LIMITATIONS OF THIS ALARM SYSTEM...........................................................35
ONE YEAR WARRANTY...........................................................................................36
Congratulations on your ownership of a First Alert Professional Security
System. You have made a wise decision in choosing it, for it represents the latest
in security protection technology today.
– 2 –
General Information
This system offers you three forms of protection: burglary, fire, and emergency,
depending on the configuration of your system. The system consists of a master keypad
for controlling system operation, various wireless sensors which provide perimeter and
interior burglary protection, and optional smoke or combustion detectors to provide early
fire warning. In addition, optional wireless keypads may have been installed to allow you
to control the system away from the master keypad.
The system uses microcomputer technology to monitor all protection zones and system
status, display appropriate information on the keypad display, and initiate appropriate
alarms. Your system may also have been programmed to automatically send alarm or
status messages over the phone lines to a central alarm monitoring station.
The user features of this security system are listed below. Ask your installer which
features have been programmed for your system.
• STAY and AWAY arming modes: You can protect either the perimeter only, or the
entire premises.
• 3 panic key functions: Designated keys allow you to manually activate fire, personal
emergency, or silent alarms. Refer to the PANIC KEYS section for detailed information.
• Paging feature: Alerts you to certain system conditions by displaying code numbers
that indicate the type of condition that has occurred. In ad dition, p ressing the AUX key
can send a predefined message to your pager, if programmed to do so (see AUX key
function below). Refer to the PAGING FEATURE section for detailed information.
• Real-time clock: Keypad displays current time. Refer to the CLOCK/CALENDAR
section for procedures for setting the time.
• Voice announcement of system status: The master keypad’s built-in speaker
announces system status at the press of a key. Refer to the CHECKING SYSTEMSTATUS section for details.
• Message center: The system allows recording and play back of brief messages. Refer
to the RECORDING/PLAYBACK MESSAGES section for procedures.
• Device activation: Designated keys allow you to turn lights and/or other devices on
and off. In addition, some devices (e.g., a light) may be programmed to activate
automatically as a result of a system event such as an alarm or trouble condition. Refer
to the USING DEVICE COMMANDS section for detailed information.
• AUX key function: Designated key lets you activate a predefined series of keystrokes
with a single press of the
feature above). Refer to the AUX FUNCTION section for detailed information.
6<67(029(59,(:
Features
key plus user code, if programmed to do so (see Paging
AUX
– 3 –
6<67(029(59,(:
General Operation
Zones
Your system's sensing devices have been assigned to various " zones." For example, the
sensing device on your entry/exit door may have been assigned to zone 01, sensing
devices on windows in the master bedroom to zone 02, and so on. These numbers appear
on the display when an alarm or trouble condition occurs.
Fire Protection
The fire protection portion of your security system (if used) is always active and will
sound an alarm if a fire condition is detected. Refer to the FIRE ALARM SYSTEM sectio n
for important information concerning fire protection, smoke detectors and planning
emergency exit routes from the premises.
Burglary Protection
Your system provides two modes of burglary protection: STAY and AWAY. STAY
mode protects the perimeter only, allowing you to freely move within inside the premises.
AWAY mode protects the entire system. Both modes provide an entry delay time that
allows you to reenter the premises without setting off an alarm. For additional security,
you can turn the entry delay off when arming the system by using the
combination with the desired arming key. The system also allows you to bypass selected
zones before arming the system, if desired. Refer to the BYPASSING PROTECTIONZONES section. The system also provides a CHIME mode, for alerting users to the
opening of protected doors and windows while the system is disarmed.
You must turn on ("arm") the burglary protection portion of your system before it will
sense burglary alarms. To arm the system, enter your security code then press the desired
arming key (AWAY or STAY). Refer to the ARMING THE SYSTEM section for detailed
procedures and information.
Security Codes
At the time of installation, you were assigned a personal 4-digit security code. You must
enter the security code when arming and disarming the system, and when performing
other system functions. As an additional security feature, other users who do not need to
know your code can be assigned up to 6 different security codes. Refer to the SECURITYCODES section for procedures on adding security codes to the system.
Alarms
When an alarm occurs, the keypad and sounders will sound, and the keypad will display
the zone(s) causing the alarm. If your system is connected to a central monitoring station,
an alarm message will be sent. To stop the alarm sounding, simply disarm the system. The
zone(s) causing the alarm remain displayed indicating memory of alarm. Refer to the
DISARMING THE SYSTEM section for information about clearing the memory of alarm
display.
NO DELAY
key in
– 4 –
48,&.9,(:2)6<67(0)81&7,216
NOTE:
=
Boxes represent the entering of your 4-digit security code.
SECURITY FUNCTIONS
Checking system status: ----------------------------
To arm in STAY mode: --------------------------To restart exit delay: ------------------------------To arm in AWAY mode: -------------------------To arm with NO DELAY: -----------------------To arm if Quick Arm is active: ------------------To disarm the system and silence alarms: -----To bypass a zone(s): -------------------------------To turn Chime mode on or off: -------------------
*
Security code is not required if Quick Arm is active. Instead, press and hold down the
STATUS
*
STAY
(only if programmed and system armed in Stay mode)
or
AWAY
FUNCTION
+
STAY
*
AWAY
+
*
+
(
STAY
hold down for at least 2 seconds)
OFF
+
+
+
CHIME
AWAY
BYPASS
or
STAY
+
2-digit zone number(s)
+
MESSAGE CENTER
To record a message: -------------------------------
To stop recording before end of 20 seconds: --To play back a message: ---------------------------
FUNCTION
OFF
FUNCTION
+
+
RECORD
PLAY
VOLUME ADJUSTMENT
To adjust message playback/announcment volume: ---
To mute system announcements: ----------------To restore announcement sounding: ------------
FUNCTION
FUNCTION
FUNCTION
+
VOLUME
+
VOLUME
+
VOLUME
+
OFF
+
[3] or [6]
+
[3] or [6]
NO DELAY
STAY or AWAY
key.
OTHER FUNCTIONS
To set the time and date: ---------------------------
To activate or deactivate devices 1-6: ---------To activate or deactivate devices 7 & 8: -------To add a user code: -------------------------------To delete a user code (except Master Code): -To turn Test mode on: -----------------------------To turn Test mode off: ----------------------------To use the defined AUX function:---------------To send message to pager: -------------------------
** Only the master code can be used to add or delete another user code.
FUNCTION
+
Press and hold
Press and hold
+
FUNCTION
LIGHTS ON
# + LIGHTS ON
+
**
+
CODE
**
+
CODE
TEST
+
OFF
+
AUX
key 2 secs (4 beeps)
AUX
key 2 seconds (4 beeps)
+
[63]
or
LIGHTS OFF
+
user no. (02-08) + user’s code
+
user number
+
or
LIGHTS OFF
device number
+
(
02-08)
+
– 5 –
dev. no.
6<67(029(59,(:
123
456
789
0
#
*
RECORD VOLUMEPLAY
LIGHTS ON TESTBYPASS
LIGHTS OFF CODECHIME
STATUS NO DELAY FUNCTION
ARMEDREADY
OFF
AWAY
STAY
AUX
About the Master Keypad
General
IMPORTANT: If the keypad beeps rapidly upon entering the premises, an alarm has occurred during your absence and an intruder may still be on the premises. LEAVE
IMMEDIATELY and CONTACT THE POLICE from a nearby safe location.
The keypad allows you to control all system functions. The keypad features telephonestyle keys and a Liquid Crystal Display (LCD) which shows the nature and location of all
occurrences.
The keypad also features a built-in sounder which will sound during alarms and troubles.
