First Alert FA160C User Manual

Page 1
USER'S
N7527-1V1 8/95
MANUAL
FFFFAAAA111166660000CCCC SSSSeeeeccccuuuurrrriiiittttyyyy SSSSyyyysssstttteeeemm
mm
Page 2
– 2 –
Page 3
TABLE OF CONTENTS
SYSTEM OVERVIEW .................................................... 4
General ...................................................................... 4
A Partitioned System................................................ 4
Zones ........................................................................ 4
Burglary Protection ................................................. 5
Security Codes ......................................................... 5
Fire Protection.......................................................... 6
Alarms....................................................................... 6
Memory of Alarm ...................................................... 6
Phone Access & Voice Response ........................... 6
ENTRY/EXIT DELAYS .................................................. 7
General Information.................................................. 7
Exit Alarms................................................................ 8
ABOUT THE KEYPADS ................................................ 9
FUNCTIONS OF THE KEYPADS ................................ 12
CHECKING FOR OPEN ZONES ................................. 14
ARMING PERIMETER ONLY (STAY)......................... 15
ARMING PERIMETER ONLY (INSTANT)................... 16
ARMING ALL PROTECTION (AWAY)........................ 17
2-Partition Away Arming........................................ 17
ARMING ALL PROTECTION (MAXIMUM)................. 19
DISARMING AND SILENCING ALARMS................... 20
Memory of Alarm .................................................... 20
BYPASSING PROTECTION ZONES .......................... 21
Quick Bypass ......................................................... 22
– 3 –
Displaying Bypassed Zones................................... 22
CHIME MODE .............................................................. 23
PANIC KEYS ............................................................... 24
USING DEVICE COMMANDS..................................... 25
USING THE KEYSWITCH ........................................... 26
SECURITY CODES ..................................................... 27
General .................................................................... 27
Babysitter Code ...................................................... 27
Duress Code........................................................... 27
Quick Arming .......................................................... 27
To Add or Change A User ...................................... 28
To Delete A User ..................................................... 28
TESTING THE SYSTEM.............................................. 29
TROUBLE CONDITIONS ............................................ 31
FIRE ALARM SYSTEM ............................................... 33
NFPA RECOMMENDATIONS..................................... 34
EMERGENCY EVACUATION...................................... 35
MAINTAINING YOUR SYSTEM .................................. 36
QUICK GUIDE TO SYSTEM FUNCTIONS.................. 38
SUMMARY OF AUDIBLE NOTIFICATIONS............... 40
GLOSSARY ................................................................. 41
INSURANCE CREDIT REQUEST FORM .................... 47
INDEX .......................................................................... 50
Page 4
SSSSYYYYSSSSTTTTEEEEMMMM OOOOVVVVEEEERRRRVVVVIIIIEEEEWW
WW
General Congratulations on your ownership of a
A Partitioned
System
Zones Your system's sensing devices have been assigned to various "zones." For example,
First Alert
System. You've made a wise decision in choosing it, for it represents the latest in security protection technology today.
This system offers you three forms of protection: burglary, fire and emergency. Your system consists of at least one keypad which provides control of system operation, and includes various sensors which provide perimeter and interior burglary protection, plus smoke or combustion detectors designed to provide early warning in case of fire.
The system uses microcomputer technology to monitor all protection zones and system status and provides appropriate information for display on the keypad(s) used with the system, and initiates appropriate alarms. Your system may also have been programmed to automatically transmit alarm or status messages over the phone lines to a central alarm monitoring station.
Simply stated, a partitioned system is a single physical alarm system that provides two independent areas of protection intended for use by separate users. For the most part, you need not know about other users and their structure in the system. However, when the system is set up for 2-partition operation, you may see display messages from time to time which indicate that the system is in use by another user. Do not be concerned, this is normal.
the sensing device on your Entry/Exit door may have been assigned to zone 01, sensing devices on windows in the master bedroom to zone 02, and so on. These numbers will appear on the display, along with a description for that zone (on Alpha display keypads only, if programmed) when an alarm or trouble condition occurs.
Professional Partitioned Security
– 4 –
Page 5
SSSSYYYYSSSSTTTTEEEEMMMM OOOOVVVVEEEERRRRVVVVIIIIEEEEWW
WW
Burglary
Protection
Security Codes At the time of installation, you were assigned a personal four-digit security code,
Your system provides four modes of burglary protection: STAY, AWAY, INSTANT and MAXIMUM, and allows you to BYPASS selected zones while leaving the rest of the system armed. You must turn on or "arm" the burglary protection portion of your system before it will sense burglary alarms. The system also provides a CHIME mode, for alerting users to the opening of protected doors and windows while the system is disarmed. Refer to the other sections of this manual for procedures for using these features.
The following table lists the four different arming modes and the results of each.
Arming
Mode Exit Delay Entry Delay Perimeter Armed Interior Armed
AWAY Yes Yes Yes Yes STAY Yes Yes Yes No INSTANT Yes No Yes No MAXIMUM Yes No Yes Yes
known only to you. You must enter the security code when arming and disarming the system, and when performing other system functions. As an additional safety feature, other users who do not have a need to know your code can be assigned different security codes. Refer to the SECURITY CODES section for procedures on adding security codes to the system.
Features For Each Arming Mode
– 5 –
Page 6
SSSSYYYYSSSSTTTTEEEEMMMM OOOOVVVVEEEERRRRVVVVIIIIEEEEWW
Fire Protection The fire protection portion of your security system (if used) is always active and will
sound an alarm if a fire condition is detected. Refer to the FIRE ALARM SYSTEM section for important information concerning fire protection, smoke detectors and planning emergency exit routes from the premises.
Alarms When an alarm occurs, both the keypad and external sounders sound, and the keypad
displays the zone(s) causing the alarm. If your system is connected to a central monitoring station, an alarm message is also sent. To stop the alarm sounding, simply disarm the system.
Memory of Alarm When an alarm condition occurs, the keypad displays the number(s) of the zone(s) that
caused the problem, and displays the type of alarm (ex. FIRE, ALARM). It remains displayed until it is cleared by disarming the system (see DISARMING THE SYSTEM section).
WW
Phone Access &
Voice
Response
Capability
Your system may include a voice module that will permit you to access the system via a Touch-tone phone, either on-premises or by call-in when away. The phone access feature will enable you to do the following:
Receive synthesized voice messages over the telephone regarding the status of the
security system.
Arm and disarm the system and perform most function commands via the telephone,
with voice confirmation provided after each command entry.
Complete information regarding the use of this feature is provided in a separate manual entitled PHONE ACCESS USER'S GUIDE, which accompanies the voice module.
– 6 –
Page 7
EEEENNNNTTTTRRRRYYYY////EEEEXXXXIIIITTTT DDDDEEEELLLLAAAAYYYYSS
SS
General
Information
Your system has preset time delays, known as exit delay and entry delay. Whenever you arm your system, exit delay gives you time to leave through the designated exit door without setting off an alarm. Exit delay begins immediately after entering any arming command, and applies to all modes of arming protection. If programmed, slow “beeps” will sound throughout the exit delay period.
Entry Delays give you time to disarm the system when you re-enter through the designated entrance door. But you must disarm the system before the entry delay period ends, or an alarm will occur. The keypad beeps during the entry delay period, reminding you to disarm the system. There are two entry delays (if programmed). The first is for your primary entrance and the second may be used for a secondary entrance, where a longer delay is required to walk to the keypad to disarm the system. The secondary entry delay is 30 seconds longer than your primary entry delay.
You can also arm the system with no entry delay at all by using either INSTANT or MAXIMUM arming modes. These modes provide greater security while on the premises or while away for extended periods of time.
See your installer for your delay times.
Partition 1 Exit Delay:
Partition 2 Exit Delay:
seconds Entry Delay 1: seconds
Entry Delay 2:
seconds Entry Delay 1: seconds
Entry Delay 2:
seconds
seconds
– 7 –
Page 8
EEEENNNNTTTTRRRRYYYY////EEEEXXXXIIIITTTT DDDDEEEELLLLAAAAYYYYSS
SS
Exit Alarms
To minimize false alarms sent to the alarm monitoring company, your system may have been programmed for this feature. Ask your installer if "Exit Alarm" is active for your system.
Exit Alarm Active
Whenever you arm the system, the exit delay begins. If an entry/exit door or interior zone is faulted when the exit delay ends (e.g., exit door left open), the system sounds an alarm and starts the entry delay timer. If you disarm the system before the entry delay ends, the alarm sound stops and the message "CANCELLED ALARM" or "CA" is displayed on the keypad, along with a zone number indicating the faulted zone. No message is sent to the alarm monitoring company.
To clear the exit alarm condition, the open zone must be made intact; to clear the display, enter your code plus OFF.
