FISCHER DE38D410, DE38 Instruction Manual

1 Safety Instructions
1.1 General
This manual contains detailed infor­mation about the product, and in­structions for its installation, opera­tion and maintenance. Operators
and other technical personnel re­sponsible for the equipment must read this tho­roughly before attempting to install or operate this equipment. A copy of this manual must always be kept accessible at the place of work for reference by concerned personnel.
Chapter 1 (sections 1.2 through 1.7) contains ge­neral as well as specific safety instructions. Chapters 2 through 10, covering topics ranging from intended purpose of the equipment to its fi­nal disposal, also include important points rela­ting to safety. Overlooking or ignoring any of the­se safety points can endanger humans and ani­mals, and possibly cause damage to other equip­ment.
1.2 Personnel Qualification
Personnel responsible for installation, operation, maintenance and inspection of this product must have the qualifications, training and experience necessary to carry out such work on this type of equipment.
1.3 Risks of Disregarding Safety Instructions
Disregarding safety instructions, use of this pro­duct for purposes for which it is not intended, and/or operation of this product outside the limits specified for any of its technical parameters, can result in harm to persons, the environment, or the plant on which it is installed. Fischer Mess- und Regeltechnik GmbH will not be responsible for consequences in such circumstances.
1.4 Safety Instructions for Operators
Safety instructions for the proper use of this pro­duct must be followed. This information must be available at all times to by personnel responsible for installation, operation, maintenance and in­spection of this product.
Adequate steps must be taken to prevent the occurrence of hazardous conditions that can be caused by electric energy and the convertible energy of the process media. Such conditions can, for example, be the result of improper electrical or process connections.
Detailed information is available in relevant pub­lished norms (DIN EN, UVW in Germany; and equivalents in other countries), industrial stan­dards such as DVWG, EG-, GL-, VDE guidelines, as well as regulations of the local authorities ( e.g., EVUs in Ger­many).
               
# 09005136 26.03.2009 BA_D_DE38_D410
Ins tru ctio n M anu al
D E 3 8
D ig ita l D iffe re ntia l P re ss ure Tra nsm itte r / S witch
DE38D410
Inhalt
1 Safety Instructions .......................................1
2 Intended Applications...................................2
3 Product Description and Functions..............2
4 Installation....................................................2
5 Commissioning ............................................3
6 Maintenance ................................................8
7 Transport......................................................8
8 Service.........................................................8
9 Accessories..................................................8
10 Disposal.......................................................8
11 Specifications...............................................9
12 Dimensions ................................................11
13 CE-Certificate.............................................12
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
1.5 Modifications Forbidden
Modification or other technical alteration of the product is not permissible. This also applies to the use of un­authorized spare parts for repair / maintenance of the product. Any modifications to this product, if and as ne­cessary, should be done only by Fischer Mess- und Re­geltechnik GmbH.
1.6 Operational Restrictions
The operational reliability of the product is guaranteed only when used for intended purposes. The product must be selected and configured for use specifically with defined process media. The limiting values of ope­rating parameters, as given in the product specification sheet, must never be crossed.
1.7 Safety Considerations during Installation and Mainte­nance
The safety instructions given in this manual, existing na­tional regulations relating to accident prevention, and the internal safety rules and procedures of the user or­ganization regarding safety during installation, operation and servicing must all be followed meticulously.
It is the responsibility of the users to ensure that only suitably qualified and experienced technical personnel are used for installation, operation and servicing of this equipment.
2 Intended Applications
The product includes the functions of sensing, signal conversion, display, signal transmission, and limit de­tection of pressure / differential pressure of gases and liquids. The product must be used only for applications and under conditions specified by the manufacturer. In case of uncertainties, the user should consult the manu­facturer before installing and using the product.
3 Product Description and Functions
3.1 Block Schematic Diagram
3.2 Principles of Operation
The instrument uses a tough, robust sensing dia­phragm, which is qualified for over-, low- and differenti­al pressure measurings. The comparative pressures work on a elastic bedded measuring diaphragm. The di­aphragm is at zero position when pressures on either side of the diaphragm are equal.Inequality of pressures results in deflecting the diaphragm towards the lower pressure side until a new equilibrium determined by the spring power is reached. This deflection is transmitted by a tappet to the center of a inductive travel sensor. The integrated electronics analyzes the deflection and converts it into display, switch contacts and output sig­nal.
4 Installation
The instrument is intended for the assembly on the base of the Flender circulatory- measurement.
At the installation of the upper part there should be paid attention to the correct adjustment. The operator must be able to regulate and read the instrument from a safe place.
The sealing faces and the O- ring seals must not be da­maged!
The instrument is adjustet for a vertical mounting positi­on. Other positions aren't sensibel because of the clear­ness of reading the digital display.