The keypad also "beeps" during certain system functions, such as during entry/exit delay
times, in Chime mode, and when depressing any of the keys (to acknowledge the key
press). In addition, a built-in speaker announces system status.
– 6 –
6<67(029(59,(:
ALARM
AWAY
INSTANT
STAY
FIRE
REC MESSAGE
BYPASS
FAULT
CHIME TEST
LOW BAT AC
About the Display and Indicators
Display Definitions
ALARM: Appears when an intrusion has
AWAY: All burglary zones, interior and
INSTANT: Entry delay is turned off.
STAY: Perimeter burglary zones, such as protected windows and doors, are
FIRE: Appears when a fire alarm or fire fault is present. Accompanied by a
LOW BAT: Low battery condition in a wireless sensor (if zone number is displayed)
AC: Appears when AC power is present. If not lit, the system is operating on
CHIME: Appears when the Chime feature is activated.
TEST:Appears when the system is in Test mode.
REC:Appears when in Recording mode.
MESSAGE:Appears when a message has been recorded and has not yet been
BYPASS: One or more burglary protection zones have been bypassed.
FAULT: Appears when a malfunction is discovered in the system at any time;
(for other displays, see
been detected and the system is
armed (also appears during a fire
alarm or audible emergency
alarm). Accompanied by the
protection zone in alarm.
perimeter, are armed.
armed.
display of the zone in alarm.
or low system battery (if no zone number is displayed). If 00 is
displayed, a wireless keypad (5827/5827BD) has a low battery
condition.
backup battery power.
played back.
or if an open is detected in a fire zone at any time; or when a fault in a
day/night burglary zone is discovered during a disarmed period.
Accompanied by a display of the zone number in trouble.
Trouble Messages
on page 27)
LED Meanings
ARMED (Red) LED:ON = System armed
READY (Green) LED:ON = System disarmed, ready to arm
OFF = System disarmed
Blinking = System armed, but a fault exists
Blinking = System disarmed, not ready to arm (a fault exists)
NOTE: When the system is armed, the READY LED turns off.
– 7 –
6<67(029(59,(:
Master Keypad Definitions
NOTE: The system functions described below are for reference only, and require additional key entries to
activate.
DISPLAY WINDOW:
1.
(LCD). Displays protection point identification
and system status, messages, and user instructions.
ARMED INDICATOR:
2.
system has been armed (STAY, AWAY, NO
DELAY). Blinks when armed and fault exists.
READY INDICATOR:
3.
system is ready to be armed; blinking indicates
system is not ready (a zone is open).
4.
one was previously recorded. See RECORD
function.
5.
sounder.
6.
zones from being monitored by the system.
Displays currently bypassed zones.
7.
codes that can be given to other system users.
8.
off. When on, any entry through a protected delay
or perimeter zone while the system is disarmed
will cause a tone and voice descriptor to sound at
the keypad.
INTERNAL SOUNDER:
9.
sounds (see "Summary of Audible Notifications"
section).
10.
functions.
11.
function to eliminate the entry delay. Alarm
sounds immediately if entry is opened.
12.
the keypad will display all open zones, and will
announce system status.
KEY:
PLAY
KEY:
TEST
BYPASS
CODE
CHIME
FUNCTION
NO DELAY
STATUS
KEY:
KEY:
KEY:
KEY:
Announces a user’s message if
KEY:
KEY:
Liquid Crystal Display
(RED) Lit when the
When lit, indicates
Tests the system and alarm
Removes individual protection
Allows entry of additional user
Turns the Chime mode on and
Source of alarm
Allows alternate key
Used with STAY or AWAY
When pressed prior to arming,
13.
LIGHTS ON / LIGHTS OFF
lights or other devices on or off, if programmed
by the installer.
14.
15.
16.
17.
18.
19.
20.
21.
––
KEY:
AUX
perform a predefined function or to send a preset
message to a pager.
STAY
protection, guarding protected doors, windows
and other perimeter protection points, and sounds
an alarm if one is opened. Interior protection is
not armed, which allows movement within your
house without causing an alarm. Entrance can be
made through an entry delay zone without
causing an alarm if the system is disarmed before
the entry delay time expires.
AWAY
and interior burglary protection for backup
protection by sensing an intruder's movements
through protected interior areas as well as
guarding protected doors, windows, etc. Entrance
can be made through an entry delay zone without
causing an alarm if the system is disarmed before
the entry delay time expires.
OFF
the system, silences alarms and audible trouble
indicators, and clears alarm trouble display after
the problem has been corrected.
MICROPHONE:
messages up to 20 seconds long.
SPEAKER:
and confirmation sounds, status announcments,
as well as alarms (see "Summary of Audible
Notifications").
RECORD:
record personal messages.
VOLUME:
announcements and status beeps.
KEYS 0-9:
security access code(s).
Can be programmed to either
KEY:
Arms the perimeter burglary
KEY:
Completely arms both perimeter
KEY:
Disarms the burglary portion of
Used to record personal
Source of audible internal warning
Activates the recording function to
Sets the volume of system
Used to enter your individual
KEYS:
Turns
– 8 –
6<67(029(59,(:
123
456
789
0
#
*
RECORD VOLUMEPLAY
STATUS NO DELAY FUNCTION
ARMEDREADY
OFF
AWAY
STAY
AUX
21
18
17
16
15
14
10
11
12
3
6
7
8
9
5
2
1
4
20
LIGHTS ON TESTBYPASS
LIGHTS OFF CODECHIME
19
13
Master Keypad Definitions
IMPORTANT!: When you use the keypad to enter codes and commands, press the keys
within 2 seconds of one another. If 2 seconds elapse without a key depression, the entry is
aborted and must be repeated from its beginning.
NOTE: Different timeouts may occur when defining auxiliary functions and setting the
real-time clock.
– 9 –
6(&85,1*7+(35(0,6(6
Checking System Status
General Information
Before arming your system, all protected doors, windows, and other protection zones
must be closed or bypassed (see the BYPASSING PROTECTION section). Pressing the
STATUS
system condition, making it easier for you to secure any open zones.
READY LIGHT: The green READY indicator on the keypad will be lit if the system is
ready to be armed. If blinking, the system is not ready.
Press the STATUS Key
key will announce all zones that are faulted, as well as any other abnormal
Press the
phrases may be heard depending on the current state of the system:
NOTE: Phrases in brackets are variable, and are announced only if appropriate in the
current state of the system
Press the
may be heard depending on the current state of the system:
VOLUME LEVEL: The volume level of system announcements can be increased or
decreased. Refer to the MESSAGE RECORDING/PLAYBACK section for the procedure.
STATUS
disarmed, ready to arm [message] [check system]
disarmed, [not ready to arm], [message]
armed [away] [stay] [instant] [check system]
STATUS
fire alarm [zone voice descriptors]
alarm [zone voice descriptors]
fire fault [zone voice descriptors]
fault [zone voice descriptors]
check system (indicates an RF Jam condition, communication failure [FC
message], or keypad low battery condition; check the display for the specific
condition occurring)
low battery [zone voice descriptors]
system low battery
AC loss
zones bypassed
chime
key once to announce the general status of the system. The following
key twice† to announce specific system status. The following phrases
†
(second press must be within 5 seconds of first press)
System Can Be Armed
The READY light will be lit when all protection zones have been either closed or
bypassed. You may now arm the system as usual.
– 10 –
Arming in Stay Mode
Use this mode when you are staying home, but expect someone to use the entrance door
later. Close all protected perimeter windows and doors before arming. The green
READY indicator on the keypad should be lit if the system is ready to be armed.
To arm in STAY mode:
** See Quick Arming paragraph.
The keypad beeps three times and displays the armed STAY message. The red ARMED
indicator lights and the system announces “armed STAY–exit now.”
