Smoke particles of varying number and size are produced in all fires.
materials rapidly and spread quickly. Sources of these fires may include
paper burning in a wastebasket, or a grease fire in the kitchen.
before bursting into flame. Sources of these fires may include cigarettes
burning in couches or bedding.
For maximum protection, use both types of Smoke Alarms on
each level and in every bedroom of your home.
fairs: (800) 323-9005 • www
®
Smoke Alar
t
Ionization technology is generally mor
technology at detecting small particles, which tend to be produced
in greater amounts by flaming fires, which consume combustible
Photoelectric technology is generally more sensitive than ionization
technology at detecting lar
in greater amounts by smoldering fires, which may smolder for hours
This user’s manual contains important information about your
Combination Carbon Monoxide & Smoke Alarm’
installing this Alarm for use by others, you must leave this manual—or
a copy of it—with the end user.
s operation. If you are
INTRODUCTION
Thank you for choosing First Alert®for your Smoke and Carbon
Monoxide Alarm needs. Y
Carbon Monoxide Alarm designed to provide you with early warning of a
smoke and/or Carbon Monoxide danger
Smoke & Carbon Monoxide Combination Alar
against two deadly household threats.
ONELINK®Enabled. Alarm automatically communicates with other
ONELINK
Exclusive Voice Warning with Location will tell you the preprogrammed
location of the initiating unit and danger detected. Pr
11 locations (ex. "basement"). When alarms sounds, if pr
basement it will say "Warning, evacuate, smoke in basement" along with
all other installed ONELINK
Spr
makes it easier for elderly with normal age related hearing loss to hear
hor
RF Interconnect. Reliable and secure radio frequency communication
between alarms. 915 MHz frequency with 65,000 security codes and 3
channel fr
Single Button Test/Silence eliminates confusion. Depending on what
mode the alarm is in, pushing the button provides different functions
such as testing
in silence and clearing the Latching features.
Two Silence Features. Temporarily silence low battery chirp for up to
eight hours befor
for several minutes.
Two Latching Features. Alarm Latch: Easily identifies initiating alarm
even after alarm condition has subsided. Low Battery Latch: Identifies
which unit is in low battery condition.
Perfect Mount System includes a gasketless base for easy installation
and a mounting bracket that keeps the alarm secure over a wide
rotation range to allow for perfect alignment.
6 Year End of Life Timer. Every 24 hours of operation a counter stored
in memory is updated. When the count equals 6 years of true operation,
meaning actually powered-up, a malfunction chirp (triple chirp) will
sound once a minute at the time of the 45 second Power-LED flash.
®
enabled alarms when installed.
ead Spectrum Horn Tone.
n. Sweeps through the 2200 – 3400 Hz range.
equency hopping.
the alarm, silencing the alarm, re-testing the alarm when
ou have purchased a state-of-the-art Smoke &
.
Key featur
®
oice alarms.
V
Lower and varying hor
es include:
m.
One alarm pr
ogrammable up to
ogrammed for
n frequency
otects
e replacing low battery or silence an unwanted alarm
WIRELESS OPERATION
First Alert®ONELINK®Technology is the easy, cost-effective way to
provide your family with whole-home safety. All ONELINK®Alarms
communicate with each other without wires or connectors. When one
Alarm sounds, they all sound. This provides your family with an earlier
warning of potential danger, and gives you more time to react.
The communication distance (range) between any two ONELINK
is typically 50 feet (15 meters) inside of a home. Some features of a
home, such as the number of floors, number/size of rooms, furniture and
types of building materials used may reduce the range of the Alarms.
Examples include: suspended ceilings, ductwork, large metallic appliances (refrigerators) and metal studs. A feature of ONELINK
that they operate as a mesh network. All Alarms will repeat any alarm
signal that is r
structural conditions can be over
route the wireless signal around obstructions.
• The range and proper operation of any wireless device will
•
•
Your First Alert®ONELINK®Smoke/CO Alarm will automatically communicate both potential fires and carbon monoxide presence with all other
First Alert®ONELINK®Smoke/CO Alarms.
FCC NOTICE: This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired
operation. FCC ID: M7U5001L
Changes or modifications not expressly approved by BRK Brands,
Inc. could void the user
eceived to all other ONELINK
y depending on its sur
var
each Alarm is tested individually before and after installation
to make sur
The
transmit between buildings. The Alarms will not communicate
properly under these conditions.
Metal objects and metallic wallpaper may inter
signals from wireless Alarms. Alarms should be tested after
changes to your home such as remodeling, moving furniture,
and with metal doors opened and closed.
ONELINK
e that all Alar
®
Alar
come by adding additional Alarms to
r
ms respond properly.
e not to be used outdoors or to
ms ar
’s authority to operate the equipment.
®
Alarms. Interfer
oundings. It is very important that
®
Alarms is
ence from
fere with
®
Alarms
1
FIRE SAFETY TIPS
Follow safety rules and pr
materials pr
away from children; 3) Store flammable materials in proper containers;
4) Keep electrical appliances in good condition and don’
electrical circuits; 5) Keep stoves, barbecue grills, fireplaces and
chimneys grease- and debris-free; 6) Never leave anything cooking on
the stove unattended; 7) Keep portable heaters and open flames, like
candles, away from flammable materials;8) Don’t let rubbish accumulate.
Keep alarms clean, and test them weekly. Replace alarms immediately
if they ar
alert you to a fir
floor, and an additional one in the kitchen. Have fire escape ladders or
other r
blocked.
operly. Never smoke in bed. 2) Keep matches or lighters
e not working properly. Smoke Alarms that do not work cannot
e. Keep at least one working fire extinguisher on every
eliable means of escape from an upper floor in case stairs are
BASIC SAFETY INFORMA
• Dangers, Warnings, and Cautions alert you to important
operating instr
Pay special attention to these items.
This Smoke/CO Alarm is approved for use in single-family
•
esidences.
r
•
This combination Smoke/Carbon Monoxide Alarm has two
separate alarms. The CO Alarm is not designed to detect fire
or any other gas. It will only indicate the pr
monoxide gas at the sensor. Carbon monoxide gas may be
present in other areas. The Smoke Alarm will only indicate the
esence of smoke that reaches the sensor. The Smoke Alarm
pr
is not designed to sense gas, heat or flames.
• This Smoke/CO Alarm cannot operate without working
batteries. Removing the batteries for any reason, or failing to
replace the batteries at the end of their service life, removes
your protection.
• NEVER ignore any alarm. See “If Your Smoke/CO Alarm
Sounds” for mor
e to respond can result in injury or death.
Failur
• The Silence Features are for your convenience only and will
not correct a problem. See "Using the Silence Features" for
details. Always check your home for a potential problem after
any alarm. Failure to do so can result in injury or death.
• Test this Smoke/CO Alarm once a week. If the Alarm ever fails
to test correctly, have it replaced immediately! If the Alarm is
not working properly, it cannot alert you to a problem.
• This product is intended for use in ordinary indoor locations
of family living units. It is not designed to measure CO levels
in compliance with Occupational Safety and Health
Administration (OSHA) commercial or industrial standards.
