Local programming requires the use of an alpha keypad connected to the keypad terminals on the control.
POWER UP, then depress
A.
mode, this method must be used to reenter program mode).
OR
Initially, key:
B.
Installer Code (4 + 1 + 1 + 2)
[✱] and [#]
both at once, within 50 seconds of powering up (if ✱98 was used to exit program
plus
8 + 0 + 0.
DATA FIELD PROGRAMMING PROCEDURES
Task Procedure
Go to a Data Field
Entering Data
Review a Data Field
Deleting an Entry
Press [∗] + [Field Number], followed by the required entry.
When the desired field number appears, simply make the required entry. When the last entry for a
field is entered, the keypad beeps three times and automatically displays the next data field in
sequence.
If the number of digits that you need to enter in a data field is less than the maximum digits available
(for example, the phone number fields *41, *42), enter the desired data, then press [
entry. The next data field number is displayed.
Press [#] + [Field Number].
Data will be displayed for that field number. No changes will be accepted in this mode.
Press [∗] + [Field Number] + [∗]. (Applies only to fields ∗40 thru *46, *94, and pager programming
(for example, ✱56). The alpha display keypad will display the first of a series of prompts
Used to Program
transmitters.
4229 or 4204 Relay modules, Powerline Carrier devices, or on-board triggers
Zone Lists for relay/powerline carrier activation, chime zones, pager zones, etc.
Zone alpha descriptors
INITIALIZE DOWNLOAD and RESET DEFAULTS
✱
Initializes download ID and subscriber account number.
96
✱
Sets all data fields to original factory default values.
97
TO EXIT PROGRAMMING MODE:
✱
Exits programming mode and
98
mode, system must be powered down, and method A above used to enter the programming mode.
See field *88 for other *98 Program mode lockout options.
✱
Exits programming mode and
99
prevents
allows
re-entry by:
re-entry by:
Installer Code + 8
Installer Code
+ 0 + 0. If
+ 8 + 0 + 0 or method 1 above.
✱
is used to exit programming
98
Special Messages
= OPEN CIRCUIT (no communication between Keypad and Control).
OC
or
EE
ENTRY ERROR
After powering up,
This will revert to a “
delay by pressing
If E4 or E8 appears, more zones than the expansion units can handle have been programmed. The display will clear after
you correct the programming.
= ERROR (invalid field number entered; re-enter valid field number).
AC, dI
Ready
[#] + [0].
(disabled) or
” message in approximately 1 minute, which allows PIRS, etc. to stabilize. You can bypass this
Busy Standby
and
NOT READY
will be displayed after approximately 4 seconds.
– 2 –
352*5$00,1*)250
Entries apply to both the FA168CPS and
FA148CP
controls, except
FA168CPS (partition entries) and are not applicable to the FA148CP.
Entry of a number other than one specified will give unpredictable results. Values shown in brackets are factory defaults.
Field Function Data Entries Programmable Values
SYSTEM SETUP (✱20–✱29)
✱
INSTALLER CODE
20
✱
QUICK ARM ENABLE
21
✱
RF JAM OPTION
22
✱
QUICK (FORCED) BYPASS
23
✱
RF HOUSE ID CODE
24
✱
CHIME BY ZONE
26
✱
27
POWERLINE CARRIER DEVICE (X–10)
HOUSE CODE
✱
ACCESS CODE FOR
28
PHONE MODULE
✱
LONG RANGE RADIO OUTPUT
29
ZONE SOUNDS AND TIMING (✱31 – ✱39)
✱
SINGLE ALARM SOUNDING per ZONE
31
✱
FIRE ALARM SOUNDER TIMEOUT
32
✱
ALARM SOUNDER (BELL) TIMEOUT
33
✱
EXIT DELAY
34
✱
ENTRY DELAY #1 (zone type 01)
35
✱
ENTRY DELAY #2 (zone type 02)
36
AUDIBLE EXIT WARNING
∗37
✱
CONFIRMATION OF ARMING DING
38
✱
POWER UP IN PREVIOUS STATE
39
| | | [4112]
[0,0]
Part. 1 Part.2
[0]
[0,0]
Part. 1 Part. 2
| | |
Part. 1 Part. 2 Common
[0]
[0]
| [00]
(Partition 1 only)
[0]
[0]
| | [60,60]
Part. 1 Part. 2
| | [30,30]
Part. 1 Part. 2
Common zones use same
delay as partition 1
| | [30,30]
Part. 1 Part. 2
Part. 1 Part. 2
[0]
[1]
[1,1]
[0,0]
[1]
DIALER PROGRAMMING (✱40 – ✱42)
Do not fill unused spaces. Enter 0–9; #+11 for '✱'; #+12 for '#'; #+13 for a 2-second pause. If fewer than the maximum digits entered, exit the
field by pressing [✶]. The next data field number is displayed.
✱
PABX ACCESS CODE
40
✱
PRIMARY PHONE No.
41
✱
SECOND PHONE No.
42
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Enter up to 20 digits. To clear entries, press ✱41✱ or ✱42
| | | | |
used, enter “∗ (#+11) 70” plus “# + 13” (pause).
entries shown in dashed boxes, which apply only to the
4 digits, 0–9
0 = no; 1 = yes
0 = no RF Jam detection; 1 = send RF Jam report
UL: must be 1 if wireless devices are used
0 = no quick bypass UL: must be “0”
.
1 = allow quick bypass (code + [6] + [#] )
00 = disable all wireless keypad usage
01–31 = using 5827, 5827BD or 5804BD keypad
[00,00,00]
0 = no; 1 = yes (select zones to chime on zone list 3,
using *81 Menu mode)
0 = A; 1 = B, 2 = C, 3 = D, 4 = E, 5 = F, 6 = G,
7 = H, 8 = I, 9 = J, #10 = K, #11 = L, #12 = M, #13 = N,
#14 = O, #15 = P UL: not for fire or UL installations
00 = disable; 1st digit: enter 1–9; 2nd digit: enter # + 11
for "✱", or # + 12 for "#".
