First Alert FA148CP, FA168CPS User Manual 2

)$&36
)$&3
66HHFFXXUULLWW\\66\\VVWWHHP
PVV
3URJUDPPLQJ*XLGH
Y D
A
E
R
D
E
M
R
STAY
3
AWAY
2
OFF
1
BYPASS
A
6
TEST
5
MAX
4
CHIME
B
9
CODE
8
INSTANT
7
C
#
0
READY
D
FA260
OFF
ON
A
R
M
E
D
R
E
A
D
Y
R
AWAY
OFF
1
AWAY
2
STAY
3
STAY
MAX
4
TEST
5
BYPASS
6
INSTANT
7
CODE
8
CHIME
9
P
A
G
E
READY
0
#
FA560
K5305-5PRV2 10/03 Rev. A
TO ENTER PROGRAMMING MODE:
Local programming requires the use of an alpha keypad connected to the keypad terminals on the control.
POWER UP, then depress
A.
mode, this method must be used to reenter program mode).
OR
Initially, key:
B.
Installer Code (4 + 1 + 1 + 2)
[✱] and [#]
both at once, within 50 seconds of powering up (if ✱98 was used to exit program
plus
8 + 0 + 0.
DATA FIELD PROGRAMMING PROCEDURES
Task Procedure
Go to a Data Field Entering Data
Review a Data Field
Deleting an Entry
Press [∗] + [Field Number], followed by the required entry. When the desired field number appears, simply make the required entry. When the last entry for a
field is entered, the keypad beeps three times and automatically displays the next data field in sequence. If the number of digits that you need to enter in a data field is less than the maximum digits available
(for example, the phone number fields *41, *42), enter the desired data, then press [ entry. The next data field number is displayed.
Press [#] + [Field Number]. Data will be displayed for that field number. No changes will be accepted in this mode.
Press [∗] + [Field Number] + [∗]. (Applies only to fields ∗40 thru *46, *94, and pager programming
fields)
] to end the
INTERACTIVE MODE PROGRAMMING (∗56, ∗57, ∗58, ∗79, ∗80, ∗81, ∗82, ∗187)
Press
[✱] + [Interactive Mode No.]
requesting entries.
Interactive Mode
56 Zone Programming Zone characteristics, report codes, alpha descriptors, and serial numbers for 5800 RF
57 Function Key Programming Unlabeled keypad keys (known as ABCD keys) for special functions
58 Zone Programming Same options as *56 mode, but with fewer prompts. Intended for those familiar with
(Expert mode) this type of programming, otherwise *56 mode is recommended.
79 Output Device Mapping Assign module addresses and map individual relays/powerline carrier devices
✱ ✱
80 Output Programming
81 Zone List Programming
82 Alpha Programming
(for example, ✱56). The alpha display keypad will display the first of a series of prompts
Used to Program
transmitters.
4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc. Zone alpha descriptors
INITIALIZE DOWNLOAD and RESET DEFAULTS
Initializes download ID and subscriber account number.
96
Sets all data fields to original factory default values.
97
TO EXIT PROGRAMMING MODE:
Exits programming mode and
98
mode, system must be powered down, and method A above used to enter the programming mode.
See field *88 for other *98 Program mode lockout options.
Exits programming mode and
99
prevents
allows
re-entry by:
re-entry by:
Installer Code + 8
Installer Code
+ 0 + 0. If
+ 8 + 0 + 0 or method 1 above.
is used to exit programming
98
Special Messages
= OPEN CIRCUIT (no communication between Keypad and Control).
OC
or
EE
ENTRY ERROR
After powering up, This will revert to a “ delay by pressing
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after you correct the programming.
= ERROR (invalid field number entered; re-enter valid field number).
AC, dI
Ready
[#] + [0].
(disabled) or
” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
Busy Standby
and
NOT READY
will be displayed after approximately 4 seconds.
– 2 –
352*5$00,1*)250
Entries apply to both the FA168CPS and
FA148CP
controls, except FA168CPS (partition entries) and are not applicable to the FA148CP. Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Field Function Data Entries Programmable Values
SYSTEM SETUP (✱20–✱29)
INSTALLER CODE
20
QUICK ARM ENABLE
21
RF JAM OPTION
22
QUICK (FORCED) BYPASS
23
RF HOUSE ID CODE
24
CHIME BY ZONE
26
27
POWERLINE CARRIER DEVICE (X–10)
HOUSE CODE
ACCESS CODE FOR
28
PHONE MODULE
LONG RANGE RADIO OUTPUT
29
ZONE SOUNDS AND TIMING (✱31 – ✱39)
SINGLE ALARM SOUNDING per ZONE
31
FIRE ALARM SOUNDER TIMEOUT
32
ALARM SOUNDER (BELL) TIMEOUT
33
EXIT DELAY
34
ENTRY DELAY #1 (zone type 01)
35
ENTRY DELAY #2 (zone type 02)
36
AUDIBLE EXIT WARNING
37
CONFIRMATION OF ARMING DING
38
POWER UP IN PREVIOUS STATE
39
| | | [4112]
[0,0]
Part. 1 Part.2
[0]
[0,0]
Part. 1 Part. 2
| | |
Part. 1 Part. 2 Common
[0]
[0]
| [00]
(Partition 1 only)
[0]
[0]
| | [60,60]
Part. 1 Part. 2
| | [30,30]
Part. 1 Part. 2
Common zones use same delay as partition 1
| | [30,30]
Part. 1 Part. 2
Part. 1 Part. 2
[0]
[1]
[1,1]
[0,0]
[1]
DIALER PROGRAMMING (✱40 – ✱42)
Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum digits entered, exit the field by pressing [✶]. The next data field number is displayed.
PABX ACCESS CODE
40
PRIMARY PHONE No.
41
SECOND PHONE No.
42
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱41✱ or ✱42
| | | | |
used, enter ∗ (#+11) 70 plus # + 13 (pause).
entries shown in dashed boxes, which apply only to the
4 digits, 0–9
0 = no; 1 = yes
0 = no RF Jam detection; 1 = send RF Jam report UL: must be 1 if wireless devices are used
0 = no quick bypass UL: must be “0”
.
1 = allow quick bypass (code + [6] + [#] )
00 = disable all wireless keypad usage 01–31 = using 5827, 5827BD or 5804BD keypad [00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3, using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G, 7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N, #14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11 for "✱", or # + 12 for "#". UL: must be “00” for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no UL: must be “0”; 1 = yes
0 = sounder stops at timeout; 1 = no sounder timeout UL: must be “1” for fire install.
0 = none; 1 = 4 min; 2 = 8 min; 3 =12 min; 4 = 16 min;
UL: For residential fire alarm installation, must be set for a minimum of 4 min (option 1); for UL Commercial Burglary installations, must be minimum 16 min (option 4)
00 - 96 = 0 - 96 secs; 97 = 120 secs SIA Installations: minimum exit delay is 45 seconds UL: see inst. instr. for requirements. Common zones use same delay as partition 1.
00 - 96 = 0 - 96 seconds 97 = 120 seconds 98 = 180 seconds 99 = 240 seconds
For UL Residential Burglary Alarm installations, must be set for a maximum of 30 seconds; entry delay plus dial delay should not exceed 1 min. For UL Commercial Burglar Alarm, total entry delay may not exceed 45 seconds.
See *35 Entry Delay 1 above for entries.