If you do not disarm the system before the entry delay ends, and an entry/exit door or interior zone is still open, the alarm sound continues and an "exit alarm" message is sent to the alarm monitoring company. The message ""EXIT ALARM" or "EA" is displayed on the keypad, along with a zone number indicating the faulted zone.
To stop the alarm, the system must be disarmed (your code plus OFF); to clear the display, enter your code plus OFF a second time.
An “exit alarm” also results if an entry/exit door or interior zone is faulted within two minutes after the end of the exit delay.
– 8 –
Page 9
AAAABBBBOOOOUUUUTTTT TTTTHHHHEEEE KKKKEEEEYYYYPPPPAAAADDDDSS
SS
General
2-Line Alpha Keypad
1-Line Alpha Keypad 1-line Alpha keypads feature a 16-character alphanumeric LCD which can display
Fixed-Word Keypad Fixed-Word keypads are functionally identical to Alpha keypads, but the LCD display
Your keypads allow you to control all system functions. The keypads feature a telephone style (digital) keypad and a Liquid Crystal Display (LCD) which shows the nature and location of all occurrences.
The keypads also feature a built-in sounder which will sound during alarms and troubles. The keypads also "beep" during certain system functions, such as during entry/exit delay times, in CHIME mode, and when depressing any of the keys (to acknowledge the key press).
There are two basic types of keypads – a Fixed-Word keypad and an Alpha key- pad (both described below). Fixed-Word and Alpha keypads are functionally the same, even though they have different types of displays.
2-line Alpha keypads feature a 2-line, 32-character alphanumeric LCD which can display system messages in friendly English. These keypads can also be programmed with custom zone descriptors. The screen displays depicted
throughout this manual are examples of displays that would typically appear on a 2-line Alpha keypad.
system messages in friendly English. Messages are the same as those for 2-line Alpha keypads, but are displayed one line at a time. To view the second line of the
message, simply press the or wait 3 seconds.
After pressing the uses pre-designated words to identify the nature and location of occurrences.
Fixed-Word keypads are available with two styles of displays, “A” or “B” (see page
11), depending on keypad used.
# key, wait at least 3 seconds before entering a command.
# key. To return to the first line, press the # again,
– 9 –
Page 10
AAAABBBBOOOOUUUUTTTT TTTTHHHHEEEE KKKKEEEEYYYYPPPPAAAADDDDSS
ARMED
READY
Professional
OFF AWAY
STAY
MAXIMUM
TEST
BYPASS
INSTANT
CODE
CHIME
READY
1
A
B
C
D
2
3
4
5
6
7
8
9
*
0#
First Alert
First Alert
®
READY
Professional
OFF AWAY STAY
MAXIMUM TEST BYPASS
INSTANT CODE CHIME
READY
PANIC
1
2
3
4
5
6
7
8
9
*
0
#
ARMED
ALARM CHECK FIRE
AWAY STAY INSTANT BYPASS
NO AC CHIME
BAT
NOT READY
ARMED
READY
Professional
OFF AWAY
STAY
MAXIMUM
TEST
BYPASS
INSTANT
CODE
CHIME
READY
1
A
B
C
D
2
3
4
5
6
7
8
9
*
0#
First Alert
ALARM FIRE
AWAY
BYPASS
STAY
CHECK INSTANT
NO AC
NOT READY CHIME BAT
SS
FA450KP/FA550KP* FA210KP Fixed-Word Keypad FA250KP Fixed-Word Keypad
Alpha Keypads
* FA450KP has a 1-line display.
FA550KP has a 2-line display.
– 10 –
Page 11
STYLE A KEYPAD DISPLAY
STYLE B KEYPAD DISPLAY
AWAY STAY INSTANT BYPASS
ALARM CHECK
FIRE
NOT READY
NO AC CHIME
BAT
ALARM FIRE
AWAY
BYPASS
STAY
CHECK INSTANT
NO AC
NOT READY
CHIME BAT
AAAABBBBOOOOUUUUTTTT TTTTHHHHEEEE KKKKEEEEYYYYPPPPAAAADDDDSS
Fixed-Word Keypad Displays
AWAY All burglary zones, interior & perimeter, are armed.
STAY Perimeter burglary zones, such as windows and doors
are armed.
INSTANT Perimeter burglary zones armed and entry
delay is turned off.
BYPASS One or more burglary protection zones have
been bypassed.
NOT READY Appears when burglary portion of the system is not ready
for arming (due to one or more open protection zones).
READY The burglary portion of the system is ready
to be armed.
NO AC Appears when AC power has been cut off.
System is operating on backup battery power.
AC Appears when AC power is present.
CHIME Appears when the CHIME feature is ON.
BAT Low battery condition in a wireless sensor (if zone number displayed) or low system battery (if no
zone number displayed).
ALARM Appears when an intrusion has been detected and the system is armed (also appears during a fire
alarm or audible emergency alarm). Accompanied by the protection zone in alarm.
CHECK Appears when a malfunction is discovered in the system at any time or if an open is detected in a
FIRE zone at any time or a fault in a DAY/NIGHT burglary zone during a disarmed period. Accompanied by a display of zone number in trouble.
FIRE Appears when a fire alarm is present. Accompanied by a display of the zone in alarm.
– 11 –
SS
Page 12
FFFFUUUUNNNNCCCCTTTTIIIIOOOONNNNSSSS OOOOFFFF TTTTHHHHEEEE KKKKEEEEYYYYPPPPAAAADD
DD
1. ALPHA DISPLAY WINDOW: A 1-line or 2-line, Liquid Crystal Display (LCD). Dispslays protection point identification and system status, messages, and user instructions.
2. OFF KEY: Disarms the burglary portion of the system, silences alarms and audible trouble
indicators, and clears visual alarm trouble after the problem has been corrected.
3. AWAY KEY: Completely arms both perimeter and interior burglary protection for backup protection by
sensing an intruder's movements through protected interior areas as well as guarding protected doors, windows, etc. Entrance can be made through an entry delay zone without causing an alarm if the system is disarmed before the entry delay time expires.
4. STAY KEY: Arms the perimeter burglary protec ­tion, guarding protected doors, windows and other
perimeter protection points, and sounds an alarm if one is opened. Interior protection is not armed, which allows movement within your house without causing an alarm. Entrance can be made through an entry delay zone without causing an alarm if the system is disarmed before the entry delay time expires.
5. MAXIMUM KEY: Arms in manner similar to AWAY mode, but eliminates the entry delay period, thus
providing maximum protection. An alarm will occur immediately upon opening any protection point, including entry delay zones.
6. TEST KEY: Tests the system and alarm sounder.
7. BYPASS KEY: Removes individual protection zones from being monitored by the system. Displays
currently bypassed protection zones.
8. INSTANT KEY: Arms in manner similar to STAY mode, but turns off the entry delay period, offering
greater security while inside and not expecting any late arrivals. An alarm will occur immediately upon opening any perimeter protection point, including entry delay zones
9. CODE KEY: Allows the entry of additional user codes that can be given to other users of the
system.
10. CHIME KEY: Turns the CHIME mode on and off. When on, any entry through a protected delay or
perimeter zone while the system is disarmed will cause a tone to sound at the Keypad(s).
– 12 –
Page 13
ARMED
READY
Professional
OFF AWAY
STAY
MAXIMUM
TEST
BYPASS
INSTANT
CODE
CHIME
READY
1
A
B
C
D
2
3
4
5
6
7
8
9
*
0#
First Alert
1
15 14
2
5
16
8
12
1311
9
10
7
6
4
17
3
SHOWN WITH FLIP-DOWN KEY COVER REMOVED
11. READY KEY: When depressed prior to arming
12. # KEY: Permits ARMING of the system without
13. KEYS 0-9: Used to enter your individual security
14. READY INDICATOR: (GREEN) This lights when
15. ARMED INDICATOR: (RED) Lit when the system
16. INTERNAL SOUNDER: Source of audible internal
17. A-B-C PANIC KEYS: Refer to the PANIC KEYS
the system, the keypad will display all open protection zones within the keypad's home partition.
use of a security code ("Quick Arm", if programmed). Also used to view the second line of single-line Alpha keypads.
access code(s).
primary power is on and system is ready to be armed. If off, system is not ready to be armed (a protection zone is open).
has been armed (STAY, AWAY, INSTANT or MAXIMUM).
warning and confirmation sounds, as well as alarms (see "Summary of Audible Notifications").
section for descriptions of these keys. Note: Certain Fixed-word display keypads (see
page 10) do not have individual panic keys, and require that certain pairs of keys be pressed at the same time to activate a panic alarm – see the PANIC KEYS section.
¥¥¥¥ DISARMED ****
READY TO ARM
Typical Alpha Keypad shown above. Fixed-Word Keypads are
functionally the same except for screen displays.
