FISCHER DE61 Instruction Manual

Page 1
Instruction Manual
DE61 Differential Pressure Transmitter
Table of Contents

1. Safety Instructions

2. Intended Applications
3. Product Description and Functions
4. Installation
5. Commissioning
6. Maintenance
7. Transport
8. Service
9. Accessories
10. Disposal
11. Specifications
12. Dimensions
13. Ordering Code
14. CE-Certificate
1. Safety Instructions

1.1. General

personnel responsible for the equipment must read this thoroughly before attempting to install or operate this equipment. A copy of this manual must always be kept accessible at the place of work for reference by concerned personnel. Chapter 1 (sections 1.2 through 1.7) contains ge­neral as well as specific safety instructions. Chap­ters 2 through 10, covering topics ranging from intended purpose of the equipment to its final dis­posal, also include important points relating to safety. Overlooking or ignoring any of these safety
16.10.07 BA_GB_DE61.fm
points can endanger humans and animals, and possibly cause damage to other equipment.

1.2. Personnel Qualification

Personnel responsible for installation, operation, maintenance and inspection of this product must have the qualifications, training and experience necessary to carry out such work on this type of equipment.
This manual contains detailed information about the product, and instructions for its installati­on, operation and maintenance. Operators and other technical
1.3. Risks of Disregarding Safety Instruc­tions
Disregarding safety instructions, use of this pro­duct for purposes for which it is not intended, and/ or operation of this product outside the limits spe­cified for any of its technical parameters, can result in harm to persons, the environment, or the plant on which it is installed. Fischer Mess- und Regel­technik GmbH will not be responsible for conse­quences in such circumstances.

1.4. Safety Instructions for Operators

Safety instructions for the proper use of this pro­duct must be followed. This information must be available at all times to by personnel responsible for installation, operation, maintenance and in­spection of this product. Adequate steps must be taken to prevent the occurrence of hazardous con­ditions that can be caused by electric energy and the convertible energy of the process media. Such conditions can, for example, be the result of impro­per electrical or process connections. Detailed in­formation is available in relevant published norms (DIN EN, UVW in Germany; and equivalents in other countries), industrial standards such as DVWG, Ex-, GL-, VDE guide­lines, as well as regulations of the local authorities (e.g., EVUs in Germany).
Page 2

1.5. Modifications Forbidden

Modification or other technical alteration of the product is not permissible. This also applies to the use of unautho­rized spare parts for repair / maintenance of the product. Any modifications to this product, if and as necessary, should be done only by Fischer Mess- und Regeltechnik GmbH.

1.6. Operational Restrictions

The operational reliability of the product is guaranteed only when used for intended purposes. The product must be selected and configured for use specifically with defi­ned process media. The limiting values of operating pa­rameters, as given in the product specification sheet, must never be crossed.

1.7. Safety Considerations during Installation and Maintenance

The safety instructions given in this manual, existing na­tional regulations relating to accident prevention, and the internal safety rules and procedures of the user organi­zation regarding safety during installation, operation and servicing must all be followed meticulously. It is the responsibility of the users to ensure that only sui­tably qualified and experienced technical personnel are used for installation, operation and servicing of this equipment.

2. Intended Applications

Measuring transmitter with limit switching functions for acquisition and transmission of lowest pressure and dif­ferential pressure. The product must be used only for ap­plications and under conditions specified by the manufacturer. Please confer with Fischer Mess- und Re­geltechnik GmbH prior to using this transmitter along with polluted or aggressive media. For use with this media it needs to be adjusted in every part with direct contact to the media.

3. Product Description and Functions

3.1. Block Schematic Diagram

1 2 3 4

3.2. Principles of Operation

The function of this transmitter is based on a capacitive sensor element. Due to modern micromechanical manu­facturing process this sensor is highly overpressure safe, shock and vibration resistant and long-time stable. The differential pressure acts on the sensor element and effects a measuring signal. The electronic amplifier then generates an electrical output signal of 0 / 4-20 mA. This output signal is used for external data processing and is shown on the LC-display e.g. in mbar. The LC-display can also be used for indication and pre­cise adjustment of the differential pressure dependent switching functions. Both change-over contacts can be adjusted to any value within the measuring range.