SIA Installations: minimum entry delay is 30 seconds
Enter up to 6 digits. To clear entries, press ✱40✱. If call waiting
0 = no; 1 = yes SIA Installations: must be enabled (enter 1)
0 = no; 1 = yes (wired keypads and RF) 2 = yes, RF only UL: must be “1” for UL Commercial Burglar Alarm inst.
0 = no; 1 = yes UL: must be “1”
– 3 –
respectively
.
NOTE: Entry of a number other than one specified will give unpredictable results.
For fields *43 thru *46:
reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are used. E.g., For Acct.
#+11| 2 | 3 | 4
, enter:
B234
PARTITION 1 PRIMARY ACCT. No.
43
PART. 1 SECONDARY ACCT. No.
44
PARTITION 2 PRIMARY ACCT. No.
45
PARTITION 2 SECONDARY ACCT.
46
47
48
No.
PHONE SYSTEM SELECT
REPORT FORMAT
Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; #+15 for F. Enter
| | | / | | | | |
| | | / | | | | |
| | | / | | | | |
| | | / | | | | |
[1]
[77]
primary secondary
as the fourth digit if a 3-digit account number (for 3+1 dialer
[✱]
Enter 4 or 10 digits, depending on selection in *48 Report Format. See box above. To clear entries, press *43
*.
[FFFF]
Enter 4 or 10 digits, depending on selection in *48 Report Format. See box above. To clear entries, press *44*. [FFFF]
Enter 4 or 10 digits, depending on selection in *48 Report Format. See box above. To clear entries, press *45*. [FFFF]
Enter 4 or 10 digits, depending on selection in *48 Report Format. See box above. To clear entries, press *46*. [FFFF]
If Cent. Sta. if Cent. Sta.
IS NOT
on a WATS line: 0=Pulse; 1=Tone;
IS on
a WATS line: 2 = Pulse; 3 = Tone
0 = 3+1, 4+1 ADEMCO L/S STANDARD 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 ADEMCO L/S STANDARD 3 = 4+2 RADIONICS STANDARD 5 = 10-digit ADEMCO CONTACT ID® REPORTING 6 = 4+2 ADEMCO EXPRESS 7 = 4-digit ADEMCO CONTACT ID® REPORTING 8 = 3+1, 4+1 ADEMCO L/S EXPANDED
SPLIT/DUAL REPORTING
49
9 = 3+1, 4+1 RADIONICS EXPANDED
[0]
0 = Standard/backup reporting only (all to primary)
Primary Phone No.
2nd Phone No.
1 = Alarms, Restore, Cancel Others 2 = All except Open/Close, Test Open/Close, Test 3 = Alarms, Restore, Cancel All 4 = All except Open/Close, Test All
BURGLARY DIALER DELAY
50
5 = All All
[2]
0 = no delay UL: must be “0” 1 = 15 seconds SIA Installations: delay 2 = 30 seconds must be minimum of
SESCOA/RADIONICS SELECT
53
DYNAMIC SIGNALING DELAY
54
3 = 45 seconds 30 seconds
[0]
[0]
0 = Radionics (0-9, B-F) 1 = SESCOA (0-9 only reporting) Select “0” for all other formats.
Select delay from 0 to 225 secs, in 15-sec increments. 0 = no delay (both signals sent), 1 = 15 secs, 2 = 30 secs, etc.
DYNAMIC SIGNALING PRIORITY
55
56, *57, *58
MENU MODES
UL: Grade AA must be “0;” Grade A must be 15 max
[0]
These are Menu Mode commands, not data fields, for Zone Programming, Function
0 = Primary Dialer first; 1 = Long Range Radio first.
For UL Commercial Burglary installations that use a DACT and LRR, this field must be “0”.
Key Programming, and Expert Mode Zone Programming respectively. See page 2 and their respective sections in the Installation and Setup Guide for procedures.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (✱59 thru *68, *70 thru ✱76, and ✱89):
first
For 3+1 or 4+1 Standard Format:
not
A 0 (
#+10) in the
For Expanded or 4+2 Format:
not
A 0 (
#+10) in the
For Ademco Contact ID® Reporting:
not
A 0 (
#+10) in the
first
second
first
Enter a code in the
box will disable a report. A 0 (
Enter codes in
box will eliminate the expanded message for that report. A 0 (
box disables the report.
both
Enter any digit (other than 0) in the
SYSTEM STATUS REPORT CODES (✱59–
EXIT ERROR REPORT CODE
59
TROUBLE REPORT CODE
60
BYPASS REPORT CODE
61
AC LOSS REPORT CODE
62
LOW BAT REPORT CODE
63
TEST REPORT CODE
64
| [00] See box above. Use Scheduling mode to set periodic test reports,
| [00] See box above.
| [00] See box above.
| [00] See box above.
| [00] See box above.
box: 1–9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
not
#+10) in the
boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
UL: see installation instructions for requirements
68)
second
box will result in automatic advance to the next field.
first
box, to enable zone to report (entries in the
[0] See box above.
not
#+10) in
both
boxes will disable the report.
second
boxes are ignored).
or use the following key commands: Each mode sets schedule 32 (FA168CPS) or installer code +[#] + [0] + 0 = test report sent every 24 hours schedule 08 (FA148CP) to the stated installer code +[#] + [0] + 1 = test report sent once per week repeat option; first test report sent 12 hours after command. installer code +[#] + [0] + 2 = test report sent every 28 days
– 4 –
OPEN REPORT CODE
65
ARM AWAY/STAY RPT CODE
66
Away Stay Away Stay Away Stay
RF XMTR LOW BAT REPORT CODE
67
CANCEL REPORT CODE
68
Part. 1 Part. 2 Common
| [00] See box on previous page.
| [00] See box on previous page.
[0,0,0] See box above.
Part. 1 Part. 2 Common
[0,0,0,0,0,0]
UL: must be enabled if wireless devices are used
RESTORE REPORT CODES (✱70 – ✱76)
ALARM RESTORE RPT CODE
70
TROUBLE RESTORE RPT CODE
71
BYPASS RESTORE RPT CODE
72
AC RESTORE RPT CODE
73
LOW BAT RESTORE RPT CODE
74
RF XMTR LO BAT RST RPT CODE
75
TEST RESTORE RPT CODE
76
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
[0] See box on previous page.
UL: must be enabled if wireless devices are used
OUTPUT AND SYSTEM SETUP (✱77 – ✱93)
DAYLIGHT SAVINGS TIME
77
START\END MONTH
DAYLIGHT SAVINGS TIME
78
START\END WEEKEND
79, *80, *81, *82
AUTO STAY ARM
84
CROSS ZONE TIMER
85
MENU MODES
This option not for use in UL installations.
CANCEL VERIFY KEYPAD DISPLAY
86
MISC. FAULT DELAY TIME
87
(used with Configurable Zone Types digit 6”)
PROGRAM MODE LOCKOUT
88
OPTIONS
EVENT LOG FULL REPORT CODE
89
EVENT LOG ENABLES
90
OPTION SELECTION
91
| [4][10]
| [1][5]
These are Menu Mode commands, not data fields, for Output Device Mapping, Output Programming, Zone List Programming, and Alpha Programming respectively. See page 2 and their respective sections in the Installation and Setup Guide for procedures.
