FISCHER ME49F Series Operating Manual

d e v elopi n g s o l u t i o n s
*09005231*
BA_EN_ME49F
08/18
*09005231*
Table of contents
1 Safety instructions 2 Application purpose 3 Product and function description 4 Installation and assembly 5 Start-up 6 Maintenance 7 Transportation 8 Service 9 Accessories 10 Waste disposal 11 Technical Data 12 Dimensional drawings 13 Order codes 15 Attachments
1 Safety instructions
1.1 General
This operating manual contains instruc­tions fundamental to the installation, operation and maintenance of the device
that must be observed unconditionally. It must be read by the assembler, operator and the specialized personnel in charge of the instrument before it is installed and put into operation. This operating manual must always be accessible at the place of installation.
The subsequent sections on general safety instruc­tions 1.2 - 1.7 as well as the following special instructions ranging from intended use to disposal 2-10 contain important safety instructions the non­observance of which can cause danger to persons, animal and physical objects.
1.2 Personnel Qualification
The instrument may only be installed and commis­sioned by specialized personnel familiar with the installation, commissioning and operation of this product.
Specialized personnel are persons who can assess the work they have been assigned and recognize
potential dangers by virtue of their specialized training, their skills and experience and their knowledge of the pertinent standards.
For explosion-proof models the specialized person­nel must have received special training or instruc­tion or be authorized to work with explosion-proof instruments in explosion hazard areas.
1.3 Risks due to Non-Observance of Safe­ty Instructions
Non-observance of these safety instructions, the intended use of the device or the limit values given in the technical specifications can be hazardous or cause harm to persons, the environment or the plant itself. Fischer Mess- und Regeltechnik GmbH will not be liable for damage claims if this should happen.
1.4 Safety Instructions for the Operating Company and the Operator
The safety instructions governing correct operation of the instrument must be observed. The operating company must make them available to the installa­tion, maintenance, inspection and operating personnel. Dangers arising from electrical components, energy
Operating Manual
ME49F
Pressure Transmitter
for applications in explosive areas According to ATEX Directive 2014/34/EU
Gas explosion protection zone 1
2 | 20 Page
discharged by the medium, escaping medium and incorrect installation of the instrument must be eliminated. For more information, please see the applicable national and international regulations, such as DIN, EN, accident prevention regulations (UVV) and - for industry-specific individual applica­tions - also in the industry guidelines issued by the DVWG, Ex, GL, etc. as well as VDE and local EVUs.
The instrument must be decommissioned and secured against inadvertent re-operation if a situa­tion arises in which it must be assumed that safe operation is no longer possible. Reasons for this assumption could be:
evident damage to the instrument failure of the electrical circuits long storage in temperatures over 85°C considerable strain due to transport
Repairs may be carried out by the manufacturer only.
A professional single conformity inspection as per DIN EN 61010, section 1, must be carried out before the instrument can be re-commissioned. This inspection must be performed at the manufac­turer's location. Correct transport and storage of the instrument are required.
1.5 Unauthorised Modification
Modifications of or other technical alterations to the instrument by the customer are not permitted. This also applies to replacement parts. Any modifica­tions/alterations required will be carried out by Fischer Mess- und Regeltechnik GmbH only.
1.6 Impermissible modes of operation
The operational safety of this instrument can only be guaranteed if it is used as intended. The instru­ment model must be suitable for the medium used in the system. The limit values given in the technical data may not be exceeded.
1.7 Safe working practices for mainte­nance and installation work
The safety instructions given in this operating manual, any nationally applicable regulations on accident prevention and any of the operating com­pany's internal work, operating and safety guide­lines must be observed.
The operating company is responsible for ensuring that all required maintenance, inspection and instal­lation work is carried out by qualified specialized personnel.
1.8 Pictogram explanation
WARNING!
… indicates a potentially dangerous
situation, non-observance of which could endanger persons, animals, the environment or objects.
INFORMATION!
… highlights important information
efficient and smooth operation.
TIP!
… indicates recommendations that are
not specifically necessary in certain situations but which could be useful.
2 Application purpose
The two-line pressure transmitter ME49F* serves precise recording of a pressure with a resistance pressure cell in the ex-area.
The supply circuit on terminals 1 and 2 must correspond to ignition protection type 'Inherent safety' of category 'ib'.