UL: must be “00” for UL Commercial Burg. installations
0 = disable; 1 = enable
0 = no UL: must be “0”; 1 = yes
0 = sounder stops at timeout;
1 = no sounder timeout UL: must be “1” for fire install.
UL: For residential fire alarm installation, must be set for a
minimum of 4 min (option 1); for UL Commercial Burglary
installations, must be minimum 16 min (option 4)
00 - 96 = 0 - 96 secs; 97 = 120 secs
SIA Installations: minimum exit delay is 45 seconds
UL: see inst. instr. for requirements.
Common zones use same delay as partition 1.
For UL Residential Burglary Alarm installations, must be set
for a maximum of 30 seconds; entry delay plus dial delay
should not exceed 1 min. For UL Commercial Burglar Alarm,
total entry delay may not exceed 45 seconds.
See *35 Entry Delay 1 above for entries.
SIA Installations:
minimum entry delay is
30 seconds
Enter up to 6 digits. To clear entries, press ✱40✱. If call waiting
0 = no; 1 = yes
SIA Installations: must be enabled (enter 1)
0 = no; 1 = yes (wired keypads and RF)
2 = yes, RF only
UL: must be “1” for UL Commercial Burglar Alarm inst.
0 = no; 1 = yes UL: must be “1”
✱
– 3 –
respectively
.
NOTE: Entry of a number other than one specified will give unpredictable results.
For fields *43 thru *46:
reporting format) is used. Enter 0 as the first digit of a 4-digit account number for Nos. 0000-0999. Exit field by pressing ✱ if only 3 digits are used. E.g., For Acct.
#+11| 2 | 3 | 4
, enter:
B234
✱
PARTITION 1 PRIMARY ACCT. No.
43
✱
PART. 1 SECONDARY ACCT. No.
44
✱
PARTITION 2 PRIMARY ACCT. No.
45
✱
PARTITION 2 SECONDARY ACCT.
46
✱
47
✱
48
No.
PHONE SYSTEM SELECT
REPORT FORMAT
Enter 0–9; #+11 for B; #+12 for C; #+13 for D; #+14 for E; #+15 for F. Enter
| | | / | | | | |
| | | / | | | | |
| | | / | | | | |
| | | / | | | | |
[1]
[77]
primary secondary
as the fourth digit if a 3-digit account number (for 3+1 dialer
[✱]
Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *43
*.
[FFFF]
Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *44*. [FFFF]
Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *45*. [FFFF]
Enter 4 or 10 digits, depending on selection in *48 Report
Format. See box above. To clear entries, press *46*. [FFFF]
0 = Standard/backup reporting only (all to primary)
Primary Phone No.
2nd Phone No.
1 = Alarms, Restore, Cancel Others
2 = All except Open/Close, Test Open/Close, Test
3 = Alarms, Restore, Cancel All
4 = All except Open/Close, Test All
✱
BURGLARY DIALER DELAY
50
5 = All All
[2]
0 = no delay UL: must be “0”
1 = 15 seconds SIA Installations: delay
2 = 30 seconds must be minimum of
✱
SESCOA/RADIONICS SELECT
53
✱
DYNAMIC SIGNALING DELAY
54
3 = 45 seconds 30 seconds
[0]
[0]
0 = Radionics (0-9, B-F)
1 = SESCOA (0-9 only reporting)
Select “0” for all other formats.
Select delay from 0 to 225 secs, in 15-sec increments.
0 = no delay (both signals sent), 1 = 15 secs,
2 = 30 secs, etc.
✱
DYNAMIC SIGNALING PRIORITY
55
✱
56, *57, *58
MENU MODES
UL: Grade AA must be “0;” Grade A must be “15” max
[0]
These are Menu Mode commands, not data fields, for Zone Programming, Function
0 = Primary Dialer first; 1 = Long Range Radio first.
For UL Commercial Burglary installations that use a
DACT and LRR, this field must be “0”.
Key Programming, and Expert Mode Zone Programming respectively. See page 2 and
their respective sections in the Installation and Setup Guide for procedures.
TO PROGRAM SYSTEM STATUS, & RESTORE REPORT CODES (✱59 thru *68, *70 thru ✱76, and ✱89):
first
For 3+1 or 4+1 Standard Format:
not
A 0 (
#+10) in the
For Expanded or 4+2 Format:
not
A 0 (
#+10) in the
For Ademco Contact ID® Reporting:
not
A 0 (
#+10) in the
first
second
first
Enter a code in the
box will disable a report. A 0 (
Enter codes in
box will eliminate the expanded message for that report. A 0 (
box disables the report.
both
Enter any digit (other than 0) in the
SYSTEM STATUS REPORT CODES (✱59–
✱
EXIT ERROR REPORT CODE
59
✱
TROUBLE REPORT CODE
60
✱
BYPASS REPORT CODE
61
✱
AC LOSS REPORT CODE
62
✱
LOW BAT REPORT CODE
63
✱
TEST REPORT CODE
64
| [00] See box above. Use Scheduling mode to set periodic test reports,
| [00] See box above.
| [00] See box above.
| [00] See box above.
| [00] See box above.
box: 1–9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F.
not
#+10) in the
boxes (1st and 2nd digits) for 1–9, 0, or B–F, as described above.
