Local programming requires the use of an alpha keypad connected to the keypad terminals on the control.
1. POWER UP, then depress [
✱
] and [#] both at once, within 50 seconds of powering up.
OR
2. Initially, key: Installer Code plus 8 + 0 + 0.
✱
(if
98 was used to exit previously, see
To Exit Programming Mode
paragraph below.
Data Field Programming Procedures
Task Procedure
Go to a Data Field Press [∗] + [Field Number], followed by the required entry.
Entering Data When the desired field number appears, simply make the required entry. When the last
entry for a field is entered, the keypad beeps three times and automatically displays the
next data field in sequence.
If the number of digits that you need to enter in a data field is less than the maximum
digits available (for example, the phone number fields *41, *42), enter the desired data,
then press [∗]. The next data field number is displayed.
Review a Data Field Press [#] + [Field Number].
Data will be displayed for that field number. No changes will be accepted in this mode.
Deleting an Entry Press [∗] + [Field Number] + [∗]. (Applies only to fields ∗40–*46, *94, and pager
4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
Zone alpha descriptors
INITIALIZE DOWNLOAD and RESET DEFAULTS
✱
96 Initializes download ID and subscriber account number.
✱
97 Sets all data fields to original factory default values.
TO EXIT PROGRAMMING MODE:
✱
98 Exits programming mode and
the system must be powered down, then powered up, then press both [
prevents
re-entry by: Installer Code + 8 + 0 + 0. To reenter the programming mode,
✱
] and [#] at same time within 50 seconds
of powering up (method 1 described above), UNLESS Local Lockout (in field *91) is enabled. If so, re-entry to
programming mode is permitted
✱
99 Exits programming mode and
only
by Installer Code + 8 + 0 + 0 (method 2 described above).
IMPORTANT-Automatic Upload: After exiting program mode, the control automatically initiates a download session and
uploads all programming information. After a successful upload (alpha keypad displays “Upload Completed”), the
following fields are locked and are no longer accessible via local programming mode: *20-installer code, *40-*46telephone and account numbers, *94-download phone number. However, these fields are accessible by the downloader.
To stop the upload, press [#] + [0] within 30 seconds of exiting program mode.
SPECIAL MESSAGES
OC = OPEN CIRCUIT (no communication between Keypad and Control).
EE or ENTRY ERROR = ERROR (invalid field number entered; re-enter valid field number).
After powering up, AC, dI (disabled) or Busy Standby and NOT READY will be displayed after approximately 4 seconds.
This will revert to a “Ready” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
delay by pressing [#] + [0].
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after
you correct the programming.
C5 or CLOCK NOT SET = System clock is not set. Set clock via keypad or downloader to clear message.
– 2 –
Page 3
PROGRAMMING FORM
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Field Function Data Entries Programmable Values
SYSTEM SETUP (✱20–✱29)
✱
20 INSTALLER CODE
✱
21 QUICK ARM ENABLE
✱
22 RF JAM OPTION
✱
23 QUICK (FORCED) BYPASS
✱
24 RF HOUSE ID CODE
✱
26 CHIME BY ZONE
✱
27
POWERLINE CARRIER DEVICE (X–10)
HOUSE CODE
✱
28 ACCESS CODE FOR
PHONE MODULE
✱
29 LONG RANGE RADIO OUTPUT
ZONE SOUNDS AND TIMING (✱31 – ✱39)
✱
31 SINGLE ALARM SOUNDING per ZONE
✱
32 FIRE ALARM SOUNDER TIMEOUT
✱
33 ALARM SOUNDER (BELL) TIMEOUT
✱
34 EXIT DELAY
✱
35 ENTRY DELAY #1 (zone type 01)
✱
36 ENTRY DELAY #2 (zone type 02)
∗∗∗∗37 AUDIBLE EXIT WARNING
✱
38 CONFIRMATION OF
ARMING/DISARMING DING
✱
39 POWER UP IN PREVIOUS STATE
| | |
[1,1]
Part. 1 Part.2
[1]
[0,0]
Part. 1 Part. 2
| | |
Part. 1 Part. 2 Common
[0]
[0]
| [00]
(Partition 1 only)
[0]
[1]
[0]
[1]
| | [60, 60]
Part. 1 Part. 2
Common zones use same
delay as partition 1.
| | [30, 30]
Part. 1 Part. 2
Common zones use same
delay as partition 1.
| | [30, 30]
Part. 1 Part. 2
[1,1]
Part. 1 Part. 2
[0,0]
Part. 1 Part. 2
[1]
4 digits, 0–9
NOTE: Installer code is automatically disabled 4 hours
after power-up.
0 = no; 1 = yes
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
0 = no quick bypass UL: must be “0”
1 = allow quick bypass (code + [6] + [#] )
00 = disable all wireless keypad usage
01–31 = using 5827, 5827BD or 5804BD keypad
[00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for "✱", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no; 1 = yes
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be “1” for fire install.
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
00 - 96 = 0 - 96 secs; 97 = 120 secs;98 = 180 secs;
99 = 240 secs
SIA Installations: minimum exit delay is 45 seconds
UL: see inst. instr. for requirements.
For UL Residential Burglary Alarm installations, must be set
for a maximum of 30 seconds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar
Alarm, total entry delay may not exceed 45 seconds.
See *35 Entry Delay 1 above for entries.
Common zones use same delay as partition 1.
0 = no; 1 = yes
SIA Installations: must be enabled (enter 1)
0 = no; 1 = yes (wired keypads and RF)
2 = yes, RF only
UL: must be “1” for UL Commercial Burglar Alarm inst.
0 = always power up disarmed
1 = power up in previous state UL: must be “1”
SIA Installations: must be “1”
SIA Installations:
DIALER PROGRAMMING (✱40 – ✱42)
Enter the number of digits shown. Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the
maximum digits entered, exit the field by pressing [✶ ]. The next field number is displayed.
