Digital differential pressure switch / transmitter
DE45##00###K0#M#R####
Gas explosion protection zone 2
II 3G
Ex nA IIC T4
-10°C ≤ T
amb
≤ 60°C
Table of Content
1 Safety guidelines
2 Intended use
3 Description of the product and functional description
4 Installation and assembly
5 Commissioning
6 Maintenance
7 Transport
8 Service
9 Accessories
10 Disposal
11 Technical data
12 Dimensional drawings
13 Order Codes
14 Manufacturer's Declarations and Certificates
1 Safety guidelines
1.1 General Information
This operating manual contains instructions fundamental to the installation, operation and maintenance of the instru-
ment that must be observed unconditionally. It must be read by the assembler, operator
and the specialized personnel in charge of the device before it is installed and put into operation.
This operating manual is part of the product and
therefore must be kept close to the device in a
place that is easily accessible for the responsible
personnel.
The following sections, in particular the instructions
about assembly, commissioning and maintenance,
contain important safety information, nonobservance of which could lead to risks to people,
animals, the environment and objects.
1.2 Personnel Qualification
*09005069* DB_BA_EN_DE45_R Rev.B 09/16
The instrument may only be installed and commissioned by specialized personnel familiar with the installation, commissioning and operation of this
product.
Specialized personnel are persons who can assess
the work they have been assigned and recognize
potential dangers by virtue of their specialized training, their skills and experience and their knowledge
of the pertinent standards.
For explosion-proof models the specialized personnel must have received special training or instruction or be authorized to work with explosion-proof
instruments in explosion hazard areas.
1.3 Risks due to Non-Observance of
Safety Instructions
Non-observance of these safety instructions, the intended use of the device or the limit values given in
the technical specifications can be hazardous or
cause harm to persons, the environment or the
plant itself.
Claims for damages from the manufacturer are excluded in this case.
WARNING!
… indicates a potentially dangerous
situation, non-observance of which
could endanger persons, animals, the
environment or objects.
INFORMATION!
… highlights important information for
efficient and fault-free operation.
TIP!
… highlights recommendations that
may be useful but which are not necessarily required in specific situations.
1.4 Safety Instructions for the Operating
Company and the Operator
The safety instructions on correct operation of the
device shall be observed. The operating company
must make them available to the installation,
maintenance, inspection and operating personnel.
Dangers arising from electrical components, energy
discharged by the medium, escaping medium and
incorrect installation of the instrument must be eliminated. For more information, please refer to the
applicable national and international regulations.
In Germany these are the DIN EN, UVV and, in industry-specific cases, the DVGW-, Ex-, GL-, etc.,
the VDE guidelines and the regulations of the local
power utility companies.
The instrument must be decommissioned and secured against inadvertent re-operation if a situation
arises in which it must be assumed that safe operation is no longer possible. Reasons for this assumption could be:
• evident damage to the instrument,
• failure of the electrical circuits,
1.7 Safe working practices for maintenance and installation work
The safety instructions given in this operating manual, any nationally applicable regulations on accident prevention and any of the operating company's
internal work, operating and safety guidelines must
be observed.
The operating company is responsible for ensuring
that all required maintenance, inspection and installation work is carried out by qualified specialized
personnel.
1.8 Explanation of the symbols
• long storage in temperatures over 70°C,
• considerable strain due to transport.
• Repairs may be carried out by the
manufacturer only.
A professional single conformity inspection as per
DIN EN 61010, section 1, must be carried out before the device can be re-commissioned. This inspection must be performed at the manufacturer's
location. Correct transport and storage of the device
is assumed.
The following sections, in particular the instructions
about assembly, commissioning and maintenance,
contain important safety information, nonobservance of which could lead to risks to people,
animals, the environment and objects.
1.5 Unauthorised Modification
Modifications of or other technical alterations to the
instrument by the customer are not permitted. This
also applies to replacement parts. Any modifications / alterations required shall be carried out by
Fischer Mess- und Regeltechnik GmbH only.
2 Intended use
Display and switching device for differential pressure of gaseous media. The instrument is to be exclusively used for the applications agreed between
the manufacturer and user.
Explosion hazard area classification
The differential pressure switch / transmitter DE45
is suitable for use in explosive areas "zone 2" as an
electrical device".