UL: see installation instructions for requirements
✱
68)
second
box will result in automatic advance to the next field.
first
box, to enable zone to report (entries in the
[0] See box above.
not
#+10) in
both
boxes will disable the report.
second
boxes are ignored).
or use the following key commands:
Each mode sets schedule 32 (FA168CPS) or installer code +[#] + [0] + 0 = test report sent every 24 hours
schedule 08 (FA148CP) to the stated installer code +[#] + [0] + 1 = test report sent once per week
repeat option; first test report sent 12 hours after command. installer code +[#] + [0] + 2 = test report sent every 28 days
– 4 –
✱
OPEN REPORT CODE
65
✱
ARM AWAY/STAY RPT CODE
66
Away Stay Away Stay Away Stay
✱
RF XMTR LOW BAT REPORT CODE
67
✱
CANCEL REPORT CODE
68
Part. 1 Part. 2 Common
| [00] See box on previous page.
| [00] See box on previous page.
[0,0,0] See box above.
Part. 1 Part. 2 Common
[0,0,0,0,0,0]
UL: must be enabled if wireless devices are used
RESTORE REPORT CODES (✱70 – ✱76)
✱
ALARM RESTORE RPT CODE
70
✱
TROUBLE RESTORE RPT CODE
71
✱
BYPASS RESTORE RPT CODE
72
✱
AC RESTORE RPT CODE
73
✱
LOW BAT RESTORE RPT CODE
74
✱
RF XMTR LO BAT RST RPT CODE
75
✱
TEST RESTORE RPT CODE
76
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
| [00] See box on previous page.
[0] See box on previous page.
UL: must be enabled if wireless devices are used
OUTPUT AND SYSTEM SETUP (✱77 – ✱93)
✱
DAYLIGHT SAVINGS TIME
77
START\END MONTH
✱
DAYLIGHT SAVINGS TIME
78
START\END WEEKEND
∗
79, *80, *81, *82
✱
AUTO STAY ARM
84
✱
CROSS ZONE TIMER
85
MENU MODES
This option not for use in UL installations.
✱
CANCEL VERIFY KEYPAD DISPLAY
86
✱
MISC. FAULT DELAY TIME
87
(used with Configurable Zone Types “digit 6”)
✱
PROGRAM MODE LOCKOUT
88
OPTIONS
✱
EVENT LOG FULL REPORT CODE
89
✱
EVENT LOG ENABLES
90
✱
OPTION SELECTION
91
| [4][10]
| [1][5]
These are Menu Mode commands, not data fields, for Output Device Mapping, Output
Programming, Zone List Programming, and Alpha Programming respectively. See page
2 and their respective sections in the Installation and Setup Guide for procedures.
[3]
[0]
(assign cross zones on
zone list 4, using *81 Menu
mode)
[1]
[0]
UL: may only be used on
non-burglar alarm/ non-fire
alarm zones when used in
fire and/or UL burglar alarm
installation
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
PAGER 1 CHARACTERS
161
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
PAGER 1 REPORT OPTIONS
162
Part. 1 Part. 2 common
[0,0,0]
For each partition, select from the following options:
0 = no reports sent
1 = Open/closes all users
4 = All alarms and troubles
5 = All alarms / troubles, and open/closes for all users
12 = Alarms / troubles for zones entered in zone list 9
13 = Alarms / troubles for zones entered in zone list 9,
✱
PAGER 2 PHONE No.
163
| | | | | | | | | | | | | | | | | | |
and open/closes for all users
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
PAGER 2 CHARACTERS
164
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
Enter up to 20 digits. 0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
0,0,0]
Part. 1 Part. 2 common
See field *162 for reporting options. Select for each
partition (use zone list 11 if using options 12 or 13).
| | | | | | | | | | | | | | |
Enter the optional prefix characters, up to 16 digits.
0–9; #+11 = '✱'; #+12 = '#'; #+13 = 2-second pause.
✱
PAGER 4 REPORT OPTIONS
171
✱
PAGER DELAY OPTION FOR ALARMS
172
[0,0,0]
Part. 1 Part. 2 common
[3]
See field *162 for reporting options. Select for each
partition (use zone list 12 if using options 12 or 13).
0 = none, 1 = 1 minute, 2 = 2 minutes, 3 = 3 minutes
This delay is for ALL pagers in the system.
– 6 –
MISCELLANEOUS SYSTEM FIELDS (*174-*181)
✱
CLEAN ME REPORTING OPTIONS
174
(for ESL smoke detectors)
✱
DEVICE DURATION 1, 2
177
(used in *80 Menu mode-Device Actions 5/6)
✱
50/60 HERTZ AC OPERATION
181
[0]
[0] [0]
1 2
[0]
CONFIGURABLE ZONE TYPE OPTIONS (*182-*185)
✱
CONFIGURABLE ZONE TYPE 90
182
✱
ZONE TYPE 90 REPORT CODES
183
IMPORTANT:
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
✱
CONFIGURABLE ZONE TYPE 91
184
✱
ZONE TYPE 91 REPORT CODES
185
IMPORTANT:
codes, if appropriate, or define unique codes
in CID code range 750-789. See important
note in installation instructions.
Use existing Contact ID®
Use existing Contact ID®
1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each entry, 1-10, based on the charts provided on the
next page. Each entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
90 ALARM ID: XXX
TROUBLE ID: XXX
1 2 3 4 5 6 7 8 9 10
Enter the appropriate value for each entry, 1-10, based on the charts provided on the
next page. Each entry is the sum of the values of its selected options
(0-9, #+10=10, #+11=11, #+12=12, #+13=13, #+14=14, #+15=15).
UL: Do not configure zones as a fire alarm or UL burglar alarm zone.
91 ALARM ID: XXX
TROUBLE ID: XXX
0 = disable; 1 = Clean Me signal reports;
Note:
If Clean Me is enabled, you must enter “3” in
field ✱56 programming for zone 1 response time.
0 = 15 seconds 6 = 2-1/2 min #+11 = 7 min
1 = 30 seconds 7 = 3 min #+12 = 8 min
2 = 45 seconds 8 = 4 min #+13 = 10 min
3 = 60 seconds 9 = 5 min #+14 = 12 min
4 = 90 seconds #+10 = 6 min #+15 = 15 min
5 = 2 minutes
0 = 60 Hz; 1 = 50 Hz
Enter the desired 3-digit Contact ID® report codes for
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [∗]
moves forward. Press [∗] when done to continue.