[3]
[0]
(assign cross zones on zone list 4, using *81 Menu mode)
[1]
[0]
UL: may only be used on non-burglar alarm/ non-fire alarm zones when used in fire and/or UL burglar alarm installation
[0]
| [00]
NOTE:
logged when any non-zero selection is made.
SIA Installations: Exit Delay should be enabled.
[3]
System messages are
[8]
– 5 –
0 = Disabled 1-12 = January-September (1 = Jan, 2 = Feb, etc) #+10 = October; #+11 = November; #+12 = December
0 = disabled, 1 = first, 2 = second, 3 = third 4 = fourth, 5 = last, 6 = next to last, 7 = third to last
0 = no, 1 = partition 1 only 2 = partition 2 only, 3 = both partitions
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 minutes #+11 = 7 min
0 = no, 1 = yes
0 = 15 seconds 6 = 2-1/2 min #+12 = 8 min 1 = 30 seconds 7 = 3 min #+13 = 10 min 2 = 45 seconds 8 = 4 min #+14 = 12 min 3 = 60 seconds 9 = 5 min #+15 = 15 min 4 = 90 seconds #+10 = 6 min 5 = 2 minutes #+11 = 7 min
0 = standard *98 installer code lockout (reentry only by
downloader or [∗] + [#] within 50 secs after power up)
1 = lockout [∗] + [#] reentry after *98 exit (reenter via
installer code or downloader only) 2 = not used 3 = lockout all local programming after *98 exit (reentry
via downloader only)
See box on previous page for report code entries.
0 = None; 1 = Alarm/Alarm Restore 2 = Trouble/Trouble Restore; 4 = Bypass/Bypass Restore; 8 = Open/Close.
Example:
Open/Close, enter 9 (1 + 8); To select all, enter #15. 0 = None
2 = Sounder Delay (delays sounding by 15 seconds) UL: if used, entry delay (*35) must be 30 sec. max.
4 = AAV UL: must use ADEMCO UVCM module 8 = Exit Delay Restart/Reset UL: must be disabled
#+12 = AAV and Exit Delay Restart/Reset
To select Alarm/Alarm Restore, and
See box above.
PHONE LINE MONITOR ENABLE
92
UL: see Inst. Instructions for requirements
No. OF REPORTS IN ARMED PERIOD
93
PER ZONE (Swinger Suppression)
[0,0]
1 2
Output Device must
NOTE:
either be programmed to be STOPPED in field ✱80 or STOPPED by Code + # + 8 + output number.
[1]
: 0 = disabled, 1-15 = 1 min - 15 min
Entry 1:
(#+10 = 10 min; #+11 = 11 min; #+12 = 12 min;
#+13 = 13 min; #+14 = 14 min; #+15 = 15 min)
:
Entry 2
0 = Keypad display when line is faulted 1 = Keypad display plus keypad trouble sound 2 = Same as “1”, plus programmed output device
STARTS. If either partition is armed, external sounder activates also.
0 = Unlimited Reports; 1 = 1 report; 2 = 2 reports UL: must be “0” SIA Installations: Must be set for option 1 or 2.
DOWNLOAD INFORMATION (✱94, ✱95)
DOWNLOAD PHONE No.
94
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits, 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. Do not fill unused
spaces. If fewer than 20 digits, exit field by pressing ✱. To clear entries from field, press ✱94✱.
UL: downloading may be performed only if a technician is at the site.
RING COUNT FOR DOWNLOADING
95
96, ∗97
98, *99
INITIALIZE/RESET DEFAULTS
EXIT COMMANDS
[15]
NOTE:
FA4285/FA4286 Phone Module.
These are commands, not data fields. See page 2.
These are commands, not data fields. See page 2.
Do not enter “0” if using
0 = Disable Station Initiated Download; 1–14 = number of rings (1–9, # +10 =10, # +11 =11, # +12 =12, # +13 =13, # +14 =14); 15 = answering machine defeat (# +15 =15).
PAGER OPTIONS (✱160- ✱172)
PAGER 1 PHONE No.
160
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
PAGER 1 CHARACTERS
161
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
PAGER 1 REPORT OPTIONS
162
Part. 1 Part. 2 common [0,0,0]
For each partition, select from the following options: 0 = no reports sent 1 = Open/closes all users 4 = All alarms and troubles 5 = All alarms / troubles, and open/closes for all users 12 = Alarms / troubles for zones entered in zone list 9 13 = Alarms / troubles for zones entered in zone list 9,
PAGER 2 PHONE No.
163
| | | | | | | | | | | | | | | | | | |
and open/closes for all users
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
PAGER 2 CHARACTERS
164
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
PAGER 2 REPORT OPTIONS
165
PAGER 3 PHONE No. | | | | | | | | | | | | | | | | | | |
166
PAGER 3 CHARACTERS | | | | | | | | | | | | | | |
167
[0,0,0]
Part. 1 Part. 2 common
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
See field *162 for reporting options. Select for each partition (use zone list 10 if using options 12 or 13).
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
PAGER 3 REPORT OPTIONS
168
PAGER 4 PHONE No. | | | | | | | | | | | | | | | | | | |
169
PAGER 4 CHARACTERS
170
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
0,0,0] Part. 1 Part. 2 common
See field *162 for reporting options. Select for each partition (use zone list 11 if using options 12 or 13).
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
PAGER 4 REPORT OPTIONS
171
PAGER DELAY OPTION FOR ALARMS
172
[0,0,0] Part. 1 Part. 2 common
[3]
See field *162 for reporting options. Select for each partition (use zone list 12 if using options 12 or 13).
0 = none, 1 = 1 minute, 2 = 2 minutes, 3 = 3 minutes This delay is for ALL pagers in the system.
– 6 –
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
CLEAN ME REPORTING OPTIONS
174
(for ESL smoke detectors)
DEVICE DURATION 1, 2
177
(used in *80 Menu mode-Device Actions 5/6)
50/60 HERTZ AC OPERATION
181
[0]
[0] [0]
1 2
[0]
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
CONFIGURABLE ZONE TYPE 90
182
ZONE TYPE 90 REPORT CODES
183
IMPORTANT:
codes, if appropriate, or define unique codes in CID code range 750-789. See important note in installation instructions.
CONFIGURABLE ZONE TYPE 91
184
ZONE TYPE 91 REPORT CODES
185
IMPORTANT:
codes, if appropriate, or define unique codes in CID code range 750-789. See important note in installation instructions.
Use existing Contact ID®
Use existing Contact ID®
1 2 3 4 5 6 7 8 9 10 Enter the appropriate value for each entry, 1-10, based on the charts provided on the next page. Each entry is the sum of the values of its selected options (0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15). UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
90 ALARM ID: XXX TROUBLE ID: XXX
1 2 3 4 5 6 7 8 9 10 Enter the appropriate value for each entry, 1-10, based on the charts provided on the next page. Each entry is the sum of the values of its selected options (0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15). UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
91 ALARM ID: XXX TROUBLE ID: XXX
0 = disable; 1 = Clean Me signal reports;
Note:
If Clean Me is enabled, you must enter “3” in
field ✱56 programming for zone 1 response time. 0 = 15 seconds 6 = 2-1/2 min #+11 = 7 min
1 = 30 seconds 7 = 3 min #+12 = 8 min 2 = 45 seconds 8 = 4 min #+13 = 10 min 3 = 60 seconds 9 = 5 min #+14 = 12 min 4 = 90 seconds #+10 = 6 min #+15 = 15 min 5 = 2 minutes
0 = 60 Hz; 1 = 50 Hz
Enter the desired 3-digit Contact ID® report codes for alarms and troubles occurring on zones assigned to this zone type. Enter the codes sequentially (all 6 digits). When entering digits, [#] moves cursor back, [∗] moves forward. Press [∗] when done to continue.