When armed in STAY mode, the system will sound an alarm if a protected door or
window is opened, but you may otherwise move freely throughout the premises. Late
arrivals can enter through the entrance door without causing an alarm, but they must
disarm the system within the entry delay period or an alarm will occur.
Restarting Exit Delay While System Armed
Ask your installer if this feature is active for your system. If active, you can restart the exit
delay at any time after arming in STAY mode. This is useful if you wish to open the
entry/exit door to let someone in after arming the system, and avoids having to disarm the
system and then re-arm it again.
6(&85,1*7+(35(0,6(6
Arming the System
+ STAY
Your security code
**
OR press and hold
STAY
**
To restart exit delay while system is armed in STAY mode: Press
Arming In Away Mode
Use this mode when no one will be staying on the premises. Close all protected perimeter
windows and doors before arming. The green READY indicator on the keypad should be
lit if the system is ready to be armed.
To arm in AWAY mode:
** See Quick Arming paragraph.
The keypad beeps twice, or beeps continuously if exit warning has been programmed for
your system, and displays the armed AWAY message. The red ARMED indicator lights
and the system announces “armed AWAY–exit now.”
When armed in AWAY mode, the system will sound an alarm if a protected door or
window is opened, or if any movement is detected inside the premises. You may leave
through the entrance door during the exit delay period without causing an alarm. You may
also re-enter through the entrance door, but you must disarm the system within the
entry delay period or an alarm will occur.
Your security code
– 11 –
+
**
OR press and hold
AWAY
STAY
key
AWAY
**
6(&85,1*7+(35(0,6(6
Arming the System
Arming the System With No Delay
Use NO DELAY with STAY mode when you are staying home and do not expect anyone
to use the entrance door.
Use NO DELAY with AWAY mode when the premises will be vacant for extended
periods of time such as vacations, etc.
When armed with NO DELAY, the system will sound an alarm if a protected door or
window is opened, including the entrance door. You may leave through the entrance door
during the exit delay period without causing an alarm, but an alarm will sound as soon as
someone reenters.
Quick Arming
or
AWAY
or
AWAY
hold down for at least 2 seconds
or
+
**
STAY
To arm with NO DELAY:
** See Quick Arming paragraph.
If Quick Arm was programmed by the installer, you do not need to enter the security code
to arm the system. Instead, simply press and hold down the desired arming key for at
least 2 seconds. The security code must always be used to disarm the system, however.
To arm if Quick Arm is active:
To arm with NO DELAY if Quick Arm is active:
IMPORTANT: The Babysitter Code and Installer Code cannot disarm the system unless
it was used to arm the system. In addition, if the system is armed by pressing and holding
the Quick-Arm buttons, neither the Babysitter Code nor Installer Code can disarm the
system.
Your security code
AWAY
hold down for at least 2 seconds
STAY
STAY
+
NO DELAY
then
NO DELAY
– 12 –
Exit Delay
6(&85,1*7+(35(0,6(6
Entry/Exit Delays
Exit delay begins immediately after arming the system, and gives you time to leave
through the designated exit door without setting off an alarm. A slow beeping will sound
throughout the exit delay period, if programmed.
Entry Delay
Exit AlarmsExit Alarm Active
To minimize false alarms sent to the alarm monitoring company, your system may have
been programmed for this feature. Ask your installer if Exit Alarm is active for your
system.
Whenever you arm the system, the exit delay begins. If an entry/exit door or interior zone
is faulted when the exit delay ends (e.g., exit door left open), the system sounds an alarm
and starts the entry delay timer. If you disarm the system before the entry delay ends, the
alarm sound stops and the message "CA" is displayed on the keypad, along with a zone
number indicating the faulted zone. No message is sent to the alarm mo nitoring company.
To clear the exit alarm condition, the open zone must be made re-secured; to clear the
display, enter your code plus OFF.
If you do not disarm the system before the entry delay ends, and an entry/exit door or
interior zone is still open, the alarm sound continues and an "exit alarm" message is sent
to the alarm monitoring company. The message "EA" is displayed on the keypad, along
with a zone number indicating the faulted zone. To stop the alarm, the system must be
disarmed (your code plus OFF); to clear the display, enter your code plus OFF a second
time. An exit alarm also results if an entry/exit door or interior zone is faulted within two
minutes after the end of the exit delay.
Entry Delays give you time to disarm the system when you re-enter through the
designated entrance door. You must disarm the system before the entry delay period ends,
or an alarm will occur. The keypad beeps during the entry delay period, reminding you to
disarm the system. There are two entry delays (if programmed). The first is for your
primary entrance and the second can be used for a secondary entrance, where a longer
delay is required to walk to the keypad to disarm the system.
You can also arm the system with no entry delay at all by using the
arming. This can provide greater security while on the premises or while away for
extended periods of time. See ARMING THE SYSTEM section for procedure.
See your installer for delay times programmed for your system.
Exit Delay:
Use the
SUMMARY OF AUDIBLE NOTIFICATION section for information which will help you
to distinguish between fire and burglary alarm sounds.
IMPORTANT: If you return and the main burglary sounder is on, DO NOT enter the
premises, but call the police from a nearby safe location. If you return after an alarm has
occurred and the main sounder has shut itself off, the keypad will beep rapidly upon
entering, indicating that an alarm has occurred during your absence and an intruder may
still be on the premises. LEAVE IMMEDIATELY and CONTACT THE POLICE from
a nearby safe location.
To disarm the system and silence burglary alarms:
The READY light will light (if no alarms have occurred while armed) and the keypad will
beep once to confirm that the system is disarmed.
Memory of Alarm
If an alarm occurs, the keypad displays the zone number (s) that caused the alarm and the
type of alarm (e.g., “FIRE ALARM”). T hese messages remain displayed until cleared by
a user.
To clear the display, note the zone number displayed and enter an OFF sequence (enter
your security code and press the
key to disarm the system and to silence alarm and trouble sounds. See the
OFF
+
OFF
OFF
* * * *
Your security code
key).
If the READY light is blinking, go to the displayed zone and correct the fault (close
windows, etc.). If the fault cannot be corrected, notify your alarm company.
– 14 –
6(&85,1*7+(35(0,6(6
Bypassing Individual Zones
Use the
intentionally unprotected. Bypassed zones are unprotected and will not cause an alarm
when violated while your system is armed. All bypasses are removed when an OFFsequence (security code plus OFF) is performed. Bypasses are also removed if the
arming procedure that follows the bypass command is not successful.
The system will not allow fire zones to be bypassed.
The system must be disarmed first.
BYPASS
key when you want to arm your system with one or more zones
Bypassing Protection Zones
To bypass a zone(s):
Important! All single-digit numbers must be preceded by a zero (for example, enter 01
for zone 1).
The keypad will display the word “BYPASS” along with each bypassed zone number.
Wait for these zones to be displayed, to be sure that intended zones are bypassed.
Arm the system as usual when the keypad displays the READY LED on steady.
Quick Bypass
Your system ma y allo w you to easily bypass all open (faulted) zones without having to
enter zone numbers individually. Ask your installer if this feature is active.
To bypass a zone(s):
In a few moments, all open zones will be displayed along with the word “BYPASS.” Wait
for these zones to be displayed before arming. Arming the system before zones are
displayed eliminates all bypasses.
Arm the system as usual when the keypad displays the READY LED on steady.
Displaying Bypassed Zones
The system allows you to determine what zones have been previously bypassed. Bypassed
zones can be displayed only when the system is disarmed, and when the “BYPASS”
message described above is displayed.