Enter the desired 3-digit Contact ID® report codes for
alarms and troubles occurring on zones assigned to
this zone type. Enter the codes sequentially (all 6
digits). When entering digits, [#] moves cursor back, [∗]
moves forward. Press [∗] when done to continue.
TOUCH SCREEN DEVICE (AUI) ENABLE
✱
AUI DEVICE 1 and 2 ENABLE
189
(for Touch Screen style keypads)
KEYPAD OPTIONS *190-*196 (NOTE
NOTE:
✱
190
NOTE:
System supports up to two touch
screen style keypads (e.g. Symphony
Advanced User Interface, and 6270 Touch
Screen keypad).
: Options for keypad address 16 are set by the factory and cannot be changed.)
Each keypad must be assigned a unique address. Keypads programmed with the same address will give unpredictable results.
KEYPAD 2 DEVICE ADDRESS 17
✱
KEYPAD 3 DEVICE ADDRESS 18
191
✱
KEYPAD 4 DEVICE ADDRESS 19
192
✱
KEYPAD 5 DEVICE ADDRESS 20
193
✱
KEYPAD 6 DEVICE ADDRESS 21
194
✱
KEYPAD 7 DEVICE ADDRESS 22
195
✱
KEYPAD 8 DEVICE ADDRESS 23
196
✱
EXIT TIME DISPLAY INTERVAL
197
✱
DISPLAY PARTITION NUMBER
198
(FA168CPS; for Alpha Display Keypads)
✱
ECP FAIL DISPLAY
199
[1] [1]
AUI 1 AUI 2
AUI 1: Must set AUI address to 1
AUI 2: Must set AUI address to 2
(see Inst. Instr. for details)
Enter each touch screen (AUI) device’s home partition.
0 = disabled
1 = partition 1; 2 = partition 2; 3 = partition 3 (common)
A minimum of one standard keypad must also be
NOTE:
installed when AUI is used. Use of AUI does not affect
the number of standard keypads supported.
Partition: 0 = keypad disabled; 1-3 = part. no. (3 = com)
Sound: 0 = no suppression
1 = suppress arm/disarm and E/E beeps
2 = Suppress chime beeps only
3 = suppress arm/disarm, E/E, and chime
beeps
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
See field ∗190 for entries.
0 = no display; 1-5 = seconds between display refresh
If enabled and using only 2-digit fixed-word
NOTE:
keypads (e.g., FA245RF), do not set exit delay time
greater than 96 seconds. See Inst. Instr. for explanation.
0 = no; 1 = yes (partition no. appears on Alpha Display)
Configurable zone types 90 and 91 can be programmed via downloader software or from a keypad using data
fields*182-*185. Configurable zone types 92 and 93 (FA168CPS only) can only be programmed using the
downloader software.
Programming Configurable Zone Type options involves making 10 entries in data field *182 for zone type 90 and
field *184 for zone type 91, where each entry represents the sum of the values of the various options shown in the
tables below. Use fields *183 and *185 to program Contact ID report codes for these zone types.
ENTRY 1
ENTRY 2
(See note 5 for RF zones)
Response when system disarmed and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone
(See note 5 for RF zones)
ENTRY 3
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
ENTRY 4
Response when armed STAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 3 = EOL + Open Entry 4 = Short + byp. disarmed + byp. armed
ENTRY 5
(See note 5 for RF zones)
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
ENTRY 6
Response when armed AWAY and zone is:
Intact EOL
RF zone normal
0 = normal
1 = alarm
2 = trouble
3 = fault
Entry 5 = EOL + Open Entry 6 = Short + dial delay + fault delay
ENTRY 7
Open
RF zone N/A
0 = normal
4 = alarm
8 = trouble
12 = fault
Shorted
RF zn off-normal
0 = normal
1 = alarm
2 = trouble
3 = fault
ENTRY 8
Display Faults Power Reset/
Verification
0 = show alarms
when armed
& disarmed
1 = don’t show
alarms when
(show
armed
alarms, trbles,
faults when
disarmed)
0 = no
4 = power reset
after fault
(by code + OFF)
12 = verification
(see zone
type 16)
0 = no
1 = delay 1
2 = delay 2
(See note 5 for RF zones)
(See note 5 for RF zones)
(See note 5 for RF zones)
Use Entry
Delay 1/2
Auto
Restore
0 = no
4 = yes
Byp. when
disarmed
0 = no
4 = yes
Dial Delay
(see field *50)
0 = no
4 = use delay
Use Exit
Delay
0 = no
4 = use exit
delay
Vent Zone
0 = no
8 = yes
Byp. when
armed
0 = no
8 = yes
Fault Delay
(see field *87)
0 = no
8 = use delay
see note 1
Respond as
Interior Type
0 = no
8 = yes
see note 2
3 = never show
any alarms,
trbles, faults
Entry 7 = fault display + power
reset/verification
ENTRY 9
Alarm Sounds Use Bell
Timeout
0 = none
1 = steady
keypad
2 = steady bell
and keypad
0 = no
4 = yes
see fields *32,
*33
Entry 8 = entry delay 1/entry delay 2 + exit delay +
interior zone type
Chime when
Chime Mode On
0 = no
4 = yes
Respond as
Fire Zone
0 = no
8 = yes
see zone type
09; see note 4
ENTRY 10
Trouble
Sounds
0 = none
1 = periodic
beep
2 = trouble
beeps
3 = pulsing bell
and keypad
Entry 9 = alarm sounds + bell timeout + fire zone Entry 10 = trouble sounds + chime
– 8 –
Entries for Fields *182 and *184
Entry Zone Type 90 Zone Type 91
(field *182) (field *184)
1
2
3
4
5
6
7
8
9
10
To calculate the value for each entry:
Simply add the values of the selected options
in each of the entry’s columns (one option per
column). For example, to program Entry 2 for
“alarm response to short,”“auto restore on,”
but not a “vent zone,” enter 5 (“1” for alarm
short + “4” for auto restore yes + “0” for vent
zone no).