✱
40 PABX ACCESS CODE or
CALL WAITING DISABLE
✱
41 PRIMARY PHONE No.
✱
42 SECOND PHONE No.
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱41
| | | | | Enter up to 6 digits. To clear entries, press ✱40✱. If call
waiting used, enter “∗ (#+11) 70” plus “# + 13” (pause). See Inst. Instr. for notes on
using the Call Waiting Disable feature.
✱ or ✱42✱ respectively
.
– 3 –
Page 4
NOTE: Entry of a number other than one specified will give unpredictable results.
For fields *43-*46: Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; #+15 for F. Enter 0 as the first digit of a 4-digit account number for Nos. 0000-0999.
Exit field by pressing ✱ if only 3 digits are used. E.g., For Acct. B234, enter: #+11| 2 | 3 | 4
✱
43 PARTITION 1 PRIMARY ACCT. No.
✱
44 PARTITION 1 SECONDARY ACCT. No.
✱
45 PARTITION 2 PRIMARY ACCT. No.
✱
46 PARTITION 2 SECONDARY ACCT. No.
✱
47 PHONE SYSTEM SELECT
✱
48 REPORT FORMAT
✱
49 SPLIT/DUAL REPORTING
| | | [FFFF]
| | | [FFFF]
| | | [FFFF]
| | | [FFFF]
[1]
[77]
primary secondary
[0]
See box above for entries. To clear entries, press *43
See box above for entries. To clear entries, press *44*.
See box above for entries. To clear entries, press *45*.
See box above for entries. To clear entries, press *46*.
If Cent. Sta.
IS NOT
on a WATS line:
0=Pulse Dial; 1=Tone Dial;
if Cent. Sta.
2 = Pulse Dial ; 3 = Tone Dial
IS on
a WATS line:
Select the desired reporting format.
2 = 4+2 ADEMCO L/S STANDARD
7 = 4-digit ADEMCO CONTACT ID® REPORTING
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
✱
50 BURGLARY DIALER DELAY
5 = All All
[1]
0 = no delay UL: must be “0”
1 = 15 seconds SIA Installations: delay
2 = 30 seconds must be minimum of
✱
54 DYNAMIC SIGNALING DELAY
3 = 45 seconds 30 seconds
[2]
Set delay from 0-225 secs in 15-sec increments.
0 = no delay (both signals sent), 1 = 15 secs,
2 = 30 secs, etc.
✱
55 DYNAMIC SIGNALING PRIORITY
[0]
UL: Grade AA must be “0;” Grade A must be “15” max
0 = Primary Dialer first; 1 = Long Range Radio first.
For UL Commercial Burglary installations that use a
DACT and LRR, this field must be “0”.
∗∗∗∗56, ∗∗∗∗57, ∗∗∗∗58 Menu Modes
These are Menu Mode commands, not data fields, for Zone Programming, Function Key Programming, and Expert Mode Zone Programming
respectively. See page 2 and their respective sections in the Installation and Setup Guide for procedures.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (∗∗∗∗59 – ∗∗∗∗68, ∗∗∗∗70 - ∗∗∗∗76, & ∗∗∗∗89)
For ADEMCO CONTACT ID® Reporting: Enter any digit (other than 0) in the
ignored). A 0 (
not
#+10) in the
first
box disables the report. UL: see installation instructions for requirements
first
box, to enable zone to report (entries in the
second
boxes are
For 4+2 Format: Enter codes in both boxes (1st and 2nd digits) for 1-9, or #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F
SYSTEM STATUS REPORT CODES (✱59–✱ 68)
✱
59 EXIT ERROR REPORT CODE
✱
60 TROUBLE REPORT CODE
✱
61 BYPASS REPORT CODE
✱
62 AC LOSS REPORT CODE
✱
63 LOW BAT REPORT CODE
✱
64 TEST REPORT CODE
| [11] See box above. Use Scheduling mode to set periodic test reports.
NOTE: A test report is automatically set for schedule 32 when the
✱
65 OPEN REPORT CODE
✱
66 ARM AWAY/STAY RPT CODE
Away Stay Away Stay Away Stay
✱
67 RF XMTR LOW BAT REPORT CODE
✱
68 CANCEL REPORT CODE
[1] See box above.
| [11] See box above.
| [00] See box above.
| [00] See box above.
| [11] See box above.
system time is initially set, and the first report is sent 12 hours later;
thereafter the test report is sent every 28 days.
[0,0,0] See box above.
Part. 1 Part. 2 Common
Part. 1 Part. 2 Common
[0,0,0,0,0,0]
| [00] See box on previous page.
UL: must be enabled if wireless devices are used
| [11] See box on previous page.
See box above.
– 4 –
Page 5
RESTORE REPORT CODES (✱70 – ✱76)
✱
70 ALARM RESTORE RPT CODE
✱
71 TROUBLE RESTORE RPT CODE
✱
72 BYPASS RESTORE RPT CODE
✱
73 AC RESTORE RPT CODE
✱
74 LOW BAT RESTORE RPT CODE
✱
75 RF XMTR LO BAT RST RPT CODE
✱
76 TEST RESTORE RPT CODE
OUTPUT AND SYSTEM SETUP (
✱
77 DAYLIGHT SAVINGS TIME
START\END MONTH
✱
78 DAYLIGHT SAVINGS TIME
START\END WEEKEND
✱
79, ✱ 80, ✱ 81, ✱ 82 Menu Modes
These are Menu Mode commands, not data fields, for Output Device Mapping, Output Programming, Zone List Programming, and Alpha
Programming respectively. See page 2 and their respective sections in the Installation and Setup Guide for procedures.
0 = disabled, 1 = first, 2 = second, 3 = third
4 = fourth, 5 = last, 6 = next to last, 7 = third to last
[0]
[0]
[4]
NOTE: System messages are
logged when any non-zero
selection is made.
E.g. (multiple choice): for AAV
(4) plus Exit Delay restart (8)
enter # + 12; for all (1 + 2 + 4 +
8), enter # + 15.
