FISCHER DE38D410, DE38 Instruction Manual

1 Safety Instructions
1.1 General
This manual contains detailed infor­mation about the product, and in­structions for its installation, opera­tion and maintenance. Operators
and other technical personnel re­sponsible for the equipment must read this tho­roughly before attempting to install or operate this equipment. A copy of this manual must always be kept accessible at the place of work for reference by concerned personnel.
Chapter 1 (sections 1.2 through 1.7) contains ge­neral as well as specific safety instructions. Chapters 2 through 10, covering topics ranging from intended purpose of the equipment to its fi­nal disposal, also include important points rela­ting to safety. Overlooking or ignoring any of the­se safety points can endanger humans and ani­mals, and possibly cause damage to other equip­ment.
1.2 Personnel Qualification
Personnel responsible for installation, operation, maintenance and inspection of this product must have the qualifications, training and experience necessary to carry out such work on this type of equipment.
1.3 Risks of Disregarding Safety Instructions
Disregarding safety instructions, use of this pro­duct for purposes for which it is not intended, and/or operation of this product outside the limits specified for any of its technical parameters, can result in harm to persons, the environment, or the plant on which it is installed. Fischer Mess- und Regeltechnik GmbH will not be responsible for consequences in such circumstances.
1.4 Safety Instructions for Operators
Safety instructions for the proper use of this pro­duct must be followed. This information must be available at all times to by personnel responsible for installation, operation, maintenance and in­spection of this product.
Adequate steps must be taken to prevent the occurrence of hazardous conditions that can be caused by electric energy and the convertible energy of the process media. Such conditions can, for example, be the result of improper electrical or process connections.
Detailed information is available in relevant pub­lished norms (DIN EN, UVW in Germany; and equivalents in other countries), industrial stan­dards such as DVWG, EG-, GL-, VDE guidelines, as well as regulations of the local authorities ( e.g., EVUs in Ger­many).
               
# 09005136 26.03.2009 BA_D_DE38_D410
Ins tru ctio n M anu al
D E 3 8
D ig ita l D iffe re ntia l P re ss ure Tra nsm itte r / S witch
DE38D410
Inhalt
1 Safety Instructions .......................................1
2 Intended Applications...................................2
3 Product Description and Functions..............2
4 Installation....................................................2
5 Commissioning ............................................3
6 Maintenance ................................................8
7 Transport......................................................8
8 Service.........................................................8
9 Accessories..................................................8
10 Disposal.......................................................8
11 Specifications...............................................9
12 Dimensions ................................................11
13 CE-Certificate.............................................12
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
1.5 Modifications Forbidden
Modification or other technical alteration of the product is not permissible. This also applies to the use of un­authorized spare parts for repair / maintenance of the product. Any modifications to this product, if and as ne­cessary, should be done only by Fischer Mess- und Re­geltechnik GmbH.
1.6 Operational Restrictions
The operational reliability of the product is guaranteed only when used for intended purposes. The product must be selected and configured for use specifically with defined process media. The limiting values of ope­rating parameters, as given in the product specification sheet, must never be crossed.
1.7 Safety Considerations during Installation and Mainte­nance
The safety instructions given in this manual, existing na­tional regulations relating to accident prevention, and the internal safety rules and procedures of the user or­ganization regarding safety during installation, operation and servicing must all be followed meticulously.
It is the responsibility of the users to ensure that only suitably qualified and experienced technical personnel are used for installation, operation and servicing of this equipment.
2 Intended Applications
The product includes the functions of sensing, signal conversion, display, signal transmission, and limit de­tection of pressure / differential pressure of gases and liquids. The product must be used only for applications and under conditions specified by the manufacturer. In case of uncertainties, the user should consult the manu­facturer before installing and using the product.
3 Product Description and Functions
3.1 Block Schematic Diagram
3.2 Principles of Operation
The instrument uses a tough, robust sensing dia­phragm, which is qualified for over-, low- and differenti­al pressure measurings. The comparative pressures work on a elastic bedded measuring diaphragm. The di­aphragm is at zero position when pressures on either side of the diaphragm are equal.Inequality of pressures results in deflecting the diaphragm towards the lower pressure side until a new equilibrium determined by the spring power is reached. This deflection is transmitted by a tappet to the center of a inductive travel sensor. The integrated electronics analyzes the deflection and converts it into display, switch contacts and output sig­nal.