If the instrument is intended for outdoor application, we highly recommend using an ade-quate protective hou­sing (or at least a big enough shelter) as permanent protection against UV-radiation on the membrane key­board and against exposure of the instrument to rain or snow.
4.1 Process Connections
 Ensure that process equipment and pressure lines
are at atmospheric pressure before making pressure connections.
 The instrument should be provided with suitable pro-
tection against pressure surges (e.g., snubber or pulsation damper).
 Ensure that the mechanical configuration and mate-
rials of construction of the instrument are compatible with the process media.
 Take account of the maximum pressure.
 Carefully check the pressure-tightness of all pressu-
re connections before start-up.
4.2 Electrical Connections
 Only qualified technicians authorized for this type of
work should undertake installation.
 Electrical connections must comply with relevant in-
ternational, national and local regulations and norms relating to electrical and instrumentation installati­ons.
2
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
 Switch off electrical power to the plant before at-
tempting electrical installation work of any kind.
 Make electrical connections to the transmitter
through a suitable energy-limiting safety device (iso­lation or zener barrier).
5 Commissioning
 Power supply and signal cabling to the transmitter
must be correctly selected to meet operational requi­rements, and installed in a way that does not cause physical stress to the instrument.
 Pressure lines must have a downward gradient
throughout from the pressure instrument to the pro­cess vessel / pipe. This is to prevent formation of air / gas pockets (for liquid applications) and liquid plugs (for air / gas applications). If this continuous down­ward gradient cannot be provided for any reason, then suitable water and / or air separation devices must be inserted into the pressure lines.
 Pressure lines must be kept as short as possible and
must not have short bends to avoid measurement errors induced by pressure line delays.
5.1 Pressure Connections
If the pressure transmitter is subjected to pressure when it is started up, zero point checking and adjust­ment is not possible. In such cases, only electrical con­nections of the instrument should be made, but not the pressure connections.
5.2 Display
The 3½ digit LED display normally indicates the current differential pressure. The backlit symbols to the right of the 3½ digit LED display indicate the unit of pressure measurement. (Note: the units shown in the illustrations of this document can be different from those of the actu­al instrument). The two LED lamps above the 3½ digit LED display respectively indicate the status of the two limit relays / solid-state switches
(LED on = relay
contacts closed / solid-state switch on). While the instrument is in set-up mode, the 3½ digit
LED display either indicates the selected menu option or a set-up parameter value. The instrument continues its pressure monitoring functions even while it is in set­up mode, except under either of two circumstances.
One is when the limit switching delay time is changed: the existing delay must time out first. The other is when the look-up table (for conversion of measured values) is re-programmed (s. 5.3.7.). In these circumstances, the output signal value and the limit relay/switch states are frozen until the changes are finalized.
5.3 Set-up
The instrument has comprehensive set-up options by means of which it can be optimized for any specific measuring or control application. This section of the document provides information and instructions about each of the set-up parameters.
Depending on the instrument configurati­on ordered (e.g.: without transmitter signal output / with voltage signal output / with current signal output) some of the menu
options may not available. Some set-up parameters may be consequentially excluded. For example, if the instrument is ordered without a transmit­ter output, all signal conversion programming options are omitted in the set-up menu (s. 5.3.6. Signal Conver­sion and Transfer Functions).
All instrument settings can be conveniently done from a PC connected to the instrument through a serial inter­face adaptor. All set-up parameters can be viewed and changed on the PC screen. Also, the entire instrument set-up configuration can be loaded, stored on the PC's hard disk drive, and printed out for plant / process docu­mentation purposes. Further information about this PC software is given in the software documentation.
5.3.1 Selecting the Unit of Pressure Measurement
Make the necessary electrical connections (signal, po­wer supply) to the instrument. Its pressure sensor must be pressure-free (i.e. vented to atmosphere; typically by disconnecting the pressure line/s).
The current valid unit of measurement is indicated by one of the back-lighted symbols to the right of the digital display. To change the unit of measurement, first press
then search for parameter EEEEIIIINNNN using . Next press again and select another unit of measurement using or . Then presse again to store the selection, and EEEEIIIINNNN will appear again in the digital display.
To exit the set-up mode, press
until EEEESSSScccc appears, and
then press
. The current pressure measured value is indicated again, and the appropriate symbol of the unit of measurement (to the right of the digital display) is lighted.
The digital display is limited to a count of
±1999. Therefore, all the available units of
measurement may not be suitable for se-
lection for a given application.
3
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
5.3.2 Zero Point Checking and Adjustment
If the instrument has been de-pressurized (vented to at­mosphere) and does not indicate precisely zero, note this non-zero value. Using the set-up parameter OOOOFFFF1111, you can trim this offset to exactly zero. If the indicated non-zero value is positive, this value must be entered and stored as a negative offset value, and vice versa.