[1]
[0]
| [00]
[15]
[9]
[0,0]
[1]
0 =Eastern, 1 = Central
2 = Mountain, 3 = Pacific
0 = no, 1 = partition 1 only
2 = partition 2 only, 3 = both partitions
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
1 = 30 seconds 7 = 3 min #+13 = 10 min
2 = 45 seconds 8 = 4 min #+14 = 12 min
3 = 60 seconds 9 = 5 min #+15 = 15 min
4 = 90 seconds #+10 = 6 min
5 = 2 minutes #+11 = 7 min
(assign cross zones on zone list 4, with *81 Menu mode)
0 = no, 1 = yes (canceled alarm display is automatically
disabled if field *199 is set to “1,” 2-digit display).
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min
1 = 30 seconds 7 = 3 min #+13 = 10 min
2 = 45 seconds 8 = 4 min #+14 = 12 min
3 = 60 seconds 9 = 5 min #+15 = 15 min
4 = 90 seconds #+10 = 6 min
5 = 2 minutes #+11 = 7 min
UL: may only be used on non-burglar alarm/ non-fire alarm
zones when used in fire and/or UL burglar alarm installation
See box on previous page for report code entries.
0 = None; 1 = Alarm/Alarm Restore
2 = Trouble/Trouble Restore;
4 = Bypass/Bypass Restore;
8 = Open/Close.
Restore”, and “Open/Close”, enter 9 (1 + 8); To select
all, enter #15.
0 = None
1 = Local Lockout
2 = Sounder Delay
UL: if used, entry delay (*35) must be 30 sec. max.
4 = AAV UL: must use UVCM module
8 = Exit Delay Restart/Reset UL: must be disabled
SIA Installations: Exit Delay should be enabled.
Entry 2:
0 = Keypad display when line is faulted
1 = Keypad display plus keypad trouble sound
2 = Same as “1”, plus programmed output device
STARTS. If either partition is armed, external sounder
activates also. NOTE: Output Device must either be
programmed to be STOPPED in field ✱80 or
STOPPED by Code + # + 8 + output number.
0 = Unlimited Reports
1 = 1 report pair; 2 = 2 report pairs
SIA Installations: Must be set for option 1 or 2.
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
161 PAGER 1 CHARACTERS
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
162 PAGER 1 REPORT OPTIONS
✱
163 PAGER 2 PHONE No.
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
164 PAGER 2 CHARACTERS
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
165 PAGER 2 REPORT OPTIONS
✱
166 PAGER 3 PHONE No.
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
167 PAGER 3 CHARACTERS
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
168 PAGER 3 REPORT OPTIONS
✱
169 PAGER 4 PHONE No.
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
170 PAGER 4 CHARACTERS
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
171 PAGER 4 REPORT OPTIONS
✱
172 PAGER DELAY OPTION FOR ALARMS
| | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | |
Part. 1 Part. 2 common
[0,0,0]
[0,0,0]
Part. 1 Part. 2 common
| | | | | | | | | | | | | | |
0,0,0]
Part. 1 Part. 2 common
[0,0,0]
Part. 1 Part. 2 common
[3]
For each partition, select from the following options:
0 = no reports sent
1 = Open/closes all users
4 = All alarms and troubles
5 = All alarms / troubles, and open/closes for all users
12 = Alarms / troubles for zones entered in zone list 9
13 = Alarms / troubles for zones entered in zone list 9,
and open\closes for all users
See field *162 for reporting options. Select for each
partition (use zone list 10 if using options 12 or 13).
See field *162 for reporting options. Select for each
partition (use zone list 11 if using options 12 or 13).
See field *162 for reporting options. Select for each
partition (use zone list 12 if using options 12 or 13).
0 = none, 1 = 1 minute, 2 = 2 minutes, 3 = 3 minutes
This delay is for ALL pagers in the system.
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
✱
174 CLEAN ME REPORTING OPTIONS
(for ESL smoke detectors)
✱
177 DEVICE DURATION 1, 2
(used in *80 Menu mode-Device Actions 5/6)
✱
181 50/60 HERTZ AC OPERATION
[0]
[0] [0]
1 2
[0]
0 = disable; 1 = Clean Me signal reports;
Note:
If Clean Me is enabled, you must enter “3” in
field ✱56 programming for zone 1 response time.
0 = 15 seconds 6 = 2-1/2 min #+11 = 7 min
1 = 30 seconds 7 = 3 min #+12 = 8 min
2 = 45 seconds 8 = 4 min #+13 = 10 min
3 = 60 seconds 9 = 5 min #+14 = 12 min
4 = 90 seconds #+10 = 6 min #+15 = 15 min
5 = 2 minutes
0 = 60 Hz; 1 = 50 Hz
– 6 –
Page 7
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
✱
182 CONFIGURABLE ZONE TYPE 90
1 2 3 4 5 6 7 8 9 10
[12-14-4-5-4-6-0-0-6-6]
Enter the appropriate value for each entry, 1-10, based on the charts provided on
next page. Each entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
✱
183 ZONE TYPE 90 REPORT CODES
IMPORTANT: Use existing Contact ID®
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
✱
184 CONFIGURABLE ZONE TYPE 91
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
90 ALARM ID: 131
TROUBLE ID: 382
Enter the desired 3-digit Contact ID® report codes for
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [∗]
moves forward. Press [∗] when done to continue.
1 2 3 4 5 6 7 8 9 10
[8-6-8-14-8-2-0-0-0-2]
Enter the appropriate value for each entry, 1-10, based on the charts provided on
next page. Each entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
✱
185 ZONE TYPE 91 REPORT CODES
IMPORTANT: Use existing Contact ID®
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
91 ALARM ID: 000
TROUBLE ID: 000
Enter the desired 3-digit Contact ID® report codes for
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [∗]
moves forward. Press [∗] when done to continue.
TOUCH SCREEN DEVICE (AUI) ENABLE
✱
189 AUI DEVICE 1 and 2 ENABLE
(for Touch Screen style keypads)
NOTE:
System supports up to two touch
screen style keypads (e.g. Symphony
Advanced User Interface, and FA700KP
Touch Screen keypad).
