3 | 20 Page
3 Product and function description
3.1 Function diagram
3.2 Design and mode of operation
The measuring pressure acts on a ceramic membrane that deforms when under pressure.
The output signal on the measurement bridge
attached to rear of the membrane changes when
the membrane deforms.
Electronics integrated into the pressure transmitter
housing converts the sensor signal into an electronic uniform signal 4...20mA um.
4 Installation and assembly
As standard, the unit has a cylindrical pipe thread
and flat seal for screwing into the screw holes.
Wall assembly is possible when the wall holder
MZ310* is used.
The manometer screw connections MZ27* allow
pipes to be connected directly.
The device is set ex-works for vertical installation,
however any installation position is possible. In
installation positions that vary from the vertical, the
zero-point can be corrected using the installed zeropoint potentiometer (5.1).
To guarantee safe working conditions during installation and maintenance, suitable stop valves must
be fitted in the system. The shutoff valves of the
Fischer series MZ5* make it possible to
depressurize or decommission the unit,
or to disconnect it from the power supply within
the applicable system for repairs or inspections
or to check the functions of the unit on site.
Thanks to their venting screws, the shut-off valves
allow the connected pipe system to be vented.
4.1 Process connection
Dangers caused by pressure on the instrument are
to be prevented with suitable measures.
By authorized and qualified specialized person-
nel only.
Only for the designated mechanical process
connection - for the model, see the order code
on the device type plate.
The pipes need to be depressurized when the
device is being connected.
Appropriate steps must be taken to protect the
device from pressure surges.
Check the suitability of the device for the media
to be measured.
Observe the maximum pressure.
The pressure measuring line must be installed
on a gradient so that no air pockets e.g. for liquid measurements or water pockets e.g. for gas
measurements can be created. If the required
incline is not reached, water and/or air filters
need to be installed at suitable points.
The pressure sensing lines need to be kept as
short as possible and installed without sharp
bends to avoid interfering delay times.
4.2 Pressure surge absorption
Dangers caused by pressure on the instrument are
to be prevented with suitable measures.
Pulsating pressure on the system side can lead to
functional problems. As a protective measure, we
recommend the installation of damping elements in
the pressure connection lines.