The units are may only be used for the purpose defined by the manufacturer in the data sheet or operating instructions.
The maximum allowed temperature range from -20°C to +60°C may not be exceeded.
If there is dirty or aggressive media in the system, or if this is to be expected, the device must be modified in terms of those parts that come into contact with the media. Please talk to the manufac­turer first before ordering.
The corresponding setup regulations are to be considered for each application case.
Designation as per guideline 2014/34/EU
II 2G Ex ib IIC T6 Gb
3 | 20 Page
3 Product and function description
3.1 Function diagram
3.2 Design and mode of operation
The measuring pressure acts on a ceramic mem­brane that deforms when under pressure.
The output signal on the measurement bridge attached to rear of the membrane changes when the membrane deforms.
Electronics integrated into the pressure transmitter housing converts the sensor signal into an electron­ic uniform signal 4...20mA um.
4 Installation and assembly
As standard, the unit has a cylindrical pipe thread and flat seal for screwing into the screw holes.
Wall assembly is possible when the wall holder MZ310* is used.
The manometer screw connections MZ27* allow pipes to be connected directly.
The device is set ex-works for vertical installation, however any installation position is possible. In installation positions that vary from the vertical, the zero-point can be corrected using the installed zero­point potentiometer (5.1).
To guarantee safe working conditions during instal­lation and maintenance, suitable stop valves must be fitted in the system. The shutoff valves of the Fischer series MZ5* make it possible to
depressurize or decommission the unit, or to disconnect it from the power supply within
the applicable system for repairs or inspections
or to check the functions of the unit on site.
Thanks to their venting screws, the shut-off valves allow the connected pipe system to be vented.
4.1 Process connection
Dangers caused by pressure on the instrument are to be prevented with suitable measures.
By authorized and qualified specialized person-
nel only.
Only for the designated mechanical process
connection - for the model, see the order code on the device type plate.
The pipes need to be depressurized when the
device is being connected.
Appropriate steps must be taken to protect the
device from pressure surges.
Check the suitability of the device for the media
to be measured.
Observe the maximum pressure. The pressure measuring line must be installed
on a gradient so that no air pockets e.g. for liq­uid measurements or water pockets e.g. for gas measurements can be created. If the required incline is not reached, water and/or air filters need to be installed at suitable points.
The pressure sensing lines need to be kept as
short as possible and installed without sharp bends to avoid interfering delay times.
4.2 Pressure surge absorption
Dangers caused by pressure on the instrument are to be prevented with suitable measures.
Pulsating pressure on the system side can lead to functional problems. As a protective measure, we recommend the installation of damping elements in the pressure connection lines.
1
3
2
4
1
Connecting shanks
2
Measuring cell
3
O-ring
4
Transformation
MZ290*
MZ310*
Sealing disc MZ290*
ME49F*
4 | 20 Page
4.2.1 For gas-like media
Fig. 1 Damping reactor MZ41*
When operational, set the throttle needle so that the output signal is settled as required.
4.2.2 In the case of fluid media
Fig. 2 Capillary throttle coils MZ40*
4.3 Electrical connections
The ME49F* is an intrinsically-safe piece of equipment for use in potentially explo­sive areas. For connection of the intrinsi­cally safety supply current circuit, the
details in the type approval certificate apply.
For ex-operations, observe the electrical data of
the EC type examination certificate (see at­tachment) and the local applicable regulations and guidelines for the installation and operation of electrical installations in potentially explosive areas.
By authorized and qualified specialized person-
nel only.
Disconnect the system from the mains before
connecting the device.
Add a fuse adapted to the energy requirements.
5 Start-up
All electrical supply, operating and measuring
lines and the pressure connections must have been correctly installed before commissioning. All supply lines are arranged so that there are no mechanical forces acting on the device.
Check that the pressure connections do not
leak before commissioning.
ME49F*
MZ41*
MZ40*
ME49F*
Output
Net-
Power Rail
certified, intrinsi-
cally-safe
power unit
Pressure transmitter ME49F
Ex-area
Not ex
-area
5 | 20 Page
5.1 Zero point and measuring range ad­justment
Please note that adjustments can only be carried out in ex-free zone.
The pressure transmitters are set in the factory before delivery so that they do not usually need to be adjusted at the assembly site. If the output signal does need to be adjusted, this can be undertaken using the 'S' and 'N' potentiometers.
The potentiometers can be accessed by unscrew­ing the lid of the housing. The unit is connected to the power supply as shown on the wiring diagram and also, an ammeter is connected between the pressure transmitter and the auxiliary energy source.
Fig. 3 Measuring switch
Fig 4 Setting potentiometer
5.2 Adjustment sequence:
Switch on auxiliary energy Depressurize the measuring system: p = 0 Display for std. measuring ranges = 4.0 mA In the case of any deviations, the output signal
of the pressure transmitter shown by the am­meter can be corrected with the zero-point po­tentiometer (N).
Set the pressure in the measuring system to
the measuring range end value (e.g. pressure is generated by means of a manual pump and pressure compensation unit) Display 20 mA. In case of differences, correct by adjusting the voltage potentiometer (S).
Then check the zero-point and measuring
range again; correct if necessary.
6 Maintenance
The instrument is maintenance-free. We recommend checking the instrument at regular
intervals to ensure reliable operation and a long service life.
Inspecting the output signal. Check the leak-tightness of the pressure con-
nection lines.
Check the electrical connection (cable clamp
connections).
The precise test cycles and operating and ambient conditions need to be adjusted. If various instru­ment components interact, the operating instruc­tions of all the other instruments also need to be observed.
7 Transportation
The measuring device must be protected against impacts. It may only be transported in packaging specifically intended for transport.
8 Service
All defective or faulty devices should be sent direct­ly to our repair department. We would ask you to please coordinate all return shipments with our
sales department so that we can ensure careful processing of all faulty devices for our customers.
Process media residues in and on dismantled devices can be a hazard to people, animals and the environment. Take adequate preventive measures. If required, the devices must be cleaned thoroughly.
9 Accessories
Not planned
10 Waste disposal
For the sake of the environment ....
Please help to protect our environ­ment and dispose of or recycle used instruments as stipulated by the applicable regulations.
Auxiliary energy
Apparent ohmic resistance Span
Zero point
Ampere meter
6 | 20 Page
11 Technical Data
Measuring range
40 mbar
60 mbar
100 mbar
160 mbar
250 mbar
400 mbar
600 mbar
1 bar
Overpressure-proof
4 bar
4 bar
4 bar
6 bar
6 bar
6 bar
10 bar
4 bar
Measuring range
1.6 bar
2.5 bar
4 bar
6 bar
10 bar
16 bar
25 bar
40 bar
Overpressure-proof
4 bar
8 bar
8 bar
12 bar
32 bar
32 bar
60 bar
60 bar
Ambient conditions
Admissible ambient temperature
-20° to +60°C
Permissible medium temperature
-20° to +60°C
Admissible storage temperature
-30° to +70°C
Electrical data
Rated Voltage
24 V DC
Allowed operating voltage Ub
15 … 30 V DC
Limit value of the supply power circuit
Voltage Ui
30 V
Current Ii
100 mA
Output Pi
≤ 750 mW
effective inner capacity Ci
15 nF
effective inner inductivity Li
90 mH
Capacity between the power circuit and housing.
2.2 nF
Output signal
4... 20 mA
Electrical connection type
Two-wire
Load at rated voltage
450
Apparent ohmic resistance
RL [] (Ub-15 V) / 0.02 A
Current/voltage limit
ca. 30 mA
Temperature drift, zero-point
0.4 % FS/10 K
Temperature drift, measuring range
0.05 % FS/10 K
Linearity
± 0.5% of the measuring range
Hysteresis
<0.1% of the measuring range
Connection, materials, assembly
Discharge port
Connection shank G1/2B acc. to DIN EN 837
Electrical connection
Inside screw terminal, cable screw connection M16 x 1.5
Protection
IP 65 acc. to DIN EN 60529
Materials of parts that come into contact with the
medium
Chromium nickel steel 1.4571, ceramic, FPM
Casing material
Aluminium, painted
Assembly
Tap of sleeve assembly acc. to DIN EN 837
Wall assembly using the wall holder MZ310* and manometer adapter MZ290*
Manometer screw connections MZ27* allow pipes to be connected directly
Identification
0044 II 2G Ex ib IIC T6 Gb
EC Examination Certificate
BVS 03 ATEX E 414
Loading...
+ 14 hidden pages