+
Your security codefor zone(s) to be bypassed
+
Your security code
BYPASS
BYPASS
2-digit zone number(s)
+
(e.g., 01, 02, 03, etc.)
WAIT
+
To display bypassed zone(s):
In a few moments, all open zones will be sequentially displayed along with the word
“BYPASS.”
+
Your security code
– 15 –
BYPASS
+
WAIT
6(&85,1*7+(35(0,6(6
Panic Keys / Chime Mode
Panic Keys
Your system may have been programmed to use special keys to manually activate panic
functions. The functions that might be programmed are listed below. See your installer for
the function(s) that may have been programmed for your system.
Active Panic Functions
Your installer should
note the functions that
are active in your
system.
To use a paire d key panic function, simply press both keys of the assigned pair at the
same time. If your keypad has lettered keys for panic functions, p ress the designated ke y
and hold down for at least 2 seconds to activate the panic function.
Types of Panic Alarms
A silent emergency sends an alarm signal to the alarm monitoring company
will be no audible alarms or visual displays.
An audible emergency sends an emergency message to the alarm monitoring company
and sounds a loud, steady alarm at your keypad and at any external sounders that may be
connected (“ALARM” plus a zone number are also displayed).
A personal emergency alarm sends an emergency message to the alarm monitoring
company
number are also displayed).
A fire alarm sends a fire alarm message to the alarm monitoring company
activates keypad and any external sounders (“FIREALARM” plus a zone number are
also displayed).
KeysZoneFunction
1 and ✴95
3 and #9 6
✴ and #99
†
and sounds at keypads, but not at external sounders. (“ALARM” plus a zone
†
,
but there
†
and uniquely
†
Chime Mode
† If your system is connected to an alarm monitoring company
Your system can be set to alert you to the opening of a door or window while it is
disarmed by using CHIME mode. When activated, three beeps will sound at the keypad
whenever a protected perimeter door is opened and the zone voice descriptor will be
announced. Pressing the
Note that the Chime mode can be turned on only when the system is disarmed.
To turn Chime mode on or off:
The “CHIME” message displays while Chime mode is on, and disappears from the
display when Chime mode is off.
STATUS
key will display the open protection points.
FUNCTION
– 16 –
+
CHIME
Automatic Paging
If the Paging feature has been programmed for your system, your pager will respond to
certain conditions as they occur in your system by displaying a message that indicates the
type of condition that has occurred. The message appears in a 7-digit format explained
below. The system can also be programmed to send up to 16 additional digits that will
appear in front of the 7-digit message. These 16 digits may consist of a PIN number or
special digits needed by the pager, account number, pauses, or any other special
characters you may choose (for example, you may want to use a special character code to
distinguish between security system messages and usual pager messages). See your
installer if these additional characters are desired.
Code Format
The Pager Code takes the following form:
AAA… = Optional 16 digits, programmed by your installer.
EEE = 3-digit number describing the event that has occurred, as follows:
00NN = First two digits are always 00, followed by 2-digit user or zone number,
Examples:
Pager displays: 911–0004
This indicates your system is reporting an alarm (911) due to a fault on zone 4 (0004).
Pager displays: 101–0005
This indicates that your system is reporting an open/disarm (101) by user 5 (0005).
86(5)81&7,216
Paging Feature
(AAAAAAAAAAAAAAAA) EEE-00NN
911 = Alarm (00NN following indicates the zone that caused the alarm)
101 = Open, system disarmed (00NN following indicates user number)
102 = Close, system armed (00NN following indicates user number)
811 = Trouble (00NN following indicates the zone that caused the trouble)
depending on the type of event that occurred. If NN = 00, it can mean an AC
loss has occurred, the system battery is low, or a 5827/5827BD wireless
keypad battery is low. The Master Keypad will indicate the specific condition.
Manual Paging
In addition, your system may have been programmed to send a unique pager message
when the
key). The actual message sent is 999-9999 (the hyphen may not appear, depending on
your pager service). This code can be used to alert the person with the pager to whatever
meaning you pre-arrange (e.g., “call home”). Ask your installer if this has been done for
your system.
To manually send the pager message, if programmed:
key is pressed (see AUX FUNCTION section for alternate function of this
AUX
(hold until 4 beeps sound)
AUX
– 17 –
86(5)81&7,216
Using Device Commands (Lights On/Lights Off Keys)
General Information
Your system may be set up so that certain lights or other devices can be turned on or off
by using the device command from the keypad. Ask your installer if this has been done in
your system. If programmed for your system, some devices may activate automatically
upon certain system conditions. In this case, the following commands can be used to
override the device activation. See your installer for a full explanation of this feature.
To activate devices 1-6: #
To deactivate devices 1-6:
To activate devices 7 & 8**:
To deactivate devices 7 & 8**:
** Devices 7 and 8 may be assigned to system devices, such as alarm bells, which should
not be activated using this command, because they are activated automatically under
certain system conditions. See your installer and the table below.
Device Descriptions
See your installer for device numbers assigned for your system.
DeviceDescription
1
2
3
4
5
6
7
8
+ LIGHTS ON + device no. (2 beeps)
# + LIGHTS OFF + device no. (2 beeps)
* * * *
Your security code(2 beeps)
****
Your security code(2 beeps)
+ # + LIGHTS ON + device no.
+ # + LIGHTS OFF + device no.
– 18 –
Message Recording/Playback/Volume Control
Recording a Message
Your system can record a brief message (up to 20 seconds) that can be played back later.
To record a message:FUNCTION
The keypad beeps and displays “REC MESSAGE.” Begin speaking into the microphone.
NOTE: The Record function can only be performed from the master keypad. It cannot
be performed from any other wireless keypad (ex. 5827BD, 5827).
86(5)81&7,216
+ RECORD
To stop recording before the end of 20 seconds: Press OFF
Otherwise, the recording automatically stops after 20 seconds. The keypad beeps twice,
the REC display turns off, but the MESSAGE display remains on.
Message Playback
The lighted word MESSAGE indicates that a new message is in memory. After playing the
message, the MESSAGE display turns off. See NOTE below if using a wireless keypad.
To play back a message:FUNCTION
Adjusting the Volume
The volume level of message playback, system announcements, and status beeps can be
changed. You can also mute system announcements if desired. See NOTE below if using
a wireless keypad.
To adjust message playback/system announcemnt volume:
FUNCTION
[6] = decreases volume one level (The keys beep at the selected volume when pressed.)
Repeat the key sequence until the desired volume level is achieved.
To mute system announcements:FUNCTION
When muted, no system announcements will be made. Recorded messages will be
announced, though, when PLAY
+ PLAY
+ VOLUME + [3] or [6] where: [3] = increases volume one level,
+ VOLUME + OFF
is pressed.
To restore announcement sounding:FUNCTION
Volume level will be restored to the level that was selected prior to muting the sound.
NOTE: If a wireless keyp ad (5827/5827BD) has been installed and is programmed for
quick arming, it cannot be used to activate message playback or adjust the volume. In this
case, you must use the master keypad to perform these functions.
– 19 –
+ VOLUME + [3] or [6]
86(5)81&7,216
AUX FUNCTION
General Information
The
send a preset message to a pager (see PAGER FEATURE section for pager operation).
Ask your installer which function has been assigned for your system.
key may have been programmed to either perform a predefined function or to
AUX
Key:
AUX
If programmed for the AUX functio n, you can use the
to 20 keystrokes that have been stored in the system’s memory. Typical functions
include:
• Seldom used but repeatable sequences
• Arming sequences that involve bypassing zones before arming
• Device activation sequences
PRE-DEFINED FUNCTION
Defining the AUX Function
The system must be disarmed before defining a function.