Individuals with medical conditions that may make them more
sensitive to carbon monoxide may consider using warning
devices which provide audible and visual signals for carbon
monoxide concentrations under 30 ppm. For additional
information on carbon monoxide and your medical condition
contact your physician.
event hazardous situations: 1) Use smoking
t overload
TION
uctions or to potentially hazardous situations.
esence of carbon
e information on how to respond to an alarm.
STEP BY STEP GUIDE TO PROGRAMMING
THIS ALARM
FOR FIRST TIME AND WHEN CHANGING BATTERIES
ill Say:
Action:
1. Insert batteries (2, AA batteries).
ess & Hold Test Button if
Pr
2.
you would like to program the
location or change the location
of the Alarm. Release button
after Alarm responds.
3. After you hear the location of
where you are placing the Alarm,
Press & Hold the Test Button.
Your Alarm has now been programmed for the location of your choice.
Available locations:
BasementKitchenChild’s Bedroom
Living Room
Family RoomNo LocationGuest Bedroom
OfficeHallwayUtility Room
Dining Room
m W
Alar
“Welcome, First Alert Smoke and
Carbon Monoxide Alarm.”
“No location programmed” if first
time
or “[Location, example:
“Basement”] location pr
when changing batteries.
“To select location, press and hold
test button now
o save location, pr
“T
test button after location is heard.”
Alarm will speak list of locations
(see below).
“[Location, example: “Basement”]
location saved.”
If no location is chosen:
“No location saved.”
ogrammed”
.”
ess and hold
Master Bedr
oom
ADDING AND LINKING ADDITIONAL ONELINK
®
ALARMS
NOTE: Steps 1 thr
e than two minutes pass, the Green power LED will stop
If mor
blinking. Simply open the battery drawer of the second Alarm and
epeat steps 1 through 3.
r
Insert the batteries into the
1.
battery drawer of the next
Alarm. DO NOT CLOSE THE
WER.
DRA
2. Press and hold the test
button and then close the
battery drawer.
Once you hear the unit chirp,
3.
elease the test button.
r
The Green power LED will start to blink indicating the ONELINK
Alarm is waiting for pr
ONELINK
4. Press and hold the test button on the first Alarm, until the second
Alarm
the test button.
If you have purchased the hardwired battery back-up ONELINK
5.
Alarm, you can now connect the har
three-wire connector on the ceiling to the Alarm.
Repeat steps 1-5 for additional ONELINK
6.
You have now successfully linked your new ONELINK®Alarms. To
add additional Alarms at a later time, follow steps 1 through 5.
evacuate smoke in [Location, example: “Basement”].
Evacuate.”
Smoke LED: Flashes Red in sync with the horn pattern
Horn: 4 fast beeps, pause, 4 fast beeps;
Voice: “Warning, evacuate carbon monoxide in [Location, example:
Voice: “Replace battery in [Location, example “Kitchen”].” Repeated
every 5 hours
Horn: chirps once a minute
Power/Smoke LED: Flashes Green On for 2 seconds/Off for
2 seconds. Low Battery Latch is now engaged.
CO LED: Off
If Alarm is Not Operating Properly (MALFUNCTION SIGNAL)
oice:
V
“Detector err
manual” (refer to Troubleshooting Guide).
Repeated every 5 hours.
Horn: Three rapid chirps every minute
Power/Smoke LED: Flashes approximately once a minute
CO LED: Off
m Levels of CO are Detected
Alar
Voice: “Warning, evacuate carbon monoxide in [Location, example:
“Kitchen”]. Evacuate.” “
Horn:4 beeps, pause, 4 beeps, voice*
Power/Smoke LED: Of
CO LED: During Alarm: Flashes Red in sync with the horn pattern.
*NOTE: If unit goes into CO alarm, the r
cycle will repeat for four minutes. After four minutes, the pause will
increase to one minute.
Smoke is Detected
Voice: “Warning, evacuate smoke in [Location, example: “Kitchen”].
Horn:3 beeps, pause, 3 beeps, voice
Power/Smoke LED: During Alarm: Flashes Red in sync with the
CO LED: Off
Smoke Alarm is Silenced
Voice: Silent
Horn:Of
Power/Smoke LED: Flashes Red
CO LED: Off
After Alarm: Flashes Red On for 2 seconds/Off for 2
seconds. CO Alarm Latch is now engaged.
Evacuate.”
hor
Off for 2 seconds. Smoke Alarm Latch is now engaged.
f
or in [Location, example “Kitchen”], please see
n pattern. After Alarm: Flashes Red On for 2 seconds/
f
once a minute
____ ppm.”
egular 4 beeps-brief pause
CO Alarm is Silenced
Voice: Silent
f
Horn:Of
Power/Smoke LED: Off
CO LED: Flashes Red
2
INSTALLATION
S
UGGESTED AREAS FOR INSTALLING
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS
SMOKE ALARM WITH
SILENCE FEATURE
CO ALARMS
BOTH, OR COMBINATION
SMOKE/CO ALARMS
SMOKE ALARMS
K
EY:
Suggested locations are based on
NFPA recommendations (NFPA 72
for Smoke Alarms and NFPA 720 for
Carbon Monoxide Alarms). Always
refer to national and local codes
before beginning any installation.
In new construction AC and AC/DC smoke alarms MUST
be interconnected to meet NFPA recommendations.
WHERE TO INSTALL THIS ALARM
Minimum coverage for Smoke Alarms, as recommended by the
National Fir
every floor
“Regulatory Information For Smoke Alarms” for details on the NFPA
ecommendations).
r
For CO Alarms, the National Fire Protection Association (NFPA)
ecommends that a CO Alarm should be centrally located outside of
r
each separate sleeping ar
For added protection, install additional CO Alarms in each separate
bedr
NOTE: For added protection, install an additional Smoke/CO Alarm at least
15 feet (4.6 meters) away from the furnace or fuel burning heat source
wher
distance cannot be maintained, install the Alarm as far away as possible
from the furnace or other fuel burning source. Installing the Alarm closer
than 15 feet (4.6 meters) will not harm the Alarm, but may incr
frequency of unwanted alarms.
In general, install combination Smoke and Carbon Monoxide Alar
•
• On every level of your home, including finished attics and basements.
•
• At the top of first-to-second floor stairs.
•
•
Recommended Placement
e Protection Association (NFPA), is one Smoke Alarm on
, in every sleeping area, and in every bedroom (See
ea in the immediate vicinity of the bedrooms.
oom, and on every level of your home.
e possible. In smaller homes or in manufactured homes where this
ease the
ms:
In the hall near every sleeping area. If your home has multiple
sleeping ar
(12 meters) long, install a unit at each end.
Inside every bedroom, especially if people sleep with the door partly
or completely closed.
eas, install a unit in each. If a hall is more than 40 feet
At the bottom of the basement stairs.
For additional coverage, install Alarms in all rooms, halls, and storage
areas, where temperatures normally remain between 40˚ F and 100˚F
(4˚ C and 38˚ C).