4 Installation
The instrument is intended for the assembly on the base of the Flender circulatory- measurement.
At the installation of the upper part there should be paid attention to the correct adjustment. The operator must be able to regulate and read the instrument from a safe place.
The sealing faces and the O- ring seals must not be da­maged!
The instrument is adjustet for a vertical mounting positi­on. Other positions aren't sensibel because of the clear­ness of reading the digital display.
If the instrument is intended for outdoor application, we highly recommend using an ade-quate protective hou­sing (or at least a big enough shelter) as permanent protection against UV-radiation on the membrane key­board and against exposure of the instrument to rain or snow.
4.1 Process Connections
 Ensure that process equipment and pressure lines
are at atmospheric pressure before making pressure connections.
 The instrument should be provided with suitable pro-
tection against pressure surges (e.g., snubber or pulsation damper).
 Ensure that the mechanical configuration and mate-
rials of construction of the instrument are compatible with the process media.
 Take account of the maximum pressure.
 Carefully check the pressure-tightness of all pressu-
re connections before start-up.
4.2 Electrical Connections
 Only qualified technicians authorized for this type of
work should undertake installation.
 Electrical connections must comply with relevant in-
ternational, national and local regulations and norms relating to electrical and instrumentation installati­ons.
2
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
 Switch off electrical power to the plant before at-
tempting electrical installation work of any kind.
 Make electrical connections to the transmitter
through a suitable energy-limiting safety device (iso­lation or zener barrier).
5 Commissioning
 Power supply and signal cabling to the transmitter
must be correctly selected to meet operational requi­rements, and installed in a way that does not cause physical stress to the instrument.
 Pressure lines must have a downward gradient
throughout from the pressure instrument to the pro­cess vessel / pipe. This is to prevent formation of air / gas pockets (for liquid applications) and liquid plugs (for air / gas applications). If this continuous down­ward gradient cannot be provided for any reason, then suitable water and / or air separation devices must be inserted into the pressure lines.
 Pressure lines must be kept as short as possible and
must not have short bends to avoid measurement errors induced by pressure line delays.
5.1 Pressure Connections
If the pressure transmitter is subjected to pressure when it is started up, zero point checking and adjust­ment is not possible. In such cases, only electrical con­nections of the instrument should be made, but not the pressure connections.
5.2 Display
The 3½ digit LED display normally indicates the current differential pressure. The backlit symbols to the right of the 3½ digit LED display indicate the unit of pressure measurement. (Note: the units shown in the illustrations of this document can be different from those of the actu­al instrument). The two LED lamps above the 3½ digit LED display respectively indicate the status of the two limit relays / solid-state switches
(LED on = relay
contacts closed / solid-state switch on). While the instrument is in set-up mode, the 3½ digit
LED display either indicates the selected menu option or a set-up parameter value. The instrument continues its pressure monitoring functions even while it is in set­up mode, except under either of two circumstances.
One is when the limit switching delay time is changed: the existing delay must time out first. The other is when the look-up table (for conversion of measured values) is re-programmed (s. 5.3.7.). In these circumstances, the output signal value and the limit relay/switch states are frozen until the changes are finalized.
5.3 Set-up
The instrument has comprehensive set-up options by means of which it can be optimized for any specific measuring or control application. This section of the document provides information and instructions about each of the set-up parameters.
Depending on the instrument configurati­on ordered (e.g.: without transmitter signal output / with voltage signal output / with current signal output) some of the menu
options may not available. Some set-up parameters may be consequentially excluded. For example, if the instrument is ordered without a transmit­ter output, all signal conversion programming options are omitted in the set-up menu (s. 5.3.6. Signal Conver­sion and Transfer Functions).
All instrument settings can be conveniently done from a PC connected to the instrument through a serial inter­face adaptor. All set-up parameters can be viewed and changed on the PC screen. Also, the entire instrument set-up configuration can be loaded, stored on the PC's hard disk drive, and printed out for plant / process docu­mentation purposes. Further information about this PC software is given in the software documentation.