1. Enter Master Code + # +
2. Press the desired command sequence, up to 20 keystrokes. Press the
between each command in the sequence.
3. Press the
For example, to bypass Zones 10 and 11 and arm AWAY with NO DELAY, enter the
following string:
Master Code + # +
Note that the
AUX
AUX
PAGING FUNCTION
key to activate a string of up
AUX
(hold down until 4 beeps sound).
AUX
key twice to end the definition.
(hold until 4 beeps sound), then
AUX
key is included in the 20 keystroke maximum.
6 10 11 AUX AWAY 0 AUX AUX
AUX
key
Performing the AUX function
Press and hold down the
security code. The defined function will begin.
key at least 2 seconds until 4 beeps sound, then enter your
AUX
– 20 –
Setting the Time and Date
Your system can display the current time (see yo ur installer). The date is not displayed,
but has an internal function. The system must be disarmed with no faults present.
86(5)81&7,216
Clock/Calendar
To set the time and date:
NOTES:
1. The keypad beeps twice for invalid data entries (e.g., an hour greater than 12), and the
entry will not be accepted. The keypad beeps once for valid entries.
2. Clock-Setting mode automatically ends if no keys are pressed for one minute.
3. Daylight savings time may have been programmed to automatically begin and end.
Hour
Enter the 2-digit hour (i.e., 01-12).
Press [*] to accept the entry and continue to the AM/PM selection.
Press [#] to exit Clock-Setting mode (keypad beeps 4 times).
AM/PM
Enter 1 for PM or 0 for AM.
Press [*] to accept the entry and continue to the minute selection.
Press [#] to return to hour-setting prompt.
Minute
Enter the 2-digit minute (i.e., 00-59).
Press [*] to accept the entry and continue to the month selection.
Press [#] to return to AM/PM setting.
Month
Enter the 2-digit month designation (i.e., 01-12).
Press [*] to accept the entry and continue to the day selection.
Press [#] to return to the minute setting.
%
(The current hour will be displayed with the AM/PM indication.)
4
(The current AM/PM setting will display A or P.)
(The current minute will display.)
(The current month will display.)
+ FUNCTION + [63]
Master Code or Installer Code
Day
Enter the 2-digit day of the month (i.e., 01-31).
Press [*] to accept the entry and continue to the year setting.
Press [#] to return to the month setting.
Year
Enter the last two digits of the year (i.e., 00-99).
Press [*] to accept the entry and exit Clock-Setting mode (keypad beeps 4 times).
Press [#] to return to the day setting.
(The current day of the month will display.)
(The current year will display.)
– 21 –
),5($/$506<67(0
(If Installed)
General
Your fire alarm system (if installed) is active 24 hours a day, providing continuous
protection. In the event of an emergency, the installed smoke and heat detectors will
automatically activate your security system, triggering a loud, intermittent sound from the
keypad. An intermittent sound will also be produced by optional exterior sounders. A
“FIRE” message will appear at your keypad and remain on until you silence and clear the
alarm display.
In Case of Fire
1. Should you become aware of a fire emergency before your detectors sense the
problem, go to your nearest keypad and press the single panic key (or panic key pair)
assigned as FIRE emergency (if programmed by the installer) and hold down for at
least 2 seconds. The alarm will sound.
2. Evacuate all occupants from the premises.
3. If flames and/or smoke are present, leave the premises and notify your local Fire
Department immediately.
4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone
number of the zone(s) in an alarm condition will appear at the keypad.
Silencing a Fire Alarm
1. Silence the alarm by pressing the CODE +
key. To clear the alarm display,
OFF
enter your code and press the
2. If the keypad indicates a trouble condition after the second OFF sequence, check that
smoke detectors are not responding to smoke- or heat-producing objects in their
vicinity. Should this be the case, eliminate the source of heat or smoke.
3. If this does not remedy the problem, there may still be smoke in the detector. Clear it
by fanning the detector for about 30 seconds.
4. When the problem has been corrected, clear the display by entering your code and
pressing the
OFF
key.
OFF
– 22 –
key again.
),5($/$506<67(0
DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
BEDROOM
BDRM
BDRM
DINING
LIVING ROOM
TV ROOM
KITCHEN
BEDROOM
BEDROOM
TO
BR
LVNG RM
BASEMENT
KTCHN
.
CLOSED
DOOR
GARAGE
Smoke Detectors for Minimum Protection
Smoke Detectors for Additional Protection
Heat-Activated Detectors
National Fire Protection Assn./Smoke Detectors
With regard to the number and placement of smoke and heat detectors, we subscribe to
the recommendations contained in the National Fire Protection Association's (NFPA)
Standard #74 noted below.
Early warning fire detection is best achieved by the installation of fire detection
equipment in all rooms and areas of the household as follows: A smoke detector installed
outside of each separate sleeping area, in the immediate vicinity of the bedrooms and on
each additional story of the family living unit, including basements and excluding crawl
spaces and unfinished attics.
In addition, the NFPA recommends that you install heat or smoke detectors in the living
room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and
storage rooms, basements and attached garages.
– 23 –
•
FRONT
•
BACK
•
BATH
BEDROOM
KITCHEN
BACK DOOR
1 FLOOR
ST
BEDROOM
2 FLOOR
ND
BATH
BEDROOM
PORCH
CLOSET
BEDROOM
BEDROOM
),5($/$506<67(0
Emergency Evacuation
Establish and regularly practice a plan of escape in the event of fire. The following steps
are recommended by the National Fire Protection Association:
1.Position your detector or your interior and/or
exterior sounders so that they can be heard by all
occupants.
2. Determine two means of escape from each room.
One path of escape should lead to the door that
permits normal exit from the building. The other
should be an alternative escape, such as a window,
should your path to that door be unpassable. Station
an escape ladder at such windows if there is a long
drop to the ground.
3. Sketch a floor plan of the building. Show windows,
doors, stairs and rooftops that can be used to escape.
Indicate escape routes for each room. Keep these
routes free from obstruction and post copies of the
escape routes in every room.
4. Assure that all bedroom doors are shut while you are
asleep. This will prevent deadly smoke from
entering while you escape.
5. T ry the door. If the door is hot, check your alternate
escape route. If the door is cool, open it cautiously.
Be prepared to slam the door if smoke or heat rushes
in.
6.When smoke is present, crawl on the ground. Do not
walk upright, since smoke rises and may overcome
you. Clearer air is near the floor.
7.Escape quickly; don't panic.
8.Establish a place outdoors, away from your house,
where everyone can meet and then take steps to
contact the authorities and account for those
missing. Choose someone to assure that nobody
returns to the house — many die going back.
– 24 –
General Information
For additional security, users other than yo u who do not need to know your code can be
assigned different security codes. These secondary users are identified by "user numbers"
when their codes are assigned. You can assign up to 6 user codes (2-digit user numbers
03-08). Note that the master (primary) user of the system is the only one who can assign
codes to secondary users, and is designated user no. 02; user no. 01 is the installer’s code.
All codes can be used interchangeably when performing system functions (a system
armed with one user's code can be disarmed by another user's code), with the exception of
the Babysitter Code described below.
Babysitter Code (User 07): This code can be used to arm the system, but cannot disarm
the system unless the system was armed with this code. This code is typically assigned to
someone (such as a babysitter) who needs to arm/disarm the system only at certain times.
The Babysitter Code is assigned to User 07.
Duress Code (User 08): This feature is intended for use when you are forced to disarm
or arm the system under threat. When used, the system will act normally, but can silently
notify the alarm monitoring company of your situatio n, if that service has been provided.
Duress Code is assigned to User 08.
The Duress Code is useful only when the system is connected to an alarm monitoring
company.