4. Installation

4.1. Process connections

• Only qualified technicians authorized for this type of work should undertake installation.
• Only for intended mechanical process connection (for model information see Type Plate of instrument).
• Ensure that process equipment and pressure lines are at atmospheric pressure before making pressure connections.
• The instrument should be provided with suitable pro­tection against pressure surges (e.g., snubber or pul­sation damper).
• Ensure that the mechanical configuration and materi­als of construction of the instrument are compatible with the process media.
• Ensure that process pressure is always less than the specified safe pressure rating.

4.2. Electrical Connections

• Only qualified technicians authorized for this type of work should undertake installation.
• Electrical connections must comply with relevant in­ternational, national and local regulations and norms relating to electrical and instrumentation installations.
• Switch off electrical power to the plant before attemp­ting electrical installation work of any kind.
• Make electrical connections to the transmitter through a suitable energy-limiting safety device (isolation or zener barrier).
Sensor element
1. Signal output
2. Option square rooted
3. 2 change-over contacts
4. LC-display

5. Commissioning

• Power supply and signal cabling to the transmitter must be correctly selected to meet operational requi­rements, and installed in a way that does not cause physical stress to the instrument.
• Carefully check tightness of all pressure connections before start-up.
2
Page 3

5.1. Pressure Connections

The instruments pressure ports are marked by + and − symbols. The pressure applications need to be installed according to the label.
• Differential pressure + = higher pressure measurement: − = lower pressure.
• Pressure measurement + = pressure port
• Gauge measurement − = negative pressure port

5.2. Shock Pressure Moderation

During pulsating pressure on the plant mechanical wear and disturbances in functional capability may occur. To avoid this we recommend installing absorbers into the pressure lines.
For Gaseous Media
Adjustable attenuator valve MZ41 During operating condition ad­just needle valve that way, that the indicator follows chan­gements of pressure delayed.
MZ41
• Connect and switch on power supply.
• Measuring system depressurized: Output signal = 0 resp. (4) mA. Correct offset using zero point potentio­meter N.
• Mount housing cover.

5.4. Switching Point Adjustment

The instrument’s main board has two calibration poten­tiometers and a coding switch to set switching points. Af­ter removing housing cover they are freely acessible.

Adjustment sequence

• Switch on supply voltage.
• Open housing cover.
• Selector setting 1: Display indicates actual value.
• Selector setting 2: Display indicates switching point I.
• Selector setting 3: Display indicates switching point II.
• The respective setpoint values for contact 1 and con­tact 2 can be set in display using potentiometers K1 and K2.
• After adjustment is done turn selector to setting 1: ac­tual value.
• Setpoint values can be displayed any time by turning selector to position 2 or 3.

5.3. Zero Point Adjustment

Usually adjustment of the instrument is not necessary for it is factory calibrated. The output signal can be adjusted with inbuilt zero point potentiometer.

Location of zero point potentiometer

Mounting holes
Selector
Switching point potentiometer
Range adjustment: N = Zero point

Selector and Set-up Potentiometer

Selector

5.5. Electrical Connection

3-wire connection 24 V DC
2-wire connection 24 V DC

Adjustment sequence

• Open housing cover.
• Connect current indicator (0-20 mA) to output signal between terminals 11 and 12.
3
Page 4

6. Maintenance

The instrument is inherently maintenance-free. However, to ensure reliable operation and maximize the operating life of the instrument, it is recommended that the instrument, its external electrical and process con­nections, and external connected devices be regularly in­spected, e.g.:
• Check the display.
• Check the switching function in connection with se­condary components.
• Check all pressure connections for leak-tightness.
• Check the integrity of all electrical connections of the instruments.
Inspection and test schedules depend on operating and site conditions. The operating manuals of other equip­ment to which the differential pressure transmitter is con­nected must be read thoroughly to ensure that all of them work correctly when connected together.

7. Transport

The product must be protected against shock and vibra­tion during transport. It must therefore be properly pak­ked, preferably in the original factory packaging, whenever it is to be transported.

8. Service

Any defective devices or devices with missing parts should be retourned to Fischer Mess- und Regeltechnik GmbH. For quick service contact our service department.
Remaining medium in and on disman­tled measuring instruments may cause danger to persons, environment and equipment. Take reasonable precau-
tions! Clean the instrument thoroughly if necessary.