[0] [0]
AUI 1 AUI 2
AUI 1: Must set AUI address to 1
AUI 2: Must set AUI address to 2
Enter each touch screen (AUI) device’s home partition.
0 = disabled
1 = partition 1; 2 = partition 2; 3 = partition 3 (common)
NOTE: Use of AUI does not affect the number of
standard keypads supported.
AUI Compatibility Note: To ensure proper AUI device
operation, connect only to controls having
microprocessor version 3.0 or higher, and use AUI
devices with the following rev levels: FA700KP series
use version 1.0.9 or higher; 8132/8142 (Symphony)
series use version 1.1.175 or higher.
KEYPAD OPTIONS (*190-*196)
NOTE: Each keypad must be assigned a unique address. Keypads programmed with the same address will give
unpredictable results. Options for keypad address 16 are set by the factory and cannot be changed.
✱
190 KEYPAD 2 DEVICE ADDRESS 17
✱
191 KEYPAD 3 DEVICE ADDRESS 18
✱
192 KEYPAD 4 DEVICE ADDRESS 19
✱
193 KEYPAD 5 DEVICE ADDRESS 20
✱
194 KEYPAD 6 DEVICE ADDRESS 21
✱
195 KEYPAD 7 DEVICE ADDRESS 22
✱
196 KEYPAD 8 DEVICE ADDRESS 23
✱
197 EXIT TIME DISPLAY INTERVAL
✱
198 DISPLAY PARTITION NUMBER
✱
199 ECP FAIL DISPLAY
[1] [0]
Partition Sound
[1] [0]
Part. Sound
[1] [0]
Part. Sound
[1] [0]
Part. Sound
[2] [0]
Part. Sound
[2] [0]
Part. Sound
[3] [0]
Part. Sound
[3]
[1]
[0]
Partition: 0 = keypad disabled; 1-3 = part. no. (3 = com)
Sound: 0 = no suppression
1 = suppress arm/disarm and E/E beeps
2 = Suppress chime beeps only
3 = suppress arm/disarm, E/E, and chime beeps
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
0 = no display; 1-5 = seconds between display refresh
NOTE: If using only 2-digit fixed-word keypads (e.g.,
FA245RF), it is recommended to use “0” or use exit delay
times not greater than 96 seconds. See Installation
Instructions for explanation.
0 = no; 1 = yes (partition no. appears on Alpha Display)
(for Alpha Display Keypads)
0 = 3-digit display (“1” + device address)
1 = 2-digit fixed-display as “91” (e.g. if using FA245RF)
Night-Stay Note: Setting this field to “1” disables the
control’s Night-Stay feature (code + [3] [3]). In addition, the
“Canceled Alarm” display is also disabled (field *86).
– 7 –
Page 8
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data
fields*182-*185. Configurable zone types 92 and 93 can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and
field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the
tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1 (see note 5 for RF zones) ENTRY 2 (see note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
see note 5
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
Auto
Restore
0 = no
4 = yes
Vent Zone
0 = no
8 = yes
ENTRY 3 (see note 5 for RF zones) ENTRY 4 (see note 5 for RF zones)
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
see note 5
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
Byp. when
disarmed
0 = no
4 = yes
Byp. when
armed
0 = no
8 = yes
ENTRY 5(see note 5 for RF zones) ENTRY 6(see note 5 for RF zones)
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
see note 5
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
see note 6
Dial Delay
(see field *50)
0 = no
4 = use delay
Fault Delay
(see field *87)
0 = no
8 = use delay
see note 1
ENTRY 7ENTRY 8
Display Faults Power Reset/
Verification
0 = show alarms
when armed
& disarmed
1 = don’t show
alarms when
armed
alarms, trbles,
faults when
disarmed)
0 = no
4 = power reset
12 = verification
(see zone
(show
after fault
(by code + OFF)
type 16)
3 = never show
any alarms,
trbles, faults
Entry 7 = fault display + power
reset/verification
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry’s columns (one option per
column). For example, to program Entry 2 for
“alarm response to short,” “auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
EOL
Zone Conditions Represented
NOTES:
1. Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2. To create an interior type zone, select
“respond as interior zone type” (Entry 8,
interior type = yes), and set zone
response to “fault” in entries 3-4 to ensure
fault displays; do not set as “normal,”
“alarm,” or “trouble.”
3. Do not set fire zones to respond as a
“fault” (entries 1-6), otherwise faults will
not display unless the [∗] key is pressed.
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
5. RF Zones: The “open” option in entries 1,
3, and 5 is not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for offnormal RF zone conditions.
6. a. Zone-Doubling/Double-Balanced: A
short on either zone of a zone-doubled
pair or on a double-balanced zone
causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones, both zones
of the doubled pair must be assigned
the same response to a short.
OPENSHORTEDINTACT
in Entries 1-6
ZONE-003-V0
– 8 –
Page 9
∗∗∗∗56 ZONE PROGRAMMING WORKSHEET
NOTES:
Zone Type: see chart on
page 12;
Report Code: enabled if
any digit entered as 1st
digit;
Hardwire Type (zns 1-8):
0 = EOL 3 = ZD
1 = NC 4 = DB
2 = NO
Input Type:
2 = AW (zones 9-48)
3 = RF (zones 9-48)
4 = UR (zones 9-48)
5 = BR (zones 49-64)
NOTE: Zones 9-16 not
available if zone
doubling enabled.
Response Time:
0 = 10msec
1 = 350msec
2 = 700msec
3 = 1.2 sec
† Reserved Zones
91 = addressable device
report enable/disable
default zone type =
[05].