5.3.1 Selecting the Unit of Pressure Measurement
Make the necessary electrical connections (signal, po­wer supply) to the instrument. Its pressure sensor must be pressure-free (i.e. vented to atmosphere; typically by disconnecting the pressure line/s).
The current valid unit of measurement is indicated by one of the back-lighted symbols to the right of the digital display. To change the unit of measurement, first press
then search for parameter EEEEIIIINNNN using . Next press again and select another unit of measurement using or . Then presse again to store the selection, and EEEEIIIINNNN will appear again in the digital display.
To exit the set-up mode, press
until EEEESSSScccc appears, and
then press
. The current pressure measured value is indicated again, and the appropriate symbol of the unit of measurement (to the right of the digital display) is lighted.
The digital display is limited to a count of
±1999. Therefore, all the available units of
measurement may not be suitable for se-
lection for a given application.
3
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
5.3.2 Zero Point Checking and Adjustment
If the instrument has been de-pressurized (vented to at­mosphere) and does not indicate precisely zero, note this non-zero value. Using the set-up parameter OOOOFFFF1111, you can trim this offset to exactly zero. If the indicated non-zero value is positive, this value must be entered and stored as a negative offset value, and vice versa.
If the instrument was in use before zero setting is done, values of set-up parame­ters OOOOFFFF1111 and nnnnPPPP would have been pre­viously programmed. In this case, set both values to zero, read the actual zero
offset, and then use this value for OOOOFFFF1111 for zero point cor­rection, as described in the previous paragraph.
Note: The registered value is a pure number: no deci­mal point is indicated.
After correcting the zero offset, the pressure connecti­ons can be made again.
5.3.3 Damping and Zero Stabilization
If the media is subject to excessive pressure fluctuati­ons, the displayed readings and the transmitter output signal can be stabilized using the instrument's DDDDAAAAMMMM and
NNNNPPPP set-up parameters. The set-up parameter DDDDAAAAMMMM has the effect of a pulsation
damper (on the displayed measurements, output signal and limit detection, - not on the sensor itself!). It adds a time-constant (averaging filter) in the user selectable range of 0.0 to 100.0 secs. When the damping is set to maximum, it took more than 2 minutes to reach the final value for a full scale pressure jump.
In many cases fluctuating pressure readings do not cause a problem, except when the plant / equipment is at zero (differential) pressure condition and readings fluctuate near about zero value. The set-up parameter NNNNPPPP is meant to take of this. Its value defines the number range across zero (similar to the zero offset correction number), within which the measured value is forced to
zero. If a value of 8 is set for NNNNPPPP any pressure measure­ment in the range -0.08 to +0.08 bar (or -8 to +8 kPa) displayed as zero. Only when the actual pressure is outside this range will the display indicate a non-zero value. The actual and displayed pressures will agree
starting from double the value of the NNNNPPPP setting (in the given example: 0.16 bar or 16 kPa).
5.3.4 Output Signal Setting
The transmitter output signal depends primarily on the measured pressure. However, this signal can be adap­ted to meet users' application requirements precisely. The basic pressure range (as marked on the product identification label) and the type of output signal (volta­ge or current) always remain unchanged for a particular instrument unit.
The set-up parameters MMMMAAAA (measuring range starting point) and MMMMEEEE (measuring range end point) specify the pressure values between which the measurements are expected to be. Both values can selected anywhere
within the specified measuring range of the instrument (e.g., 400 kPa). This user-programmed pressure range will correspond to the output signal (current or voltage) range, which will be as specified on the product identifi­cation plate: i.e., 0 ... 10V or 4 ... 20 mA.
If MMMMAAAA is lower than MMMMEEEE, the signal is said to have a positi­ve slope: i.e., the output signal increases as the pressu-
re increases. If MMMMEEEE is lower than MMMMAAAA, the output signal has a negative slope: i.e., the output signal decreases as the pressure increases.