IMPORTANT!: When you use the keypad to enter codes and commands, press the keys within 2 seconds of one another. If 2 seconds elapse without a key depression, the entry is aborted and must be repeated from its beginning.
– 13 –
Page 14
CCCCHHHHEEEECCCCKKKKIIIINNNNGGGG FFFFOOOORRRR OOOOPPPPEEEENNNN ZZZZOOOONNNNEEEESS
SS
Using the
READY Key
Before arming your system, all protected doors, windows and other protection zones must be closed or bypassed (see BYPASSING section). Otherwise the keypad will display a "Not Ready " message. Using the READY key will display all zones that are faulted, making it easier for you to secure any open zones.
To show faulted zones:
DISARMED - PRESS TO SHOW FAULT S is ready. If not lit, the system is not ready to be armed.
READY
1. PRESS THE READY KEY
2.
FAUL T 05 FRONT
UPSTAIRS BEDROOM
3.
DISARMED
***
READY TO ARM
***
Note: Keypads light a green READY indicator when system
Do not enter security code, but simply press the READY key.
SECURE FAULTED ZONES
Typical fault display shows open zones. Secure or bypass the zones displayed before arming the system.
SYSTEM CAN BE ARMED
The "Ready" message will be displayed when all pro­tection zones have been either closed or bypassed.
You may now arm the system as usual.
– 14 –
Page 15
AAAARRRRMMMMIIIINNNNGGGG PPPPEEEERRRRIIIIMMMMEEEETTTTEEEERRRR OOOONNNNLLLLYY
YY
(With Entry Delay ON)
Using the 3
STAY key
Use this key when you are staying home, but might expect someone to use the entrance door later.
When armed in STAY mode, the system will sound an alarm if a protected door or window is opened, but you may otherwise move freely throughout the premises. Late arrivals can enter through the entrance door without causing an alarm, but they must disarm the system within the entry delay period or an alarm will occur.
Close all protected perimeter windows and doors before arming (see CHECKING FOR OPEN ZONES section). The green READY indicator on the keypad should be lit if the system is ready to be armed.
STAY
1. + 3 ENTER SECURITY CODE THEN PRESS STAY
(Security Code)
2.
ARMED
***
S
TAY
***
Example: 7 2 9 6 then press the STAY key.
LISTEN FOR 3 BEEPS
The keypad will beep three times and will display the armed STAY message. The red ARMED indicator also lights.
– 15 –
Page 16
AAAARRRRMMMMIIIINNNNGGGG PPPPEEEERRRRIIIIMMMMEEEETTTTEEEERRRR OOOONNNNLLLLYY
YY
(With Entry Delay OFF)
Using the INSTANT
7
Key
Use this key when you are staying home and do not expect anyone to use the entrance door.
When armed in INSTANT mode, the system will sound an alarm if a protected door or window is opened, but you may otherwise move freely throughout the premises. The alarm will also sound immediately if anyone opens the entrance door.
Close all protected perimeter windows and doors before arming (see CHECKING FOR OPEN ZONES section). The green READY indicator on the keypad should be lit if the system is ready to be armed.
INSTANT
1. + 7 ENTER SECURITY CODE THEN PRESS INSTANT
(Security Code)
2.
ARMED
I NSTANT
*
*
Example: 7 2 9 6 then press the INSTANT key.
LISTEN FOR 3 BEEPS
The keypad will beep three times and will display the armed INSTANT message. The red ARMED indicator also lights.
– 16 –
Page 17
AAAARRRRMMMMIIIINNNNGGGG AAAALLLLLLLL PPPPRRRROOOOTTTTEEEECCCCTTTTIIIIOOOONN
NN
(With Entry Delay ON)
Using the
AWAY Key
2
2-Partition AWAY
Arming
Use this key when no one will be staying on the premises. When armed in AWAY mode, the system will sound an alarm if a protected door or
window is opened, or if any movement is detected inside the premises. You may leave through the entrance door during the exit delay period without causing an alarm. You may also re-enter through the entrance door, but must disarm the system within the entry delay period or an alarm will occur.
Close all protected perimeter windows and doors before arming (see CHECKING FOR OPEN ZONES section). The green READY indicator on the keypad should be lit if the system is ready to be armed.
AWAY
1. + 2 ENTER SECURITY CODE THEN PRESS AWAY
(Security Code)
2.
ARMED YOU MAY EXIT NOW
The "You May Exit Now" portion of the message disappears when the exit delay expires.
In a two-partition system, you can arm both partitions in the AWAY mode at the same time if the same master code is assigned to both partitions. You can do this from either partition's keypad.
This procedure is not applicable to disarming or any other system function.
**
AWAY
**
Example: 7
LISTEN
The keypad will beep twice, or beep continuously if exit warning has been programmed for your system, and displays the armed AWAY message. The red ARMED indicator also lights.
2 9 6 then press the AWAY key.
(Continued)
– 17 –
Page 18
AAAARRRRMMMMIIIINNNNGGGG AAAALLLLLLLL PPPPRRRROOOOTTTTEEEECCCCTTTTIIIIOOOONN
NN
(With Entry Delay ON)
2-Partition AWAY
Arming
(Continued)
To arm both partitions, first make sure both partitions are READY TO ARM.
AWAY AWAY
1. + 2 + 2 ENTER MASTER CODE THEN PRESS AWAY
(Master Code) TWICE
2 9 6 and press the AWAY key,
2.
ARMED YOU MAY EXIT NOW
The "You May Exit Now" portion of the message disappears when the exit delay expires.
**
AWAY
**
Example: 7 then press the AWAY key again. The first press of AWAY arms the local partition, the
second press of AWAY arms the other (remote) partition. The “Armed Away” display should appear, and remain displayed (with exit warning beeps, if programmed) throughout the exit delay period if both partitions were successfully armed AWAY. The red ARMED indicator should also light.
If the “READY TO ARM” message re-appears when the second AWAY key press is made, both partitions have failed to arm due to an open zone in the remote partition.
If the remote partition is not ready to arm, neither partition will arm when using this particular procedure.
– 18 –
Page 19
AAAARRRRMMMMIIIINNNNGGGG AAAALLLLLLLL PPPPRRRROOOOTTTTEEEECCCCTTTTIIIIOOOONN
NN
(With Entry Delay OFF)
MAXIMUM
4
Using the
Key
Use this key when the premises will be vacant for extended periods of time such as vacations, etc., or when no one will be moving through protected interior areas.
When armed in MAXIMUM mode, the system will sound an alarm if a protected door or window is opened, or if any movement is detected inside the premises. You may leave through the entrance door during the exit delay period without causing an alarm, but an alarm will be sounded as soon as someone re-enters.
Close all protected perimeter windows and doors before arming (see CHECKING FOR OPEN ZONES section). The green READY indicator on the keypad should be lit if the system is ready to be armed.
MAXIMUM
1. + 4 ENTER SECURITY CODE THEN PRESS MAXIMUM
(Security Code)
2.
ARMED YOU MAY EXIT NOW
The "You May Exit Now" portion of the message disappears when the exit delay expires.
MAXIMUM
*
*
Example: 7 2 9 6 then press the MAXIMUM key.
LISTEN
The keypad will beep twice, or beep continuously if exit warning has been programmed for your system, and will display the armed MAXIMUM message (AWAY/INSTANT on fixed-word keypads). The red ARMED indicator also lights.
– 19 –
Page 20
DDDDIIIISSSSAAAARRRRMMMMIIIINNNNGGGG AAAANNNNDDDD SSSSIIIILLLLEEEENNNNCCCCIIIINNNNGGGG AAAALLLLAAAARRRRMMMMSS
SS
Using the
OFF Key
1
Memory of Alarm If an alarm occurs, the keypad displays the zone number (s) that caused the alarm and
Use the OFF key to disarm the system and to silence alarm and trouble sounds. See "SUMMARY OF AUDIBLE NOTIFICATION" section for information which will help you to distinguish between FIRE and BURGLARY alarm sounds.
IMPORTANT: If you return and the main burglary sounder is on, DO NOT enter the premises, but call the police from a nearby safe location. If you return after an alarm has occurred and the main sounder has shut itself off, the keypad will beep rapidly upon entering, indicating that an alarm has occurred during your absence and an intruder may still be on the premises. LEAVE IMMEDIATELY and CONTACT THE POLICE from a nearby safe location.
To disarm the system and silence burglary alarms:
OFF
1. + 1 ENTER SECURITY CODE, THEN PRESS OFF
(Security Code)
2.
the type of alarm. These messages remain displayed until cleared by a user. To clear the display, note the zone number displayed and repeat step 1 above. If the “Ready“ message will not display, go to the displayed zone and correct the fault (close windows, etc.). If the fault cannot be corrected, notify your alarm company.