EOL
Zone Conditions Represented
NOTES:
1. Do not use the “fault delay” option with a
configurable zone type if it is set for an
entry or exit delay, otherwise
unpredictable results may occur.
2. To create an interior type zone, select
“respond as interior zone type” (entry 8,
interior type = yes), and set zone
response to “fault” in entries 3-4 to ensure
fault displays; do not set as “normal,” “alarm,” or “trouble.”
3. Do not set fire zones to respond as a
“fault” (entries 1-6), otherwise faults will
not display unless the [∗] key is pressed.
4. 4219/4229 modules must use EOLRs or
unpredictable results may occur.
5. RF Zones: The “open” option in entries 1,
3, and 5 is not applicable for RF zones.
Use the “intact EOL” option for normal RF
zone conditions and “shorted” for offnormal RF zone conditions.
6. a. Zone-Doubling/Double-Balanced: A
short on either zone of a zone-doubled
pair or on a double-balanced zone
causes a tamper condition.
b. For double-balanced zones, this entry
must be “0.”
c. For zone-doubled zones,
of the doubled pair must be assigned
the same response to a short.
OPENSHORTEDINTACT
ZONE-003-V0
in Entries 1-6
both
zones
*56 ZONE PROGRAMMING WORKSHEET
NOTES:
Zone Type: see chart on
page 12;
Report Code: enabled if
any digit entered as 1st
digit;
Hardwire Type (zns 1-8):
0 = EOL 3 = ZD
1 = NC 4 = DB
2 = NO
Input Type:
2 = AW (zones 9-48)
3 = RF (zones 9-48)
4 = UR (zones 9-48)
5 = BR (zones 49-64)
Zones 9-16 not
NOTE:
available if zone
doubling enabled.
Response Time:
0 = 10msec
1 = 350msec
2 = 700msec
3 = 1.2 sec
Reserved Zones
addressable device
91 =
report enable/disable
default zone type =
[05].
Duress report
92 =
enable/disable
Zone Zn Type Part. Report Hardwire
1
2
3
4
5
6
7
8
Zone Zn Type Part. Report Input Type Loop Serial No. Location
(FA148CP supports up to 32 zones: 1-6, 9-34, 49-56) [default shown in brackets]
*57 FUNCTION KEY PROGRAMMING
Option Function A B C D Comments
01 Paging
02 Time Display
03 Arm AWAY
04 Arm STAY
05 Arm NIGHT-STAY
06 Step Arming
07 Device Activation Device:
08 Comm. Test
09 Macro Key 1
10 Macro Key 2
11 Macro Key 3
12 Macro Key 4
00 Emergency Keys:
Personal Emergency
Silent Alarm
Audible Alarm
Fire
Emergency Keys:
zone 95 zone 99 zone 96 paging
A = paired keys [1] / [∗] (zone 95); B = paired keys [∗] / [#] (zone 99); C = paired keys [3] / [#] (zone 96)
n/a
n/a
n/a
n/a
OUTPUT RELAYS/POWERLINE CARRIER (X-10) DEVICES WORKSHEET FOR ∗79, ∗80 and ∗81.
Applicable only if Relays and/or Powerline Carrier Devices are to be used.
∗
79 RELAY/POWERLINE CARRIER (X-10) DEVICE MAPPING (Must program before using *80)
Pos
(1-4)
Unit
No.
Description
OUTPUT TYPE
Relay X10
Output
No.
01
02
03
04
05
06
07
08
✱
81 ZONE LISTS FOR OUTPUT DEVICES
Module
Addr.
Fill in the required data on the worksheet below and follow the procedure in the installation manual as you enter the
data during the displays and prompts that appear in sequence.
Record desired zone numbers below, noting that a list may include
NOTE:
List No. Used For…Contains These Zones…
01
02
03
04
05
06
07
08
09
10
11
12
General Purpose (GP)
General Purpose
Chime-by-Zone or GP
Cross Zones
Night-Stay Zones or GP
General Purpose
General Purpose
General Purpose
Zones activating pager 1
Zones activating pager 2
Zones activating pager 3 (FA168CPS)
Zones activating pager 4 (FA168CPS)
OUTPUT TYPE
Relay X10
Output
Module
No.
09
10
11
12
13
14
15
16
17
18
Addr.
On-Board Trigger 1 norm output =
On-Board Trigger 2 norm output =
(09-16 apply to FA168CPS only)
Pos
(1-4)
any
Unit
No.
or
of system's zone numbers.
all
Description
– 10 –
✱
80 OUTPUT DEFINITIONS
Fill in the required data on the worksheet below and follow the programming procedure in the installation manual as you
enter the data during the displays and prompts that appear in sequence.
1. For Relays, 4229 and 4204 devices are programmed in *79, *80, and *81 modes.
Notes:
2. For Powerline Carrier devices (plcd), field
✱
27 must be programmed with a House Code.