6<67(0)81&7,216
Security Codes
To Add/Delete a User or Change a User's Code
Changing the Master Code
Follow the procedure for changing a user's code, but enter User No. 02 and enter the new code
twice.
IMPORTANT:
shown how to use any system function they do not need to know, such as bypassing protection
zones for example.
Sequential key depressions for all steps in a procedure must be made within 2 seconds of
one another, or else the entire entry is aborted and must be repeated from its beginning.
Add a user code:
Delete a user code:
Wait (about 3 seconds) until the keypad beeps once before p ressing any other key. The
code is automatically deleted.
Temporary users of the system (e.g., babysitters, cleaning staff) should not be
+
Master Code
+
Master Code
– 25 –
CODE
CODE
Key + user number (03-08) + user’s code
Key + user number (03-08)
6<67(0)81&7,216
Testing the System (to be conducted weekly)
Entering Test Mode
The
to be checked for proper operation. The keypad sounds a single beep every 45 seconds as
a reminder that the system is in the Test mode.
Note: An alarm message will not be sent to your alarm monitoring company during the
following tests.
Disarm the system and close all protected windows, doors, etc. The “READY” message
should be displayed and the green READY indicator (if present on the keypad) should
also be lit.
Enter the security code then press TEST
WATCH: All LED display segments will light for 3 seconds.
LISTEN. The external sounder should sound for 2 seconds and then turn off.
If the sounder does not sound, notify your service company.
FAULT ZONES. Open each protected door and window in turn and listen for three
beeps from the keypad. Identification of each faulted protection point should appear on
the display. The display will clear when the door or window is closed.
Walk in front of any interior motion detectors (if used) and listen for three beeps. T he
identification of the detector should appear on the d isplay when it is activated, and its
voice descriptor will be announced. The display will clear when no motion is detected.
Note that if wireless motion detectors are used, there is a 3-minute delay between
activations. This is to conserve battery life.
To test all smoke detectors, follow the manufacturer's instructions. The identification of
each detector should appear on the display when each is activated.
If a problem is experienced with any protection point (no confirming sounds, no display),
notify your service company.
When all protection points have been checked and are intact (closed), there should be no
zone identification numbers displayed on the keypad.
key puts your system into the Test mode, which allows each protection point
TEST
Exit Test Mode
When testing is completed, exit the TEST mode by entering your security code and
pressing the
If the Test mode is inadvertently left active, it automatically turns off after 4 hours.
OFF
key.
– 26 –
Typical Trouble Condition Displays
To silence the beeping sound for fault conditions, press any key.
FAULTIndicates that a problem exists with the zone(s) displayed, accompanied by
rapid beeping. First, determine if the zone(s) displayed are intact and make
them so if they are not. If the zone uses a wireless detector, check that
changes in the room (moving furniture, televisions, etc.) are not blocking
wireless signals from the detector. If the problem has been corrected, the
zone descriptor(s) and FAULT should disappear from the display. If not,
key an OFF sequence (security code plus OFF) to clear the display. A fault
condition can also indicate a wiring problem. If the “FAULT” display
persists, notify your service company. Note that the system will not allow
arming if a fault condition exists. To arm the system with a fault condition
present, you must first bypass the zone(s) having the fault condition.
FCIndicates that a failure has occurred in the telephone communication
portion of your system or a problem with the phone line existed when
dialing was attempted.
CCIndicates that the control is on-line with the central station's remote
computer. The control will not operate while on-line. Wait a few minutes.
The display should disappear.
dIIf this remains displayed for more than 1 minute, the system is disabled.
CAIndicates a cancelled alarm. See Entry/Exit Delay section (page 13).
EAIndicates an exit alarm. See Entry/Exit Delay section (page 13).
90Indicates that the system has detected an RF jam condition or excessive
interference. If the condition persists, notify your service company.
LOW BATAccompanied by a once-per-45 seconds beeping at the keypad, indicates
no zone no.
Notify your
†
service company
(
LOW BATAccompanied by a once-per-45 seconds beeping at the keypad, indicates
with zone no.
(
LOW BATAccompanied by a once-per-45 seconds beeping at the keypad, indicates
with zone 00
(
.
)
a low system battery condition exists. Refer to the procedure on the next page
to replace the system battery.
)
a low battery condition exists in the wireless transmitter displayed.
)
a low battery condition exists in a wireless keypad.
6<67(0)81&7,216
Trouble Messages
†
†
†
†
†
Routine Care
• Treat the components of your security system as you would any other electrical
equipment. Do not slam sensor-protected doors or windows.
• Keep dust from accumulating on the keypad and all protective sensors, particularly on
motion sensors and smoke detectors.
• The keypad and sensors should be cleaned carefully with a dry soft cloth. Do not
spray water or any other fluid on the units.
– 27 –
6<67(0)81&7,216
Maintaining your system
The components of your security system are designed to be as maintenance-free as
possible. To make sure that your system is in working condition, do the following:
1. Test your system weekly.
2. Test your system after any alarm occurs (see the TESTING THE SYSTEM section).
Low Battery Conditions in Wireless Sensors
Each wireless sensor in your system has a 9-volt or 3-volt battery. The system detects low
battery conditions in wireless sensors, including smoke detectors, personal emergency
transmitter, and the portable wireless keypad, and displays a “LOW BAT” message on the
master keypad, which also beeps. (A low battery in a wireless keypad is detected as soon
as one of its keys is pressed, and the master keypad will display “00.”). In addition, a
wireless smoke detector with a low battery also emits a "chirp" sound approximately once
every 20–30 seconds, identifying itself as the smoke detector with the weak battery.
NOTE: A low battery message means that battery replacement in the indicated sensor(s)
is due within 30 days. In the meantime, a sensor with a low battery is still operational.
Silencing Low Battery Warning Tones at the Keypad: Press the
The low battery message display will remain on as a reminder. When you replace the
weak battery with a fresh one, the sensor will send a "good battery" signal to the control
when the sensor is activated (opening/closing of door, window, etc.). To clear the “LOW
BAT” display, enter your code + OFF.
When replacing batteries, use only those recommended by your installer.
Alkaline batteries provide a minimum of 1 year of operation, and in most units and applications, provide 2–4
years of service. 3-volt lithium batteries may provide from 4-7 years of operation. Actual battery life will
depend on the environment in which the sensor is used, the number of signals that the transmitter in the sensor
has had to send, and the specific type of sensor. Factors such as humidity, high or low temperatures, and large
swings in temperature may all lead to the reduction of actual battery life in an installation.
OFF
key.
Changing the System Battery
In the event of an AC power loss, the system is
NOTE:
Battery
should be
changed at
least once
per year.
powered by a non-rechargeable, alkaline battery,
located in the battery drawer in the back of the
master keypad. The battery should be replaced
when a “LOW BAT” message with no zone
number is displayed.
Slide out the battery drawer. Remove the old
battery and replace with a fresh battery. Carefully
slide the drawer back into the master keypad.
The “LOW BAT” display should clear
automatically within 4 hours.
– 28 –
TYPICAL
9-VOLT
ALKALINE
BATTERY
(1)
OBSERVE POLARITY!
Use either a single 9-volt alkaline battery (e.g.,
Duracell PC1604 Procell) or six 1.5V “AA”
alkaline batteries (e.g., Duracell MN1500).
TYPICAL 1.5V
ALKALINE "AA"
BATTERY (6)
USE ALKALINE
BATTERIES ONLY
ONE 9-VOLT
OR
SIX 1.5V "AA"
6XPPDU\2I$XGLEOH1RWLILFDWLRQ
**
UPPER CASE indicates announcements after pressing
Lower case indicates announcements after pressing
STATUS
STATUS
once.
twice.