92 = Duress report
enable/disable
Zone Zn Type Part. Report Hardwire Type Rsp. Time Location
1
2
3
4
5
6
7
8
Zone Zn Type Part. Report Input Type Loop Serial No. Location
01 Paging
02 Time Display
03 Arm AWAY
04 Arm STAY
05 Arm NIGHT-STAY
06 Step Arming
07 Device Activation Device:
08 Comm. Test
09 Macro Key 1 Assign each macro key to only a single partition.†
10 Macro Key 2 Assign each macro key to only a single partition. †
11 Macro Key 3 Assign each macro key to only a single partition. †
12 Macro Key 4 Assign each macro key to only a single partition. †
00 Emergency Keys: zone 95 zone 99 zone 96 paging
Personal Emergency n/a [key A (zone 95, zone type 15) = p1,2,3]
One-Button Paging n/a
Audible Alarm n/a [key B (zone 99, zone type 07) = p1,2,3]
Fire n/a [key C (zone 96, zone type 09) = p1,2,3]
Emergency Keys: A = paired keys [1] / [∗] (zone 95); B = paired keys [∗] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
† There are only four macros system-wide.
A
P1 P2 com B P1 P2 comC P1 P2 comD P1 P2 com
Comments
[key D = p1,2,3]
OUTPUT RELAYS/POWERLINE CARRIER DEVICES (X-10) WORKSHEET FOR ∗∗∗∗79, ∗∗∗∗80 and ∗∗∗∗81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
∗∗∗∗79 RELAY/POWERLINE CARRIER DEVICE (X-10) MAPPING (Must program before using ∗∗∗∗80)
OUTPUT TYPE
Relay X10
Output
No.
01
02
03
04
05
06
07
08
✱
81 ZONE LISTS FOR OUTPUT DEVICES
Module
Addr.
Pos
(1-4)
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear in sequence.
Note:
Record desired zone numbers below, noting that a list may include
List No. Used For…Contains These Zones…
01 General Purpose (GP)
02 General Purpose
03 Chime-by-Zone or GP
04 Cross Zones
05 Night-Stay Zones or GP (Night-Stay feature is disabled if field *199 is set to “1”)
Activated by: 0=delete; 1=zn list; 2=zn type; 3=zn no.; Zone List (ZL): 1-8 = list; Zone Type (ZT): (see table below); Zone No.(ZN): 00=none; 01-64
Partition Number (P) (if using ZT trig): 0 = any; 1 = partition 1; 2 = partition 2; 3 = common
Event (for zone list/activated by): By Zone List: 0 = restore; 1 = alarm; 2 = fault; 3 = trouble; By Zone No.: 0 = restore; 1 = alarm/fault/trouble
Action: 0 = off; 1 = close 2 secs; 2 = stay closed; 3 = pulse; 4 = toggle; 5 = duration 1
Output Number: 1-18;
Device Type: R = relay; T = trigger; X = X10
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 23 = No Alarm Response
01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 24 = Silent Burglary
02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide 77 = Keyswitch
03 = Perimeter 08 = 24 Hr Aux 15 = 24 Hr Medical/Personal 81 = AAV Monitor Zone
04 = Interior Follower 09 = Fire 16 = Fire w/Verification 90-93 = Configurable
Choices for System Operation are:20 = Arming–Stay (RF) 38 = Chime 54 = Fire Zone Reset 21 = Arming–Away (RF) 39 = Any Fire Alarm 58 = Duress 22 = Disarming (RF) 40 = Bypassing 60 = AAV Trigger
31 = End of Exit Time 41 = **AC Power Failure 66 = Function key† 32 = Start of Entry Time 42 = **System Battery Low 67 = Bell Failure 33 = Any Burglary Alarm 43 = Communication Failure 68 = TELCO Line Fault
36 = **At Bell Timeout***52 = Kissoff76 = Arming–Maximum (RF)78 = Keyswitch Red LED††† 79 = Keyswitch Green LED†††
Description
Activation Type and Detail Event Function
Act. by Zn List Zn Type Zn No.
††; 6 = duration 2†† (†† duration is set in program field *177)
Part. (P)
By Zn List By Zn No.
Note: In normal operation mode:
Code + # + 7 + NN Key Entry starts Device
Code + # + 8 + NN Key Entry stops Device
** Use 0 (any) for Partition No. (P) entry.
*** Or at Disarming, whichever occurs earlier.
† Use *57 Menu mode to assign the function key.
††† Device action not used for these choices.
Action
Out.
No.
Device
Type
– 11 –
Page 12
Type 00
Zone Not Used
Type 01
Entry/Exit Burglary #1
Type 02
Entry/Exit Burglary #2
Type 03
Perimeter Burglary
Type 04
Interior Follower
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour Silent Alarm
Type 07
24-hour Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Fire
Type 10
Interior w/Delay
Type 12
Monitor Zone
Type 14
Carbon Monoxide
Type 15
24-Hour
Medical/Personal
Emergency
Type 16
Fire w/Verification
Type 20
Arm-Stay
Use this zone type if the zone is not used.
Zone Type Definitions
• Assign to zones that are used for primary entry and exit.
• Provides entry delay if the control is armed in the Away or Stay modes.
• No entry delay is provided when the panel is armed in the Instant mode.
• Entry delay #1 is programmable for each partition.
• Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is
independently programmable.
• Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.
• Provides a secondary entry delay, in same manner as entry delay #1.
• Entry delay #2 is programmable for each partition.
• Exit delay is same as described for Type 01.
• Assign to all sensors or contacts on exterior doors and windows.
• Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Instant, or
Maximum modes.
• Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon
entry (to and from the keypad).
• Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first.
Otherwise this zone type gives an instant alarm.
• Active when the panel is armed in the Away mode.
• Bypassed automatically when the panel is armed in the Stay or Instant modes.
• Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering a
sensitive area such as a stock room, drug supply room, etc.
• Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
• Provides an instant alarm if faulted when armed in the Away, Stay, Instant, or Maximum (night) modes.
• During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a
central station report, if desired).
• Usually assigned to a zone containing an emergency button.
• Sends a report to the central station but provides no keypad display or sounding.
• Assign to a zone that has an emergency button.
• Sends a report to the central station, and provides a keypad alarm sound, and an audible external alarm.
• Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as water
or temperature sensors.