Designation as per guideline 94/9/EC
II 3G Ex nA IIC T4
-10°C ≤ T
≤ 60°C
amb
1.6 Inadmissible Modes of Operation
The operational safety of this device can only be
guaranteed if it is used as intended. The device
model must be suitable for the medium used in the
system. The limit values given in the technical data
may not be exceeded.
3 Description of the product and func-
tional description
3.1 Function diagram
3.2 Design and mode of operation
The device is based on a piezo-resistive sensor element that is suitable for measuring overpressure,
underpressure and differential pressure. The pressures to be compared directly act on a silicon diaphragm equipped with piezo-resistive resistors. In
case of equal pressure, the measuring diaphragm is
in its idle state. In case of pressure difference, the
force acting on the measuring membrane causes it
to be moved towards the side of the lower pressure.
This movement of the diaphragm induces a change
of resistance, which is evaluated by the device's
electronics and transformed into signals on the display, switch contacts and an output signal.
4 Installation and assembly
The unit is designed for mounting on flat assembly
plates. For screw connection to the assembly plate,
the device features four assembly bores on its
back, which can be used for 3.5 mm tapping
screws.
Optionally, the device can be delivered with a wallmounting plate (see 13, order code).
At the factory, the device is calibrated for vertical
installation, but the installation position is arbitrary.
For installation positions deviating from the vertical,
the zero-point signal can be corrected by the integrated zero-point adjuster (see 5.3.2).
The enclosure protection type IP 65 is only guaranteed, if a suitable power supply cable is used (see
accessories).
4.1 Process connection
•By authorized and qualified specialized person-
nel only.
•Check that the pressure connections do not
leak before commissioning.
•Maximum pressures shall be observed.
Do not blow into the pressure connections!
The pressure connections are marked with (+) and
(-) symbols on the device. For differential pressure
measurements, the higher pressure is connected to
the (+) side and the lower pressure to the (-) side of
the device.
The pressure measuring lines must be installed on
a gradient so that no air pockets e.g. for liquid
measurements, water pockets or for gas measurements can be created. If the required incline is not
reached, water and/or air filters need to be installed
at suitable points.
The pressure sensing lines need to be kept as short
as possible and installed without sharp bends to
avoid interfering delay times.
If the pressure sensing lines are already
pressurised at the time of commissioning, zero-point control and adjustment
cannot be performed. In such cases, the
device should be only connected to the mains without the pressure sensing lines.
4.2 Electronic connection
•By authorized and qualified specialized person-
nel only.
•The electrical connection of the device shall be
performed according to relevant VDE and local
electricity board regulations.
•Disconnect the system from the mains before
connecting the device.
Refer to the technical data for the recommended
power supply.
To guarantee safe operation of the device, the
supply circuit must satisfy the requirements for
zone 2, category 3, and the local applicable
regulations and guidelines for the installation
and operation of electrical systems in explosion
hazard areas (e.g. EN 60079-14).
The supply voltage (24 V DC/AC) may not ex-
ceed 32V DC/AC. The supply circuit must be
protected by a 200mAT fuse.
•The pipes need to be depressurized when the
instrument is being connected.
•Appropriate steps must be taken to protect the
device from pressure surges.
•Check the suitability of the device for the media
to be measured.
The device may be configured with the
EU03.F300 configuring adaptor outside of the
explosion hazard areas only (i.e. not in zone 2).
ÿ
Page down menu
Reduce value
û
Enter key
þ
Page up menu
Increase value
1
bridged internally
Signal -Sig
Power supply -
U
b
Signal +Sig
n.c.
Power supply
+U
b
SP1SP2SP2SP1
p
Delivery
Analysis
e.g. SPS
Reception
+ - -Sig /
+Ub
+Sig
-Ub
Delivery
230V ~
L
N
+Ub
-Ub
Switching output 1
Switching output 2
3.5 character LED display
Operating keys
Measuring unit
3 conductor circuit
Connector 1: Power supply and output signal
•
Connector 2: Switching outputs
5.1 Display
•The 3.5 digit LCD display represents the current
differential pressure in normal mode.
•The selected measuring unit is illuminated on
the right of the display.
The units shown in the picture may vary from
the actual model.