Enter the desired 3-digit Contact ID® report codes for alarms and troubles occurring on zones assigned to this zone type. Enter the codes sequentially (all 6 digits). When entering digits, [#] moves cursor back, [∗] moves forward. Press [∗] when done to continue.
TOUCH SCREEN DEVICE (AUI) ENABLE
AUI DEVICE 1 and 2 ENABLE
189
(for Touch Screen style keypads)
KEYPAD OPTIONS *190-*196 (NOTE
NOTE:
190
NOTE:
System supports up to two touch screen style keypads (e.g. Symphony Advanced User Interface, and 6270 Touch Screen keypad).
: Options for keypad address 16 are set by the factory and cannot be changed.)
Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results.
KEYPAD 2 DEVICE ADDRESS 17
KEYPAD 3 DEVICE ADDRESS 18
191
KEYPAD 4 DEVICE ADDRESS 19
192
KEYPAD 5 DEVICE ADDRESS 20
193
KEYPAD 6 DEVICE ADDRESS 21
194
KEYPAD 7 DEVICE ADDRESS 22
195
KEYPAD 8 DEVICE ADDRESS 23
196
EXIT TIME DISPLAY INTERVAL
197
DISPLAY PARTITION NUMBER
198
(FA168CPS; for Alpha Display Keypads)
ECP FAIL DISPLAY
199
[1] [1]
AUI 1 AUI 2
AUI 1: Must set AUI address to 1 AUI 2: Must set AUI address to 2 (see Inst. Instr. for details)
[0] [0]
Partition/ Sound
Enable FA168CPS: enter partition FA148CP: 1 = enable 0 = disable
Part./Enable† Sound
[0] [0]
[0] [0]
[0] [0]
[0] [0]
[0] [0]
[0] [0]
[0]
[0]
[0]
– 7 –
Enter each touch screen (AUI) devices home partition. 0 = disabled 1 = partition 1; 2 = partition 2; 3 = partition 3 (common)
A minimum of one standard keypad must also be
NOTE:
installed when AUI is used. Use of AUI does not affect the number of standard keypads supported.
Partition: 0 = keypad disabled; 1-3 = part. no. (3 = com) Sound: 0 = no suppression 1 = suppress arm/disarm and E/E beeps 2 = Suppress chime beeps only 3 = suppress arm/disarm, E/E, and chime
beeps
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
0 = no display; 1-5 = seconds between display refresh
If enabled and using only 2-digit fixed-word
NOTE:
keypads (e.g., FA245RF), do not set exit delay time greater than 96 seconds. See Inst. Instr. for explanation. 0 = no; 1 = yes (partition no. appears on Alpha Display)
0 = 3-digit display (“1” + device address) 1 = 2-digit fixed-display as “91”
Configurable Zone Types Worksheets
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data fields*182-*185. Configurable zone types 92 and 93 (FA168CPS only) can only be programmed using the downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1
ENTRY 2
(See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone
(See note 5 for RF zones)
ENTRY 3
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault
ENTRY 4
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 5
(See note 5 for RF zones)
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault
ENTRY 6
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal 1 = alarm 2 = trouble 3 = fault Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay
ENTRY 7
Open
RF zone N/A
0 = normal 4 = alarm 8 = trouble 12 = fault
Shorted
RF zn off-normal
0 = normal 1 = alarm 2 = trouble 3 = fault
ENTRY 8
Display Faults Power Reset/
Verification
0 = show alarms
when armed & disarmed
1 = dont show
alarms when
(show
armed
alarms, trbles, faults when disarmed)
0 = no 4 = power reset
after fault
(by code + OFF)
12 = verification (see zone
type 16)
0 = no 1 = delay 1 2 = delay 2
(See note 5 for RF zones)
(See note 5 for RF zones)
(See note 5 for RF zones)
Use Entry
Delay 1/2
Auto
Restore
0 = no 4 = yes
Byp. when
disarmed
0 = no 4 = yes
Dial Delay
(see field *50)
0 = no 4 = use delay
Use Exit
Delay
0 = no 4 = use exit
delay
Vent Zone
0 = no 8 = yes
Byp. when
armed
0 = no 8 = yes
Fault Delay
(see field *87)
0 = no 8 = use delay
see note 1
Respond as
Interior Type
0 = no 8 = yes
see note 2
3 = never show
any alarms,
trbles, faults Entry 7 = fault display + power reset/verification
ENTRY 9
Alarm Sounds Use Bell
Timeout
0 = none 1 = steady
keypad 2 = steady bell
and keypad
0 = no 4 = yes
see fields *32, *33
Entry 8 = entry delay 1/entry delay 2 + exit delay + interior zone type
Chime when
Chime Mode On
0 = no 4 = yes
Respond as
Fire Zone
0 = no 8 = yes
see zone type 09; see note 4
ENTRY 10
Trouble Sounds
0 = none 1 = periodic
beep
2 = trouble
beeps
3 = pulsing bell
and keypad Entry 9 = alarm sounds + bell timeout + fire zone Entry 10 = trouble sounds + chime
– 8 –
Entries for Fields *182 and *184
Entry Zone Type 90 Zone Type 91 (field *182) (field *184)
1 2 3 4 5 6 7 8 9 10
To calculate the value for each entry:
Simply add the values of the selected options in each of the entrys columns (one option per column). For example, to program Entry 2 for alarm response to short, auto restore on, but not a vent zone,” enter 5 (“1” for alarm short + “4” for auto restore yes + “0” for vent zone no).
EOL
Zone Conditions Represented
NOTES:
1. Do not use the “fault delay” option with a configurable zone type if it is set for an entry or exit delay, otherwise unpredictable results may occur.
2. To create an interior type zone, select respond as interior zone type (entry 8, interior type = yes), and set zone response to “fault” in entries 3-4 to ensure fault displays; do not set as “normal,” alarm, or trouble.
3. Do not set fire zones to respond as a fault (entries 1-6), otherwise faults will not display unless the [∗] key is pressed.
4. 4219/4229 modules must use EOLRs or unpredictable results may occur.
5. RF Zones: The “open” option in entries 1, 3, and 5 is not applicable for RF zones. Use the intact EOL option for normal RF zone conditions and “shorted” for off­normal RF zone conditions.
6. a. Zone-Doubling/Double-Balanced: A
short on either zone of a zone-doubled pair or on a double-balanced zone causes a tamper condition.
b. For double-balanced zones, this entry
must be 0.
c. For zone-doubled zones,
of the doubled pair must be assigned the same response to a short.
OPEN SHORTEDINTACT
ZONE-003-V0
in Entries 1-6
both
zones
*56 ZONE PROGRAMMING WORKSHEET
NOTES:
Zone Type: see chart on page 12;
Report Code: enabled if any digit entered as 1st digit;
Hardwire Type (zns 1-8):
0 = EOL 3 = ZD 1 = NC 4 = DB 2 = NO
Input Type:
2 = AW (zones 9-48) 3 = RF (zones 9-48) 4 = UR (zones 9-48) 5 = BR (zones 49-64)
Zones 9-16 not
NOTE:
available if zone doubling enabled.