• Sends a report to the central station and provides a keypad alarm sound. (No bell output is provided.)
• Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a
pulsing bell output.
• This zone type is always active and cannot be bypassed.
Note: Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire
smoke detectors; any wireless zone can be used as a fire zone.
• Provides entry delay (using the programmed entry time), if tripped when the panel is armed in Away mode.
• Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit
delay zone was tripped first.
• Bypassed when the panel is armed in the Stay or Instant modes.
• Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "ALARM -2 4
Hr. Non-Burg. -#XXX " (where XXX is the zone number) will be sent to the Central Station. The system
keypad will display a “check” message indicating the appropriate zone (but keypad beeping does not
occur). Upon restoral of the zone, the message, "RESTORE-24 Hr. Non-Burg. -#XXX " will be sent to the
Central Station.
• The “check” message will automatically disappear from the keypad dynamically when the zone restores; a
user code + off sequence is not needed to reset the zone.
• Faults of this zone type are independent of the system, and can exist at the time of arming without
interference.
• Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”
• Assigned to any zone with a carbon monoxide detector.
• The bell output will pulse when this zone type is alarmed.
• Always active and cannot be bypassed.
• Usually assigned to a zone containing an emergency button.
• Sends report to the central station (Contact ID event code “100”) and provides an alarm sound at the
keypad (no bell output is provided).
• UL: may not use this zone type in UL installations.
• Provides a fire alarm when zone is shorted, but only after alarm verified.
• System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit
within 90 seconds triggers fire alarm.
• Provides a trouble response when zone is open.
• Arms the system in Stay mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User code for button must be assigned.
– 12 –
Page 13
Type 21
Arm-Away
Type 22
Disarm
Type 23*
No Alarm Response
Type 24
Silent Burglary
Type 76
Arm Maximum
Type 77
• Arms the system in Away mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User code for button must be assigned.
• Disarms the system when the zone is activated.
• User code for button must be assigned.
• Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
• Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
• Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.
• A report is sent to the central station.
• Arms the system in Maximum mode when the zone is activated.
• Pushbutton units send the user number to the central station when arming or disarming.
• User code for button must be assigned.
• Assign to zone wired to a keyswitch.
Keyswitch
Type 81
AAV Monitor Zone
Types 90-93
Installer Defined
*The system can still be armed when these zone types are in a faulted condition.
Schedules(installer code + [#] + [6] [4];
No. Description Event Device No. Group Partition Start Time/ Days Stop Time/ Days Repeat Random
• Assign to zone connected to AAV module.
• Monitors 2-way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting stops, except for fire alarms,
which immediately terminate the voice session and cause a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell timeout has not expired)
and reports that were stopped are sent.
• These zone types can be programmed for various custom responses. See data fields *182-*185.
• Types 92 and 93 can only be programmed via the downloader.
UL: Zone types 90-93 may not be used as fire or burglar zones in fire or UL burglar alarm installations.
master code can only access schedules 01-16 and events 00-07
Events: Master/Installer Installer Only Device No. (for 01 event): 01-18
00 = clear event 04 = forced STAY arm 10 = display custom words 8-10 Group No. (for 02 event): 1-8
01 = device on/off 05 = forced AWAY arm 11 = periodic test report Partition (for 04-06 events): 1, 2, or 3
02 = user access 06 = auto disarm Repeat: 0 = none; 1 = repeat weekly
03 = latch key report 07 = display “reminder” 2 = repeat every other week
3 = repeat every third week
4 = repeat every fourth week
Random: 0= no; 1 = yes
– 13 –
Page 14
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
000
– A –
• 001 AIR
• 002 ALARM
004 ALLEY
005 AMBUSH
• 006 AREA
• 007 APARTMENT
• 009 ATTIC
010 AUDIO
– B –
• 012 BABY
• 013 BACK
• 014 BAR
• 016 BASEMENT
• 017 BATHROOM
• 018 BED
• 019 BEDROOM
020 BELL
• 021 BLOWER
• 022 BOILER
023 BOTTOM
025 BREAK
• 026 BUILDING
028 CABINET
•029 CALL
030 CAMERA
031 CAR
033 CASH
034 CCTV
035 CEILING
036 CELLAR
• 037 CENTRAL
038 CIRCUIT
• 040 CLOSED
• 046 COMPUTER
047 CONTACT
– D –
• 048 DAUGHTERS
049 DELAYED
• 050 DEN
051 DESK
• 052 DETECTOR
• 053 DINING
054 DISCRIMINATOR
055 DISPLAY
Note: Bulleted (•) words in boldface type are those that are also available for use by the 4285/4286 Phone Module. If
(Word Space)
– C –
• 057 DOOR
• 059 DOWN
• 060 DOWNSTAIRS
061 DRAWER
• 062 DRIVEWAY
• 064 DUCT
– E –
• 065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
• 069 EQUIPMENT
• 071 EXIT
072 EXTERIOR
– F –
• 073 FACTORY
075 FAMILY
• 076 FATHERS
• 077 FENCE
• 079 FIRE
• 080 FLOOR
081 FLOW
082 FOIL
• 083 FOYER