•Two light diodes and above the display in-
dicate the status of the switching outputs. As
soon as the switch is closed, the respective
LED shines.
The nominal supply voltage and the permissible
range can be found in the technical data.
The admissible load / resistance for the signal output is stated in the technical data.
The connection "Signal ground“(-Sig) is connected
internally to the supply ground. It only serves as the
ground connection for the output signal. This means
that the output signal is free of interference levels
on the power supply lines.
5 Commissioning
All electrical supply, operating and measuring lines,
and the pressure connections must have been correctly installed before commissioning. All supply
lines are arranged so that there are no mechanical
forces acting on the device.
Check that the pressure connections do not leak
before commissioning.
5.2 Operating keys
The operating keys have the following function:
5.3 Configuration
For commissioning there is a multitude of setting
options for optimum adaptation of the device to the
measuring point and task at hand. This section covers these options step by step.
Depending on the device model 1 some menu items
may not be available. For example, all characteristic
curve functions are faded out in the menu if the device does not have a signal output.
It is possible to completely configure the
device using a PC adapter at the PC.
Here all parameters are directly visible
and accessible. Also, the entire configuration can be loaded, saved and documented as a
printout. For more information about this program,
please refer to the program documentation (cf. Accessories).
with regard to the transmitter signal, voltage output, current
output, etc.
2
3
5.3.1 General points
Connect the device to the power supply and ensure
that it is not under any pressure (if necessary, disconnect any pressure lines).
Proceed as follows to set a parameter:
•Press the enter key û to switch to the menu.
ESc will appear on the display.
•Use the arrow keys ÿþ to select a parameter
from the list.
• Press the enter key û to call up the parameter.
• Use the arrow keys ÿþ to set the required val-
ue.
•Press the enter key û to save the value.
After setting all parameters, leave the menu as follows:2
•Use the arrow keys ÿþ to set the ESc parame-
ter. You will find these at the start and also at
the end of the list of parameters.
•Press the enter key û to leave to the menu.
5.3.2 Selecting the pressure unit
First select the pressure measuring unit. The unit
that is currently valid is illuminated to the right of the
number displays. Press the middle key û to make
the setting and then search for the parameter EIN
using the right-hand key þ. Press û again an then
change the displayed value using þ or ÿ.
1 = top
2 = middle
3 = bottom
Once the value has been selected, save it with û
and EIN will appear again in the display.
Then leave the setting mode. Press ÿ until Esc and
the û appear. The current measured pressure is
shown again. The correct pressure unit is now illuminated to the right of this.
The display can only show up to ±1999.
Therefore in some cases it may not be
possible to select all stated pressure
units.
5.3.3 Zero point control and adjustment
Ensure that the device is not under any pressure (if
necessary, disconnect any pressure lines).
If the device does precisely indicate zero at this
point of time, parameter OF1 enables you to adjust
the measuring value exactly to zero. To do so, you
All set parameter values are only valid once you leave the
menu via the ESC parameter.
have to set the measuring value indicated below OF1
to zero.
After zero-point adjustment, the pressure sensing
lines can be reconnected.
5.3.4 Damping and zero-point stabilising
If there are unsteady pressure readings at this point
of time or during operation, you can use parameters
DAM and NP to stabilise the reading (and the output
signal).
The parameter DAM functions like a capillary throttle.
However, it only acts on the display, output signal
and switch points (if these exist) but not on the
measuring cell itself. With this parameter, the response time can be set to pressure jumps. The value range comprises 0.0 s to 100.0 s.
But with maximum attenuation, it will
take more than 2 minutes for the reading to also reach zero after a pressure
jump from nominal pressure (100 %) to
zero!
In many cases, unsteady readings are not a problem during normal operating mode, but this is not
true for the idle state, i.e. if zero (differential) pressure is expected.
In such situations, parameter NP can be applied. Its
value defines a measuring value range around zero. Within this range, the measuring value is set to
zero.
Example:
A value of 0.08 mbar 3 is entered for NP. In this
case all pressures within the range of -0.08
mbar to +0.08 mbar are set to zero. The reading will only not indicate zero anymore if the
pressure exceeds these limits. However the
pressure value and display do not correspond
to one hundred percent. The measuring pressure and reading match again when the double
value, in this case 0.16 mbar, is reached again.