DISARMED
***
READY TO ARM
***
Example: 7 2 9 6 then press the OFF key.
LISTEN FOR 1 BEEP
The “Ready” message will be displayed (if no alarms have occurred while armed) and the keypad will beep once to confirm that the system is disarmed.
– 20 –
Page 21
BBBBYYYYPPPPAAAASSSSSSSSIIIINNNNGGGG PPPPRRRROOOOTTTTEEEECCCCTTTTIIIIOOOONNNN ZZZZOOOONNNNEEEESS
SS
Using the 6
BYPASS Key
This key is used when you want to arm your system with one or more zones intentionally unprotected. Bypassed zones are unprotected and will not cause an alarm when violated while your system is armed. All bypasses are removed when an OFF sequence (security code plus OFF) is performed. Bypasses are also removed if the arming procedure that follows the bypass command is not successful.
The system will not allow fire zones to be bypassed.
To bypass zones, the system must be disarmed first.
BYPASS
1. + 6 ENTER SECURITY CODE THEN PRESS BYPASS
(Security Code)
2.
3.
4.
ENTER ZONE NUMBERS
(Zone Numbers) Enter the zone number(s) for the zones to be bypassed
BYPASS 07 FRONT UPSTAIRS BEDROOM
Typical bypass message
DISARMED BYPASS
READY TO ARM
Example: 7 2 9 6 then press the BYPASS key.
(e.g., 01, 02, 03, etc.). Important! All single-digit numbers must be preceded
by a zero (for example, enter 01 for zone 1).
WAIT
The keypad will display the word BYPASS along with each bypassed zone number. Wait for these zones to be displayed, to be sure that intended zones are bypassed.
ARM AS USUAL
Arm the system as usual when the keypad displays the "Ready ” message.
(Continued)
– 21 –
Page 22
Quick Bypass
BYPASSING PROTECTION ZONES (Continued)
Your system may allow you to easily bypass all open (faulted) zones without having to enter zone numbers individually. Ask your installer if this feature is active.
All open (faulted) zones All open zones, plus these zones as checked: 17 30 31 46 47
BYPASS
1. + 6 ENTER SECURITY CODE THEN PRESS BYPASS
(Security Code)
Example: 7 2 9 6 then press the BYPASS key.
Displaying
Bypassed Zones
2.
BYPASS 07 FRONT UPSTAIRS BEDROOM
Typical bypass message
WAIT. In a few moments, all open zones will be displayed along with the word BYPASS. Wait for these zones to be displayed before arming. Arming the system before zones are displayed eliminates all bypasses.
3.
DISARMED BYPASS
READY TO ARM
ARM AS USUAL. Arm the system as usual when the keypad displays the "Ready" message.
Previously bypassed zones can be displayed only when the system is disarmed, and when the “Bypass” message shown in step 3 above is displayed.
BYPASS
1. + 6 ENTER SECURITY CODE THEN PRESS BYPASS
(Security Code)
2.
BYPASS 07 FRONT UPSTAIRS BEDROOM
Typical bypass message
Example: 7 2 9 6 then press the BYPASS key.
WAIT
In a few moments, all open zones will be sequentially displayed along with the word BYPASS.
– 22 –
Page 23
CCCCHHHHIIIIMMMMEEEE MMMMOOOODDDDEE
EE
Using the 9
Key
Your system can be set to alert you to the opening of a door or window while it is disarmed by using CHIME mode. When activated, three beeps will sound at the keypad whenever a protected perimeter door or window is opened. Pressing the READY key will display the open protection points.
Note that the Chime mode can be activated only when the system is disarmed.
To turn Chime Mode on:
CHIME
1. + 9 ENTER SECURITY CODE THEN PRESS CHIME
(Security Code)
2.
DISARMED CHIME
READY TO ARM
To turn Chime Mode off:
CHIME
1. + 9 ENTER SECURITY CODE THEN PRESS CHIME
(Security Code) Example: 7 2 9 6 then press the CHIME key.
2.
DISARMED
***
READY TO ARM
***
Example: 7 2 9 6 then press the CHIME key.
VIEW
The “Chime” message displays while chime mode is on.
VIEW
The “Chime” message disappears from the display.
– 23 –
Page 24
PPPPAAAANNNNIIIICCCC KKKKEEEEYYYYSS
SS
(FOR MANUALLY ACTIVATING SILENT AND/OR AUDIBLE ALARMS)
Using
Panic Keys
Your installer should note the functions that are are active in your system.
Types of Panic
Alarms
* If your system is connected to an alarm monitoring company.
Your system may have been programmed to use special keys to manually activate panic functions. The functions that might be programmed are listed below. See your installer for the function(s) that may have been programmed for your system.
Keys Zone Active Panic Function
A* 95 B* 99
C* 96 1 and 95 3 and # 96
and # 99
* Not be present on certain Fixed-word keypads, which use paired keys to activate panic alarms (e.g., 1 and , etc.).
If your keypad has lettered keys for panic functions, press the designated key and hold down for at least 2 seconds to activate the panic function. To use a paired key panic function, simply press both keys of the assigned pair at the same time.
A silent emergency sends an alarm signal to the alarm monitoring company,* but there will be no audible alarms or visual displays.
An audible emergency sends an emergency message to the alarm monitoring company* and sounds a loud, steady alarm at your keypad and at any external sounders that may be connected (ALARM plus a zone number is also displayed).
– 24 –
A personal emergency alarm sends an
emergency message to the alarm monitoring company* and sounds at keypads, but not at external sounders. (ALARM plus a zone number is also displayed)
A fire alarm sends a fire alarm message to the alarm monitoring company* and uniquely activates keypad and any external sounders (FIRE plus a zone number is also displayed).
Page 25
USING DEVICE COMMANDS
General
Information
To activate devices
To deactivate
devices
Your system may be set up so that certain lights or other devices can be turned on or off by using the device command from the keypad. Ask your installer if this has been done in your system. If programmed for your system, some devices may activate automatically upon certain system conditions. In this case, the following commands can be used to override the device activation. See your installer for a full explanation of this feature.
ENTER SECURITY CODE THEN PRESS # + 7 + DEVICE NUMBER
+ # + 7 +
(Security Code) (Device Number)
Example:
device you wish to activate. See your installer for device numbers assigned for your system.
ENTER SECURITY CODE THEN PRESS # + 8 + DEVICE NUMBER
+ # + 8 +
(Security Code) (Device Number)
Example:
device you wish to deactivate. See your installer for device numbers assigned for your system.
Device Description Device Description
1 5 2 6 3 7 4 8
7 2 9 6 then press #, then press 7, then enter the number representing the
7 2 9 6 then press #, then press 8, then enter the number representing the
– 25 –
Page 26
UUUUSSSSIIIINNNNGGGG TTTTHHHHEEEE KKKKEEEEYYYYSSSSWW
GREEN
RED
WWIIIITTTTCCCCHHHH
General
Your system may be equipped with a keyswitch for use when arming and disarming. A red and green light on the keyswitch plate will indicate the status of your system.
Green Light: This indicator lights when the system is disarmed and ready to
be armed (no open zones). If the system is disarmed and the green light is off, it indicates the system is not ready (one or more zones are open).
Red Light: This indicator lights when the system is armed or memory of
alarm exists.
Lit Steady: Slow Flashing: Rapid Flashing:
Arming
To arm in the AWAY mode, turn the key to the right for 1/2 second and release. Keypads will beep twice and the red light will stay on steady.
To arm in the STAY mode , turn the key to the right and hold for longer than 1 second, then release. Keypads will beep three times and the red light will flash slowly.
Disarming
To disarm the system, turn the key to the right and release. If an alarm has occurred, the red light will be flashing rapidly (memory of alarm).
System is armed in AWAY mode. System is armed in STAY mode. Memory of alarm, indicating an
alarm has occurred .
– 26 –
Page 27
SSSSEEEECCCCUUUURRRRIIIITTTTYYYY CCCCOOOODDDDEEEESS
SS
General
Information
Babysitter Code This code can be used to arm the system in assigned partitions, but cannot disarm the
Duress Code This feature is intended for use when you are forced to disarm or arm the system
Quick Arming
As an additional safety feature, other users who do not have a need to know your code can be assigned different security codes. These secondary users are identified by "user numbers," which are selected when assigning a user's security code. You can assign up to 14 additional user codes (user numbers 03-16), including the babysitter and duress codes. Note that the master (primary) user of the system is the only one who can assign codes to secondary (or temporary) users, and is user number 02; user number 01 is reserved for the installer of the system.
All codes can be used interchangeably when performing system functions (a system armed with one user's code can be disarmed by another user's code), with the exception of the babysitter code described below.
system unless the system was armed with this code. This code is typically assigned to someone (such as a babysitter) who has a need to arm/disarm the system only at certain times. The babysitter code is assigned to user 15. The user of this code should not use the “Quick Arming” feature described below.
under threat. When used, the system will act normally, but can silently notify the alarm monitoring company of your situation, if that service has been provided. Duress code is assigned to user 16.
Important: This code is useful only when the system is connected to a alarm monitoring company.
Note that if "Quick Arming" was programmed by the installer, the pressed in place of the security code when arming the system. The security code must
always be used to disarm the system, however.
– 27 –
# key can be
Page 28
SSSSEEEECCCCUUUURRRRIIIITTTTYYYY CCCCOOOODDDDEEEESS
SS
To Add a User
or Change a User's Code
(Master Code) CODE
1. + 8 Enter your 4-digit master code then press CODE key.
2.
3.
To Delete a User
1. + 8 Enter master code then press CODE key.
2. Enter 2-digit user number to be deleted.
To Change Your Master Code
Original Master Code CODE Master’s User No. New Master Code New Master Code
Enter 2-digit user number.
(User Number) Enter the 2-digit User Number (03-16) for the user you are adding or changing.
Enter 4-digit user's code.
(User's Code) Enter the new 4-digit security code for that user.
(Master Code) CODE
(User Number) Enter the 2-digit User Number (03-16) for the user whose code you are deleting.
+ 8 + 0 2 + +
Important:
should not be shown how to use any system function they do not need to know, such as bypassing protection zones for example.
Sequential key depressions for all steps in a procedure must be made within 2 seconds of one another, or else the entire entry is aborted and must be repeated from its beginning (e.g., perform steps 1, 2, and 3 below with no delay between steps).
Temporary users of the system (e.g., babysitters, cleaning staff, etc.)
Wait (about 3 seconds) until the keypad beeps once before pressing any other key. The code is automatically deleted.
Note that the new Master
Code must be entered twice.
– 28 –
Page 29
TTTTEEEESSSSTTTTIIIINNNNGGGG TTTTHHHHEEEE SSSSYYYYSSSSTTTTEEEEMM
MM
(TO BE CONDUCTED WEEKLY)
Using the
TEST Key
5
The TEST key puts your system into the Test mode, which allows each protection point to be checked for proper operation. The keypad sounds a single beep every 40 seconds as a reminder that the system is in the Test mode.
Note:
1.
2. + 5 ENTER THE SECURITY CODE THEN PRESS TEST
3. LISTEN
4. FAULT ZONES
An alarm message will not be sent to be sent to your alarm monitoring company during the following tests.
DISARMED
***
READY TO ARM
(Security Code)
***
TEST
DISARM THE SYSTEM
Disarm the system and close all protected windows, doors, etc. The “Ready” message should be displayed and the green READY indicator lit.
Example: 7 2 9 6 then press the TEST key.
The external sounder should sound for 2 seconds and then turn off.
If the sounder does not sound, CALL FOR SERVICE IMMEDIATELY.
Open each protected door and window in turn and listen for three beeps from the keypad. Identification of each faulted protection point should appear on the display. The display will clear when the door or window is closed.
(Continued)
– 29 –
Page 30
TTTTEEEESSSSTTTTIIIINNNNGGGG TTTTHHHHEEEE SSSSYYYYSSSSTTTTEEEEMM
Walk in front of any interior motion detectors (if used) and listen for three beeps. The identification of the detector should appear on the display when it is activated. The display will clear when no motion is detected. Note that if wireless motion detectors are used, there is a 3-minute delay between activations. This is to conserve battery life.
To test all smoke detectors, follow the manufacturer's instructions. The identification of each detector should appear on the display when each is activated.
If a problem is experienced with any protection point (no confirming sounds, no display), CALL FOR SERVICE IMMEDIATELY .
When all protection points have been checked and are intact (closed), there should be no zone identification numbers displayed on the keypad.
When testing is completed, exit the TEST mode by continuing with step 5.
OFF
5. + 1 EXIT TEST MODE
(Security Code) Enter your security code and press the OFF key.
If the test mode is inadvertently left active, it automatically turns off after 4 hours.
MM
– 30 –
Page 31
TTTTRRRROOOOUUUUBBBBLLLLEEEE CCCCOOOONNNNDDDDIIIITTTTIIIIOOOONNNNSS
SS
Typical "Check"
Displays
* Note that zone
number 9 repre­sents a problem with wireless re­ceivers or other system devices, which are not user serviceable. CALL FOR SERVICE IMMEDIATELY.
The word CHECK on the Keypad's display, accompanied by a rapid "beeping" at the Keypad, indicates that there is a trouble condition in the system. The displays in parenthesis may appear on non-alpha keypads when the associated trouble condition is present. To silence the beeping sound for "check" conditions, press any key.
1. CHECK + Indicates that a problem exists with those zone(s)*. First, deter-
Zone No. mine if the zone(s) displayed are intact and make them so if they and/or are not. If the zone uses a wireless detector, check that changes descriptor in the room (moving furniture, televisions, etc.) are not blocking (or CHECK wireless signals from the detector. If the problem has been cor­and Zone No. rected, the zone descriptor(s) and CHECK should disappear. If not, only) key an OFF sequence (security code plus OFF) to clear the dis-
play. A CHECK condition can also indicate a wiring problem. If the “check” display persists, CALL FOR SERVICE IMMEDIATELY.
Note that the system will not allow arming if a CHECK condition exists. To arm the system with a CHECK condition present, you must first bypass the zone(s) having the CHECK condition.
2. Telco Fault
(or CHECK and zone 94)
3. COMM.
FAILURE
(or
FC)
If the telephone line monitor feature has been programmed for your system, this display indicates that the telephone line has been disconnected or cut. In some systems, this display will be accompanied by a trouble sound from the keypad and the external sounder may be activated. CONTACT YOUR SERVICE COMPANY IMMEDIATELY.
To silence the trouble sound, enter your security code plus OFF. Indicates that a failure has occurred in the telephone
communication portion of your system. CALL FOR SERVICE IMMEDIATELY.
– 31 –
Page 32
TROUBLE CONDITIONS (Continued)
* The beeping that accompanies a low battery display (items 4 & 5) can be stopped by entering an OFF sequence (code + OFF).
** Not all systems use
wireless transmitters.
4. SYSTEM LO BAT Indicates that a low system battery condition exists;
(or BAT with no zone No.) this is accompanied by a once-per-minute "beeping"*
at the Keypad. CALL FOR SERVICE AT ONCE.
5. LO BAT + zone descriptor Indicates
that a low battery condition exists in the
(or BAT with zone No.) wireless transmitter** displayed; accompanied by a
once-per-minute "beeping"* at the Keypad. Replace the battery in the affected wireless transmitter as soon as possible (see page 36), or CALL FOR SERVICE.
6. MODEM COMM Indicates that the control is on-line with the central
(or CC) station's remote computer. The control will not
operate while on-line. Wait a few minutes. The display should disappear.
7. POWER indicator (if present) The system is operating on battery power only.
is off. AC LOSS is displayed If only some lights are out on the premises, check (or NO AC ) circuit breakers and fuses and reset or replace as
necessary. CALL FOR SERVICE IMMEDIATELY if AC power cannot be restored to the system.
8. Busy-Standby (or dI) If this remains displayed for more than 1 minute, the
system is disabled. CALL FOR SERVICE IMMEDIATELY.
9. OPEN CIRCUIT (or OC) The keypad is not receiving signals from the control.
CALL FOR SERVICE IMMEDIATELY.
10. Long Rng Trbl (or bF)
If programmed, your back-up Long Range Radio communication has failed. CALL FOR SERVICE IMMEDIATELY.
– 32 –
Page 33
FFFFIIIIRRRREEEE AAAALLLLAAAARRRRMMMM SSSSYYYYSSSSTTTTEEEEMMMM ((((IIIIFFFF IIIINNNNSSSSTTTTAAAALLLLLLLLEEEEDDDD))
General Your fire alarm system (if installed) is active 24 hours a day, providing continuous
protection. In the event of an emergency, the installed smoke and heat detectors will automatically activate you security system, triggering a loud, interrupted sound from the Keypad. An interrupted sound will also be produced by optional exterior sounders. A FIRE message will appear at your Keypad and remain on until you silence and clear the alarm display.
))
In Case Of Fire
Silencing A Fire
Alarm
1. Should you become aware of a fire emergency
problem, go to your nearest Keypad and press the single panic key (or panic key pair) assigned as FIRE emergency (if programmed by the installer) and hold down for at least 2 seconds. The alarm will sound.
2. Evacuate all occupants from the premises.
3. If flames and/or smoke are present, leave the premises and notify your local Fire
Department immediately.
4. If no flames or smoke are apparent, investigate the cause of the alarm. The zone
descriptor of the zone(s) in an alarm condition will appear at the Keypad.
1. Silence the alarm by pressing the OFF key. To clear the alarm display, enter your
code and press the OFF key again.
2. If the Keypad indicates a trouble condition after the second OFF sequence, check
that smoke detectors are not responding to smoke or heat producing objects in their vicinity. Should this be the case, eliminate the source of heat or smoke.
3. If this does not remedy the problem, there may still be smoke in the detector. Clear
it by fanning the detector for about 30 seconds.
4. When the problem has been corrected, clear the display by entering your code and
pressing the OFF key.
– 33 –
before
your detectors sense the
Page 34
NATIONAL FIRE PROTECTION ASSN.
DINING
KITCHEN
BEDROOM
BEDROOM
BEDROOM
BEDROOM
LIVING ROOM
BEDROOM
BDRM
BDRM
DINING
LIVING ROOM
TV ROOM
KITCHEN
✪✪
BEDROOM
BEDROOM
TO BR
LVNG RM
BASEMENT
KTCHN
.
CLOSED DOOR
GARAGE
Smoke Detectors for Minimum Protection Smoke Detectors for Additional Protection Heat-Activated Detectors
RECOMMENDATIONS ON SMOKE DETECTORS
With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #74 noted below.
Early warning fire detection is best achieved by the installation of fire detection equipment in all rooms and areas of the household as follows: A smoke detector installed outside of each separate sleeping area, in the immediate vicinity of the bedrooms and on each additional story of the family living unit, including basements and excluding crawl spaces and unfinished attics.
In addition, the NFPA recommends that you install heat or smoke detectors in the living room, dining room, bedroom(s), kitchen, hallway(s), attic, furnace room, utility and storage rooms, basements and attached garages.
– 34 –
Page 35
EEEEMMMMEEEERRRRGGGGEEEENNNNCCCCYYYY EEEEVVVVAAAACCCCUUUUAAAATTTTIIIIOOOONN
FRONT
BACK
BEDROOM
BATH
BEDROOM
KITCHEN
BACK DOOR
1 FLOOR
ST
BEDROOM
BEDROOM
2 FLOOR
ND
BATH
BEDROOM
PORCH
CLOSET
NN
Steps to Safety
Establish and regularly practice a plan of escape in the event of fire. The following steps are recommended by the National Fire Protection Association:
1. Plan on your detector or your interior and/or exterior sounders warning all oc­cupants.
2. Determine two means of escape from each room. One path of escape should lead to the door that permits normal exit from the build ing. The other may be a window, should your path be unpassable. Station an escape ladder at such windows if there is a long drop to the ground.
3. Sketch a floor plan of the building. Show windows, doors, stairs and rooftops that can be used to escape. Indicate escape routes for each room. Keep these routes free from obstruction and post copies of the escape routes in every room.
4. Assure that all bedroom doors are shut while you are asleep. This will prevent deadly smoke from entering while you escape.
5. Try the door. If the door is hot, check your alternate escape route. If the door is cool, open it cautiously. Be prepared to slam the door if smoke or heat rushes in.
6. In smoky areas, crawl close to floor, hold your breath, and/or cover mouth and nose with a wet cloth.
7. Escape quickly; don't panic.
8. Establish a common meeting place outdoors, away from your premises, where everyone can meet and then take steps to contact the authorities and account for those missing. Choose someone to assure that nobody returns to the premises — many die going back.
See
“How to Prepare a Fire Escape Plan”
, published by First Alert Professional, for
more details.
– 35 –
Page 36
MAINTAINING YOUR SYSTEM
Taking Care of
Your System
Replacing
Batteries in
Wireless
Sensors
Wireless sensors may not have been used in your security system
The components of your security system are designed to be as maintenance-free as possible. However, to make sure that your system is in reliable working condition.
1. Test your system weekly.
2. Test your system after any alarm occurs (see Each wireless sensor in your system has a 9-volt or 3-volt battery. The system detects
a low battery in any wireless sensor, including smoke detectors, the optional personal emergency transmitter, and the optional portable wireless keypad. (A low battery in a portable wireless keypad is detected as soon as one of its keys is pressed, and the wired keypad will display “00”.)
Alkaline batteries provide a minimum of 1 year of operation, and in most units and applications, provide 2–4 years of service. 3-volt lithium batteries provide up to 4 or more years of operation. Actual battery life will depend on the environment in which the sensor is used, the number of signals that the transmitter in the sensor has had to send, and the specific type of sensor. Factors such as humidity, high or low temperatures or large swings in temperature, may all lead to the reduction of actual battery life in an installation.
If you have a low battery in a wireless sensor, a low battery message is displayed on the keypad.
In addition, a battery-operated smoke detector with a low battery also emits a single "chirp" sound approximately once every 20–30 seconds, identifying itself as the smoke detector with the weak battery.
Note:
indicated sensor(s) is due within 30 days. In the meantime, a sensor causing a low battery indication is still fully operational.
Important: Use only batteries recommended by your installer as replacement.
The low battery message comes on as a warning that battery replacement in
– 36 –
TESTING THE SYSTEM
).
Page 37
MAINTAINING YOUR SYSTEM
Silencing Low
Battery Warning
Tones at the
Keypad
Routine Care
You can silence the keypad’s warning tones by pressing the OFF key, but the keypad's low battery message display will remain on as a reminder that you have a low battery condition in one or more of your sensors. When you replace the weak battery with a fresh one, the sensor will send a "good battery" signal to the control as soon as the sensor is activated (opening/closing of door, window, etc.), causing the low battery display to turn off. If the sensor is not activated, the display will automatically clear within approximately 1 hour.
Treat the components of your security
equipment. Do not slam sensor-protected doors or windows.
system as you would any other electrical
Keep dust from accumulating on the keypad and all protective sensors, particularly on
motion sensors and smoke detectors.
The keypad and sensors should be cleaned carefully with a dry soft cloth.
spray water or any other fluid on the units.
Do not
– 37 –
Page 38
QUICK GUIDE TO
SYSTEM FUNCTIONS
FUNCTION PROCEDURE COMMENTS
Check Zones Press [] Do this to view faulted zones when system not ready. Arm System Enter code Do this to arm the system in the mode selected.
Press arming key desired
(AWAY, STAY, INSTANT,
MAXIMUM)
Disarm System Enter code Do this to disarm the system and silences alarms.
Press OFF [1]
Bypass zones Enter code Do this to bypass protection zones. Bypassed zones are un-
Press BYPASS [6] protected and will not cause an alarm if violated. Enter zone numbers to be bypassed (use 2-digit entries)
Quick Bypass Enter code Do this to bypass all faulted zones automatically, if programmed.
Press BYPASS [6] and stop Zones 17, 30, 31, 46, and 47 will also be bypassed, even if not
faulted (depending on programming, and if used in your particular system).
Chime Mode ON Enter code Do this to turn on chime mode. Keypad will sound if doors or
Press CHIME [9] windows are violated while system disarmed.
Chime Mode OFF Enter code Do this to turn chime mode off.
Press CHIME [9]
– 38 –
Page 39
QUICK GUIDE TO
SYSTEM FUNCTIONS
(Continued)
FUNCTION PROCEDURE COMMENTS
Test Mode ON Enter code Do this to enter test mode. Sounds alarm sounder and allows
Press TEST [5] sensors to be tested.
Test Mode OFF Enter code Do this to turn test mode off. System returns to normal mode.
Press OFF [1]
Add or Change Enter master code Do this to add or change a user code. a User Press CODE [8]
Enter user's 2-digit user No. Enter code for that user
Delete a User Enter master code Do this to delete a user code from the system.
Press CODE [8] Enter user number. to be deleted
– 39 –
Page 40
SUMMARY OF AUDIBLE NOTIFICATIONS
(ALPHA DISPLAY KEYPADS)
SOUND CAUSE DISPLAY
LOUD, INTERRUPTED* Keypad & External
LOUD, CONTINUOUS* Keypad & External
ONE SHORT BEEP (not repeated)
Keypad only
ONE SHORT BEEP (once every 40 seconds)
Keypad only ONE BEEP every 40 sec.
Keypad only TWO SHORT BEEPS
Keypad only THREE SHORT BEEPS
Keypad only
FIRE ALARM FIRE is displayed; descriptor of zone in alarm is displayed.
BURGLARY/AUDIBLE EMERGENCY ALARM
a. SYSTEM DISARM b. SYSTEM ARMING ATTEMPT
WITH AN OPEN ZONE. c. BYPASS VERIFY
SYSTEM IS IN TEST MODE Opened Zone identifications will appear.
LOW BATTERY AT A TRANSMITTER LO BAT displayed with description of transmitter. ARM AWAY OR MAXIMUM ARMED AWAY or ARMED MAXIMUM is displayed. Red ARMED indicator is
a. ARM STAY OR INSTANT
b. ZONE OPENED WHILE SYSTEM
IS IN CHIME MODE.