3. Tampers of expansion units cannot be used to operate devices.
Function
Number
(FA168CPS:
1-48)
(FA148CP:
1-24)
ZONE TYPE/SYSTEM OPERATION – Choices for Zone Types are:
00 = Not Used 05 = Trouble Day/Alarm Night 10 = Interior w/Delay 24 = Silent Burglary
01 = Entry/Exit#1 06 = 24 Hr Silent 12 = Monitor Zone 77 = Keyswitch
02 = Entry/Exit#2 07 = 24 Hr Audible 14 = Carbon Monoxide 81 = AAV Monitor Zone
03 = Perimeter 08 = 24 Hr Aux 16 = Fire w/Verification 90-91 = Configurable
04 = Interior Follower 09 = Fire 23 = No Alarm Response
Choices for System Operation are:
20 = Arming–Stay 38 = Chime 52 = Kissoff 21 = Arming–Away 39 = Any Fire Alarm 54 = Fire Zone Reset 22 = Disarming (Code + OFF) 40 = Bypassing 58 = Duress
31 = End of Exit Time 41 = **AC Power Failure 60 = AAV Trigger 32 = Start of Entry Time 42 = **System Battery Low 66 = Function key†
33 = Any Burglary Alarm 43 = Communication Failure 67 = Bell Failure
Activated by
0=delete
1=zn list
2=zn type
3=zn no.
Assign to zones that are used for primary entry and exit.
•
Provides entry delay if the control is armed in the Away or Stay modes.
•
No entry delay is provided when the panel is armed in the Instant mode.
•
Entry delay #1 is programmable for each partition.
•
Exit delay begins whenever the control is armed, regardless of the arming mode selected, and is
independently programmable.
•
Assign to zones that are used for entry and exit and require more time than the primary entry/exit point.
•
Provides a secondary entry delay, in same manner as entry delay #1.
•
Entry delay #2 is programmable for each partition.
•
Exit delay is same as described for Type 01.
•
Assign to all sensors or contacts on exterior doors and windows.
•
Provides an instant alarm if the zone is faulted when the panel is armed in the Away, Stay, Instant, or
Maximum modes.
•
Assign to a zone covering an area such as a foyer, lobby, or hallway through which one must pass upon
entry (to and from the keypad).
•
Provides a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first.
Otherwise this zone type gives an instant alarm.
•
Active when the panel is armed in the Away mode.
•
Bypassed automatically when the panel is armed in the Stay or Instant modes.
•
Assign to a zone that contains a foil-protected door or window (such as in a store), or to a zone covering
a sensitive area such as a stock room, drug supply room, etc.
•
Can also be used on a sensor or contact in an area where immediate notification of an entry is desired.
•
Provides an instant alarm if faulted when armed in the Away, Stay, Instant or Maximum (night) modes.
•
During the disarmed state (day), the system will provide a latched trouble sounding from the keypad (and a
central station report, if desired).
•
Usually assigned to a zone containing an emergency button.
•
Sends a report to the central station but provides no keypad display or sounding.
•
Assign to a zone that has an emergency button.
•
Sends a report to the central station, and provides an alarm sound at the keypad, and an audible external
alarm.
•
Assign to a zone containing an emergency button, or to a zone containing monitoring devices such as
water or temperature sensors.
•
Sends a report to the central station and provides an alarm sound at the keypad.
provided.)
•
Provides a fire alarm on short circuit and a trouble condition on open circuit. A fire alarm produces a
pulsing bell output.
•
This zone type is always active and cannot be bypassed.
Note:
•
Provides entry delay (using the programmed entry time), if tripped when the panel is armed in the Away
mode.
•
Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an entry/exit
delay zone was tripped first.
•
Bypassed when the panel is armed in the Stay or Instant modes.
•
Works as a dynamic monitor of a zone fault/trouble. In the case of a short/open, the message, "
24 Hr. Non-Burg. -#XXX
system keypad will display a “check” message indicating the appropriate zone (but keypad beeping does
not occur). Upon restoral of the zone, the message, "
the Central Station.
•
The “check” message will automatically disappear from the keypad dynamically when the zone restores; a
user code + off sequence is not needed to reset the zone.
•
Faults of this zone type are independent of the system, and can exist at the time of arming without
interference.
•
Since this is a “trouble” zone type, do not use this zone type with relays set to activate upon “alarm.”
•
Assigned to any zone with a carbon monoxide detector.
•
The bell output will pulse when this zone type is alarmed.
•
Always active and cannot be bypassed.
•
Provides a fire alarm when zone is shorted, but only after alarm verified.
•
System verifies alarm by resetting zones for 12 seconds after short is detected. A subsequent short circuit
within 90 seconds triggers fire alarm.
•
Provides a trouble response when zone is open.
•
Arms the system in Stay mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User code for button must be assigned.
Hardwired zone 1 should be used with 2-wire smoke detectors; zones 2-8 can be used with 4-wire
smoke detectors; any wireless zone can be used as a fire zone.
" (where XXX is the zone number) will be sent to the Central Station. The
RESTORE-24 Hr. Non-Burg. -#XXX
(No bell output is
ALARM-
" will be sent to
– 12 –
•
Type 21
Arm-Away
Type 22
Disarm
Type 23*
No Alarm Response
Type 24
Silent Burglary
Type 77
Arms the system in Away mode when the zone is activated.
•
Pushbutton units send the user number to the central station when arming or disarming.
•
User code for button must be assigned.
•
Disarms the system when the zone is activated.
•
User code for button must be assigned.
•
Can be used on a zone when an output relay action is desired, but with no accompanying alarm (e.g.,
lobby door access).
•
Usually assigned to all sensors or contacts on exterior doors and windows where bells and/or sirens are
NOT desired.
•
Provides an instant alarm, with NO audible indication at any keypad or external sounder, if the zone is
faulted when the system is armed in the Away, Stay, Instant, or Maximum modes.
•
A report is sent to the central station.
•
Assign to zone wired to a keyswitch.
Keyswitch
•
Type 81
AAV Monitor Zone
Types 90-93
Installer Defined
The system can still be armed when these zone types are in a faulted condition.
*
Schedules
events 00-07 for both controls; FA148CP supports up to 8 schedules, FA168CPS supports up to 32 schedules
(installer code + [#] + [6] [4];
Assign to zone connected to AAV module.