Response Time:
0 = 10msec 1 = 350msec 2 = 700msec 3 = 1.2 sec
Reserved Zones
addressable device
91 =
report enable/disable
default zone type =
[05].
Duress report
92 =
enable/disable
Zone Zn Type Part. Report Hardwire
1 2 3 4 5 6 7 8
Zone Zn Type Part. Report Input Type Loop Serial No. Location
[09] [1] [01] [1] [03] [1] [03] [1] [03] [1] [03] [1] [03] [1] [03] [1]
Type
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
[1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1] [1]
49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 95 96 99
[00] [00] [06]
Rsp. Time Location
[EOL] [1] [EOL] [EOL] [EOL] [EOL] [EOL] [EOL] [EOL]
[BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR] [BR]
N/A N/A N/A
[1] [1] [1] [1] [1] [1] [1]
keypad [1] / [∗] N/A N/A N/A keypad [3] / [#] N/A N/A N/A
– 9 –
keypad [∗] / [#]
(FA148CP supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets]
*57 FUNCTION KEY PROGRAMMING
Option Function A B C D Comments
01 Paging 02 Time Display 03 Arm AWAY 04 Arm STAY 05 Arm NIGHT-STAY 06 Step Arming 07 Device Activation Device: 08 Comm. Test 09 Macro Key 1 10 Macro Key 2 11 Macro Key 3 12 Macro Key 4 00 Emergency Keys:
Personal Emergency Silent Alarm Audible Alarm Fire
Emergency Keys:
zone 95 zone 99 zone 96 paging
A = paired keys [1] / [∗] (zone 95); B = paired keys [∗] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
n/a n/a n/a n/a
OUTPUT RELAYS/POWERLINE CARRIER (X-10) DEVICES WORKSHEET FOR ∗79, ∗80 and ∗81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
79 RELAY/POWERLINE CARRIER (X-10) DEVICE MAPPING (Must program before using *80)
Pos
(1-4)
Unit No.
Description
OUTPUT TYPE Relay X10 Output No. 01
02 03 04 05 06 07 08
81 ZONE LISTS FOR OUTPUT DEVICES
Module Addr.
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence.
Record desired zone numbers below, noting that a list may include
NOTE:
List No. Used For Contains These Zones
01 02 03 04 05 06 07 08 09 10 11 12
General Purpose (GP)
General Purpose
Chime-by-Zone or GP
Cross Zones
Night-Stay Zones or GP
General Purpose
General Purpose
General Purpose
Zones activating pager 1
Zones activating pager 2
Zones activating pager 3 (FA168CPS)
Zones activating pager 4 (FA168CPS)
OUTPUT TYPE Relay X10 Output
Module No. 09
10 11 12 13 14 15 16 17 18
Addr.
On-Board Trigger 1 norm output =
On-Board Trigger 2 norm output =
(09-16 apply to FA168CPS only)
Pos
(1-4)
any
Unit No.
or
of system's zone numbers.
all
Description
– 10 –
80 OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you enter the data during the displays and prompts that appear in sequence.
1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
Notes:
2. For Powerline Carrier devices (plcd), field
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Function
Number (FA168CPS: 1-48) (FA148CP: 1-24)
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 24 = Silent Burglary 01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 77 = Keyswitch 02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide 81 = AAV Monitor Zone 03 = Perimeter 08 = 24 Hr Aux 16 = Fire w/Verification 90-91 = Configurable
04 = Interior Follower 09 = Fire 23 = No Alarm Response
Choices for System Operation are:
20 = Arming–Stay 38 = Chime 52 = Kissoff 21 = Arming–Away 39 = Any Fire Alarm 54 = Fire Zone Reset 22 = Disarming (Code + OFF) 40 = Bypassing 58 = Duress 31 = End of Exit Time 41 = **AC Power Failure 60 = AAV Trigger 32 = Start of Entry Time 42 = **System Battery Low 66 = Function key† 33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure
Activated by 0=delete 1=zn list 2=zn type 3=zn no.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
36 = **At Bell Timeout***
Activation Type and Detail Event (for zone list/activated by) Output
Zone List
1-8 = list
(ZL)
Zone Type
(ZT)
(see table
below)
Zone No.
(ZN)
00=none FA168CPS: 01-64 FA148CP: 01-06, 09-34, 49-56
Partition
Number
(if using ZT trig)
0 = any 1 = partition 1 2 = partition 2 3 = common
(P)
By Zone List
0 = restore 1 = alarm 2 = fault 3 = trouble
68 = TELCO Line Fault 78 = Keyswitch red LED††† 79 = Keyswitch green LED†††
By Zone No.
0 = restore 1 = alrm/flt/trbl
Note:
Code + # + 7 + NN Key Entry
Code + # + 8 + NN Key Entry
** Use 0 (any) for Partition No. (P) entry. *** Or at Disarming, whichever occurs earlier.
Use *57 Menu mode to assign the function key. †† Duration is set in program field *177. ††† Device action not used for these choices.
Action 0 = off 1 = close 2 secs 2 = stay closed 3 = pulse 4 = toggle 5 = duration 1 6 = duration 2
In normal operation mode:
Output
Number
FA168CPS: 1-18
FA148CP:
††
1-8, 17, 18
††
starts
stops
Device
Device
Type
R = relay T = trigger X = X10
Device
– 11 –
Zone Type Definitions
Type 00
Zone Not Used
Type 01
Entry/Exit Burglary #1
Type 02
Entry/Exit Burglary #2
Type 03
Perimeter Burglary
Type 04
Interior Follower
Type 05
Trouble by Day/
Alarm by Night
Type 06
24-hour Silent Alarm
Type 07
24-hour Audible Alarm
Type 08
24-hour
Auxiliary Alarm
Type 09
Fire
Type 10
Interior w/Delay
Type 12
Monitor Zone
Type 14
Carbon Monoxide
Type 16
Fire w/Verification
Type 20
Arm-Stay
Use this zone type if the zone is not used.
Assign to zones that are used for primary entry and exit.
Provides entry delay if the control is armed in the Away or Stay modes.
No entry delay is provided when the panel is armed in the Instant mode.
Entry delay #1 is programmable for each partition.
Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is
independently programmable.
Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.
Provides a secondary entry delay, in same manner as entry delay #1.
Entry delay #2 is programmable for each partition.
Exit delay is same as described for Type 01.
Assign to all sensors or contacts on exterior doors and windows.
Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Instant, or
Maximum modes.
Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon
entry (to and from the keypad).
Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first.
Otherwise this zone type gives an instant alarm.
Active when the panel is armed in the Away mode.
Bypassed automatically when the panel is armed in the Stay or Instant modes.
Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering
a sensitive area such as a stock room, drug supply room, etc.
Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
Provides an instant alarm if faulted when armed in the Away, Stay, Instant or Maximum (night) modes.
During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a
central station report, if desired).
Usually assigned to a zone containing an emergency button.
Sends a report to the central station but provides no keypad display or sounding.
Assign to a zone that has an emergency button.
Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external
alarm.
Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as
water or temperature sensors.
Sends a report to the central station and provides an alarm sound at the keypad.
provided.)
Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a
pulsing bell output.
This zone type is always active and cannot be bypassed.
Note:
Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away
mode.
Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit
delay zone was tripped first.