084 FREEZER
• 085 FRONT
– G –
• 089 GARAGE
• 090 GAS
091 GATE
• 092 GLASS
093 GUEST
094 GUN
– H –
• 095 HALL
• 096 HEAT
098 HOLDUP
099 HOUSE
100 INFRARED
• 101 INSIDE
102 INTERIOR
103 INTRUSION
– J –
104 JEWELRY
– K –
• 105 KITCHEN
– L –
• 106 LAUNDRY
• 107 LEFT
108 LEVEL
• 109 LIBRARY
• 110 LIGHT
111 LINE
• 113 LIVING
• 114 LOADING
115 LOCK
116 LOOP
117 LOW
• 118 LOWER
– M –
• 119 MACHINE
121 MAIDS
122 MAIN
• 123 MASTER
• 125 MEDICAL
126 MEDICINE
128 MONEY
129 MONITOR
• 130 MOTHERS
• 131 MOTION
132 MOTOR
– N –
• 134 NORTH
135 NURSERY
– O –
• 136 OFFICE
• 138 OPEN
139 OPENING
• 140 OUTSIDE
142 OVERHEAD
– P –
143 PAINTING
• 144 PANIC
145 PASSIVE
• 146 PATIO
147 PERIMETER
• 148 PHONE
150 POINT
151 POLICE
152 POOL
• 153 POWER
– R –
155 RADIO
• 156 REAR
157 RECREATION
159 REFRIGERATION
160 RF
• 161 RIGHT
• 162 ROOM
163 ROOF
– S –
164 SAFE
165 SCREEN
166 SENSOR
• 167 SERVICE
• 168 SHED
169 SHOCK
• 170 SHOP
171 SHORT
• 173 SIDE
174 SKYLIGHT
175 SLIDING
• 176 SMOKE
• 178 SONS
• 179 SOUTH
180 SPRINKLER
• 182 STATION
184 STORE
• 185 STORAGE
186 STORY
190 SUPERVISED
191 SUPERVISION
192 SWIMMING
193 SWITCH
– T –
194 TAMPER
196 TELCO
197 TELEPHONE
• 199 TEMPERATURE
200 THERMOSTAT
• 201 TOOL
202 TRANSMITTER
– U –
• 205 UP
• 206 UPPER
• 207 UPSTAIRS
• 208 UTILITY
245 Custom Word #1
246 Custom Word #2
247 Custom Word #3
248 Custom Word #4
249 Custom Word #5
250 Custom Word #6
251 Custom Word #7
252 Custom Word #8
253 Custom Word #9
254 Custom Word #10
– V –
209 VALVE
210 VAULT
212 VOLTAGE
– W –
213 WALL
214 WAREHOUSE
• 216 WEST
• 217 WINDOW
• 219 WING
220 WIRELESS
– X –
222 XMITTER
– Y –
223 YARD
– Z –
224 ZONE (No.)
• 225 ZONE
• 226 0
• 227 1
• 228 1ST
• 229 2
• 230 2ND
• 231 3
• 232 3RD
• 233 4
• 234 4TH
• 235 5
• 236 5TH
• 237 6
• 238 6TH
• 239 7
• 240 7TH
• 241 8
• 242 8TH
• 243 9
• 244 9TH
using a Phone module, and words other than these are selected for Alpha descriptors, the module will not provide
annunciation of those words.
77 M
78 N
79 O
80 P
81 Q
82 R
83 S
84 T
85 U
86 V
87 W
88 X
89 Y
90 Z
– 14 –
Page 15
5800 Series Transmitter Input Loop Identification
• All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes.
of the inputs requires its own programming zone
• Transmitter inputs entered as:
"RF" (Supervised RF) Type send periodic check-in
signals, as well as fault, restore and low battery signals.
The transmitter must remain within the receiver's range.
“UR" (Unsupervised RF) Type send all the signals that
the "RF" Type does, but the control does not supervise
the check-in signals. The transmitter may, therefore, be
carried off-premises.
"BR" (Unsupervised Button RF) Type only send fault
signals. They do not send restore or check-in signals.
They will indicate a low battery condition when tested or
activated normally. The transmitter may be carried offpremises.
Note: For information on any transmitter not shown
above, refer to the instructions accompanying that
transmitter for details regarding loop numbers, etc.
UL NOTE: The following transmitters are not intended for
use in UL installations: 5802MN, 5802MN2, 5804, 5804BD,
5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed
Residential Burglar installations.
(e.g., a 5804's four inputs require four programming zones).
LOOP 4
YOU MUST
ENROLL
BUTTON
LOOP 1
LOOP 1
LOOP 2
(REED)
LOOP 3
(TERMINALS)
THIS
5801
ENROLL AS
"UR" OR "RF"
5808
ENROLL AS
5809
ENROLL AS
5819
ENROLL AS
"RF"
"RF"
"RF"
LOOP 3
LOOP 2
LOOP 1
LOOP 1
(TERMINALS)
ENROLL AS
"UR" OR "RF"
ENROLL AS
LOOP 2
(REED)
LOOP 3
(TERMINALS)
5802MN
LOOP 2
(REED)
LOOP 1
(TERMINALS)
5816
"RF"
5819S (WHS & BRS)
ENROLL AS
LOOP
LOOP 4
YOU MUST
ENROLL
THIS
1
BUTTON
ENROLL AS "BR"
ALTERNATE
POSITION
FOR LOOP 2
LOOP 1
(INTERNAL
SHOCK
SENSOR
"RF"
ON
OFF
5804
5816MN
ENROLL AS
"RF"
5850 (GBD)
ENROLL AS
LOOP 3
LOOP 2
LOOP 1
LOOP 2
(REED)
LOOP 1
(TERMINALS)
"RF"
(Green)
(Red)
(Yellow)
LOOP 3
Wireless Key Predefined Default Templates
For 5804
Loop Function Zone Type
TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23
2 Disarm 22 2 No Response 23
3 Arm Away 21 3 Arm Away 21
4 No Response 23 4 Disarm 22
TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
TEMPLATE 3 1 24-hour audible 7 TEMPLATE 6 1 24-hour audible 7
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
For 5804BD
Loop Function Zone Type
Table of Device Addresses
This Device Uses Address
Reports as
RF Receiver 00 100 *56 zone programming: input device type entry
Long Range Radio 03 103 automatic if output to long range radio field *29 enabled
4286 Voice Module 04 104 automatic if phone module access code field *28 enabled
Zone Expanders (4219/4229):
module 1 (for zones 09 - 16)
module 2 (for zones 17 - 24)
module 3 (for zones 25 - 32)
module 4 zones 33 - 40
module 5 zones 41 - 48
automatic if zone no. 9-16 entered as AW type or relay assigned
automatic if zone no. 17-24 entered as AW type or relay assigned
automatic if zone no. 25-32 entered as AW type or relay assigned
automatic if zone no. 33-40 entered as AW type or relay assigned
automatic if zone no. 41-48 entered as AW type or relay assigned
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
always enabled, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
ENROLL AS
LOOP 2
5804BD
5817
ENROLL AS
5890
ENROLL AS
"RF" OR "RM"
Each
LOOP 4
YOU MUST
ENROLL
THIS BUTTON
LOOP 1
HOUSE
CODE
"BR"
"RF"
SET
LOOP 1
(PRIMARY)
LOOP 2
(AUX.