SOUNDCAUSEDISPLAYANNOUNCEMENT**
INTERRUPTED
Speaker and external
piezo and bell
CONTINUOUS
Speaker and external
piezo and bell
ONE SHORT BEEP
(not repeated)
Speaker and external
piezo
ONE SHORT BEEP
(once every 45 secs)
Speaker and external
piezo
TWO SHORT BEEPS
Speaker and ext. piezo
THREE SHORT
BEEPS
Speaker and external
piezo
RAPID BEEPING
Speaker and external
piezo
SLOW BEEPING
Speaker and external
piezo
FIRE ALARM
BURGLARY/AUDIBLE
EMERGENCY ALARM
a. SYSTEM DISARM
b. SYSTEM ARMING
ATTEMPT WITH AN OPEN
ZONE.
c. BYPASS VERIFY
a. SYSTEM IS IN TEST MODE
b. LOW BATTERY AT A
TRANSMITTER
c. SYSTEM LOW BATTERY
d. FAIL TO COMMUNICATE
e. RF JAM
f. KEYPAD LOW BATTERY
ARM AWAY OR MAXIMUM
a. ARM STAY OR INSTANT
b. ZONE OPENED WHILE
SYSTEM IS IN CHIME
MODE.
a. TROUBLE
b. MEMORY OF ALARM
a. ENTRY DELAY WARNING
b. EXIT DELAY WARNING
Additional Announcements:
Pressing STATUS key once will announce the following primary messages, depending on the system’s status at the time:
Disarmed–Ready to Arm [check system] or Disarmed [not ready to arm]
Armed [away] [stay] [instant] [check system] [exit now]
Pressing the STATUS key twice will announce the following secondary messages, depending on the system’s status at the time:
Fire Alarm + zone voice descriptorChime
Alarm + zone voice descriptorZones Bypassedthe primary status messages will be announced.
Fire Fault + zone voice descriptorSystem Low Battery
Fault + zone voice descriptorAC Loss
Low Battery + zone voice descriptor
LED Meanings:
ARMED (Red) LED:ON = System armed
READY (Green) LED:ON = System disarmed, ready to arm
FIRE ALARM
alarm displayed.
ALARM
alarm displayed.
a. Green LED on steady
b. The number of the open protection zone
is displayed after pressing
c. Numbers of the bypassed protection
zones are displayed (One beep is heard
for each zone displayed).
a. Opened zone identifications will appear.
LOW BAT
b.
of transmitter.
LOW BAT
c.
d.FC displayed with no zone no.
e.90 displayed
LOW BAT
f.
AWAY or AWAY + INSTANT
Red ARMED indicator is lit.
STAY
a.
Red ARMED indicator is lit.
CHIME
b.
protection zone will be displayed if the
Status key is pressed.
FAULT
a.
protection zone is displayed.
FIRE ALARM
b.
zone number in alarm is displayed.
a. Exceeding the delay time without
disarming causes alarm.
AWAY
b.
displayed
is displayed; zone number in
is displayed; zone number in
STATUS
displayed with zone number
displayed with no zone no.
displayed with zone 00
STAY + INSTANT
or
displayed, number of open
displayed. Number of troubled
ALARM
or
AWAY + INSTANT
or
is displayed.
is displayed.
is displayed;
is
If there are no secondary messages,
NOTE:
fire alarm + zone voice descriptor
alarm + zone voice descriptor
a. DISARMED–READY TO ARM
.
b. DISARMED–NOT READY TO
ARM
c. zones bypassed
a. No announcement
b. low battery + zone voice
descriptor
c. system low battery
d. check system
e. check system
f. check system
ARMED AWAY [INSTANT] –
EXIT NOW
a. ARMED STAY [INSTANT] –
EXIT NOW
b. zone voice descriptor
a. fault + zone voice descriptor
b. fire alarm or alarm + zone
voice descriptor
a. DISARM SYSTEM NOW
b. ARMED [AWAY] [INSTANT] –
EXIT NOW
When the system is armed,
NOTE:
OFF = System disarmedthe READY LED turns off.
Blinking = System armed, but a fault exists
Blinking = System disarmed, not ready to arm (a fault exists)
– 29 –
UL NOTICE: This is a "Grade A" residential system.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE
FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE,
AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC req uires the
following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict
accordance with the manufacturer's instructions, may cause interference to radio and television receptio n . It has b een
type tested and found to comply with the limits for a Class B computing device in accordance with the specifications
in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a
residential installation. However, there is no guarantee that interference will not occur in a particular installation. If
this equipment does cause interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encou raged to try to correct the interference by one or more of the following
measures:
If using an indoor antenna, have a quality outdoor antenna installed.
•
Reorient the receiving antenna until interference is reduced or eliminated.
•
Move the receiver away from the control/communicator.
•
Move the antenna leads away from any wire runs to the control/communicator.
•
Plug the control/communicator into a different outlet so that it and the receiver are on different branch circuits.
•
If necessary, the user should consult the dealer or an experienced radio/television technician for additional
suggestions.
The user or installer may find the following booklet prepared by the Federal Communications Commission helpful:
"Interference Handbook". This booklet is available from the U.S. Government Printing Office, Washington, DC
20402.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation
Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the
equipment.
IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS
In the event of telephone operational problems, disconnect the control by removing the plug from the RJ31X (CA38A
in Canada) telephone wall jack. We recommend that your certified installer demonstrate disconnecting the phones on
installation of the system. Do not disconnect the phone connection inside the control/communicator. Doing so will
result in the loss of your phone lines. If the regular phone works correctly after the control/communicator has been
disconnected from the phone lines, the control/communicator has a problem and should be returned for repair. If upon
disconnection of the control/communicator, there is still a problem on the line, notify the telephone company that they
have a problem and request prompt repair service. The user may not under any circumstances (in or out of warranty)
attempt any service or repairs to the system. It must be returned to the factory or an authorized service agency for all
repairs.
– 30 –
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 NOTICE
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that
contains, among other info rmation, the FCC r egistra tio n number and ringe r e quiva lence number ( REN) for
this equipment. If requested, this information must be provided to the telephone company.
This equipment uses the following jacks:
An RJ31X is used to connect this equipment to the telephone network.
The REN is used to determine the quantity of devices which may be connected to the telephone line.
Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming
call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the
number of devices that may be connected to the line, as determined by the total RENs, contact the
telephone company to determine the maximum REN for the calling area.
If this equipment causes harm to the telephone network, the telephone company will notify you in advance
that temporary discontinuance of service may be required. If advance notice is not practical, the telephone
company will notify the customer as soon as possible. Also, you will be advised of your right to file a
complaint with the FCC if you believe necessary.
The telephone company may ma ke changes in its facilities, equip ment, operatio ns, or procedures that could
affect the operation of the equipment. If this happens, the telephone company will p rovide advance notice
in order for you to make the necessary modifications in order to maintain uninterrupted service.
If trouble is experienced with this equipment, please contact the manufacturer for repair and warranty
information. If the trouble is causing harm to the telephone network, the telephone company may request
you remove the equipment from the network until the problem is resolved.
There are no user serviceable components in this product, and all necessary repairs must be made by the
manufacturer. Other repair methods may invalidate the FCC registration on this product.
This equipment cannot be used on telephone company-provided coin service. Connection to Party Line
Service is subject to state tariffs.
When programming or making test calls to an emergency number, briefly explain to the dispatcher the
reason for the call. Perform such activities in the off-peak hours; such as early morning or late evening.