Bypassed when the panel is armed in the Stay or Instant modes.
Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "
24 Hr. Non-Burg. -#XXX
system keypad will display a “check” message indicating the appropriate zone (but keypad beeping does not occur). Upon restoral of the zone, the message, " the Central Station.
The “check” message will automatically disappear from the keypad dynamically when the zone restores; a
user code + off sequence is not needed to reset the zone.
Faults of this zone type are independent of the system, and can exist at the time of arming without
interference.
Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon alarm.
Assigned to any zone with a carbon monoxide detector.
The bell output will pulse when this zone type is alarmed.
Always active and cannot be bypassed.
Provides a fire alarm when zone is shorted, but only after alarm verified.
System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit
within 90 seconds triggers fire alarm.
Provides a trouble response when zone is open.
Arms the system in Stay mode when the zone is activated.
Pushbutton units send the user number to the central station when arming or disarming.
User code for button must be assigned.
Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire smoke detectors; any wireless zone can be used as a fire zone.
" (where XXX is the zone number) will be sent to the Central Station. The
RESTORE-24 Hr. Non-Burg. -#XXX
(No bell output is
ALARM-
" will be sent to
– 12 –
Type 21
Arm-Away
Type 22
Disarm
Type 23*
No Alarm Response
Type 24
Silent Burglary
Type 77
Arms the system in Away mode when the zone is activated.
Pushbutton units send the user number to the central station when arming or disarming.
User code for button must be assigned.
Disarms the system when the zone is activated.
User code for button must be assigned.
Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.
A report is sent to the central station.
Assign to zone wired to a keyswitch.
Keyswitch
Type 81
AAV Monitor Zone
Types 90-93
Installer Defined
The system can still be armed when these zone types are in a faulted condition.
*
Schedules
events 00-07 for both controls; FA148CP supports up to 8 schedules, FA168CPS supports up to 32 schedules
(installer code + [#] + [6] [4];
Assign to zone connected to AAV module.
Monitors 2-way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting stops, except for fire alarms, which immediately terminate the voice session and cause a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell timeout has not expired) and reports that were stopped are sent.
These zone types can be programmed for various custom responses. See data fields *182-*185.
Types 92 and 93 can only be programmed via the downloader.
UL: Zone types 90-93 may not be used as fire or burglar zones in fire or UL burglar alarm installations.
master code can only access schedules 01-16 for FA168CPS, 01-04 for FA148CP, and
)
No. Event Device No. Group No. Partition Start Time/ Stop Time/ Repeat Random
(see list below) for “01” events: for “02” events: for “04-06” events: enter 01-18 enter 1-8 enter 1, 2, or 3
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
Events: Master/Installer Installer Only 00 = clear event 04 = forced STAY arm 10 = display custom words 8-10 01 = device on/off 05 = forced AWAY arm 11 = periodic test report 02 = user access 06 = auto disarm 03 = latch key report 07 = display “reminder” Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week
Days Days
– 13 –
(1-4) (yes/no)
000
– A –
001 AIR
002 ALARM
004 ALLEY 005 AMBUSH
006 AREA
007 APARTMENT
009 ATTIC
010 AUDIO
012 BABY
013 BACK
014 BAR
016 BASEMENT
017 BATHROOM
018 BED
019 BEDROOM
020 BELL
021 BLOWER
022 BOILER
023 BOTTOM 025 BREAK
026 BUILDING
028 CABINET
• 029 CALL
030 CAMERA 031 CAR 033 CASH 034 CCTV 035 CEILING 036 CELLAR
037 CENTRAL
038 CIRCUIT
040 CLOSED
046 COMPUTER
047 CONTACT
048 DAUGHTERS
049 DELAYED
050 DEN
051 DESK
052 DETECTOR
053 DINING
054 DISCRIMINATOR 055 DISPLAY
Note:
Italicized words followed by an asterisk indicate those words supported by the FA560VKP Voice Keypad.
(Word Space)
B
C
D
Bulleted (•) words in
057 DOOR
059 DOWN
060 DOWNSTAIRS
061 DRAWER
062 DRIVEWAY
064 DUCT E
065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
069 EQUIPMENT
071 EXIT
072 EXTERIOR
F
073 FACTORY
075 FAMILY
076 FATHERS
077 FENCE
079 FIRE
080 FLOOR
081 FLOW 082 FOIL
083 FOYER
084 FREEZER
085 FRONT
G
089 GARAGE
090 GAS
091 GATE
092 GLASS
093 GUEST 094 GUN
H –
095 HALL
096 HEAT
098 HOLDUP 099 HOUSE 100 INFRARED
101 INSIDE
102 INTERIOR 103 INTRUSION
J
104 JEWELRY
105 KITCHEN
K
boldface type
106 LAUNDRY
107 LEFT
108 LEVEL
109 LIBRARY
110 LIGHT
111 LINE
113 LIVING
114 LOADING
115 LOCK 116 LOOP 117 LOW
118 LOWER
119 MACHINE
121 MAIDS
122 MAIN
123 MASTER
125 MEDICAL
126 MEDICINE 128 MONEY 129 MONITOR
130 MOTHERS
131 MOTION
132 MOTOR
134 NORTH
135 NURSERY
136 OFFICE
138 OPEN
139 OPENING
140 OUTSIDE
142 OVERHEAD
143 PAINTING
144 PANIC
145 PASSIVE
146 PATIO
147 PERIMETER
148 PHONE
150 POINT
151 POLICE 152 POOL
153 POWER
155 RADIO
are those that are also available for use by the FA4285/FA4286 Phone Module.
L
M
N
O
P
R
156 REAR
157 RECREATION 159 REFRIGERATION 160 RF
161 RIGHT
162 ROOM
163 ROOF
S
164 SAFE 165 SCREEN 166 SENSOR
167 SERVICE
168 SHED
169 SHOCK
170 SHOP
171 SHORT
173 SIDE
174 SKYLIGHT
175 SLIDING
176 SMOKE
178 SONS
179 SOUTH
180 SPRINKLER
182 STATION
184 STORE
185 STORAGE
186 STORY
190 SUPERVISED
191 SUPERVISION 192 SWIMMING 193 SWITCH
T
194 TAMPER 196 TELCO 197 TELEPHONE
199 TEMPERATURE
200 THERMOSTAT
201 TOOL
202 TRANSMITTER
– V –
– U –
205 UP
206 UPPER
207 UPSTAIRS
208 UTILITY
209 VALVE 210 VAULT 212 VOLTAGE
W
213 WALL 214 WAREHOUSE
216 WEST
217 WINDOW
219 WING
220 WIRELESS
X
222 XMITTER
Y
223 YARD
Z
224 ZONE (No.)
225 ZONE
226 0
227 1
228 1ST
229 2
230 2ND
231 3
232 3RD
233 4
234 4TH
235 5
236 5TH
237 6
238 6TH
239 7
240 7TH
241 8
242 8TH
243 9
244 9TH
245 Custom Word #1 246 Custom Word #2 247 Custom Word #3 248 Custom Word #4 249 Custom Word #5 250 Custom Word #6 251 Custom Word #7 252 Custom Word #8 253 Custom Word #9 254 Custom Word #10
If using a Phone module, and words other than these are selected for Alpha descriptors, the module will not provide annunciation of those words.