The difference between the values of MMMMAAAA and MMMMEEEE must be at least 25% of the specified measuring range of the in­strument (100 kPa for 400 kPa instrument example mentioned above). The software does not permit a smaller pressure span to be entered (the instrument will
not allow storing of, nor exit from an inva­lid span).
Note: If you change MMMMAAAA and/or MMMMEEEE the look­up table (s .5.3.6., 5.3.7.) that existed up to that instant is deleted!
5.3.5 Output Signal Limiting (Namur)
The three set-up parameters ooooGGGG1111, ooooGGGG2222 and ooooEEEErrrr specify the limits of the signal output current or voltage that are not to be exceeded, irrespective of the actual pressure. These limit values have higher priority than the MMMMAAAA and
MMMMEEEE pressure span settings. These settings serve mainly to prevent control systems
from interpreting brief pressure excursions outside the measuring range as error / fault events. ooooGGGG1111 sets the output signal minimum value, and is useful only for a 4 ... 20 mA current signal, because sometimes a value below 3.8 mA is defined as a sensor fault condition. ooooGGGG22
22 sets the upper signal limit and is valid for either current or voltage signal (e.g., voltage signal output can be limi­ted at 10.2 V).
An instrument fault condition can be transmitted as an output signal value set as parameter ooooEEEErrrr. However, it
should be understood that not all instrument fault and error conditions can be detected and signaled by the self-diagnostic functions of the instrument.
5.3.6 Signal Conversion and Transfer Functions
In certain cases other process variables are derived from primary pressure measurement. Examples are flow rate derived from differential pressure across an orifice plate, and liquid level derived from hydrostatic pressure of liquid measured at the bottom of the tank. Such derivations often involve non-linear transfer functi­ons, while it is necessary for the output signal to be line­arly proportional to the derived variable (e.g. liquid volu­me in a tank in m³, or flow rate in cm/sec).
The set-up parameter FFFF allows the user to select the ap­propriate signal conversion function from those
4
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
available:
FF
FF
= 0: Linear characteristic (default)
FFFF
= 1: Square root extraction
FF
FF
= 2: Horizontal cylindrical tank
FF
FF
= 3...30: Look-up table with 3 to 30 pairs of values
The tables generated by functions FFFF = 0, FFFF = 1 and
FF
FF
= 2 are not visible. For these functions, internal va­lues are used for table computation. These values can­not be modified directly in the table by the user. For all conversion functions, when the actual pressure is equal to the MMMMAAAA value, the output signal will be at the lowest end of its range (0 V, 0 mA or 4 mA). When the
actual pressure is equal to the MMMMEEEE value, the output sig­nal will be at the highest end of its range (10 V or 20 mA). The user can enter only the 1...28 intermediate va-
lues of the look-up table function FFFF = 3....30. The para-
meters MMMMAAAA and MMMMEEEE relate to the start and end values of the look-up table. A change in either of these parameter
values causes the conversion function to be re-set to
FF
FF
= 0.
Whenever the value of FFFF is changed, the instrument internally generates a new
look-up table. All previous table values are deleted and replaced by new linear progression va­lues.
5.3.7 Look-up Table Programming (F = 3..30)
If the value of set-up parameter FFFF is selected equal to or greater than 3, a sub-menu LLLLIIIInnnn is invoked. Through this
sub-menu all the required look-up table values can be entered, except the first and last pairs of table values (respectively corresponding to MMMMAAAA and MMMMEEEE). This sub­menu has its own entry and exit points, the latter being the last of the value pairs to be entered. The table is stored only when the user exits to the sub-menu prompt
LLLLIIIInnnn, by pressing
. If the table is not correctly entered,
the display will indicate EE
EE
rr
rr
rrrr, indicating an error conditi­on. If this happens, it is not possible to exit this sub­menu mode until the error is corrected.
The table entries consist of 1 to 28 pairs of values. Va­lues IIII00002222 through IIII22229999 (or uuuu00002222 through uuuu22229999) specify the
amplitude of the out the signal output, and the values PPPP00002222 through PPPP22229999 are the corresponding pressure values.
Entering or changing table values through the instru­ment's membrane keyboard is a tedious and error-pro­ne method. It should only be used as a stopgap method when a PC and/or the PC interface module is not available.
The table is accepted as correct if each output value is larger than its preceding value. Pressure values can be steadily increasing or steadily decreasing. However, a transition from falling to rising pressure values is not permitted; nor are pressure values allowed to turn back along the same curve.
5.3.8 Limit Setting
The two limit switching outputs
(relay contacts or solid-state switches) are each configured by four set-up parameters:
Switching output 1 is configured by parameters RRRR1111AAAA, RRRR1111EEEE, RRRR1111DDDD and RRRR1111FFFF .
Switching output 2 is configured by parameters RRRR2222AAAA, RRRR2222EEEE, RRRR2222DDDD and RRRR2222FFFF.
The turn-on and turn-off points of switching output 1 are defined respectively by parameters RRRR1111AAAA and RRRR1111EEEE. The va-
lues for these are set in the currently valid unit of mea­surement (indicated by the lighted symbol to the right of the digital display).
The two parameters RRRR1111AAAA and RRRR1111EEEE together determine the logic of switching output 1:
If RRRR1111AAAA is smaller than RRRR1111EEEE, the output turns on when the measured value exceeds RRRR1111EEEE. It turns off again only when the measured value falls below RRRR1111AAAA (hysteresis function).
If RRRR1111AAAA and RRRR1111EEEE have the same value, there is no hystere­sis: the switching output turns on when the measured value exceeds RRRR1111AAAA / RRRR1111EEEE, and turns off again when the
measured value falls below RRRR1111AAAA / RRRR1111EEEE. If RRRR1111AAAA is larger than RRRR1111EEEE, the switching output turns on
when the measured value falls between RRRR1111AAAA and RRRR1111EEEE: i.e., when RRRR1111EEEE < measured value < RRRR1111AAAA (window limit
function). Both parameters can be independently adjusted over
the full measuring range. If the unit of measurement is changed, the switching
points are changed accordingly. In this event, rounding error can cause a deviation in the least significant (right­most) digit.
The value of the set-up parameter RRRR1111DDDD determines the delay time for switching output 1, after the measured value reaches the switching point. The delay value can be selected in the range 0.0 to 100.0 secs. This value applies equally to turn on and turn off.
The set-up parameter RRRR1111FFFF determines the action of the switching output. If RRRR1111FFFF = 1, the switching output acts as normally open (NO) contacts. If RRRR1111FFFF = 2, it acts as nor-
mally closed (NC) contacts.
5.3.9 Password
The last set-up parameter allows a password to be en­tered. A password value of 001 to 999 can be selected. A value of 000 disables the password function.
If a password was set previously the digital display indi­cates PPPPAAAASSSS after EEEESSSScccc is displayed and
is pressed. The
password is then entered, by pressing and then , . Only then will the set-up menu options be accessible. If an incorrect password is entered, the display jumps
5
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
back to beginning of the menu (i.e., EEEESSSScccc).
New Functions! (as of April 2008)
5.3.10 DD
DD0000
– Display options
This parameter allows smoothing the displayed values in cases where they are frequently deviating. The filter
function is similar to the dd
ddAAAAMMMM
function, but acts only upon the display, having no impact on the output signal. Additionally the display can be turned off partially
(DD
DD0000
= -1, only the setpoint LEDs are driven) or comple-
tely (DD
DD0000
= -2).
5.3.11 rr
rreeeessss
– Reset to default values
This function will reset all parameters to default when activated. Default values can be defined only by using the PC interface.
5.3.12 MM
MMAAAAFFFF,,,, MMMMEEEEFFFF,,,, ddddPPPPFFFF
– Free Unit
If the device is configured to have a free third unit
(symbol:
) then the display can be scaled as desired
by using these three parameters. The measuring range as defined by parameters MMMMAAAA and
MMMMEEEE is rescaled to MMMMAAAAFFFF and MMMMEEEEFFFF. If the table function (FFFF ) is enabled, table values will be taken into account too.
The ddddPPPPFFFF value controls the position of the decimal point.
5.4 Overview of Set-up Parameters
When the instrument is turned on, it briefly displays the software version number, and then switches automati­cally to normal operating mode. Pressing
causes the set-up menu to be called up, indicated by EEEESSSScccc on the di­gital display. After that, by pressing repeatedly, each
of the set-up parameters is called up in sequence:
Note: Depending on the version of the instru­ment that was ordered, some of the individual parameters might not be available.
PPPPAAAASS
SS
Password input (appears only if password function has been enabled). Values: 001 to 999
DDDDAAAAMM
MM
Damping (time constant). Range of values = 0.0 to 100.0 secs
DDDD00
00
Damping (display only), range of values
0..100. Additional: -1 = no digital value and
-2 = display turned off completely.
RRRR1111AA
AA
Switching output 1: turn-off point.
RRRR1111EE
EE
Switching output 1: turn-on point.
RRRR1111DD
DD
Switching output 1: delay. Range of values = 0.0 to 100.0 sec. This values applies equally for turn-on and turn-off delays.
RRRR1111FF
FF
Switching output 1 action. If RR
RR1111FFFF
= 1, acts as
NO contacts. If RR
RR1111FFFF
= 2, acts as NC contacts.
RRRR2222AA
AA
Switching output 2: turn-off point.
RRRR2222EE
EE
Switching output 2: turn-on point.
RRRR2222DD
DD
Switching output 2: delay. Range of values = 0.0 to 100.0 sec. This values applies equally for turn-on and turn-off delays.
RRRR2222FF
FF
Switching output 2 action. If RR
RR1111FFFF
= 1, acts as
NO contacts. If RR
RR1111FFFF
= 2, acts as NC contacts.
EEEEiiiiNN
NN
Unit of measurement. The selection is indica­ted by the lighted symbol to the right of the di­gital display. A particular unit can be selected only if it can be meaningfully represented within the basic measuring range of the instru­ment.
MMMMAA
AA
Measuring range start point. The value of the measured variable corresponding with the mi­nimum value of the output signal (0 V, 0 mA or 4 mA, depending on the instrument version).
MMMMEE
EE
Measuring range end point. The value of the measured variable corresponding with the maximum value of the output signal (10 V or 20 mA, depending on the instrument version).
DDDDPPPPFF
FF
Position of decimal place for free unit.
MMMMAAAAFF
FF
Measuring range start point (displayed value) for free unit.
MMMMEEEEFF
FF
Measuring range end point (displayed value) for free unit.
NNNNPP
PP
Zero stabilization. Range = 0 to 100 counts. The value spans symmetrically around the ac­tual zero point.
OOOOFFFF11
11
Zero offset correction, input 1. Range = -100 to +100 counts.
FF
FF
Signal conversion function. (0 = linear, 1 = square root, 2 = horizontal cylindrical tank,
3..30 = look-up table)
llllIIIInn
nn
Look-up table entry (sub-menu)
ooooGGGG11
11
Output signal limiting, minimum
OOOOGGGG22
22
Output signal limiting, maximum
OOOOEEEErr
rr
Fault signaling (output signal value on detec­tion of instrument fault).
RRRREEEESS
SS
Reset all values to default. (Default values can be defined only by using the PC inter-
face.)
----PPPP--
--
Password setting. Permissible password va­lues = 001 to 999. "000" disables password protection.
6
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
If the password is lost, the instrument can be unlocked only through a serial interfaced PC, or the instrument has to be sent to the manu­facturer for this purpose
If ooooGGGG1111 and OOOOGGGG2222 are both set to "0", the out­put signal will not be subjected to limiting.
If ooooGGGG1111 is set at the maximum value (11 V or 21 mA), the output signal can be ad-
justed using OOOOGGGG2222 to any arbitrary value
between zero and maximum value, irre­spective of pressure measurement. This feature enab­les the instrument to be used as a simulated signal source to test signal lines and other instruments or sys­tems.
5.5 Electrical Connections, Switching Outputs
Switching outputs:
Switching output 1 is configured by parameters RRRR1111AAAA, RRRR1111EEEE, RRRR1111DDDD, and RRRR1111FFFF.
Switching output 2 is configured by parameters RRRR2222AAAA, RRRR2222EEEE, RRRR2222DDDD, and RRRR2222FFFF.
Power supply voltage and output signal load:
Nominal supply voltage and the operating supply volta­ge range are indicated under 11. Specifications.
The maximum output signal loads are indicated under
11. Specifications. The signal ground line is internally connected to the in-
strument ground, and serves only as an alternative ground connection for the output signal. This usually in­creases the noise margin.
5.6 Default parameter (Model C)
Does not apply to replacement instruments of model B, see thererfore chapter 5.7.
5.7 Default parameter (instruments as a replacement for model B)
7
Parameter Einstellwert Einhe
BASE MEASURING RANGE OFFSET-ADJUSTMENT
0
0
1 bar
DAMPING ZERO WINDOW DISPLAY OPTION DISPLAY OF DAMPING
5
100
Display of damping [do>0]
2
s
s DENOTATION UNIT RELAY TRIPPING POINT 1 RELAY SWITCHING POINT 1
DE3802DYYPKD410
l/min acc. to equipment list acc. to equipment list
RELAY DECELERATION 1 RELAY FUNCTION 1 RELAY TRIPPING POINT 2 RELAY SWITCHING POINT 2
10
Shutter acc. to equipment list acc. to equipment list
s
RELAY DECELERATION 2 RELAY FUNCTION 2 MEASURING RANGE 4 mA at
MEASURING RANGE 20 mA at
10
Shutter
0
acc. to adjustment of oil
density
LINEARISATION RATE OF FLOW at start RATE OF FLOW at last DECIMAL PLACES
0
acc. to equipment list
s
bar bar
LIMITATION Imin LIMITATION Imax LIMITATION Ierror
1 21 21
mA mA mA
Parameter Einstellwert Einheit
BASE MEASURING RANGE OFFSET-ADJUSTMENT
0
0
1 bar
DAMPING ZERO WINDOW DISPLAY OPTION DISPLAY OF DAMPING
5
100
Display of damping [do>0]
2
s
s DENOTATION UNIT RELAY TRIPPING POINT 1 RELAY SWITCHING POINT 1
DE3802DYYPKD410
bar
0
0 RELAY DECELERATION 1 RELAY FUNCTION 1 RELAY TRIPPING POINT 2 RELAY SWITCHING POINT 2
10
Shutter
0
0
s
RELAY DECELERATION 2 RELAY FUNCTION 2 MEASURING RANGE 4 mA at MEASURING RANGE 20 mA at
10
Shutter
0
1 LINEARISATION RATE OF FLOW at start RATE OF FLOW at last DECIMAL PLACES
0 (straight line)
0
1000
0.000
s
bar bar
LIMITATION Imin LIMITATION Imax LIMITATION Ierror
1
21 21
mA mA mA
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
6 Maintenance
The instrument is inherently maintenance-free. However, to ensure reliable operation and maximize the
operating life of the instrument, it is recommended that the instrument, its external electrical and process con­nections, and external connected devices be regularly inspected, e.g.:
 Check the display.
 Check the switching function in connection with ex-
ternal devices.
 Check all pressure connections for leak-tightness.
 Check the integrity of all electrical connections of the
instruments.
Inspection and test schedules depend on operating and site conditions. The operating manuals of other equip­ment to which the transmitter is connected must be read thoroughly to ensure that all of them work correctly when connected together.
7 Transport
The product must be protected against shock and vibra­tion during transport. It must therefore be properly pa­ked, preferably in the original factory packaging whene­ver it is to be transported.
8 Service
Any defective devices or devices with missing parts should be retourned to Fischer Mess- und Regeltechnik GmbH. For quick service contact our service depart­ment.
Remaining medium in and on dismantled measuring in­struments may cause danger to persons, environment and equipment. Take reasonable precautions! Clean the instrument thoroughly if necessary.
9 Assessories
 M12 connectors with pre-wired cable lengths
(on request)
 PC serial interface adaptor with software:
model EU03.F300
10 Disposal
P rote ct yo u r e n v i ro nm en t! Use the product
in accordance with relevant regulations. Please be aware of environmental conse­quences of disposal at the end of the pro­duct's life, and take care accordingly.
8
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
9
Measuring range
bar 0-1,000
max. static operating pressure straight line error (max.)°
bar
%FS
25 bar
2,50%
Straight line error (typ.)°
Tc span (max.)°° Tc span (typ.)°° Tc zero point (max.)°°
%FS
%FS /
10K
0,80%
0,40%
%FS /
10K
%FS /
10K
0,20%
0,50%
°: Straight line error = nonlinearity + hystere­sis; at 25°C; pressure within specified range (characteristic linear, not spreaded)
°°: Pressure within specified range (characte­ristic linear, not spreaded); compensated tem­perature range 0 to 60°C
Tc zero point (typ.)°°
%FS /
10K
0,20%
Operating temp. (ambient) -10  70°C
Operating temp. (media)
Storage temperature
-10  70°C
-20  70°C
Protection class (housing)
Nominal supply voltage
IP 65 acc. to DIN EN 60529
E lectrica l
24 V DC/AC
Operating supply voltage
Output signal
Output signal load
Power consumption
12  32 V DC/AC
4  20 mA square root
For output current RL
(UB - 4 V) / 0,02 A (UB 26V), else RL 1100
Approx. 2 W/VA
Switching contacts
Display
2 sets of programmable voltage free relay contacts: NO or NC Umax = 32 V DC/AC, Imax = 2 A, Pmax = 64 W/VA 3½ digit. LED
Electrical connections
C o n n e ctio n s
Two round-shell multi-pin connector sockets (M12, male) Connector 1: 5-pin: power input and analog signal output Connector 2: 4-pin: relay contacts / solid-state switch outputs
Pressure connections
Materials, housing
at the upper part of the volume flow-measurement
M ate ria ls, M ountin g
Polyamid PA 6.6
Materials, media contact
Mounting
Aluminum hartcoat, VITON® Rear mounting holes for panel mounting
11 Specifications
11.1 General
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
10
11.2 User- specific Data
Differential pressure transmitter DE38D410
Measurement range 0  1 bar
Static operating pressure 25 bar Diaphragm and sealing of Viton Pressure chamber Alu/hartcoat output signal 4-20 mA square rooted, three-wire-system Operating voltage 24 V DC/AC 3 ½-digit LED display Display unit: bar, l/min., m³/h 2 voltage free relay contacts Electrical connection M12-Stecker Protection class IP65 nach DIN EN 60529 Mounting form as flow control device- top Flender-works standard W3 5927 Housing cover blue RAL 5005 User-specific membrane keyboard with Flender-Logo
S e ttings:
Input filtering
Relay / switch 1 / 2
0.0 ... 100.0 secs (10 / 90% step response time) for signal output, display seperated
activation point, de-activation point, response time delay (0.0 ...
100.0 secs), logic (N/O or N/C)
Measurement unit selection
Zero suppression
Setting of oil-density
Zero pressure calibration
bar, l/min, m³/h 0 ... 100 Digits (1)
±100 counts (3)
Output characteristic
Password range
linear, square rooted, horizontal cylindr. tank, table (3...30 entries) 001 ... 999 (000 = password protection disabled)
0,88
0,830
0,890,839
0,900,848
0,910,858
0,920,867
0,930,877
0,940,886
0,950,896
0,960,905
0,970,914
0,980,924
0,990,933
1,000,943
1,010,952
1,020,962
1,030,971
1,040,980
1,050,990
Oil density differential pressure [bar]
"measuring range 20mA bei 0, xxx bar"
11.3 Programming
Via membrane key switches or by using PC-programming interface (accessory), programming mode can be pas-
word protected.
Notes: (1): Measured value deviations up to 100 counts symmetric about zero are set to zero. Used for zero drift suppression. (2): Maximum effective turn-down ratio = 4:1. Only the output signal is affected. Transfer function is inverted if start value > end value. (3): Zero calibration setting may change with mounting orientation.
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
11
12 Dimensions (all units in mm unless stated otherwise)
Anschlussschema / Schaltfunktion
view of rear side
rear side
M 12 connector
No. 1
M 12 connector
No. 2
Electrical Connections / Switching Outputs
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
12
13 CE- Certificate
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
Loading...