5.3.5 Setting the output signal
The transmitter output signal primarily depends on
the sensed pressure. However, you have the option
of adjusting the output signal to a large extent to
suit your requirements.
However the basic measuring range
(indicated on the type label) and the
type of output signal (voltage / current)
are not variable.
Parameters MA (start of measuring range) and ME
(end of measuring range) define the two pressures
between which the output signal can generally
change. Both values are adjustable across the entire basic measuring range. The set values always
0.08 mbar ≙ 8 Pa
F
0
linear characteristic curve (standard)
1
square rooted characteristic curve
2
flat cylindrical tank
3...30
Support point table with 3 to 30 pairs of values
refer to pressure (in the relevant measuring unit)
and are converted when the measuring unit is
changed.
The assigned signal values for MA and ME are invariable (type label, e.g. 0…10V or 4…20 mA).
If MA is smaller than ME this is referred ´to a rising
characteristic curve. The output signal grows as the
pressure increases.
If ME is smaller than MA, this is a decreasing characteristic curve and the output signal decreases with
the falling pressure.
The difference between values MA and ME must at
least be 25 % of the basic measuring range. The
software does not allow any larger spreads. If the
range information is stated wrongly, you cannot
leave the menu.
Example:
The following must apply for a basic measuring
range of 400 Pa: MA – ME 100 Pa.
5.3.6 Output signal limits (Namur)
Regardless of the pressure, the three parameters
oG1, oG2 and oEr define the limit values for output
currents or voltages that may not be undercut or
exceeded.
These limit values have priority over the
range defined by the MA and ME. They
primarily serve to prevent error messages in downstream systems caused by a
brief overstepping of measuring ranges.
The parameter oG1 defines the limit value for the
minimum output signal. The output signal may not
undercut this value. Usually, this parameter is only
recommended for devices with an output signal of
4…20 mA because in these devices, a value below
3.8 mA is often assessed as an error signal.
output is directly changed. You operate the device
then as a transducer and can simply check the further signal processing.
5.3.7 Characteristic curve function F
In some applications, measuring pressure is an indirect unit for the actual measuring variable. Flow
measurements via a panel or determining the filling
level by means of hydrostatic pressure measurements are two typical examples of this. In these
cases, you might want to change the output signal
of the transmitter to a non-linear characteristic
curve so that the following analysis receives a signal that is linear-proportional to the actual measuring variable (e.g. volume in m³ or volume flow cm³/s
etc.)
The parameter F allows you to select between the
following variants:
Whenever you change the value from F, the program creates a new table. All previous values in the
table are rejected and replaced with new linear entries.
The tables of type F = 0 to F = 2 are not visible. Internal values are used here to calculate the table.
These values are invariable.
For F = 3...30 you can only influence the 1..28 intermediate values (cf. 5.3.8) You only have access
to the start and end values via the MA and ME parameters.
When the parameters MA and ME are
changed the table is deleted and F = 0 is
set.
The parameter OG2 defines the limit value for the
maximum output signal. The output signal may not
exceed this value. This parameter can be used for
all outputs (voltage and current) to limit the maximum value of e.g. 10.2 V.
The parameter oer defines the value for the error
signal. The value defined via the oEr is issued as an
output signal, if the device detects an internal error
and can no longer work correctly. However, the device is not able to recognise all possible errors and
defects.
If you set oG1 = OG2 = 0, the output signal will no
longer be checked for limits.
If you set oG1 to the maximum value (11
V or 21 mA), you can use OG2 to adjust
the output signal independent of the
pressure from zero to the maximum
value. You do not need to leave the menu item, the
At the start of the measuring range (MA) 0% of the
output signal (e.g. 0 mA) is issued.
At the end of the measuring range (ME) 100% of the
output signal (e.g. 20 mA) is issued.
5.3.8 Menu jump LIN
If the value of F is greater than or equal to 3, there
is a submenu LIn. here you can access all table values apart from the table start (MA) and end (ME).
This submenu has its own entry and exit point that
is shown with End. The table is only saved if you return to the main menu at this point, i.e. if you
change to the parameter LIN again via the key û.
If the table is not structured correctly, an error message Err will appear here and you cannot quit the
submenu.
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.