FISCHER DE45 Operating Manual

Operating manual
DE45
Digital differential pressure switch / transmitter
with colour-change LCD
09005352 BA_EN_DE45_LCD Rev. ST4-D 09/15
*09005352*
ii BA_EN_DE45_LCD_Rev. ST4-D
Table of Content
1 Safety instructions.........................................................................................................................................4
1.1 General.....................................................................................................................................................4
1.2 Personnel Qualification ............................................................................................................................4
1.3 Risks due to Non-Observance of Safety Instructions...............................................................................4
1.4 Safety Instructions for the Operating Company and the Operator ...........................................................4
1.5 Unauthorised Modification........................................................................................................................4
1.6 Inadmissible Modes of Operation.............................................................................................................4
1.7 Safe working practices for maintenance and installation work.................................................................5
1.8 Pictogram explanation..............................................................................................................................5
2 Product and functional description.............................................................................................................. 6
2.1 Intended use.............................................................................................................................................6
2.2 Part designations......................................................................................................................................6
2.3 Function diagram......................................................................................................................................7
2.4 Design and mode of operation .................................................................................................................7
3 Installation ......................................................................................................................................................8
3.1 General.....................................................................................................................................................8
3.2 Process connection ..................................................................................................................................8
3.3 Electrical connection ................................................................................................................................8
4 Commissioning ............................................................................................................................................10
4.1 General...................................................................................................................................................10
4.2 Configuration ..........................................................................................................................................10
4.3 Control Elements....................................................................................................................................10
4.4 Menu levels ............................................................................................................................................12
5 Maintenance .................................................................................................................................................22
5.1 Maintenance...........................................................................................................................................22
5.2 Transport ................................................................................................................................................22
5.3 Service ...................................................................................................................................................22
5.4 Disposal..................................................................................................................................................22
6 Technical data ..............................................................................................................................................23
6.1 Input variables ........................................................................................................................................23
6.2 Output parameters .................................................................................................................................23
6.3 Auxiliary energy .....................................................................................................................................24
6.4 Measuring accuracy ...............................................................................................................................24
6.5 Application conditions.............................................................................................................................25
6.6 Construction design................................................................................................................................25
6.7 Display and operating interface..............................................................................................................27
6.8 Certificates and approvals......................................................................................................................27
7 Order Codes .................................................................................................................................................28
7.1 Device specification................................................................................................................................30
7.2 Accessories ............................................................................................................................................30
8 Attachments .................................................................................................................................................31
8.1 EC Declaration of conformity..................................................................................................................31
8.2 EAC Declaration.....................................................................................................................................32
Fischer Mess- und Regeltechnik GmbH Masthead |
BA_EN_DE45_LCD_Rev. ST4-D 3 / 32
Masthead
Manufacturer: FISCHER Mess- und Regeltechnik GmbH
Bielefelderstr. 37a 32107 Bad Salzuflen
Telefon: +49 5222 974 0 Telefax: +49 5222 7170
eMail: info@fischermesstechnik.de web: www.fischermesstechnik.de
Technical editorial team: Documentation representative: S. Richter
Technical editor: R.Kleemann
All rights, also those to the translation, reserved. No part of these instructions may be reproduced or processed, duplicated or distributed using electronic sys­tems or any other form (print, photocopy, microfilm or another process) without the written consent of the company Fischer Mess- und Regeltechnik GmbH, Bad Salzuflen.
Reproduction for internal use is expressly allowed.
Brand names and procedures are used for information purposes only and do not take the respective patent situation into account. Great care was taken when compiling the texts and illustrations; nevertheless, errors cannot be ruled out. The company FISCHER Mess- und Regeltechnik GmbH will not accept any legal responsibility or liability for this.
Subject to technical amendments.
© FISCHER Mess- und Regeltechnik 2014
1 | Safety instructions Fischer Mess- und Regeltechnik GmbH
4 / 32 BA_EN_DE45_LCD_Rev. ST4-D
1 Safety instructions
1.1 General
WARNING
This operating manual contains instructions fundamental to the installation, op­eration and maintenance of the device that must be observed unconditionally. It must be read by the assembler, operator and the specialized personnel in charge of the instrument before it is installed and put into operation.
This operating manual is an integral part of the product and therefore needs to be kept close to the instrument in a place that is accessible at all times to the responsible personnel.
The following sections, in particular instructions about the assembly, commis­sioning and maintenance, contain important information, non-observance of which could pose a threat to humans, animals, the environment and property.
The instrument described in these operating instructions is designed and manu­factured in line with the state of the art and good engineering practice.
1.2 Personnel Qualification
The instrument may only be installed and commissioned by specialized person­nel familiar with the installation, commissioning and operation of this product.
Specialized personnel are persons who can assess the work they have been assigned and recognize potential dangers by virtue of their specialized training, their skills and experience and their knowledge of the pertinent standards.