WHERE THIS ALARM SHOULD NOT BE INST
Do NOT locate this Smoke/CO Alar
In garages, furnace rooms, crawl spaces and unfinished attics. Avoid
•
emely dusty, dirty or greasy areas.
extr
Where combustion particles are produced. Combustion particles
•
form when something bur
kitchens, garages, and furnace rooms. Keep units at least 20 feet
(6 meters) fr
water heater
(6 meter) distance is not possible – in modular, mobile, or smaller
homes, for example – it is r
placed as far fr
placement recommendations are intended to keep these Alarms at
a r
“unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm is
placed directly next to a fuel-burning source. Ventilate these areas
as much as possible.
Within 5 feet (1.5 meters) of any cooking appliance. In air streams
•
near kitchens. Air curr
sensor and cause unwanted alarms.
• In extremely humid areas. This Alarm should be at least 10 feet
(3 meters) from a shower, sauna, humidifier, vaporizer, dishwasher,
laundry r
In direct sunlight.
•
• In turbulent air, like near ceiling fans or open windows. Blowing air
may pr
In areas where temperature is colder than 40˚ F (4˚ C) or hotter than
•
100˚ F (38˚ C). These areas include non-airconditioned crawl spaces,
unfinished attics, uninsulated or poorly insulated ceilings, porches,
and garages.
• In insect infested areas. Insects can clog the openings to the sensing
chamber
Less than 12 inches (305 mm) away from fluorescent lights.
•
Electrical “noise” can interfere with the sensor.
om the sources of combustion particles (stove, furnace,
, space heater) if possible. In areas where a 20-foot
om these fuel-burning sources as possible. The
easonable distance from a fuel-burning source, and thus reduce
ents can draw cooking smoke into the smoke
oom, utility room, or other source of high humidity.
event CO or smoke from reaching the sensors.
.
m:
ns. Areas to avoid include poorly ventilated
ecommended the Smoke Alarm be
ALLED
• In “dead air” spaces. See “Avoiding Dead Air Spaces”.
• When installing on the wall, the top edge of Smoke Alarms should
be placed between 4 inches (102 mm) and 12 inches (305 mm) from
the wall/ceiling line.
• When installing on the ceiling, place the Alarm as close to the center
as possible.
• In either case, install at least 4 inches (102 mm) from where the
wall and ceiling meet. See “Avoiding Dead Air Spaces” for more
information.
NOTE: For any location, make sure no door or other obstruction could
keep carbon monoxide or smoke fr
eaching the Alarm.
om r
Installing Smoke/CO Alarms in Mobile Homes
For minimum security install one Smoke/CO Alarm as close to each
sleeping area as possible. For more security, put one unit in each room.
Many older mobile homes (especially those built before 1978) have little
or no insulation. If your mobile home is not well insulated, or if you ar
e of the amount of insulation, it is important to install units on
unsur
inside walls only.
e
AVOIDING DEAD AIR SPACES
“Dead air” spaces may prevent smoke from reaching the Smoke/CO
Alarm. To avoid dead air spaces, follow installation recommendations
below.
On ceilings, install Smoke/CO Alarms as close to the center of the
ceiling as possible. If this is not possible, install the Smoke/CO Alarm at
least 4 inches (102 mm) from the wall or corner.
For wall mounting (if allowed by building codes), the top edge of
Smoke/CO Alarms should be placed between 4 inches (102 mm) and
12 inches (305 mm) from the wall/ceiling line, below typical “dead air”
spaces.
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO
Alarm within 3 feet (0.9 meters) of the peak of the ceiling, measured
horizontally. Additional Smoke/CO Alarms may be required depending
on the length, angle, etc. of the ceiling's slope. Refer to NFPA 72 for
details on requirements for sloped or peaked ceilings.
3
HOW TO INSTALL THIS ALARM
For quick installation instructions see the “Quick and Easy Guide to
Programming Your ONELINK®Alarm and Using the Optional Features”.
This combination Smoke/CO Alarm was designed to be mounted
on the ceiling or wall. It is not a tabletop device.
device on the ceiling or wall as outlined below. Read “Where To Install
This Alarm” before starting.
PARTS OF THIS SMOKE/CO ALARM
Test/Silence Button
1
Battery Compartment
2
Power/Smoke Alarm LED
3
CO Alarm LED
4
Tools you will need: pencil, drill with 3/16” or 5mm drill bit,
Phillips scr
If you want to lock the battery compartment, or lock the Smoke/CO
Alar
Featur
Your ONELINK
before you begin installation.
ewdriver, hammer.
Do not install this unit over an electrical junction box. Air
•
currents around junction boxes can prevent smoke from
eaching the sensing chamber and prevent the unit from
r
alarming. Only AC powered units are intended for installation
over junction boxes.
m to the mounting bracket, please read the “Optional Locking
es” section in the “Quick and Easy Guide to Programming
®
Alarm and Using the Optional Features” attachment
ou must install this
Y
Hold the mounting bracket against the ceiling (or wall) so the vertical
1.
mounting slot is aligned in the 12 o’clock position and trace around
the inside of the mounting slots (vertical and horizontal mounting).
Put the unit where it won’t get covered with dust when you drill the
2.
mounting holes.
Using a 3/16” (5 mm) drill bit, drill a hole through the center of the
3.
oval outlines you traced.
4. Insert the plastic screw anchors (in the plastic bag with screws) into
the holes. Tap the screw anchors gently with a hammer, if necessary,
until they ar
Line the mounting bracket up over the plastic screw anchors.
5.
Screw the mounting bracket to the ceiling or wall through the
6.
mounting slots using the two screws provided.
7. Attach the Smoke/CO Alarm to the
mounting bracket. Line up the guides
on the alarm’
on the mounting bracket. When guides
e lined up, turn the base clockwise
ar
(right) until it snaps into place.
NOTE: Once the Alarm is snapped
onto the mounting bracket, you
can r
alignment.
8. Test the Smoke/CO Alarm.
See “Weekly Testing” for details.
e flush with the ceiling or wall.
s base with the guides
otate the Alarm to adjust the
OPTIONAL LOCKING FEATURES
The optional locking features are designed to prevent unauthorized removal of the batteries or alarm. It is not necessary to activate the locks
in single-family households where unauthorized battery or Alarm removal is not a concern.
These Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the
Alarm to the mounting bracket. You can choose to use either feature independently, or use them both.
Tools you will need: • Needle-nose pliers • Standard flathead screwdriver.
Both locking features use locking pins, which are molded into the mounting bracket. Depending on which locking
features you use, remove one or both pins from the mounting bracket using needle-nose pliers.
To permanently remove either locking pin, insert a flathead screwdriver between the locking pin and the
lock, and pry the pin out of the lock.
TO LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment until you install the
batteries and test the Alarm.
If the unit does not alarm during
testing, DO NOT lock the batter
compartment! Install new batteries
and test again. If the Alarm still does
not alarm, replace it immediately.
1. Using needle-nose pliers, detach
one locking pin from the mounting
bracket.
After batteries are inserted, then
2.
push the locking pin through the
hole near the battery door latch on
the back of the Alarm.
y
TO UNLOCK THE BATTERY COMPARTMENT
1. Remove the Alarm from the
mounting bracket. If the unit is
locked to the bracket, see the
section “To Unlock the Mounting
Bracket.”
2. Insert a flathead screwdriver under
the head of the locking pin, and
gently pry it out of the battery
compartment lock. (If you plan to
elock the battery compartment,
r
save the locking pin.)