32 (space) 33 ! 34 " 35 # 36 $ 37 % 38 & 39 ' 40 (
CHARACTER (ASCII) CHART (For Adding Custom Words)
41 ) 42 * 43 + 44 , 45 – 46 . 47 / 48 0 49 1
50 2 51 3 52 4 53 5 54 6 55 7 56 8 57 9 58 :
59 ; 60 < 61 = 62 > 63 ? 64 @ 65 A 66 B 67 C
68 D 69 E 70 F 71 G 72 H 73 I 74 J 75 K 76 L
77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
86 V 87 W 88 X 89 Y 90 Z
– 14 –
5800 Series Transmitter Input Loop Identification
All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes.
inputs requires its own programming zone
(e.g., a 5804's four inputs require four programming zones).
WIRELESS INPUT TYPES
"RF" (Supervised RF) Type
send periodic check-in signals, as well as fault, restore and low battery signals. The transmitter must remain within the receiver's range.
UR" (Unsupervised RF) Type
send all the signals that the "RF" Type does, but the control does not supervise the check-in signals. The transmitter may, therefore, be carried off-premises.
"BR" (Unsupervised Button RF) Type
only send fault signals. They do not send restore or check-in signals. They will indicate a low battery condition when tested or activated normally. They can be carried off-premises.
: For information on any transmitter not shown
Note
above, refer to the instructions accompanying that transmitter for details regarding loop numbers, etc.
:
UL NOTE
use in UL installations: 5802MN, 5802MN2, 5804, 5804BD, 5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed Residential Burglar installations.
The following transmitters are not intended for
ENROLL AS "UR" OR "RF"
YOU MUST ENROLL THIS BUTTON
LOOP 4
5804
ENROLL
AS "BR"
ENROLL AS "RF"
ENROLL AS "RF"
LOOP 3
LOOP 2
LOOP 1
LOOP 4 YOU MUST ENROLL THIS BUTTON
5801
LOOP 3
LOOP 2
LOOP 1
LOOP 3
LOOP
1
5809
LOOP
1
5808
5802MN
ENROLL AS "UR" OR "RF"
5804BD
ENROLL AS "BR"
5816
ENROLL AS "RF"
ENROLL THIS
(TERMINALS)
LOOP 2
YOU MUST
BUTTON
LOOP 4
LOOP 1
SET
HOUSE
CODE
LOOP
2
(REED)
LOOP 1
LOOP
1
LOOP
2
(REED)
ALTERNATE
POSITION
FOR LOOP2
LOOP
2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS "RF"
5819
ENROLL AS "RF"
5827
SET HOUSE CODE
5850 (GBD)
ENROLL AS "RF"
(TERMINALS)
5816MN
(TERMINALS)
LOOP 2 (REED)
LOOP 1
LOOP 1
(Green)
(Red) (Yellow)
(TERMINALS)
Each of the
5817
ENROLL AS "RF"
LOOP
2
(REED)
LOOP 3
5819S (WHS & BRS)
ENROLL AS "RF"
5827BD
SET HOUSE CODE
5890
ENROLL AS "RF"
LOOP
1
(PRIMARY)
2
(AUX. CENTER)
3
(AUX. RIGHT)
LOOP 1
(INTERNAL
SHOCK
SENSOR)
LOOP
1
(MOTION)
Wireless Key Predefined Default Templates
For 5804
Loop Function Zone Type
TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23 2 Disarm 22 2 No Response 23 3 Arm Away 21 3 Arm Away 21 4 No Response 23 4 Disarm 22 TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22 TEMPLATE 3 1 24-hour audible 7 TEMPLATE 6 1 24-hour audible 7 2 Disarm 22 2 Arm Stay 20 3 Arm Away 21 3 Arm Away 21 4 Arm Stay 20 4 Disarm 22
For 5804BD
Loop Function Zone Type
Table of Device Addresses
This Device
RF Receiver AUI 1 AUI 2 Long Range Radio FA4286 Voice Module Zone Expanders (4219/4229):
module 1 (for zones 09 - 16) module 2 (for zones 17 - 24) module 3 (for zones 25 - 32) module 4 zones 33 - 40 module 5 zones 41 - 48
Relay Modules (4204):
module 1 module 2 module 3 module 4
Keypads:
keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8
5800TM Module
** These module addresses apply to FA168CPS only. †† Addressable devices are identified by 1 plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
Uses Address
00 01 02 03 04
07
08 09** 10** 11**
12
13 14** 15**
16
17
18
19
20
21
22
23
28
Reports as
100 101 102 103 104
107 108 109 110 111
112 113 114 115
†† Enabled By…
*56 zone programming: input device type entry automatic if AUI enable field *189 enabled for AUI 1 automatic if AUI enable field *189 enabled for AUI 2 automatic if output to long range radio field *29 enabled automatic if phone module access code field *28 enabled *56 zone programming: input device type entry, then:
*79 output device programming: device address prompt:
n/a n/a n/a n/a n/a n/a
data field programming as listed below:
n/a n/a n/a
automatic
automatic if zone no. 9-16 entered as AW type or relay assigned automatic if zone no. 17-24 entered as AW type or relay assigned automatic if zone no. 25-32 entered as AW type or relay assigned automatic if zone no. 33-40 entered as AW type or relay assigned automatic if zone no. 41-48 entered as AW type or relay assigned
entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt
always enabled, all sounds enabled. data field *190 data field *191 data field *192 data field *193 data field *194 data field *195 data field *196
– 15 –
EOL
POWER
SUPERVISION
RELAY MODULE
RED
+
N.O.
_
BLK
4-WIRE SMOKE DETECTOR CONNECTIONS
N.C.
RELAY
5
4
AS ZONE TYPE 54
PROGRAM RELAY
_
+
4219
8-PIN CONNECTOR
USED FOR 4300/1321X10
BATTERY FUSE
CONTACT OPENS MOMENTARILY
(FIRE ZONE RESET)
OR
OUTPUT
AUX PWR
TERMINALS
SET UNIT’S
DIP SWITCH
FOR DEVICE
ADDRESSES
7 - 15
SEE
-OR-
4229
OUTPUT RELAYS)
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
BLK
RED
CABLE)
(USE SA4120XM-1
78
TRANSFORMER
SEE INSTRUCTIONS.
ON-BOARD TRIGGERS
CONNECTIONS AND FOR
1234 5 6
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
3A
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
VIOLET
2000
OHMS
EOLR
_
+
DETECTOR
4-WIRE SMOKE
OR COMBUSTION
TO OUTPUT 17
UPON FIRE ALARM RESET
(UP TO 16 DETECTORS
MAX. CURRENT = 100 mA
"OUT NORM LOW" = YES IN
PROGRAM OUTPUT 17 FOR
TYPE 54 IN 80 MENU MODE
79 MENU MODE AND AS ZONE
INSTRUCTIONS.
SET
RECEIVER’S
DIP SWITCH
FOR DEVICE
-OR-
AND/OR
5881* Type
RF RECEIVER
WIRELESS ZONES
(4 OUTPUT RELAYS)
4204 RELAY MODULE
GRN
YEL
BLK
OPTIONAL
TO
TRANS.
COM
DATA
SYNC
TO TERM 4
(TRIG. 2)
GND
+12 AUX
(TRIG. 1)
FLYING LEADS
FOR BATTERY
CONNECTION
+
BLACK
RED
+
HEAT
DETECTOR
+
_
PLUS EOL MODULE)
TO ZONE TERM. ( )
TO ZONE TERM. ( )
ADDRESS
OF “0”.