9. Accessories

10. Disposal

Protect your environment! Use the product in accordance with re­levant regulations. Please be aware of environmental consequences of dispo­sal at the end of the product's life, and take care accordingly.
4
Page 5

11. Specifications

General
Measuring ranges 0...0.25 to 0...4.0 mbar (see 13. Ordering Code)
Nominal pressure 0.6 bar
Max. static pressure overpressure safe up to permitted nominal pressure
Linearity 1% FS
Hysteresis 0.1% FS
Temperature drift 0.5% FS / 10K Perm. ambient temperature -10°...60°C Perm. medium temperature -20°...70°C
Protection class IP 54 per DIN EN 60529
Electrical
Electrical connections 3-wire 3-wire 2-wire
Operating voltages 24 V DC 24 V DC 24 V DC
Power consumption approx. 3 VA approx. 3 VA approx. 3 VA
Output signal 0-20 mA 4-20 mA 4-20 mA
Apparent ohmic resistance 700 Ω 700 Ω max. 450 Ω
Current limit approx. 30 mA approx. 30 mA approx. 30 mA
Square-rooted output ± 0.5%
with suppression of leak flow volume 2% set up
Span adjustment approx. 10% FS
Zero point adjustment approx. 10% FS
Measuring Indication /
Switching Sections
Measuring indication 3½ digit LC-Display
Switching point adjustment The digital display can be switched over between the differential pressure
actual value and the switch point adjustments via selector. The display then indicates the related setpoint value. Setpoint values are adjustable within full scale range.
Switching point hysteresis approx. 2%
Contact output 1 or 2 potential-free change-over contacts
Load data of contacts
U~ U=
Connection
Electrical Connections internal connector bloc, M16x1.5 connection
M12 plug connection
Pressure Connections female thread G¼, threaded hose coupling (al) for 6/8 mm flexible tube,
cutting ring connection (brass) for 6/8/10 mm tube
Materials
Housing diecasted aluminium, varnished
Housing cover ABS, self-extinguishing
Measuring element silicium, glass, aluminium
Installation
wallmounting vertical, pressure ports downward
any other orientation correction of zero point recommended
= 250 V AC, I~
max.
= 30 V, I=
max.
max.
= 2 A, P=
max.
= 2 A, P~
max.
= 250 VA ohmic resistance
max.
= 60 W ohmic resistance
5
Page 6

12. Dimensions (all units in mm unless stated otherwise)

Mounting holes ∅ 4.5 mm
Cable gland M16 x 1.5
6
Page 7

13. Ordering Code

Differential Pressure
Transmitter DE61
Measuring Range
0...0.25 mbar....................................................................> 9 4
0...0.4 mbar....................................................................> 9 5
0...0.6 mbar....................................................................> 9 6
0...1.0 mbar....................................................................> 5 1
0...1.6 mbar....................................................................> 9 7
0...2.5 mbar....................................................................> 9 8
0...4.0 mbar....................................................................> 5 2
other measuring ranges (please indicate in plain text) ....> 9 9
Pressure Connection
Female thread G ¼..........................................................................> 0 1
Cutting ring connection brass for 6 mm tube...................................> 2 8
Cutting ring connection brass for 8 mm tube...................................> 2 9
Cutting ring connection brass for 10 mm tube.................................> 3 0
Screw connection AI for 6 mm flexible tube.....................................> 4 0
Screw connection AI for 8 mm flexible tube.....................................> 4 1
Electrical Output Signal
0–20 mA linear, 3-wire.....................................................................................> A
4–20 mA linear, 2-wire, only 24 V DC, without contacts and square-root
extraction .........................................................................................................> B
0–20 mA square-rooted, 3-wire .......................................................................> E
4–20 mA square-rooted, 3-wire .......................................................................> F
4–20 mA linear, 3-wire.....................................................................................> P
9
Supply Voltage
24 V DC ....................................................................................................................> 9
Indication / Switching Sections
Without indication / without contacts.................................................................................> 0
3½ digit LC-display / without contacts...............................................................................> 1
3½ digit LC-display / with 1 potential-free contact ............................................................> 2
3½ digit LC-display / with 2 potential-free contacts...........................................................> 5
Electrical Connection
Internal connector bloc .............................................................................................................> E
M12 plug connection.................................................................................................................> M
7
Page 8

14. CE-Certificate

Technische Änderungen vorbehalten • Subject to change without notice • Changements techniques sous réserve
Fischer Mess- und Regeltechnik GmbH • Bielefelder Str. 37a • D-32107 Bad Salzuflen • Tel. +49 5222 9740 • Fax +49 5222 7170
eMail: [email protected] • www.fischermesstechnik.de
8