ALARM is displayed; descriptor of zone in alarm is also displayed.
a. DISARMED/READY TO ARM is displayed. b. The number and descriptor of the open protection zone is displayed.
c. Numbers and descriptors of the bypassed protection zones are displayed (One beep is heard for each zone displayed). Subsequently, the following is displayed: DISARMED BYPASS ...Ready to Arm
lit. a. ARMED STAY or ARMED INSTANT is displayed. Red ARMED indicator is
lit. b. CHIME displayed, descriptor of open protection zone will be displayed if the
[] key is pressed.
RAPID BEEPING Keypad only
SLOW BEEPING Keypad only
a. TROUBLE b. MEMORY OF ALARM
a. EXIT DELAY WARNING (if programmed)
b. ENTRY DELAY WARNING
* If a bell is used as external sounder, fire alarm is
pulsed ring;
a. CHECK displayed. Descriptor of troubled protection zone is displayed. b. FIRE or ALARM is displayed; descriptor of zone in alarm is displayed.
a. ARMED AWAY or ARMED MAXIMUM is displayed along with You May
Exit Now
b. DISARM SYSTEM OR ALARM WILL OCCUR is displayed. Exceeding the delay time without disarming causes alarm.
burglary/audible emergency is
steady ring
.
– 40 –
Page 41
GGGGLLLLOOOOSSSSSSSSAAAARRRRYY
The following terms are used throughout the manual.
ARM/DISARM: "Armed" simply means that the burglary portion of your system is turned ON and is in a
state of readiness. "Disarmed" means that the burglary system is turned OFF, and must be rearmed to become operational. However, even in a "disarmed" state, "emergency" and "fire" portions of your system are still operational.
KEYPAD: This is the area on your Keypad containing numbered pushbuttons similar to those on
telephones or calculators. These keys control the arming or disarming of the system, and perform other functions which were previously described in this manual.
ZONE: A specific area of protection.
PARTITION: An independent group of zones that can be armed and disarmed without affecting
other zones or users.
BYPASS: To disarm a specific area of burglary protection while leaving other areas operational.
DELAY ZONE: An area of protection containing doors most frequently used to enter or exit (typically, a
front door, back door, or door from the garage into the building). The delay zone allows sufficient time for authorized entry or exit without causing an alarm. Consult your installer for the entry and exit delay times that have been set for your system during installation and record them in the space provided in this manual on page 7.
DAY/NIGHT ZONE: An area of protection whose violation causes a trouble indication during the disarmed
(DAY) mode and an alarm during the armed (NIGHT) mode.
YY
– 41 –
Page 42
UL NOTICE: This is a "GRADE A" system.
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
If using an indoor antenna, have a quality outdoor antenna installed.
Reorient the receiving antenna until interference is reduced or eliminated.
Move the receiver away from the control/communicator.
Move the antenna leads away from any wire runs to the control/communicator.
Plug the control/communicator into a different outlet so that it and the receiver are on different branch circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions. The user or installer may find the following booklet prepared by the Federal Communications Commission helpful: "Interference
Handbook". This booklet is available from the U.S. Government Printing Office, Washington, DC 20402. The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's
Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.
IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS
In the event of telephone operational problems, disconnect the control by removing the plug from the RJ31X (CA38A in Canada) telephone wall jack. We recommend that your certified installer demonstrate disconnecting the phones on installation of the system. Do not disconnect the phone connection inside the control/communicator. Doing so will result in the loss of your phone lines. If the regular phone works correctly after the control/communicator has been disconnected from the phone lines, the control/communicator has a problem and should be returned for repair. If upon disconnection of the control/communicator, there is still a problem on the line, notify the telephone company that they have a problem and request prompt repair service. The user may not under any circumstances (in or out of warranty) attempt any service or repairs to the system. It must be returned to the factory or an authorized service agency for all repairs.
– 42 –
Page 43
FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 NOTICE
This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.
This equipment uses the following jacks:
An RJ31X is used to connect this equipment to the telephone network.
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
If this equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuance of service may be required. If advance notice is not practical, the telephone company will notify the customer as soon as possible. Also, you will be advised of your right to file a complaint with the FCC if you believe necessary.
The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of the equipment. If this happens, the telephone company will provide advance notice in order for you to make the necessary modifications in order to maintain uninterrupted service.
If trouble is experienced with this equipment, please contact the manufacturer for repair and warranty information. If the trouble is causing harm to the telephone network, the telephone company may request you remove the equipment from the network until the problem is resolved.
There are no user serviceable components in this product, and all necessary repairs must be made by the manufacturer. Other repair methods may invalidate the FCC registration on this product.
This equipment cannot be used on telephone company-provided coin service. Connection to Party Line Service is subject to state tariffs.
This equipment is hearing-aid compatible. When programming or making test calls to an emergency number, briefly explain to the dispatcher the reason for the
call. Perform such activities in the off-peak hours; such as early morning or late evening.
– 43 –
Page 44
WARNING!
THE LIMITATIONS OF THIS ALARM SYSTEM
While this system is an advanced design security system, it does not offer guaranteed protection against burglary or fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example:
• Intruders may gain access through unprotected openings or have the technical sophistication to bypass an alarm sensor or disconnect an alarm warning device.
• Intrusion detectors (e.g. passive infrared detectors), smoke detectors, and many other sensing devices will not work without power. Battery operated devices will not work without batteries, with dead batteries, or if the batteries are not put in properly. Devices powered solely by AC will not work if their AC power supply is cut off for any reason, however briefly.
• Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if a metal object is moved into the path.
• A user may not be able to reach a panic or emergency button quickly enough.
• While smoke detectors have played a key role in reducing residential fire deaths in the United States, they may not activate or provide early warning for a variety of reasons in as many as 35% of all fires, according to data published by the Federal Emergency Management Agency. Some of the reasons smoke detectors used in conjunction with this System may not work are as follows. Smoke detectors may have been improperly installed and positioned. Smoke detectors may not sense fires that start where smoke cannot reach the detectors, such as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level of a residence or building. A second floor detector, for example, may not sense a first floor or basement fire. Moreover, smoke detectors have sensing limitations. No smoke detector can sense every kind of fire every time. In general, detectors may not always warn about fires caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. Depending upon the nature of the fire and/or the locations of the smoke detectors, the detector, even if it operates as anticipated, may not provide sufficient warning to allow all occupants to escape in time to prevent injury or death.
• Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual. Passive Infrared Detectors do not provide volumetric area protection. They do create multiple beams of protection, and intrusion can only be detected in unobstructed areas covered by those beams. They cannot detect motion or intrusion that takes place behind walls, ceilings, floors, closed doors, glass partitions, glass doors, or windows. Mechanical tampering, masking, painting or spraying of any material on the mirrors, windows or any part of the optical system can reduce their detection ability. Passive Infrared Detectors sense changes in temperature; however, as the ambient temperature of protected area approaches the temperature range of 90° to 105°F, the detection performance can decrease.
– 44 –
Page 45
WARNING!
THE LIMITATIONS OF THIS ALARM SYSTEM
(continued)
• Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices sound on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms. Even persons who are awake may not hear the warning if the alarm is muffled from a stereo, radio, air conditioner or other appliance, or by passing traffic. Finally, alarm warning devices, however loud, may not warn hearing-impaired people or waken deep sleepers.
• Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may be out of service or temporarily out of service. Telephone lines are also subject to compromise by sophisticated intruders.
• Even if the system responds to the emergency as intended, however, occupants may have insufficient time to protect themselves from the emergency situation. In the case of a monitored alarm system, authorities may not respond appropriately.
• This equipment, like other electrical devices, is subject to component failure. Even though this equipment is designed to last as long as 10 years, the electronic components could fail at any time.
The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. Installing an alarm system may make one eligible for lower insurance rates, but an alarm system is not a substitute for insurance. Homeowners, property owners and renters should continue to act prudently in protecting themselves and continue to insure their lives and property.
We continue to develop new and improved protection devices. Users of alarm systems owe it to themselves and their loved ones to learn about these developments.
– 45 –
Page 46
CANADIAN DEPARTMENT OF COMMUNICATIONS (DOC) STATEMENT
NOTICE
The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. In some cases, the company's inside wiring associated with a single line individual service may be extended by means of certified connector assembly (telephone extension cord). The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations.
Repairs to certified equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Caution: User should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
The Load Number (LN) assigned to each terminal device denotes the percentage of the total load to be connected to a
telephone loop which is used by the device, to prevent overloading. The termination on a loop may consist of any combination of devices subject only to the requirement that the total of the Load Numbers of all the devices does not exceed 100.