1.3 Risks due to Non-Observance of Safety Instructions
Non-observance of these safety instructions, the intended use of the device or the limit values given in the technical specifications can be hazardous or cause harm to persons, the environment or the plant itself.
The supplier of the equipment will not be liable for damage claims if this should happen.
1.4 Safety Instructions for the Operating Company and the Operator
The safety instructions governing correct operation of theinstrument must be observed. The operating company must make them available to the installation, maintenance, inspection and operating personnel.
Dangers arising from electrical components, energy discharged by the medium, escaping medium and incorrect installation of the device must be eliminated. See the information in the applicable national and international regulations.
Please observe the information about certification and approvals in the Tech­nical Data section.
1.5 Unauthorised Modification
Modifications of or other technical alterations to the instrument by the customer are not permitted. This also applies to replacement parts. Only the manufac­turer is authorised to make any modifications or changes.
1.6 Inadmissible Modes of Operation
The operational safety of this instrument can only be guaranteed if it is used as intended. The instrument model must be suitable for the medium used in the system. The limit values given in the technical data may not be exceeded.
The manufacturer is not liable for damage resulting from improper or incorrect use.
Fischer Mess- und Regeltechnik GmbH Safety instructions | 1
BA_EN_DE45_LCD_Rev. ST4-D 5 / 32
1.7 Safe working practices for maintenance and installation work
The safety instructions given in this operating manual, any nationally applicable regulations on accident prevention and any of the operating company's internal work, operating and safety guidelines must be observed.
The operating company is responsible for ensuring that all required mainten­ance, inspection and installation work is carried out by qualified specialized per­sonnel.
1.8 Pictogram explanation
DANGER
Type and source of danger
This indicates a direct dangerous situation that could lead to death or serious injury (highest danger level).
a) Avoid danger by observing the valid safety regulations.
WARNING
Type and source of danger
This indicates a potentially dangerous situation that could lead to death or ser­ious injury (medium danger level).
a) Avoid danger by observing the valid safety regulations.
CAUTION
Type and source of danger
This indicates a potentially dangerous situation that could lead to slight or seri­ous injury, damage or environmental pollution (low danger level).
a) Avoid danger by observing the valid safety regulations.
NOTICE
Note / advice
This indicates useful information of advice for efficient and smooth operation.
2 | Product and functional description Fischer Mess- und Regeltechnik GmbH
6 / 32 BA_EN_DE45_LCD_Rev. ST4-D
2 Product and functional description
2.1 Intended use
The DE45 is a multi-functional switching unit with an optional transmitter output. It is suitable for measuring overpressure, underpressure and differential pres­sure in gaseous media. The device is to be exclusively used for the applications agreed between the manufacturer and user.
Typical applications
▪ Monitoring of roll filters, extraction systems etc.
▪ Draft measurement in chimneys
▪ Flow and control pressure measurements
▪ Surface coating systems
Important features
▪ Robust, resistant to overpressure and maintenance-free
▪ Optional signal output with possibility of characteristic curve spread and re-
versal with any offset
▪ Characteristic curve implementation via table with max. 30 measuring points
▪ 4...6-digit LCD, full graphic, colour backlighting
2.2 Part designations
1
2 3
4
5
68 7
Illustration1: Part designations
1 Membrane keyboard 5 M12 connector 2 (4-pin, male) 2 LC display 6 M12 connector 1 (5-pin, male) 3 Casing lid 7 Process connection (-) 4 Lower part of casing 8 Process connection (+)
Fischer Mess- und Regeltechnik GmbH Product and functional description | 2
BA_EN_DE45_LCD_Rev. ST4-D 7 / 32
2.3 Function diagram
21 3
4
5
6
7
Illustration2: Function diagram DE45_LCD
1 Sensor element 5 LC display 2 Signal processing 6 Analogue output 3 Switching outputs 7 Microcontroller 4 Membrane keyboard
2.4 Design and mode of operation
The device is based on a piezo-resistive sensor element that is suitable for measuring overpressure, underpressure and differential pressure. The pres­sures to be compared directly act on a silicon diaphragm equipped with piezo­resistive resistors.
When the pressure is equal, the measuring diaphragm is in its idle state. In the event of differential pressure, the diaphragm is moved toward the lower pres­sure which changes the resistance of the attached resistors. This change is evaluated by the device's electronics and transformed into the display, switch contacts or an optional output signal.
The optional output signal can be dampened, spread, inverted and transformed via a table function even if it is non-linear.
3 | Installation Fischer Mess- und Regeltechnik GmbH
8 / 32 BA_EN_DE45_LCD_Rev. ST4-D
3 Installation
3.1 General
The device is designed for installation onto flat assembly plates. For screw con­nection to the assembly plate, the device features four assembly bores on its back, which can be used for Ø 3.5 mm tapping screws.
Optionally, the device can be delivered with a wall-mounting plate.