SEE
INSTRUCTIONS.
*5882 IN CANADA
5881L: UP TO 8
5881H: UP TO 64
5881M: UP TO 16
RED
GRN
YEL
( FROM EITHER OR BOTH GROUPS)
FOR UP TO 40 ADDITIONAL ZONES
BLK
YEL
RED
GRN
TO TERM 5
TO TERM 6
TO TERM 7
OUTPUT 18
OUTPUT 17
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM
RESISTOR DIRECTLY ACROSS
SOUNDER.
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
RING
(RED)
}
INCOMING
TIP
PHONE LINE
(GREEN)
RING
(GRAY)
TIP
(BROWN)
HI
20
LO
19
LO
HI
18
HI
17
LO
16
LO
HI
15
HI
14
LO
13
LO
HI
12
HI
11
LO
}
HANDSET
CONNECT CORD)
*CA38A IN CANADA
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
10
LO
8 9
HI
654
+
}
AUX. POWER
OUTPUT
+
)
-
) RETURN
FOR UL
600mA MAX.
(500mA MAX.
10.5-13.8VDC INSTALLATIONS)
TO PREVENT RISK OF SHOCK,
DOC LOAD NO.: 3
WARNING:
DISCONNECT TELEPHONE LINE AT TELCO
FOR CONNECTION OF OPTIONAL FA4285 OR FA4286 VIP
MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.
FA168CPS ONLY
ZONE 8
2000
EOLR
OHMS
ZONE 7
2000
EOLR
OHMS
ZONE 6
2000
EOLR
OHMS
ZONE 5
2000
EOLR
OHMS
ZONE 4
2000
EOLR
OHMS
ZONE 3
2000
EOLR
OHMS
ZONE 2
2000
EOLR
OHMS
ZONE 1
2000
EOLR
OHMS
YELLOW: KEYPAD DATA OUT
GREEN: DATA IN FROM KEYPAD
RED: KEYPAD PWR (
BLACK: KEYPAD GROUND (
ALL OUTPUTS
ARE POWER
LIMITED.
NOTE:
KEYPAD (S)
CURRENT (IN
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
RINGER EQUIVALENCE: 0.1B.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
POWER SHUTDOWN NOTE:
ZONE
PAIRS
2k
TAMPER
CONTACTS
2k
DEVICES
(e.g. 5800TM,
4285/4286, LRR,
POWER FROM
TERMS 4 & 5
SYSTEM SHUTS DOWN SENSOR
DETECTION PROCESSING IF
CONTROL'S VOLTAGE DROPS
2 / 10
3 / 11
4 / 12
5 / 13
ZONE 2
10 11
TAMPER
4219, 4229,
4204, 5881)
MUST BE
INCLUDED IN
AUX CURRENT
THAT MAY CAUSE UNDESIRED OPERATION.
BELOW 9.6V.
6 / 14
3k
2k
CONTACTS
2k
REMOTE KEYPADS
DRAIN
7 / 15
CAN USE FA215KP, FA260KP,
CALCULATIONS.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS
8 / 16
FA260RF, OR FA560KP
JACK BEFORE SERVICING THIS UNIT.
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
1312 14
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
REMOTE
KEYPADS
AND OTHER
ADDRESSABLE
BOTH
PARTITIONS)
AND ALL
OTHER DEVICES
DRAWING
SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE (3) YEARS.
ZONE 10
2k
2k
KEYPADS. LOCAL
FA168CPS148CP-SOC-V0
ALL DEVICES AND ACCESSORIES
USED IN A CANADIAN INSTALLATION
MUST BE LISTED FOR USE IN CANADA
6.2k
ZONE DOUBLING
(FA168CPS ONLY)
TYPICAL WIRING FOR
ZONE 4
FA168CPS / FA148CP
SUMMARY OF CONNECTIONS
(FA168CPS ONLY)
TYPICAL WIRING FOR
ZONE 3
DOUBLE BALANCED ZONE
PROGRAMMING MUST BE
DONE WITH A FA560KP,
BUT NEED NOT REMAIN IN
THE SYSTEM
(SET TO ADDRESS 16).
+
UNSWITCHED
OUTLET (24HR)
ALARM OUTPUT
USAGE, INCLUDING
(600mA MAX. FOR UL
10.5–13.8VDC, 2A MAX.
12 3 7 21 22 23 24 25
TO 110VAC
TEMPORAL PULSE
CAN USE 702 SIREN,
AUX POWER) STEADY
SOUNDING FOR FIRE.
FOR BURGLARY/PANIC,
OR 12V BELL).
SEE INSTRUCTIONS.
FOR COMPLETE
INFORMATION, SEE
INSTRUCTIONS K5305-5V1
12V, 4AH
BATTERY
650mA.
13.8VDC. MAXIMUM
FIRE INSTALLATIONS. USE 12V, 17.2AH
BATTERY FOR 600mA AUX POWER. SEE
INSTRUCTIONS.
BATTERY CAPACITY FOR EMERGENCY
CHARGING VOLTAGE
BURGLARY STANDBY USE AT LEAST 4 HRS
CHARGING CURRENT
SEALED LEAD-ACID TYPE.
BATTERY NORMALLY NEED NOT BE
TO DETERMINE TOTAL STANDBY LOAD
ON BATTERY, ADD 100mA TO TOTAL OF
AUX. POWER OUTPUT AND REMOTE
REPLACED FOR AT LEAST 3 YRS.
24-HR BATTERY STANDBY REQUIRED FOR
Copyright © 2003 Honeywell International Inc.
¬.3594l
K5305-5PRV2 10/03 Rev. A
(e.g. 1321).
16.5VAC, 25VA
(USE No. 1321CN IN CANADA)
CLASS 2 PLUG-IN TRANSFORMER
USE UL LISTED LIMITED ENERGY
CABLE FOR ALL CONNECTIONS
KEYPAD CURRENTS.
149 Eileen Way, Syosset, NY 11791
THIS EQUIPMENT SHOULD BE INSTALLED
USE 4300 / 1321X10 TRANSFORMER
INTERFACE IN PLACE OF 1321 OR
1321CN WHEN POWER LINE CARRIER
DEVICES ARE BEING USED. (SEE
INSTRUCTIONS FOR CONNECTIONS)
IN ACCORDANCE WITH THE NATIONAL
FIRE PROTECTION ASSOCIATION'S
STANDARD 72, CHAPTER 2 (NATIONAL
FIRE PROTECTION ASSOCIATION,
BATTERY-MARCH PARK, QUINCY,MA
02269).
www.firstalertpro.com
PRINTED INFORMATION
DESCRIBING PROPER INSTALLATION,
OPERATION,TESTING, MAINTENANCE,
EVACUATION PLANNING AND REPAIR
SERVICE IS TO BE PROVIDED WITH THIS
EQUIPMENT.
CONNECTION OF THE FIRE ALARM
SIGNAL TO A FIRE ALARM
HEADQUARTERS OR A CENTRAL STATION
SHALL BE PERMITTED ONLY WITH THE
PERMISSION OF THE LOCAL AUTHORITY
HAVING JURISDICTION. THE BURGLAR
ALARM SIGNAL SHALL NOT BE
CONNECTED TO A POLICE EMERGENCY
NUMBER.
Loading...