3. To relock the battery compartment,
close the battery door and reinsert
locking pin in lock.
Reattach the Alarm to the mounting
4.
bracket.
eplacing the batteries, always
When r
test the Alarm before relocking the
battery compartment.
TO LOCK THE MOUNTING BRACKET
Using needle-nose pliers, detach
1.
one locking pin from the mounting
bracket.
2. Insert the locking pin through the
hole on the back of the Alarm as
shown in the diagram.
3. When you attach the Alarm to the
mounting bracket, the locking pin’
head will fit into a notch on the
bracket.
s
TO UNLOCK THE MOUNTING BRACKET
Insert a flathead scr
1.
rectangular cut-out on the mounting
bracket near
2. Pry the Alarm away from the bracket
by pushing up on the screwdriver and
ning the Alarm counter
tur
(left) at the same time.
4
ewdriver into the
est to the locking pin.
clockwise
IF YOUR SMOKE/CO ALARM SOUNDS
WHAT TO DO FIRST–IDENTIFY THE TYPE OF
ALARM SIGNAL
Refer to previous section “What You Will See and Hear With This
m”.
Alar
IF THE CO ALARM SOUNDS
“ALARM-MOVE TO FRESH AIR”
If you hear the CO alar
Actuation of your CO Alarm indicates the presence of carbon
monoxide (CO) which can kill you. In other wor
m sounds, you must not ignore it!
Alar
IF THE CO ALARM SIGNAL SOUNDS:
1. Operate the Test/Silence button.
Call your emergency services, fire department or 911. Write down the
2.
number of your local emergency service here:
____________________________________________________________
Immediately move to fresh air—outdoors or by an open door or
3.
window. Do a head count to check that all persons are accounted
for
or window until the emer
premises have been aired out, and your CO Alarm remains in its
normal condition.
After following steps 1-3, if your CO Alarm reactivates within a
4.
24-hour period, r
nician to investigate for sources of CO from fuel-burning equipment
and appliances, and inspect for proper operation of this equipment.
If problems are identified during this inspection have the equipment
serviced immediately. Note any combustion equipment not inspected
by the technician, and consult the manufacturers’ instructions, or
contact the manufactur
safety and this equipment. Make sure that motor vehicles are not,
and have not, been operating in an attached garage or adjacent
to the residence. Write down the number of a qualified appliance
technician here:
After the emergency responders arrive, the premises aired out, and
your CO Alarm remains in its normal condition, you can check what
the highest carbon monoxide level sensed was:
Action:
1. Press & Hold Test Button
2. Press & Hold Test Button, if you
would like to clear the highest
level sensed.
If you would like to keep the
highest level in memory, do not
ess anything.
pr
move ever
. Do not re-enter the premises, or move away from the open door
m horn and the CO red light is flashing,
yone to a source of fresh air.
DO NOT remove the batteries!
ds, when your CO
gency services responder has arrived, the
epeat steps 1-3 and call a qualified appliance tech-
ers directly, for more information about CO
Alarm Will Say:
“Highest carbon monoxide level
was ___ ppm. Please see manual.”
“To clear highest carbon monoxide
level, press and hold test button
now.”
“Highest carbon monoxide level
cleared.”
Alarm will say nothing.
IF THE SMOKE ALARM SOUNDS
RESPONDING TO AN ALARM
• If the unit alarms and you are not testing the unit, it is warning
you of a potentially danger
immediate attention. NEVER ignor
alarm may result in injury or death.
Never remove the batteries from a battery operated Smoke/CO
•
m to stop an unwanted alarm (caused by cooking smoke,
Alar
etc.). Removing batteries disables the alarm so it cannot sense
smoke, and r
or fan the smoke away fr
matically.
If the unit alarms get everyone out of the house immediately.
•
T TO DO IN CASE OF FIRE
WHA
• Don’t panic; stay calm. Follow your family escape plan.
• Get out of the house as quickly as possible. Don’t stop to get
essed or collect anything.
dr
• Feel doors with the back of your hand before opening them.
If a door is cool, open it slowly. Don’t open a hot door. Keep doors
and windows closed, unless you must escape thr
• Cover your nose and mouth with a cloth (preferably damp).
Take short, shallow breaths.
• Meet at your planned meeting place outside your home, and
do a head count to make sur
• Call the Fire Department as soon as possible from outside.
Give your addr
Never go back inside a burning building for any reason.
•
• Contact your Fire Department for ideas on making your home
safer.
Alarms have various limitations. See "General Limitations of
Smoke/CO Alarms" for details.
emoves your protection. Instead open a window
ess, then your name.
ous situation that requires your
e any alarm. Ignoring the
om the unit. The alarm will reset auto-
ough them.
e everybody got out safely
.
USING THE SILENCE FEATURES
Never remove the batteries to quiet an unwanted alarm. Removing
the batteries disables the alarm and removes your protection.
The Silence Feature is intended to temporarily silence the horn while
you identify and correct the problem. Do not use the Silence Feature in
emergency situations. It will not correct a CO problem or extinguish a
fire.
The Silence Feature can temporarily quiet an unwanted alarm for several
minutes. You can silence this Smoke/CO Alarm by pressing the
Test/Silence button on the alarm cover for at least 3-5 seconds.
After the Test/Silence button is released, the Red LED blinks during the
silence mode.
When the Smoke Alarm
is Silenced
The Smoke Alarm will remain
silent for up to 15 minutes, then
return to normal operation.
If the smoke has not cleared–or
continues to increase–the device
will go back into alarm.
When the CO Alarm
is Silenced
The CO Alarm will remain silent
for up to 4 minutes.
After 4 minutes, if CO levels
remain potentially dangerous the
horn will start sounding again.
5
A
B
SILENCING THE LOW BA
This silence featur
for up to 8 hours. Y
essing the Test/Silence button on the alarm cover.
pr
Once the low battery war
continues to flash the Green light twice a minute for 8 hours. After 8
hours, the low battery “chirp” will r
soon as possible; this unit will not operate without batter
o deactivate this feature:
T
will go into Test Mode and the low battery warning will resume (LED
flashes and unit sounds “chirp” once a minute).
e can temporarily quiet the low battery warning “chirp”
ou can silence the low battery warning “chirp” by
TTERY WARNING
ning “chirp” silence feature is activated, the unit
esume.
Replace the batteries as
ess the Test/Silence button again. The unit
Pr
y power!
LATCHING FEATURES
Alarm Latch is activated after an Alarm is exposed to alarm levels of
smoke or carbon monoxide. After smoke or CO levels dr
levels, the
flash On for 2 seconds/Off for 2 seconds. It will continue to flash or
“latch” for about 15 minutes, to give you time to determine which unit
initiated the alarm.
Low Battery Latch is activated when the Alarm is in the "low battery
condition".
On for 2 seconds/Of
is designed to help you identify which Alarm needs to have the battery
replaced. Although, the Alarm will sound the low battery chirp approximately once every minute, sometimes during the initial stages of "low
battery", the Alarm will chirp in greater intervals than one minute, sometimes up to several hours, until the battery reaches a steady low battery
level. This innovative featur
and/or identifying which unit is chirping.