At the factory, the device is calibrated for vertical installation, but the installation position is arbitrary. For any installation positions that are not vertical, the zero­point signal can be corrected via the installed offset correction.
The enclosure protection type IP 65 is only guaranteed, if a suitable power sup­ply cable is used.
If the device is intended for outdoor use, we recommend permanently protect­ing the membrane keypad against UV radiation and using a suitable enclosure or at least the erection of a sufficiently dimensioned canopy as a protection measure against constant rain or snow.
3.2 Process connection
▪ By authorized and qualified specialized personnel only.
▪ The pipes need to be depressurized when the instrument is being connec-
ted.
▪ Appropriate steps must be taken to protect the device from pressure surges.
▪ Check the suitability of the instrument for the media that is to be measured.
▪ Maximum pressures must be observed (cf. Tech. data)
CAUTION
Do not blow into the pressure connections.
This can damage the pressure sensor.
Illustration3: Process connection
The pressure measuring lines must be installed on a gradient so that no water pockets for gas measurements can be created. If the required incline is not reached, water filters need to be installed at suitable points.
The pressure sensing lines need to be kept as short as possible and installed without sharp bends to avoid interfering delay times.
The pressure connections are marked with (+) and (-) symbols on the device. When the differential pressure is measured, the higher pressure is connected to the (+) side and the lower pressure to the (-) side.
If the pressure sensing lines are already pressurised at the time of commission­ing, zero-point control and adjustment cannot be performed. In such cases, the device should be only connected to the mains without the pressure sensing lines.
3.3 Electrical connection
Electrical connection
▪ By authorized and qualified specialized personnel only.
▪ When connecting the device, the relevant national and international electro-
technical rules must be observed.
▪ Disconnect the system from the mains, before electrically connecting the
device.
▪ Switch the consumer-adapted fuses.
Fischer Mess- und Regeltechnik GmbH Installation | 3
BA_EN_DE45_LCD_Rev. ST4-D 9 / 32
The nominal supply voltage and the permissible range can be found in the tech­nical data.
The admissible load / resistance for the signal output is stated in the technical data.
The connection "Signal ground“ (-Sig) is connected internally to the supply ground. It only serves as the ground connection for the output signal. This means that the output signal is free of interference levels on the power supply lines.
3-wire connection
The device is connected as follows in a 3-wire switch:
The connection "Signal ground“ (-Sig) is connected internally to the supply ground. It only serves as the ground connection for the output signal. This means that the output signal is free of interference levels on the power supply lines.
Input
Output
AC
DC
Sensor
Signal
+U
b
- U
b
- Sig
+Sig
+U
b
- U
b
p
1
3
2
4
Illustration4: 3L-switch with internal bridge –Ub / -Sig
Connector 1: Supply and output signal
Illustration5: M12 Plug 5-pin
Pos Description Cable colour
A Coding A B Internal bridge 1 +UbSupply brown 2 -Sig Signal white 3 -UbSupply blue 4 +Sig Signal black 5 n.c.
Connector 2: Switching outputs
Illustration6: M12 Plug 4-pin
Pos Description Cable colour
A Coding A 1 SP1 Switch point 1 (no) brown 2 SP2 Switch point 2 (no) white 3 SP2 Switch point 2 (com) blue 4 SP1 Switch point 1 (com) black
4 | Commissioning Fischer Mess- und Regeltechnik GmbH
10 / 32 BA_EN_DE45_LCD_Rev. ST4-D
4 Commissioning
4.1 General
All electrical supply, operating and measuring lines, and the pressure connec­tions must have been correctly installed before commissioning. All supply lines are arranged so that there are no mechanical forces acting on the device.
Check that the pressure connections do not leak before commissioning.
4.2 Configuration
During commissioning there are a number of setting options that allow the device to be adapted to the measuring point and measuring task. To facilitate the input, the individual parameters are placed into groups in so-called menu levels.
Depending on the device model some menu items are not available. For in­stance, no switch points can be set on a device without contacts.
NOTICE
Parameter configuration on the PC
All the device settings can be made easily on the PC using the PC adapter. You will need a EU03 Transmitter PC Interface and the associated software Trans­Para for this. For more details, please refer to the Accessories section. The TransPara software makes all parameters directly visible and accessible. Also, the entire configuration can be loaded, saved and documented as a printout.
4.3 Control Elements
LC display
Illustration7: DE45 LCD display
1 LCD with back lighting 4 Unit 2 Measurement display 4…6 digits 5 Bar chart display 3 Status display of the switch
points
6 Keyboard
In normal mode, the current measured value is shown on a 4-digit LC display. To show very large values, it is possible to switch to a 5 or 6-digit presentation (see Parameter MB decimal place).
Illustration8: Display SP1 SP2
The unit is shown on the right of the display. If the device is equipped with con­tacts, a closed contact is always symbolised by an inverted text "SP1" or "SP2".