FISCHER ME01 Series Data Sheet And Operating Manual

d e v e l oping s o l u t i o n s
*09005086* DB_BA_EN_ME01_R Rev.A 12/16
*09005086*
Data Sheet and Operating Manual
ME01
Digital manometer
ME01 ## # 87 # HL R####
Gas explosion protection zone 2
Table of Contents
1 Safety guidelines 2 Application purpose 3 Product and function description 4 Installation and assembly 5 Commissioning 6 Maintenance 7 Transportation 8 Service 9 Accessories 10 Waste disposal 11 Technical Data 12 Dimensional drawings 13 Order Codes 14 Attachments

1 Safety guidelines

1.1 General Information

This operating manual contains instruc­tions fundamental to the installation, op­eration and maintenance of the device
that must be observed unconditionally. It must be read by the assembler, operator and the specialized personnel in charge of the instrument before it is installed and put into operation. This op­erating manual must always be accessible at the place of installation.
The subsequent sections on general safety instruc­tions 1.2 - 1.7 as well as the following special in­structions ranging from intended use to disposal 2­10 contain important safety instructions the non­observance of which can cause danger to persons, animal and physical objects.

1.2 Personnel Qualification

The instrument may only be installed and commis­sioned by specialized personnel familiar with the in­stallation, commissioning and operation of this product.
Specialized personnel are persons who can assess the work they have been assigned and recognize potential dangers by virtue of their specialized train-
ing, their skills and experience and their knowledge of the pertinent standards.
For explosion-proof models the specialized person­nel must have received special training or instruc­tion or be authorized to work with explosion-proof instruments in explosion hazard areas.
1.3 Risks due to Non-Observance of Safe­ty Instructions
Non-observance of these safety instructions, the in­tended use of the device or the limit values given in the technical specifications can be hazardous or cause harm to persons, the environment or the plant itself. The supplier of the equipment will not be liable for damage claims if this should happen.

1.4 Safety Instructions for the Operating Company and the Operator

The safety instructions governing correct operation of the instrument must be observed. The operating company must make them available to the installa­tion, maintenance, inspection and operating per­sonnel. Dangers arising from electrical components, energy discharged by the medium, escaping medi­um and incorrect installation of the instrument must be eliminated. The particulars can be found in the respective regulations such as DIN, EN, explosion hazard,
WARNING!
… indicates a potentially dangerous
situation, non-observance of which could endanger persons, animals, the environment or objects.
INFORMATION!
… highlights important information ef­ficient and smooth operation.
TIP!
… indicates recommendations that are
not specifically necessary in certain situations but which could be useful.
accident prevention regulations and also in the in­dustry guidelines issued by the DVWG, GL, etc. and the VDE as well as the local EVUs.
The instrument must be decommissioned and se­cured against inadvertent re-operation if a situation arises in which it must be assumed that safe opera­tion is no longer possible. Reasons for this assump­tion could be:
evident damage to the instrument
failure of the electrical circuits
long storage in temperatures over 85°C
considerable strain due to transport
Repairs may be carried out by the manufacturer on­ly.
A professional single conformity inspection as per DIN EN 61010, section 1, must be carried out be­fore the instrument can be re-commissioned. This inspection must be performed at the manufacturer's location. Correct transport and storage of the in­strument are required.

1.5 Unauthorised Modification

Modifications of or other technical alterations to the instrument by the customer are not permitted. This also applies to replacement parts. Any modifica­tions/alterations required will be carried out by Fischer Mess- und Regeltechnik GmbH only.

1.6 Impermissible modes of operation

The operational safety of this instrument can only be guaranteed if it is used as intended. The instru­ment model must be suitable for the medium used in the system. The limit values given in the technical data may not be exceeded.
1.7 Safe working practices for mainte­nance and installation work
The safety instructions given in this operating man­ual, any nationally applicable regulations on acci­dent prevention and any of the operating company's internal work, operating and safety guidelines must be observed.
The operating company is responsible for ensuring that all required maintenance, inspection and instal­lation work is carried out by qualified specialized personnel.