“Smoke/Power” LED and/or the “CO” Red LED will begin to
When this occurs, the Smoke/Power LED flashes Green
f for 2 seconds for about 15 minutes. This feature
e eliminates the frustration of waiting for
op below alarm
WEEKLY TESTING
•
NEVER use an open flame of any kind to test this unit. You
might accidentally damage or set fire to the unit or to your
home. The built-in test switch accurately tests the unit’s
operation as required by Underwriters Laboratories, Inc. (UL).
NEVER use vehicle exhaust! Exhaust may cause permanent
damage and voids your warranty.
• DO NOT stand close to the Alarm when the horn is sounding.
Exposure at close range may be harmful to your hearing.
When testing, step away when horn starts sounding.
It is important to test this unit every week to make sure it is working
properly. Using the test button is the recommended way to test this
Smoke/CO Alarm.
You can test this Smoke/CO Alarm by pressing and holding the
Test/Silence button on the Alarm cover until Alarm Voice says “Testing”
(typically 3-5 seconds).
During testing, you will see and hear the following sequence:
• The Alarm
pause, 3 beeps. The Alarm Voice will say “Warning, evacuate
smoke in [Location, example: “Kitchen”]. Evacuate.” The
Power/Smoke LED flashes Red and the CO LED will be Off.
• Next the Horn will sound 4 beeps, pause, 4 beeps. The Alarm
Voice will say “Warning, evacuate carbon monoxide in [Location,
example: “Kitchen”]. Evacuate.” The
Off and the
If the unit does not alarm, make sure the batteries are correctly installed,
and test again. If the unit still does not alarm, replace it immediately.
Voice will say “Testing.” The Horn will sound 3 beeps,
CO LED flashes Red.
Power/Smoke LED will be
REGULAR MAINTENANCE
This unit has been designed to be as maintenance-fr
there are a few simple things you must do to keep it working properly.
ee as possible, but
REGULAR MAINTENANCE, Continued
Choosing a r
our Smoke/CO Alarm requires two standard AA batteries.
Y
The following batteries ar
These batteries are available at many local retail stores.
Actual battery service life depends on the Smoke/CO Alarm and the
environment in which it is installed. All the batteries specified above
e acceptable replacement batteries for this unit. Regardless of the
ar
manufacturer’s suggested battery life, you MUST replace the battery
immediately once the unit starts “chirping” (the “low battery warning”).
o replace the batteries (without removing Alarm from
T
the ceiling or wall):
Open the battery compartment.
1.
2. Press tabs A and B as shown in the
diagram and r
Insert the new batteries, making sure
3.
they snap completely into the battery
compartment. Match the terminals
on the ends of the batteries with the
terminals on the unit.
Close the battery compartment, and
4.
then test the unit by pr
Test/Silence button.
eplacement battery:
e acceptable as replacements:
emove each battery.
essing the
Ener
gizer E91
WHAT YOU NEED TO KNOW ABOUT CO
WHAT IS CO?
CO is an invisible, odorless, tasteless gas produced when fossil fuels
do not bur
appliances typically do not produce CO.
These fuels include: Wood, coal, charcoal, oil, natural gas, gasoline,
kerosene, and propane.
Common appliances are often sources of CO. If they are not properly
maintained, are improperly ventilated, or malfunction, CO levels can rise
quickly. CO is a real danger now that homes are more energy efficient.
“Air-tight” homes with added insulation, sealed windows, and other
weatherproofing can “trap” CO inside.
SYMPTOMS OF CO POISONING
These symptoms are related to CO POISONING and should be
discussed with ALL household members.
Medium Exposure: Throbbing headache, drowsiness, confusion, fast
heart rate.
Extreme Exposure: Convulsions, unconsciousness, heart and lung
failure. Exposure to Carbon Monoxide can cause brain damage, death.
This CO Alarm measures exposure to CO over time. It alarms if CO
levels are extremely high in a short period of time, or if CO levels reach
a certain minimum over a long period of time. The CO Alarm generally
sounds an alarm before the onset of symptoms in average, healthy
adults. Why is this important? Because you need to be war
potential CO pr
cases of CO exposure, victims may be aware that they are not feeling
well, but become disoriented and can no longer react well enough to
exit the building or get help. Also, young children and pets may be the
first affected. The average healthy adult might not feel any symptoms
when the CO Alarm sounds. However
problems, infants, unborn babies, pregnant mothers, or elderly people
can be more quickly and severely affected by CO. If you experience
even mild symptoms of CO poisoning, consult your doctor immediately!
n completely, or are exposed to heat (usually fire). Electrical
oblem while you can still r
, people with car
eact in time. In many reported
ned of a
diac or respiratory
.
Use only the replacement batteries listed below. The unit may not
operate pr
batteries since they may not provide a constant charge.
•
•
•
•
operly with other batteries. Never use r
est it at least once a week.
T
Clean the Smoke/CO Alarm at least once a month; gently vacuum the
outside of the Smoke/CO Alarm using your household vacuum’
brush attachment. A can of clean compressed air (sold at computer
or office supply stores) may also be used. Follow manufacturer
instructions for use. Test the Smoke/CO Alarm. Never use water,
cleaners or solvents since they may damage the unit.
If the Smoke/CO Alarm becomes contaminated by excessive dirt,
dust and/or grime, and cannot be cleaned to avoid unwanted
alarms, replace the unit immediately.
Relocate the unit if it sounds fr
This Alarm Should Not Be Installed” for details.
equent unwanted alarms. See “Where
echargeable
s soft
FINDING THE SOURCE OF CO AFTER AN ALARM
Carbon monoxide is an odorless, invisible gas, which often makes it
difficult to locate the source of CO after an alarm. These are a few of
the factors that can make it difficult to locate sources of CO:
• House well ventilated before the investigator arrives.
oblem caused by “backdrafting.”
• Pr
ransient CO pr
• T
Because CO may dissipate by the time an investigator arrives, it may
be difficult to locate the source of CO.
obligated to pay for any carbon monoxide investigation or ser
call.
6
oblem caused by special cir
BRK Brands, Inc. shall not be
cumstances.
vice
POTENTIAL SOURCES OF CO IN THE HOME
Fuel-burning appliances like: portable heater, gas or wood burning
eplace, gas kitchen range or cooktop, gas clothes dryer.
fir
Damaged or insuf
heater vent pipe, leaking chimney pipe or flue, or cracked heat
exchanger
oper use of appliance/device:
Impr
vehicle in an enclosed area (like a garage or screened porch).
Transient CO Problems: “transient” or on-again-off-again CO problems
can be caused by outdoor conditions and other special cir
The following conditions can r
1. Excessive spillage or reverse venting of fuel appliances caused by
outdoor conditions such as:
Wind direction and/or velocity, including high, gusty winds.
•
Heavy air in the vent pipes (cold/humid air with extended periods
between cycles).
Negative pressure differential resulting from the use of exhaust
•
fans.
Several appliances running at the same time competing for
•
limited fresh air.
Vent pipe connections vibrating loose from clothes dryers,
•
furnaces, or water heaters.