•
Monitors 2-way voice sessions as follows:
- When the zone is faulted, all alarm sounding and dialer reporting stops, except for fire alarms,
which immediately terminate the voice session and cause a fire report to be sent.
- When the zone is restored (session ended), sounding resumes (if bell timeout has not expired)
and reports that were stopped are sent.
•
These zone types can be programmed for various custom responses. See data fields *182-*185.
•
Types 92 and 93 can only be programmed via the downloader.
UL: Zone types 90-93 may not be used as fire or burglar zones in fire or UL burglar alarm installations.
master code can only access schedules 01-16 for FA168CPS, 01-04 for FA148CP, and
)
No. Event Device No. Group No. Partition Start Time/ Stop Time/ Repeat Random
(see list below) for “01” events: for “02” events: for “04-06” events:
enter 01-18 enter 1-8 enter 1, 2, or 3
Events: Master/Installer Installer Only
00 = clear event 04 = forced STAY arm 10 = display custom words 8-10
01 = device on/off 05 = forced AWAY arm 11 = periodic test report
02 = user access 06 = auto disarm 03 = latch key report 07 = display “reminder”
Repeat Options: 0 = none; 1 = repeat weekly; 2 = repeat every other week; 3 = repeat every third week; 4 = repeat every fourth week
Days Days
– 13 –
(1-4) (yes/no)
000
– A –
• 001 AIR
• 002 ALARM ∗
004 ALLEY
005 AMBUSH
• 006 AREA
• 007 APARTMENT
• 009 ATTIC ∗
010 AUDIO
• 012 BABY ∗
• 013 BACK ∗
• 014 BAR
• 016 BASEMENT ∗
• 017 BATHROOM ∗
• 018 BED
• 019 BEDROOM ∗
020 BELL
• 021 BLOWER
• 022 BOILER
023 BOTTOM
025 BREAK
• 026 BUILDING
028 CABINET
• 029 CALL
030 CAMERA
031 CAR
033 CASH
034 CCTV
035 CEILING
036 CELLAR
• 037 CENTRAL
038 CIRCUIT
• 040 CLOSED ∗
• 046 COMPUTER
047 CONTACT
• 048 DAUGHTERS
049 DELAYED
• 050 DEN ∗
051 DESK
• 052 DETECTOR ∗
• 053 DINING
054 DISCRIMINATOR
055 DISPLAY
Note:
Italicized words followed by an asterisk indicate those words supported by the FA560VKP Voice Keypad.
(Word Space)
– B –
– C –
– D –
Bulleted (•) words in
• 057 DOOR ∗
• 059 DOWN
• 060 DOWNSTAIRS
061 DRAWER
• 062 DRIVEWAY
• 064 DUCT
– E –
• 065 EAST
066 ELECTRIC
067 EMERGENCY
068 ENTRY
• 069 EQUIPMENT
• 071 EXIT ∗
072 EXTERIOR
– F –
• 073 FACTORY
075 FAMILY
• 076 FATHERS
• 077 FENCE
• 079 FIRE ∗
• 080 FLOOR ∗
081 FLOW
082 FOIL
• 083 FOYER
084 FREEZER
• 085 FRONT ∗
– G –
• 089 GARAGE ∗
• 090 GAS
091 GATE
• 092 GLASS
093 GUEST
094 GUN
H –
–
• 095 HALL ∗
• 096 HEAT
098 HOLDUP
099 HOUSE
100 INFRARED
• 101 INSIDE ∗
102 INTERIOR
103 INTRUSION
– J –
104 JEWELRY
∗
• 105 KITCHEN
– K –
–
boldface type
• 106 LAUNDRY ∗
• 107 LEFT
108 LEVEL
• 109 LIBRARY ∗
• 110 LIGHT
111 LINE
• 113 LIVING ∗
• 114 LOADING
∗
115 LOCK
116 LOOP
117 LOW
• 118 LOWER
• 119 MACHINE
121 MAIDS
122 MAIN
• 123 MASTER ∗
• 125 MEDICAL ∗
126 MEDICINE
128 MONEY
129 MONITOR
• 130 MOTHERS
• 131 MOTION ∗
132 MOTOR
• 134 NORTH
135 NURSERY
• 136 OFFICE ∗
• 138 OPEN ∗
139 OPENING
• 140 OUTSIDE
142 OVERHEAD
143 PAINTING
• 144 PANIC ∗
145 PASSIVE
• 146 PATIO ∗
147 PERIMETER
• 148 PHONE
150 POINT
151 POLICE
152 POOL
• 153 POWER
∗
155 RADIO
are those that are also available for use by the FA4285/FA4286 Phone Module.