1.8 Explanation of symbols

2 Application purpose

Electronic manometer for measuring over-pressure and under-pressure of fluid and gas-like measuring substances. The device is to be exclusively used for the applications agreed between the manufacturer and the user.
Explosion hazard area classification
The digital manometers ME01 are suitable for use as 'Electrical equipment for use in areas with com­bustible gases', zone 2.
Designation as per guideline 2014/34/EU
II 3G Ex nA IIC T4

3 Product and function description

3.1 Design and mode of operation

A ceramic measuring cell acts as the pressure transducer. The high resistance of the ceramic ma­terials that are used allow use even for aggressive media. There is a resistance measuring bridge at­tached to the side of the measuring diaphragm that faces away from the medium. When pressure is ex­erted, the membrane distorts in the elastic range. t the same time, the resistance values of the bridge change proportionally to the measuring pressure. These values are implemented and displayed by the installed electronics. There are electrical uni­form signals 0/4…20 mA and 0…10 V in a 3-wire system available for remote transmission.
Three-conductor circuit
output Signal
Operating voltage

4 Installation and assembly

As standard, the device with the connecting port for connection to pipes and other connection parts, such as the welding sleeve, union nut with soldering and welding nipples, is equipped with soldering and welding nipples (see data sheet MZ...). It can be mounted to a wall using the wall bracket (see data sheet MZ...). Manometer screw connections for 10, 8, 6 mm dia. pipes can be supplied for connection to pipes.The enclosure protection type IP 65 is only guaranteed, if a suitable power supply cable is used.

4.1 Process connection

By authorized and qualified specialized person- nel only.
Only for the designated mechanical process connection - for the model, see the order code on the device type plate.
The pipes need to be depressurized when the device is being connected.
Do not mount the device against existing water columns, and secure suitably against pressure surges.
Use only with media suitable for operation.
Observe the maximum pressure.
Check that the pressure connections do not
leak before commissioning.

4.2 Electrical connection

By authorized and qualified specialized person- nel only.
Disconnect the system from the mains before connecting the device.
Do not take out the connecting plug while ener- gized
Explosion protection instructions
To guarantee safe operation of the in­strument, the supply circuit must satisfy the requirements for zone 2, category 3,
and the locally applicable regulations and guidelines for the installation and operation of electrical systems in explosion hazard areas (e.g. EN 60079-0).

4.3 Wiring diagram

Do not take out the connecting plug while energized
Static electricity
The case must be equipped with an earth connection to reduce the surface resistance.

5 Commissioning

All electrical supply, operating and measuring lines, and the pressure connections must have been correctly installed before commissioning. All supply lines are arranged so that there are no mechanical forces acting on the device.
If liquid measuring media are used the pressure connection line must be vented, as liquid col­umns of different heights in the pipes can cause measuring errors. The instrument must be pro­tected against frost if water is used as a medi­um.
The pressure sensing lines must be installed on an incline so that no condensation pools can form.
The pressure sensing lines need to be kept as short as possible and installed without sharp bends to avoid interfering delay times.
Appropriate shutoff valves must be provided to ensure safety during installation, maintenance and inspection
The supply voltage may not exceed 30 V DC. The supply circuit must be protected by a slow 200 mA fuse. Only a CE-compliant power supply unit may be used as a power supply.

6 Maintenance

The instrument is maintenance-free. We recommend checking the instrument at regular
intervals to ensure reliable operation and a long service life.
Inspecting the output signal.
Check the leak-tightness of the pressure con-
nection lines.
Check the electrical connection (cable clamp connections).
The precise test cycles and operating and ambient conditions need to be adjusted. If various instru­ment components interact, the operating instruc­tions of all the other instruments also need to be observed.

7 Transportation

The measuring device must be protected against impacts. It may only be transported in packaging specifically intended for transport.

8 Service

All defective or faulty devices should be sent direct­ly to our repair department. We would ask you to please coordinate all return shipments with our sales department so that we can ensure careful processing of all faulty devices for our customers.
Measuring residues in and on disman­tled devices can be a hazard to people, animals and the environment. Take ad­equate preventive measures. If required,
the devices must be cleaned thoroughly.

9 Accessories

Manometer accessories acc. to data sheet MZ...