CENTER)
LOOP 3
(AUX.
RIGHT)
LOOP
1
MOTION
V20P-006-V0
– 15 –
Page 16
EOL
RED
+
_
BLK
4-WIRE SMOKE DETECTOR CONNECTIONS
RELAY
RELAY
TYPE 54
AS ZONE
PROGRAM
(FIRE ZONE
5
+
OUTPUT
AUX PWR
TERMINALS
SET UNIT’S
DIP SWITCH
FOR DEVICE
-OR-
4219
4229
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
WIRED EXPANSION/RELAY MODULE
TRANSFORMER
8-PIN CONNECTOR
USED FOR 1361X10
SEE INSTRUCTIONS.
ON-BOARD TRIGGERS
CONNECTIONS AND FOR
POWER
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
N.O.
VIOLET
2000
_
+
4-WIRE SMOKE
OR COMBUSTION
N.C.
RESET)
OR
4
_
CONTACT OPENS MOMENTARILY
UPON FIRE ALARM RESET
TO OUTPUT 17
FOR "OUT NORM
PROGRAM OUTPUT 17
ADDRESSES
7 - 15
SEE
INSTRUCTIONS.
SET
RECEIVER’S
-OR-
AND/OR
5881* Type
OUTPUT RELAYS)
(4 OUTPUT RELAYS)
4204 RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
BLK
RED
GRN
YEL
OPTIONAL
TO
TRANS.
CABLE)
(USE SA4120XM-1
COM
DATA
SYNC
78
GND
1234 56
FLYING LEADS
FOR BATTERY
CONNECTION
+
BLACK
RED
+
OHMS
EOLR
DETECTOR
HEAT
DETECTOR
+
_
TYPE 54 IN
80 MENU MODE
MODE AND AS ZONE
TO ZONE TERM. ( )
TO ZONE TERM. ( )
LOW" = YES IN 79 MENU
DIP SWITCH
FOR DEVICE
ADDRESS
OF “0”.
SEE
INSTRUCTIONS.
RF RECEIVER
5881L: UP TO 8
5881H: UP TO 64
5881M: UP TO 16
*5882 IN CANADA
WIRELESS ZONES
BLK
RED
GRN
YEL
( FROM EITHER OR BOTH GROUPS)
FOR UP TO 40 ADDITIONAL ZONES
BLK
YEL
RED
GRN
TO TERM 4
TO TERM 5
TO TERM 6
TO TERM 7
(TRIG. 2)
OUTPUT 18
+12 AUX
(TRIG. 1)
OUTPUT 17
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM
RESISTOR DIRECTLY ACROSS
20
19
18
17
16
15
14
13
12
11
10
89
654
SOUNDER.
12 372122232425
RING
TIP
RING
TIP
HI
LO
LO
HI
HI
LO
LO
HI
HI
LO
LO
HI
HI
LO
LO
HI
+
}
EARTH
GROUND
(RED)
}
(GREEN)
(GRAY)
}
(BROWN)
▲
▲
AUX. POWER
SEE
INCOMING
HANDSET
OUTPUT
GROUNDING
FOR PROPER
INSTRUCTIONS
PHONE LINE
CONNECT CORD)
*CA38A IN CANADA
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
+
)
-
) RETURN
FOR UL
600mA MAX.
(500mA MAX.
10.5-13.8VDC
INSTALLATIONS)
TO 110VAC
UNSWITCHED
OUTLET (24HR)
TO PREVENT RISK OF SHOCK,
DOC LOAD NO.: 3
FOR CONNECTION OF OPTIONAL 4285 OR 4286 VIP
MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.
DISCONNECT TELEPHONE LINE AT TELCO
JACK BEFORE SERVICING THIS UNIT.
WARNING:
ZONE 8
2000
EOLR
OHMS
ZONE 7
2000
EOLR
OHMS
ZONE 6
2000
EOLR
OHMS
ZONE 5
2000
EOLR
OHMS
ZONE 4
2000
EOLR
OHMS
ZONE 3
ZONE 2
ZONE 1
ALL OUTPUTS
ARE POWER
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
•
2000
EOLR
OHMS
2000
EOLR
OHMS
2000
EOLR
OHMS
YELLOW: KEYPAD DATA OUT
GREEN: DATA IN FROM KEYPAD
RED: KEYPAD PWR (
REMOTE
BLACK: KEYPAD GROUND (
LIMITED.
NOTE:
KEYPAD (S)
CURRENT (IN
BOTH
+
ALARM OUTPUT
USAGE, INCLUDING
(600mA MAX. FOR UL
AUX POWER) STEADY
10.5–13.8VDC, 2A MAX.
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
RINGER EQUIVALENCE: 0.1B.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
POWER SHUTDOWN NOTE:
SYSTEM SHUTS DOWN SENSOR
ZONE
PAIRS
2 / 10
1011
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
•
•
2k
131214
TAMPER
CONTACTS
2k
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
DEVICES
KEYPADS
PARTITIONS)
FOR BURGLARY/PANIC,
4219, 4229,
AND OTHER
(e.g. 5800TM,
4285/4286, LRR,
ADDRESSABLE
AND ALL
OTHER DEVICES
DRAWING
POWER FROM
TERMS 4 & 5
MUST BE
OR 12V BELL).
TEMPORAL PULSE
SEE INSTRUCTIONS.
CAN USE 702 SIREN,
SOUNDING FOR FIRE.
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
THAT MAY CAUSE UNDESIRED OPERATION.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS
SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED