exceeded.
133 Series
Table 1. 133 Series Outlet Pressure Ranges
TYPE
(1)
133H
(1)
133HP
(1)
and 133H
133L
133Z
1. Pressure ranges shown are correct if the regulator is installed with the actuator portion above the body portion. If the regulator is installed with the actuator portion below the body, the
pressure ranges will be lowered by approximately 5 mbar / 2 in. w.c. for the Type 133L and by approximately 7 mbar / 3 in. w.c. for the Types 133H and 133Z.
2. If the 5 mbar to 0.14 bar / 2 in. w.c. to 2 psig springs (all 6 ranges) are used in the Type 133H, the pressure ranges will increase by approximately 2 mbar / 1 in. w.c. due to the weight of the
Type 133H parts (assuming that the actuator is installed above the body).
(2)
(1)
barpsig
0.10 to 0.21
0.14 to 0.34
0.34 to 0.69
0.14 to 0.34
0.31 to 0.69
0.41 to 1.4
1.1 to 2.1
1.8 to 2.8
2.5 to 3.4
3.1 to 4.1
5 to 10 mbar
9 to 15 mbar
12 to 22 mbar
21 to 45 mbar
35 to 70 mbar
0.05 to 0.14
-3 to 3 mbar-1 to 1 in. w.c.
0 to 10 mbar0 to 4 in. w.c.
Note
It is important that the regulator be installed
so that the vent hole in the spring case
is unobstructed at all times. For outdoor
installations, the regulator should be located
away from vehicular trafc and positioned
so that water, ice and other foreign materials
cannot enter the spring case through the
vent. Avoid placing the regulator beneath
eaves or downspouts and be sure it is above
the probable snow level.
OUTLET PRESSURE RANGE
1.5 to 3
2 to 5
5 to 10
2 to 5
4.5 to 10
6 to 20
16 to 30
26 to 40
36 to 50
45 to 60
2 to 4 in. w.c.
3.5 to 6 in. w.c.
5 to 9 in. w.c.
8.5 to 18 in. w.c.
14 to 28 in. w.c.
0.75 to 2
must be taken when placing the 133 Series
in service. The outlet of the regulator must
never be subjected to pressures higher
than the inlet pressure or the balancing
diaphragm may be damaged. Also, the
control line pressure must never exceed
the set point dictated by the spring setting
by more than 0.21 bar / 3 psig or the valve
seat or diaphragm plates can be damaged.
The regulator is factory set at approximately the midpoint
of the spring range or the pressure requested, so an
initial adjustment may be required to give the desired
Overpressure Protection
The recommended pressure limitations are stamped on
the regulator nameplate. Some type of overpressure
protection is needed if the actual inlet pressure
exceeds the maximum operating outlet pressure rating.
Overpressure protection should also be provided if the
regulator inlet pressure is greater than the safe working
pressure of the downstream equipment.
Regulator operation below the maximum pressure
limitations does not preclude the possibility of damage from
external sources or debris in the line. The regulator should
be inspected for damage after any overpressure condition.
Startup
results. With proper installation completed and relief
valves properly adjusted, slowly open the upstream and
downstream shutoff valves.
Adjustment
To change the outlet pressure, remove the closing cap or
loosen the locknut and turn the adjusting screw clockwise
to increase outlet pressure or counterclockwise to
decrease pressure. Monitor the outlet pressure with a test
gauge during the adjustment. Replace the closing cap or
tighten the locknut to maintain the desired setting.
Taking Out of Service (Shutdown)
WARNING
!
CAUTION
To avoid personal injury resulting from
If the downstream system is already
pressured by another regulator or by a
manual bypass, then extra precautions
sudden release of pressure, isolate
the regulator from all pressure before
attempting disassembly.
2
133 Series
Table 2. Maximum Inlet and Outlet Pressures
TYPE NUMBER
PRESSURES
Maximum Operating Inlet Pressure4.160
Maximum Emergency Inlet Pressure8.61258.61258.6125
The contents of this publication are presented for information purposes
only, and while effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied,
regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which
are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not
assume responsibility for the selection, use or maintenance of any
product. Responsibility for proper selection, use and maintenance of any
Emerson Process Management Regulator Technologies, Inc. product
remains solely with the purchaser.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.