– 31 –
CANADIAN DEPARTMENT OF COMMUNICATIONS
(DOC) STATEMENT
The Canadian Department of Communications label identifies
certified equipment. This certification means that the equipment
meets certain telecommunications network protective,
operational and safety requirements. The Department does not
guarantee the equipment will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is
permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be
installed using an acceptable method of connection. In some
cases, the company's inside wiring associated with a single line
individual service may be extended by means of certified
connector assembly (telephone extension cord). The customer
should be aware that compliance with the above conditions may
not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized
Canadian maintenance facility designated by the supplier. Any
repairs or alterations made by the user to this equipment, or
equipment malfunctions, may give the telecommunications
company cause to request the user to disconnect the equipment.
Users should ensure for th eir own protection t hat the electric al
ground connections of the power utility, telephone lines and
internal metallic water pipe system, if present, are connected
together. This precaution may be particularly important in rural
areas.
Caution:
themselves, but should contact the appropriate electric
inspection authority, or electrician, as appropriate.
The Load Number (LN) assigned to each terminal device
denotes the percentage of the total load to be connected to a
telephone loop which is used by the device, to prevent
overloading. The termination on a loop may consist of any
combination of devices subject only to the requirement that the
total of the Load Numbers of all the devices does not exceed
100.
User should not attempt to make such connections
NOTICE
L'étiquette du ministère des Communications du Canada
AVIS
identifie le matériel homologué. Cette étiquette certifie que le
matériel est conforme à certaines normes de protection,
d'exploitation et de sécurité des réseaux de télécommunications.
Le ministère n'assure toutefois pas que le matériel fonctionnera à
la satisfaction de l'utilisateur.
Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est
permis de le raccorder aux installations de l'entreprise locale de
télécommunications. Le matériel doit également être installé en
suivant une méthode acceptée de raccordement. Dans certains
cas, les fils intérieurs de l'entreprise utilisés pour un service
individuel à la ligne unique peuvent être prolongés au moyen
d'un dispositif homologué de raccordement (cordon
prolongateur téléphonique interne). L'abonné ne doit pas oublier
qu'il est possible que la conformité aux conditions énoncées cidessus n'empèchet pas la dégradation du service dans certaines
situations. Actuellement, les entreprises de télécommunications
ne permettent pas que l'on raccorde leur matériel aux prises
d'abonnés, sauf dans les cas precis prévus par les tarifs
particuliers de ces entreprises.
Les réparations du matériel homologué doivent être effectuées
pas un centre d'entretien canadien autorisé désigné par le
fournisseur. La compagnie de télécommunications peut
demander à l'utilisateur de débrancher un appareil à la suite de
réparations ou de modifications effectuées par l'utilisateur ou à
cause de mauvais fonctionnement.
Pour sa propre protection, l'utilisateur doit s'assurer que tous les
fils de mise en terre de la s ource d'én ergie électri que, d es lignes
téléphoniques de réseau de conduites d'eau s'il y en a, soient
raccordés ensemble. Cette précaution est particulièrement
importante dans les régions rurales.
Avertissement:
raccordements lui-même; il doit avoir recours à un service
d'inspection des installations électriques, ou à un électricien,
selon le cas.
L'indice de charge (IC) assigné à chaque dispositif terminal pour
éviter toute surcharge indique le pourcentage de la charge totale
qui peut être raccordé à un circuit téléphonique bouclé utilisé
par ce dispositif. La terminaison du circuit bouclé peut être
constituée de n'importe quelle combinaison de dispositifs,
pourvu que la somme des indices de charge de l'ensemble des
dispositifs ne dépasse pas 100.
L'utilisateur ne doit pas tenter de faire ces
– 32 –
OWNER'S INSURANCE PREMIUM CREDIT REQUEST
This form should be completed and forwarded to your homeowner's insurance carrier for possible premium credit.
All Accessible Openings, Including Skylights, Air Conditioners and Vents
Basement Door
All Windows
Rear Door
I
nterior Locations
All Exterior Doors
G. ADDITIONAL PERTINENT INFORMATION:
Signature: Date:
– 34 –
SERVICING INFORMATION
Your local First Alert Professional dealer is the person best qualified to service your
alarm system. Arranging some kind of regular service program with him is advisable.
Your local First Alert Professional dealer is:
Name:
Address:
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or other
emergency. Any alarm system, whether commercial or residential, is sub ject to compromise or failure to warn for a variety of
reasons. For example:
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or
disconnect an alarm warning device.
• Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work without
power. Battery operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly.
Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the
signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or
provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal
Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are
as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start
where smoke cannot reach the detectors , such as i n chimneys, i n walls, or roofs, or on th e other side of closed doors. Smoke
detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not
sense a first floor or basement fire. Moreover, smoke detectors have sensing limitations. No smoke detector can sense every kind
of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking
in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children
playing with matches, or arson. Depending upon the nature of the fire and/or the locations of the smoke detectors, the detector,
even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or
death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation
manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and
intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes
place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking,
painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability.
Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of protected area approaches the
temperature range of 90° to 105°F, the detection performance can decrease.
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other
side of closed or partly open doors. If warn ing devices sound on a different level of the residence from the bedrooms, then they
are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm
is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however
loud, may not warn hearing-impaired people or waken deep sleepers.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or
temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves
from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as
long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This
alarm system should be tested weekly to make sure all sensors and transmitters are working properly.
Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insurance.
Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their
lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to
learn about these developments.
– 39 –
ONE YEAR LIMITED WARRANTY
Pittway Corporation, and it s divisions, subs idiaries and affiliates (" Seller"), 165 Eileen Way, Syosset , New York 11791,
warrants its First A lert security equipment (the "product") to be f ree from defect s in material s and workmanship for one
year from date of original purchas e, under normal use and service. Seller's obligation is l imited t o repairing or replacing,
at its option, free of charge for parts, labor, or transportation, any product proven to be defective in materials or
workmanship under normal use and service. Seller shall have no obligation under this warranty or otherwise if the
product is altered or improperly repaired or serviced by anyone other than the Seller. In case of defect, contact the
security professional who installed and maintains your security equipment or the Seller for product repair.
This one year Limited Warranty is in lieu of all other express warranties, obligations or liabilities. THERE ARE NO
EXPRESS WARRANTIES, WHICH EXTEND BEYOND THE FACE HEREOF. ANY IMPLIED WARRANTIES,
OBLIGATIONS OR LIABILITIES MADE BY SELLER IN CONNECTION WITH THIS PRODUCT, INCLUDING ANY
IMPLIED WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE,
ARE LIMITED IN DURATION TO A PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE. ANY
ACTION FOR BREACH OF ANY WARRANTY, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF
MERCHANTABILITY , MUST BE BROUGHT WITHIN 12 MONTHS FROM DATE OF ORIGINA L PURCHASE. IN NO
CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR
BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF
LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE
OR FAULT. Some states do not allow limitation on how long an i mplied warranty lasts or the exc lusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply to you.
Seller does not represent that the product may not be compromised or circumvented; that the product will prevent any
personal injury or property loss by burglary, robbery, fire or otherwise; or that the product will in all cases provide
adequate warning or protection. Buy er understands that a properly ins talled and maintained alarm may only reduce the
risk of a burglary, robbery, fire or ot her event s oc curri ng wit hout prov iding an alarm , but it i s not ins urance or a guarant ee
that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY , SELLER
SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A
CLAIM THE PRODUCT FAILED TO GIVE WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR
OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE
EXCEED THE PURCHASE PRICE OF THE PRODUCT, WHICH SHALL BE THE COMPLETE AND EXCLUSIVE
REMEDY AGAINST SE LLER. This warranty gives you s pecific legal rights, and you m ay also have other rights which
vary from state to state. No increase or alteration, written or verbal, to this warranty is authorized.