10 Waste disposal

For the sake of the environment ....
Please help to protect our environ­ment and dispose of or recycle used instruments as stipulated by the ap­plicable regulations.
Measuring range in bar
0-1.6
0-2.5
0-4
0-6
0-10
0-16
0-25
0-40
0-60
Overpressure-proof in bar
3.2 5 8
12
20
32
50
80
120
Permissible ambient temperature
-10°C  60°C
Admissible medium temperature
Max. 60°C
Pressure connection
Connection ports with external thread G½ B stainless steel, rustproof
Electrical connection
Standardised plug DIN EN 175 301-803-A
Protection class:
IP 65 acc. to DIN EN 60529
Parts in contact with the medium
AISI 316L (1.4404), Seal: Viton®
Material: Casing
AISI 304 (1.4305)
Electrical data
Power supply
Only CE-compliant power supply units with a slow 200 mA fuse may be used.
Rated voltage
24V DC
Allowed operating voltage Ub
15....30 V DC
inner effective capacity Ci
max. 270nF
effective inner inductivity Li
max. 980H
Electrical connection type
Three-conductor
Output signal
0..20 mA / 4..20 mA / 0..10 V
Load at rated voltage
450
Current/voltage limit
for output 0..10V: ca. 10.5 V for output 0/4..20 mA: ca. 24 mA
Zero-point, temperature drift
0.4 % FS/10 K
Measuring range, temperature drift
0.05 % FS/10 K
Linearity
< 1 % of the measuring range
Hysteresis
< 0.5 % of the measuring range
Identification acc. to
ATEX guideline 2014/34/EU
II 3G Ex nA IIC T4
Measuring range in bar
- 1..0
-1..0.6
-1..1.5
-1..3
-1..5
-1..9
-1..15
0...-1
Overpressure-proof in bar
2 3 3 8 12
20
32
2

11 Technical Data

M16 x 1.5
Manometer connection port G1/2 nach DIN EN 837
SW22

12 Dimensional drawings

(all dimensions in mm unless otherwise specified)
Digital manometer
Type ME01
8 7 H L R####
Measuring range
0 ... 1 bar ............................................... >
0 2
0 ...1.6 bar ............................................... >
0 3
0 ...2.5 bar ............................................... >
0 4
0 ... 4 bar ............................................... >
0 5
0 ... 6 bar ............................................... >
0 6
0 ... 10 bar ............................................... >
0 7
0 ... 16 bar ............................................... >
0 8
0 ... 25 bar ............................................... >
0 9
0 ... 40 bar ............................................... >
1 0
0 ... 60 bar ............................................... >
1 1
-1 ... 0 bar ............................................... >
3 1
-1 ...0.6 bar ............................................... >
3 2
-1 ...1.5 bar ............................................... >
3 3
-1 ... 3 bar ............................................... >
3 4
-1 ... 5 bar ............................................... >
3 5
-1 ... 9 bar ............................................... >
3 6
-1 ... 15 bar ............................................... >
3 7
Measurement accuracy
Characteristic curve dev. Relative pressure 1.0 ............>
M
Characteristic curve dev. Absolute pressure 1.0 ............>
S
Discharge port
Connection ports with external thread G½ B bottom,
Stainless steel ............................................................. >
8
7
Electrical output signal
0 – 20 mA 3-wire (STANDARD) .................................................... >
A
0 – 10 V DC 3-wire (STANDARD) ................................................. >
C
4 – 20 mA 3-wire (STANDARD) .................................................... >
P
Electrical connection
Plug 4-pin, standardised plug DIN EN 175 301-803-A .............. >
H
Operating voltage
24 V DC / AC ............................................................................................. >
L
Customer-specific no.
Code for use in Zone 2 -
Risk from vapours: II 3G Ex nA IIC T4 ........................................................ >
R####

13 Order Codes

14 Attachments

Technische Änderungen vorbehalten • Subject to change without notice • Changements techniques sous réserve
Fischer Mess- und Regeltechnik GmbH • Bielefelder Str. 37a • D-32107 Bad Salzuflen • Tel. +49 5222 9740 • Fax +49 5222 7170 •
eMail: info@fischermesstechnik.de • www.fischermesstechnik.de
Loading...