AVIS
L'étiquette du ministère des Communications du Canada identifie le matériel homologué. Cette étiquette certifie que le matériel est conforme à certaines normes de protection, d'exploitation et de sécurité des réseaux de télécommunications. Le ministère n'assure toutefois pas que le matériel fonctionnera à la satisfaction de l'utilisateur.
Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le raccorder aux installations de l'entreprise locale de télécommunications. Le matériel doit également être installé en suivant une méthode acceptée de raccordement. Dans certains cas, les fils intérieurs de l'entreprise utilisés pour un service individuel à la ligne unique peuvent être prolongés au moyen d'un dispositif homologué de raccordement (cordon prolongateur téléphonique interne). L'abonné ne doit pas oublier qu'il est possible que la conformité aux conditions énoncées ci-dessus n'empèchet pas la dégradation du service dans certaines situations. Actuellement, les entreprises de télécommunications ne permettent pas que l'on raccorde leur matériel aux prises d'abonnés, sauf dans les cas precis prévus par les tarifs particuliers de ces entreprises.
Les réparations du matériel homologué doivent être effectuées pas un centre d'entretien canadien autorisé désigné par le fournisseur. La compagnie de télécommunications peut demander à l'utilisateur de débrancher un appareil à la suite de réparations ou de modifications effectuées par l'utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise en terre de la source d'énergie électrique, des lignes téléphoniques de réseau de conduites d'eau s'il y en a, soient raccordés ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissement: L'utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir recours à un service d'inspection des installations électriques, ou à un électricien, selon le cas.
L'indice de charge (IC) assigné à chaque dispositif terminal pour éviter toute surcharge indique le pourcentage de la charge totale qui peut être
raccordé à un circuit téléphonique bouclé utilisé par ce dispositif. La terminaison du circuit bouclé peut être constituée de n'importe quelle combinaison de dispositifs, pourvu que la somme des indices de charge de l'ensemble des dispositifs ne dépasse pas 100.
– 46 –
Page 47
OWNER'S INSURANCE PREMIUM CREDIT REQUEST
This form should be completed and forwarded to your homeowner's insurance carrier for possible premium credit.
A. GENERAL INFORMATION:
Insured's Name and Address:
Insurance Company: Policy No.
First Alert Professional FA160C Other _____________
Type of Alarm: Burglary Fire Both
Installed by: Serviced by:
B. NOTIFIES (Insert B = Burglary, F = Fire)
Local Sounding Device Police Dept. Fire Dept. Alarm Monitoring Company Name:
C. POWERED BY: A.C. With Rechargeable Power Supply D. TESTING: Quarterly Monthly Weekly Other
Name Name
Address Address
Address:
Phone:
(continued on other side)
– 47 –
Page 48
OWNER'S INSURANCE PREMIUM CREDIT REQUEST (cont.)
E. SMOKE DETECTOR LOCATIONS
Furnace Room Kitchen Bedrooms Attic Basement Living Room Dining Room Hall
F. BURGLARY DETECTING DEVICE LOCATIONS:
Front Door Basement Door Rear Door All Exterior Doors 1st Floor Windows All windows Interior locations All Accessible Openings, Including Skylights, Air Conditioners and Vents
G. ADDITIONAL PERTINENT INFORMATION:
Signature: Date:
– 48 –
Page 49
SERVICING INFORMATION
Your local Arranging some kind of regular service program with him is advisable.
Your local Name:_________________________________________________________________
Address: _______________________________________________________________
Phone: _______________________________
First Alert
First Alert
_______________________________________________________________
dealer is the person best qualified to service your alarm system.
dealer is:
– 49 –
Page 50
– INDEX –
1-Line Alpha Keypads ...................... 9
2-Line Alpha keypads ....................... 9
2-Partition AWAY Arming................ 17
AC Loss ......................................... 32
Add A User ............................... 28, 39
Alpha Keypad ............................. 9, 13
Arming ......... 13, 15, 16, 17, 18, 19, 38
Audible Emergency ............ 11, 24, 40
Audible Notifications ....................... 40
Away ............ 5, 11, 12, 17, 26, 38, 40
Away Mode .................. 12, 17, 26, 38
Babysitter Code ............................. 27
Burglary Protection ................. 4, 5, 41
Bypass ................... 12, 14, 21, 38, 41
Check ....................................... 11, 31
Chime ............................... 5, 7, 23, 38
Chime Mode ......... 5, 9, 11, 23, 38, 40
Comm. Failure ................................ 32
Delete A User ........................... 28, 39
Disarming ..................... 20, 26, 38, 41
Displaying Bypassed Zones............ 22
Duress Code ............................ 13, 27
Emergency Evacuation .................. 35
Entry Delay ............................. 5, 7, 11
Exit Delay ... 5, 7, 8, 17, 18, 19, 40, 41
Exit Alarm .......................................... 8
Fire .......... 4, 6, 11, 20, 21, 33, 35, 41
Fire Alarm .......................... 24, 33, 40
Fire Protection ..................... 6, 34, 35
Fire Emergency .............................. 33
Fire Escape .................................... 35
Fixed-Word Keypads ................. 9, 11
Instant ............... 5, 11, 12, 16, 38, 40
Instant Mode ........................... 16, 38
Keypads .................. 9, 10, 11, 12, 13
Keyswitch ...................................... 26
Lo Bat ...................................... 32, 40
Low Battery ............ 11, 32,36, 37, 40
Maximum ............. 5, 7, 12, 19, 38, 40
Maximum Mode ....................... 19, 38
Memory Of Alarm .......... 6, 20, 26, 40
Modem Comm ............................... 32
National Fire Protect Assn. ..... 34, 35
Not Ready ............. 11, 14, 18, 26, 38
Off Key .......................................... 20
Panic Functions ............................. 24
Panic Keys ......................... 13, 33, 24
Partitioned System .......................... 4
Personal Emergency ..................... 24
Quick Arming ................................. 27
Quick Bypass ........................... 22, 38
Quick Guide to System Functions .. 38 Replacing Batteries in Wireless
Sensors ....................................... 36
Ready Key ............................... 14, 33
Security Codes .................... 5, 27, 28
Servicing Information ...................... 49
Silencing Alarms ...................... 20, 33
Silencing Low Battery Warning ...... 37
Silent Emergency .......................... 24
Sounder ....... 76, 9, 12, 20, 24, 29, 40
Special AWAY Arming .................... 17
Stay ............. 5, 11, 12, 15, 26, 38, 40
Stay Mode ................... 12, 15, 26, 38
System Lo Battery ......................... 32
Summary of Audible Notifications .. 40
Telephone Problems ...................... 42
Temporary Users ........................... 28
Test Key ........................................ 29
Test Mode .................... 29, 30, 39, 40
Trouble Conditions .................. 31, 32
User Codes .............................. 12, 27
User Number ..................... 27, 38, 39
Voice Module ................................... 6
Wireless Sensor ...................... 11, 36
Zones .............................................. 4
– 50 –
Page 51
ONE YEAR LIMITED WARRANTY
Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its First Alert Professional security equipment (the "product") to be free from defects in materials and workmanship for one year from date of original purchase, under normal use and service. Seller's obligation is limited to re pairing or replacing, at its option, free of charge for parts, labor, or transportation, any product proven to be defective in materials or workmanship under normal use and ser­vice. Seller shall have no obligation under this warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than the Seller. In case of defect, contact the security professional who installed and maintains your security equipment or the Seller for product repair.
This one year Limited Warranty is in lieu of all other express warranties, obligations or liabilities. THERE ARE NO EXPRESS WARRANTIES, WHICH EXTEND BEYOND THE FACE HEREOF. ANY IMPLIED WARRANTIES, OBLIGATIONS OR LIABILITIES MADE BY SELLER IN CONNECTION WITH THIS PRODUCT, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, ARE LIMITED IN DURATION TO A PERIOD OF ONE YEAR FROM THE DATE OF ORIGINAL PURCHASE. ANY ACTION FOR BREACH OF ANY WARRANTY, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY, MUST BE BROUGHT WITHIN 12 MONTHS FROM DATE OF ORIGINAL PURCHASE. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT. Some states do not allow limitation on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
Seller does not represent that the product may not be compromised or circumvented; that the product will prevent any personal injury or property loss by burglary, robbery, fire or oth erwise; or that the product will in all cases provide adequate warning or protection. Buyer understands that a properly installed and maintained alarm may only reduce the risk of a burglary, robbery, fire or other events occurring without providing an alarm, but it is not insurance or a guaran tee that such will not occur or that there will be no personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARN ING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT, WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST SELLER. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. No increase or alteration, written or verbal, to this warranty is authorized.
– 51 –
Page 52
N7527-1V1 8/95
172 Michael Drive Syosset, New York 11791
Copyright © 1995 PITTWAY CORPORATION
Loading...