If the instrument was in use before zero setting is done, values of set-up parame­ters OOOOFFFF1111 and nnnnPPPP would have been pre­viously programmed. In this case, set both values to zero, read the actual zero
offset, and then use this value for OOOOFFFF1111 for zero point cor­rection, as described in the previous paragraph.
Note: The registered value is a pure number: no deci­mal point is indicated.
After correcting the zero offset, the pressure connecti­ons can be made again.
5.3.3 Damping and Zero Stabilization
If the media is subject to excessive pressure fluctuati­ons, the displayed readings and the transmitter output signal can be stabilized using the instrument's DDDDAAAAMMMM and
NNNNPPPP set-up parameters. The set-up parameter DDDDAAAAMMMM has the effect of a pulsation
damper (on the displayed measurements, output signal and limit detection, - not on the sensor itself!). It adds a time-constant (averaging filter) in the user selectable range of 0.0 to 100.0 secs. When the damping is set to maximum, it took more than 2 minutes to reach the final value for a full scale pressure jump.
In many cases fluctuating pressure readings do not cause a problem, except when the plant / equipment is at zero (differential) pressure condition and readings fluctuate near about zero value. The set-up parameter NNNNPPPP is meant to take of this. Its value defines the number range across zero (similar to the zero offset correction number), within which the measured value is forced to
zero. If a value of 8 is set for NNNNPPPP any pressure measure­ment in the range -0.08 to +0.08 bar (or -8 to +8 kPa) displayed as zero. Only when the actual pressure is outside this range will the display indicate a non-zero value. The actual and displayed pressures will agree
starting from double the value of the NNNNPPPP setting (in the given example: 0.16 bar or 16 kPa).
5.3.4 Output Signal Setting
The transmitter output signal depends primarily on the measured pressure. However, this signal can be adap­ted to meet users' application requirements precisely. The basic pressure range (as marked on the product identification label) and the type of output signal (volta­ge or current) always remain unchanged for a particular instrument unit.
The set-up parameters MMMMAAAA (measuring range starting point) and MMMMEEEE (measuring range end point) specify the pressure values between which the measurements are expected to be. Both values can selected anywhere
within the specified measuring range of the instrument (e.g., 400 kPa). This user-programmed pressure range will correspond to the output signal (current or voltage) range, which will be as specified on the product identifi­cation plate: i.e., 0 ... 10V or 4 ... 20 mA.
If MMMMAAAA is lower than MMMMEEEE, the signal is said to have a positi­ve slope: i.e., the output signal increases as the pressu-
re increases. If MMMMEEEE is lower than MMMMAAAA, the output signal has a negative slope: i.e., the output signal decreases as the pressure increases.
The difference between the values of MMMMAAAA and MMMMEEEE must be at least 25% of the specified measuring range of the in­strument (100 kPa for 400 kPa instrument example mentioned above). The software does not permit a smaller pressure span to be entered (the instrument will
not allow storing of, nor exit from an inva­lid span).
Note: If you change MMMMAAAA and/or MMMMEEEE the look­up table (s .5.3.6., 5.3.7.) that existed up to that instant is deleted!
5.3.5 Output Signal Limiting (Namur)
The three set-up parameters ooooGGGG1111, ooooGGGG2222 and ooooEEEErrrr specify the limits of the signal output current or voltage that are not to be exceeded, irrespective of the actual pressure. These limit values have higher priority than the MMMMAAAA and
MMMMEEEE pressure span settings. These settings serve mainly to prevent control systems
from interpreting brief pressure excursions outside the measuring range as error / fault events. ooooGGGG1111 sets the output signal minimum value, and is useful only for a 4 ... 20 mA current signal, because sometimes a value below 3.8 mA is defined as a sensor fault condition. ooooGGGG22
22 sets the upper signal limit and is valid for either current or voltage signal (e.g., voltage signal output can be limi­ted at 10.2 V).
An instrument fault condition can be transmitted as an output signal value set as parameter ooooEEEErrrr. However, it
should be understood that not all instrument fault and error conditions can be detected and signaled by the self-diagnostic functions of the instrument.
5.3.6 Signal Conversion and Transfer Functions
In certain cases other process variables are derived from primary pressure measurement. Examples are flow rate derived from differential pressure across an orifice plate, and liquid level derived from hydrostatic pressure of liquid measured at the bottom of the tank. Such derivations often involve non-linear transfer functi­ons, while it is necessary for the output signal to be line­arly proportional to the derived variable (e.g. liquid volu­me in a tank in m³, or flow rate in cm/sec).
The set-up parameter FFFF allows the user to select the ap­propriate signal conversion function from those
4
Contact: EK Engineering (www.ekeindia.com) Email: india.eke@gmail.com Mob: +91-9680966000
Loading...
+ 8 hidden pages