• Obstructions in or unconventional vent pipe designs which can
3. Temperature inversions, which can trap exhaust close to the ground.
4. Car idling in an open or closed attached garage, or near a home.
These conditions are dangerous because they can trap exhaust in your
home. Since these conditions can come and go, they are also hard to
recreate during a CO investigation.
ficient venting:
, blocked or clogged chimney opening.
oded or disconnected water
corr
operating a barbecue grill or
cumstances.
esult in transient CO situations:
REGULATORY INFORMATION FOR
SMOKE/CO ALARMS
REGULATORY INFORMATION FOR CO ALARMS
T LEVELS OF CO CAUSE AN ALARM?
WHA
Underwriters Laboratories Inc. Standar
Alarms to sound when exposed to levels of CO and exposur
described below. They are measured in parts per million (ppm) of CO
over time (in minutes).
UL2034 Required Alarm Points*:
If the alarm is exposed to 400 ppm of CO, IT MUST ALARM
•
BETWEEN 4 and 15 MINUTES.
If the alarm is exposed to 150 ppm of CO, IT MUST ALARM
•
BETWEEN 10 and 50 MINUTES.
If the alarm is exposed to 70 ppm if CO, IT MUST ALARM
•
BETWEEN 60 and 240 MINUTES.
oximately 10% COHb exposure at levels of 10% to 95% Relative
* Appr
Humidity (RH).
The unit is designed not to alarm when exposed to a constant level
of 30 ppm for 30 days.
CO Alarms are designed to alarm before there is an immediate life
threat. Since you cannot see or smell CO, never assume it’s not present.
An exposure to 100 ppm of CO for 20 minutes may not affect
•
average, healthy adults, but after 4 hours the same level may cause
headaches.
• An exposure to 400 ppm of CO may cause headaches in average,
healthy adults after 35 minutes, but can cause death after 2 hours.
Standards: Underwriters Laboratories Inc. Single and Multiple Station
carbon monoxide alarms UL2034.
ding to Underwriters Laboratories Inc. UL2034, Section 1-1.2:
Accor
“Carbon monoxide alarms covered by these requirements ar
espond to the presence of carbon monoxide from sources such as,
to r
but not limited to, exhaust fr
operation of fuel-fired appliances, and fireplaces. CO Alarms are intended
to alarm at carbon monoxide levels below those that could cause a loss
of ability to r
Alarm monitors the air at the Alarm, and is designed to alarm before CO
levels become life threatening. This allows you precious time to leave
the house and correct the problem. This is only possible if Alarms are
located, installed, and maintained as described in this manual.
Gas Detection at Typical Temperature and Humidity Ranges: The
CO Alarm is not formulated to detect CO levels below 30 ppm typically.
UL tested for false alarm resistance to Methane (500 ppm), Butane (300
ppm), Heptane (500 ppm), Ethyl Acetate (200 ppm), Isopropyl Alcohol
(200 ppm) and Carbon Dioxide (5000 ppm). Values measure gas and
vapor concentrations in parts per million.
Audible Alarm: 85 dB minimum at 10 feet (3 meters).
eact to the dangers of Carbon Monoxide exposure.” This CO
om internal-combustion engines, abnormal
d UL2034 requires residential CO
e times as
e intended
HOW CAN I PROTECT MY FAMILY FROM
CO POISONING?
A CO Alarm is an excellent means of protection. It monitors the air and
sounds a loud alarm before Carbon Monoxide levels become threatening
for average, healthy adults.
A CO Alarm is not a substitute for proper maintenance of home
appliances.
To help prevent CO problems and reduce the risk of CO poisoning:
Clean chimneys and flues yearly
•
leaves, and nests for proper air flow. Also, have a professional
check for rust and corrosion, cracks, or separations. These
conditions can pr
drafting. Never “cap” or cover a chimney in any way that would
block air flow.
• Test and maintain all fuel-burning equipment annually. Many local
gas or oil companies and HVAC companies offer appliance
inspections for a nominal fee.
egular visual inspections of all fuel-bur
Make r
•
Check appliances for excessive rust and scaling. Also check the
flame on the bur
yellow flame means fuel is not being burned completely and CO
may be present. Keep the blower door on the furnace closed.
Use vents or fans when they ar
appliances. Make sure appliances are vented to the outside. Do
not grill or barbecue indoors, or in garages or on screen porches.
• Check for exhaust backflow from CO sources. Check the draft
hood on an operating furnace for a backdraft. Look for cracks on
nace heat exchangers.
fur
Check the house or garage on the other side of shar
•
Keep windows and doors open slightly
•
is escaping into your home, open a window or a door. Opening
windows and doors can significantly decr
In addition, familiarize yourself with all enclosed materials. Read
this manual in its entirety, and make sure you understand what to
do if your CO Alarm sounds.
event pr
ner and pilot lights. The flame should be blue. A
. Keep them fr
oper air movement and cause back
e available on all fuel-bur
ee of debris,
-
ning appliances.
ning
ed wall.
. If you suspect that CO
ease CO levels.
7
REGULA
RECOMMENDED LOCA
Installing Smoke Alar
The National Fire Protection Association (NFPA), recommends one
Smoke Alarm on every floor
bedroom. In new construction, the Smoke Alarms must be AC powered
and interconnected. See “Agency Placement Recommendations” for
details. For additional coverage, it is r
Smoke Alarm in all rooms, halls, storage areas, finished attics, and
basements, where temperatures normally remain between 40˚ F (4˚ C)
and 100˚ F (38˚ C). Make sur
smoke from reaching the Smoke Alarms.
Mor
•
• Inside every bedroom, especially if people sleep with the door partly
•
• At the top of the first-to-second floor stairway, and at the bottom of
Specific requirements for Smoke Alarm installation vary from state to
state and fr
for curr
units be inter
TORY INFORMATION FOR SMOKE ALARMS
TIONS FOR SMOKE ALARMS
ms in Single-Family Residences
, in every sleeping area, and in every
ecommended that you install a
e no door or other obstruction could keep
e specifically, install Smoke Alarms:
On every level of your home, including finished attics and basements.
or completely closed.
In the hall near every sleeping area. If your home has multiple
sleeping ar
long (12 meters), install a unit at each end.
the basement stairway.
eas, install a unit in each. If a hall is more than 40 feet
om region to region. Check with your local Fire Department
ent requirements in your area.
connected for added protection.
ecommended AC or AC/DC
It is r
ABOUT SMOKE ALARMS
Battery (DC) operated Smoke Alarms: Provide protection even when
electricity fails, pr
e easy to install, and do not require professional installation.
Units ar
AC power
senses smoke, all units alarm. They do not operate if electricity fails.
AC with batter
the batteries ar
be installed by a qualified electrician.
ONELINK®Smoke Alar
with all ONELINK
or connectors, so when one alarm sounds, they all sound. Will operate if
electricity fails, pr
Units are easy to install, and do not require professional installation.
Smoke/CO Alarms for Solar or Wind Energy users and battery
backup power systems: AC power
be operated with true or pur
with most battery-powered UPS (uninterruptible power supply) products
or squar
If you ar
the manufacturer to verify.
Smoke Alarms for the hearing impaired: Special purpose Smoke Alarms
should be installed for the hearing impaired. They include a visual alarm
and an audible alarm hor
With Disabilities Act. Can be interconnected so if one unit senses smoke,
all units alarm.
Smoke alarms are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.
All these Smoke Alarms ar
located, installed and car
smoke reaches the Alarm. If you are unsure which type of Smoke Alarm
to install, refer the National Fire Protection Association (NFPA) Standard
72 (National Fir
National Fire Protection Association, One Batterymarch Park, Quincy, MA
02269-9101. Local building codes may also require specific units in new
construction or in different areas of the home.
ovided the batteries are fresh and correctly installed.
ed Smoke Alarms:
y (DC) back-up:
e fresh and correctly installed. AC and AC/DC units must
®
enabled Smoke and Smoke/CO Alarms without wires
ovided the batteries are fresh and correctly installed.
e wave or “quasi sine wave” inverters
e not sure about your inverter or UPS type, please consult with
e Alarm Code) and NFPA 101 (Life Safety Code).
Can be inter
will operate if electricity fails, pr
ms with battery (DC) back-up:
e sine wave inverters. Operating this Alarm
n, and meet the requirements of the Americans
e designed to provide early warning of fires if
ed for as described in the user’s manual, and if
connected so if one unit
ovided
connects
Inter
ed Smoke/CO Alarms should only
will damage the Alarm.
AGENCY PLACEMENT RECOMMENDATIONS
NFPA 72 (National Fire Code) Chapter 11
“For your information, the National Fire Protection Association's
Standard 72, reads as follows:”
“11.5.1 One- and Two-Family Dwelling Units.”
“11.5.1.1 Smoke Detection.
standards for the specified occupancy, approved single- and multiple
-station Smoke Alarms shall be installed as follows: (1) In all sleeping
ooms Exception: Smoke Alarms shall not be required in sleeping rooms
r
in existing one- and two-family dwelling units. (2) Outside of each sepa
rate sleeping area, in immediate vicinity of the sleeping rooms.
(3) On each level of the dwelling unit, including basements Exception: In
existing one- and two family dwelling units, approved Smoke Alarms
ed by batteries are permitted.”
power
“A.11.8.3 Are More Smoke Alarms Desirable? The required number
of Smoke Alarms might not provide reliable early warning protection
for those areas separated by a door from the areas protected by the
ed Smoke Alarms. For this r
equir
r
householder consider the use of additional Smoke Alarms for those
areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways
not protected by the required Smoke Alarms. The installation of Smoke
Alarms in kitchens, attics (finished or unfinished), or garages is not
normally recommended, as these locations occasionally experience
conditions that can result in improper operation.”
nia State Fir
Califor
Early warning detection is best achieved by the installation of fire detection
equipment in all rooms and areas of the household as follows: A Smoke
Alarm installed in each separate sleeping ar
bedrooms), and Heat or Smoke Alarms in the living rooms, dining rooms,
bedrooms, kitchens, hallways, finished attics, furnace rooms, closets,
utility and storage rooms, basements, and attached garages.
Where required by applicable laws, codes, or
eason, it is recommended that the
e Marshal (CSFM)
ea (in the vicinity
, but outside
SPECIAL COMPLIANCE CONSIDERATIONS
This unit alone is not a suitable substitute for complete fire detection
systems
in places housing many people—like apartment buildings,
condominiums, hotels, motels, dormitories, hospitals, long-term health
care facilities, nursing homes, day care facilities, or group homes of
any kind—even if they were once single-family homes. It is not a
suitable substitute for complete fire detection systems in warehouses,
industrial facilities, commercial buildings, and special-purpose nonresidential buildings which require special fire detection and alarm
systems. Depending on the building codes in your area, this unit may
be used to provide additional protection in these facilities.
The following information applies to all five types of buildings listed
below:
In new construction, most building codes require the use of AC or AC/DC
powered Smoke Alarms only. AC, AC/DC, or DC powered Smoke Alarms
can be used in existing construction as specified by local building codes.
Refer to NFPA 72 (National Fire Alarm Code) and NFPA 101 (Life Safety
Code), local building codes, or consult your Fire Department for detailed
fire protection requirements in buildings not defined as “households.”
1. Single-Family Residence:
-
Single family home, townhouse. It is recommended this unit be installed
on every level of the home, in every bedroom, and in each bedroom
hallway.
2. Multi-Family or Mixed Occupant Residence:
Apartment building, condominium. This unit is suitable for use in
individual apartments or condos, provided a primary fire detection
system already exists to meet fire detection requirements in common
ar
eas like lobbies, hallways, or porches. Using this unit in common areas
may not pr
protection ordinances/regulations.
3. Institutions:
Hospitals, day car
suitable for use in individual patient sleeping/resident rooms, provided
a primary fir
requirements in common areas like lobbies, hallways, or porches.
Using this unit in common areas may not provide sufficient warning to
esidents or meet local fir
all r
4. Hotels and Motels:
Also boarding houses and dormitories. This unit is suitable for use inside
individual sleeping/r
system already exists to meet fire detection requirements in common
eas like lobbies, hallways, or por
ar
may not provide sufficient warning to all residents or meet local fire
otection ordinances/regulations.
pr
ehouses/Commercial Buildings:
ar
5. W
DO NOT use this Smoke/CO Alarm in warehouses, industrial or
commercial buildings, special-purpose non-residential buildings, RVs,
boats, or airplanes. This Smoke/CO Alarm is specifically designed for
residential use, and may not provide adequate protection in non-residential applications.
ficient war
ovide suf
e facilities, long-term health car
e detection system alr
esident r
ning to all r
e pr
ooms, pr
esidents or meet local fire
e facilities. This unit is
eady exists to meet fire detection
otection or
dinances/r
ovided a primary fir
ches. Using this unit in common areas
egulations.
e detection
8
GENERAL LIMITATIONS OF SMOKE/CO ALARMS
This Smoke/CO Alarm is intended for r
for use in industrial applications where Occupational Safety and Health
Administration (OSHA) r
be met. The Smoke Alarm portion of this device is not intended to alert
hearing impaired residents. Special purpose Smoke Alarms should be
installed for hearing impair
for the hearing impair
Smoke/CO Alar
plan at least twice a year, making sure that everyone is involved – from
kids to grandpar
practice befor
If children or others do not readily waken to the sound of the Smoke/CO
Alarm, or if ther
e that someone is assigned to assist them in fire drill and in the
make sur
event of an emergency. It is recommended that you hold a fire drill while
family members ar
sound of the Smoke/CO Alarm while sleeping and to determine whether
they may need assistance in the event of an emergency.
Smoke
/CO
cannot work if the batteries ar
type of batteries ar
AC units cannot work if the AC power is cut off for any reason (open fuse
or cir
e that burns the electrical wires, etc.). If you are concerned about the
fir
limitations of battery or AC power, install both types of units.
This Smoke/CO Alarm will not sense smoke or CO that does not
each the sensors.
r
or CO may be present in other areas. Doors or other obstructions may
affect the rate at which CO or smoke reaches the sensors. If bedroom
doors ar
device (Combination CO and Smoke Alarm, or separate CO Alarms and
Smoke Alarms) in each bedroom and in the hallway between them.
This Smoke/CO Alar
of the home.
may not sense smoke or CO in the basement. For this reason, one
alarm device may not give adequate early warning.
Alarms cannot work without power. Battery operated units
cuit breaker, failure along a power line or at a power station, electrical
e usually closed at night, we recommend you install an alarm
equirements for Carbon Monoxide Alarms must
ed residents (CO Alarms are not yet available
ed).
ms may not waken all individuals.
ents. Allow children to master fire escape planning and
e holding a fire drill at night when they are sleeping.
e are infants or family members with mobility limitations,
e sleeping in order to determine their response to the
e used, or if the batteries are not installed correctly.
Example: This alarm device, installed on the second floor
e missing, disconnected or dead, if the wrong
It will only sense smoke or CO at the sensor
m may not sense smoke or CO on another level
esidential use. It is not intended
Practice the escape
Smoke
.
Recommended minimum pr
sleeping area, every bedroom, and on every level of your home. Some
ecommend battery powered Smoke and CO Alarms be used in
experts r
conjunction with inter
see “About Smoke Alarms” for details.
Smoke/CO Alarms may not be heard. The alarm horn loudness meets or
exceeds curr
the Smoke/CO Alarm is installed outside the bedr
a sound sleeper or one who has recently used drugs or has been drinking
alcoholic beverages. This is especially true if the door is closed or only
partly open. Even persons who ar
if the sound is blocked by distance or closed doors. Noise from traffic,
ster
event alert persons from hearing the alarm horn. This Smoke/CO Alarm
pr
is not intended for people who are hearing impaired.
The Alarm may not have time to alarm before the fire itself causes
damage, injur
each the unit immediately. Examples of this include persons
r
smoking in bed, children playing with matches, or fires caused by
violent explosions r
This Smoke/CO Alar
Though this Smoke/CO Alarm war
presence of smoke, BRK Brands, Inc. does not warrant or imply in any
way that they will pr
their lives.
This Smoke/CO Alar
Alarm and all of its parts have passed many stringent tests and ar
designed to be as r
any time. Therefore, you must test this device weekly. The unit should
be r
Alarms need to be r
replaced every 10 years.
,
This Smoke/CO Alar
devices, this Smoke/CO Alarm has limitations. It can only detect smoke
or CO that reaches the sensors. It may not give early warning of the
sour
alarm device.
ent UL standards of 85 dB at 10 feet (3 meters). However, if
eo, radio, television, air conditioner, or other appliances may also
y, or death, since smoke from some fires may not
eplaced immediately if it is not operating properly. All Smoke/CO
ce of smoke or CO is in a remote part of the home, away from the
otection is one alarm device in every
connected AC powered Smoke Alarms. For details,
oom, it may not wake up
e awake may not hear the alarm horn
esulting from escaping gas.
m is not a substitute for life insurance.
otect lives. Homeowners and renters must still insure
m has a limited life.
eliable as possible, any of these parts could fail at
eplaced every 5 years. All Smoke Alarms need to be
m is not foolproof.
ns against increasing CO levels or the
Although this Smoke/CO
Like all other electr
e
onic
TROUBLESHOOTING GUIDE
If the Alarm...Problem...You should...
Horn "chirps" about once per minute;
Voice: "Replace battery in [Location]" every 5
hours
Horn does three rapid "chirps" every minute;
Voice: "Detector error in [Location, example
"Kitchen"], please see manual" repeated every
5 hours; LED has 3 rapid flashes with "chirps".
The Alarms are linked but do not communicate
with each other.
Carbon Monoxide Alarm ONLY:
CO Alarm goes back into alarm 4 minutes after
you Silence it.
CO Alarm sounds frequently even though no high
levels of CO are revealed in an investigation.
:
Y
Smoke Alar
Smoke Alarm sounds when no smoke is visible.
*For a list of acceptable replacement batteries, see “Regular Maintenance.”
If you have questions that cannot be answered by reading this manual, call Consumer Affairs at 1-800-323-9005, M-F 7:30 a.m. to 5:00 p.m. (CST)
m ONL
Low battery warning.Install two new AA batteries*.
MALFUNCTION SIGNAL. Device is not working
properly, and needs to be replaced.
Possible interference. Reference the Wireless
Operation section of this manual.
CO levels indicate a potentially danger
situation.
The CO Alarm may be improperly located. Refer
to “Where to Install This Alarm” for details.
Unwanted alarm may be caused by nonemergency source like cooking smoke.
ous
Units under warranty should be returned to
manufacturer for replacement. See “Limited
Warranty” for details.
Move Alarms to different locations. Add an
additional Alarm between the unresponsive
Alarms to route the signal around obstructions.
IF YOU ARE FEELING SYMPTOMS OF CO
POISONING, EVACUATE your home and call
911 or the Fire Department. Refer to "If The CO
Alarm Sounds" for details.
Relocate your Alarm. If frequent alarms
continue, have home rechecked for potential
oblems. Y
CO pr
intermittent CO pr
Silence Alarm using manual button; clean the
Alarm’s cover with a soft, clean cloth. If frequent
unwanted alarms continue, r
Alarm may be too close to a kitchen, cooking
appliance, or steamy bathr
ou may be experiencing an
oblem.
oom.
elocate your Alarm.
9
LIMITED WARRANTY
BRK Brands, Inc., ("BRK") the maker of First Alert®brand pr
free from defects in material and workmanship. BRK, at its option, will repair or replace this product or any component of the product found to be defective
during the warranty period. Replacement will be made with a new or r
ment may be made with a similar pr
This warranty is valid for the original r
purchase is required to obtain warranty performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to alter,
modify or any way change the terms and conditions of this warranty
This warranty does not cover normal wear of parts or damage r
voltage or curr
Further, the warranty does not cover Acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.
BRK shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty. Except to the extent prohibited
by applica
Some states, pr
warranty lasts, so the above limitations or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights
that vary fr
How to Obtain Warranty Service
vice:
Ser
1-800-323-9005, 7:30 AM - 5:00 PM Central Standar
purchase available when calling.
For W
Battery:BRK Brands, Inc. make no warranty
respect to battery.
For your records, please record:
Date Pur
Wher
ent, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center.
ble law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above warranty.
ovinces or jurisdictions do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied
om state to state or province to province.
If service is r
arranty Service return to:
chased: _______________________________
e Purchased: __________________________________________
equired, do not return the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division at
oduct of equal or greater value. This is your exclusive warranty.
etail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. Proof of
BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
, express or implied, written or oral, including that of merchantability or fitness for any particular purpose with
oducts warrants that for a period of five years from the date of purchase, this product will be
emanufactured product or component. If the product is no longer available, replace-
.
esulting from any of the following: negligent use or misuse of the product, use on improper
d Time, Monday through Friday. To assist us in serving you, please have the model number and date of
Date Installed: ____________/____________Month/Year
Replacement date is five years after installation: ________/______
NOTE: End of Life Signal — Once the unit reaches the end of its
lifecycle, the MALFUNCTION SIGNAL will sound once a minute to
indicate the need to immediately replace the Alarm.
Month/Year
10
First Alert®is a r
under license.
®
ONELINK
is a r
ed trademark of the First Alert T
egister
ed trademark of BRK Brands, Inc.
egister
Printed in Mexico M08-0146-004 J1 03/07
rust used
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.