7
5.4. Overview of Set-up Parameters
the instrument is turned on, it briefly displays the software version number, and then switches automatically to
normal operating mode. Pressing û causes the set-up
menu to be called up, indicated by Esc on the digital display. After that, by pressing þ repeatedly, each of the
set-up parameters is called up in sequence:
Note: Depending on the version of
the instrument that was ordered,
some of the individual parameters
might not be available.
• PAS Password input (appears only if password
function has been enabled). Values: 001 to 999
• DAM Damping (time constant). Range of values
= 0.0 to 100.0 secs
• D0 Damping (display only), range of values 0..100.
Additional: -1 = no digital value and -2 = display
turned off completely.
• R1A Switching output 1: turn-off point.
• R1E Switching output 1: turn-on point.
• R1D Switching output 1: delay. Range of values =
0.0 to 100.0 sec. This values applies equally for
turn-on and turn-off delays.
• R1F Switching output 1 action. If R1F = 1, acts as
NO contacts. If R1F = 2, acts as NC contacts.
• R2A Switching output 2: turn-off point.
• R2E Switching output 2: turn-on point.
• R2D Switching output 2: delay. Range of values =
0.0 to 100.0 sec. This values applies equally for
turn-on and turn-off delays.
• R2F Switching output 2 action. If R1F = 1, acts as
NO contacts. If R1F = 2, acts as NC contacts.
• EIN Unit of measurement. The selection is indicated by the lighted symbol to the right of the
digital display. A particular unit can be selected
only if it can be meaningfully represented within
the basic measuring range of the instrument.
• MA Measuring range start point. The value of the
measured variable corresponding with the
minimum value of the output signal (0 V, 0 mA
or 4 mA, depending on the instrument version).
• ME Measuring range end point. The value of the
measured variable corresponding with the maximum value of the output signal (10 V or
20 mA, depending on the instrument version).
• dPF Position of decimal place for free unit.
• MAF Measuring range start point (displayed value)
for free unit.
• MEF Measuring range end point (displayed value)
for free unit.
• NP Zero stabilization. Range = 0 to 100 counts.
The value spans symmetrically around the
actual zero point.
• OF1 Zero offset correction, input 1. Range = -100 to
+100 counts.
• F Signal conversion function. (0 = linear,
1 = square root,
2 = horizontal cylindrical tank,
3..30 = look-up table)
• lIn Look-up table entry (sub-menu)
• oG1 Output signal limiting, minimum
• OG2 Output signal limiting, maximum
• OEr Fault signaling (output signal value on detec-
tion of instrument fault).
• res Reset all values to default. (Default values can
be defined only by using the PC interface.)
• -P- Password setting. Permissible password valu-
es = 001 to 999. "000" disables password protection.
If the password is lost, the instrument can be unlocked only through a
serial interfaced PC, or the instrument has to be sent to the manufacturer for this purpose.
If oG1 and oG2 are both set to "0", the
output signal will not be subjected to
limiting.
If oG1 is set at the maximum value
(11 V or 21 mA), the output signal can
be adjusted using oG2 to any arbitrary
value between zero and maximum val-
ue, irrespective of pressure measurement. This feature enables the instrument to be used as
a simulated signal source to test signal lines and other instruments or systems.