L –
– M –
– N –
– O –
– P –
– R –
• 156 REAR
157 RECREATION
159 REFRIGERATION
160 RF
• 161 RIGHT
• 162 ROOM ∗
163 ROOF
– S –
164 SAFE
165 SCREEN
166 SENSOR
• 167 SERVICE
• 168 SHED ∗
169 SHOCK
• 170 SHOP ∗
171 SHORT
∗
• 173 SIDE ∗
174 SKYLIGHT
175 SLIDING
∗
• 176 SMOKE ∗
• 178 SONS
• 179 SOUTH
180 SPRINKLER
• 182 STATION
184 STORE
• 185 STORAGE ∗
186 STORY
190 SUPERVISED
191 SUPERVISION
192 SWIMMING
193 SWITCH
– T –
194 TAMPER
196 TELCO
197 TELEPHONE
• 199 TEMPERATURE
200 THERMOSTAT
• 201 TOOL
202 TRANSMITTER
– V –
– U –
∗
∗
• 205 UP
• 206 UPPER
• 207 UPSTAIRS ∗
• 208 UTILITY ∗
209 VALVE
210 VAULT
212 VOLTAGE
– W –
213 WALL
214 WAREHOUSE
• 216 WEST
• 217 WINDOW ∗
• 219 WING
220 WIRELESS
– X –
222 XMITTER
– Y –
223 YARD
– Z –
224 ZONE (No.)
• 225 ZONE ∗
• 226 0
• 227 1
• 228 1ST ∗
• 229 2
• 230 2ND ∗
• 231 3
• 232 3RD ∗
• 233 4
• 234 4TH
• 235 5
• 236 5TH
• 237 6
• 238 6TH
∗
• 239 7
• 240 7TH
• 241 8
• 242 8TH
• 243 9
• 244 9TH
245 Custom Word #1
246 Custom Word #2
247 Custom Word #3
248 Custom Word #4
249 Custom Word #5
250 Custom Word #6
251 Custom Word #7
252 Custom Word #8
253 Custom Word #9
254 Custom Word #10
If using a Phone module, and words other than these are selected for Alpha descriptors, the module will not provide
annunciation of those words.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors)
86 V
87 W
88 X
89 Y
90 Z
– 14 –
5800 Series Transmitter Input Loop Identification
All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes.
inputs requires its own programming zone
(e.g., a 5804's four inputs require four programming zones).
WIRELESS INPUT TYPES
"RF" (Supervised RF) Type
send periodic check-in
signals, as well as fault, restore and low battery signals.
The transmitter must remain within the receiver's range.
“UR" (Unsupervised RF) Type
send all the signals that
the "RF" Type does, but the control does not supervise
the check-in signals. The transmitter may, therefore, be
carried off-premises.
"BR" (Unsupervised Button RF) Type
only send fault
signals. They do not send restore or check-in signals.
They will indicate a low battery condition when tested or
activated normally. They can be carried off-premises.
: For information on any transmitter not shown
Note
above, refer to the instructions accompanying that
transmitter for details regarding loop numbers, etc.
:
UL NOTE
use in UL installations: 5802MN, 5802MN2, 5804, 5804BD,
5814, 5816TEMP, 5819, 5819WHS & BRS, and 5850.
The 5827BD and 5800TM can be used in UL Listed
Residential Burglar installations.
The following transmitters are not intended for
ENROLL AS "UR" OR "RF"
YOU MUST
ENROLL THIS
BUTTON
LOOP 4
5804
ENROLL
AS "BR"
ENROLL AS "RF"
ENROLL AS "RF"
LOOP 3
LOOP 2
LOOP 1
LOOP 4
YOU MUST
ENROLL THIS
BUTTON
5801
LOOP 3
LOOP 2
LOOP 1
LOOP 3
LOOP
1
5809
LOOP
1
5808
5802MN
ENROLL AS "UR" OR "RF"
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
5804BD
ENROLL AS "BR"
5816
ENROLL AS "RF"
ENROLL THIS
(TERMINALS)
LOOP 2
YOU MUST
BUTTON
LOOP 4
LOOP 1
SET
HOUSE
CODE
LOOP
2
(REED)
LOOP 1
LOOP
1
LOOP
2
(REED)
ALTERNATE
POSITION
FOR LOOP2
LOOP
2
(REED)
LOOP 3
(TERMINALS)
ENROLL AS "RF"
5819
ENROLL AS "RF"
5827
SET HOUSE CODE
5850 (GBD)
ENROLL AS "RF"
(TERMINALS)
5816MN
(TERMINALS)
LOOP 2
(REED)
LOOP 1
LOOP 1
(Green)
(Red)
(Yellow)
(TERMINALS)
Each of the
5817
ENROLL AS "RF"
LOOP
2
(REED)
LOOP 3
5819S (WHS & BRS)
ENROLL AS "RF"
5827BD
SET HOUSE CODE
5890
ENROLL AS "RF"
LOOP
1
(PRIMARY)
2
(AUX. CENTER)
3
(AUX. RIGHT)
LOOP 1
(INTERNAL
SHOCK
SENSOR)
LOOP
1
(MOTION)
Wireless Key Predefined Default Templates
For 5804
Loop Function Zone Type
TEMPLATE 1 1 No Response 23 TEMPLATE 4 1 No Response 23
2 Disarm 22 2 No Response 23
3 Arm Away 21 3 Arm Away 21
4 No Response 23 4 Disarm 22
TEMPLATE 2 1 No Response 23 TEMPLATE 5 1 No Response 23
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
TEMPLATE 3 1 24-hour audible 7 TEMPLATE 6 1 24-hour audible 7
2 Disarm 22 2 Arm Stay 20
3 Arm Away 21 3 Arm Away 21
4 Arm Stay 20 4 Disarm 22
For 5804BD
Loop Function Zone Type
Table of Device Addresses
This Device
RF Receiver
AUI 1
AUI 2
Long Range Radio
FA4286 Voice Module
Zone Expanders (4219/4229):
module 1 (for zones 09 - 16)
module 2 (for zones 17 - 24)
module 3 (for zones 25 - 32)
module 4 zones 33 - 40
module 5 zones 41 - 48
** These module addresses apply to FA168CPS only.
†† Addressable devices are identified by “1” plus the device address when reporting. Enter report code for zone 91 to enable addressable device
reporting (default = reports enabled). See field *199 for addressable device (ECP) 3-digit/2-digit identification keypad display options.
Uses Address
00
01
02
03
04
07
08
09**
10**
11**
12
13
14**
15**
16
17
18
19
20
21
22
23
28
Reports as
100
101
102
103
104
107
108
109
110
111
112
113
114
115
†† Enabled By…
*56 zone programming: input device type entry
automatic if AUI enable field *189 enabled for AUI 1
automatic if AUI enable field *189 enabled for AUI 2
automatic if output to long range radio field *29 enabled
automatic if phone module access code field *28 enabled
*56 zone programming: input device type entry, then:
automatic if zone no. 9-16 entered as AW type or relay assigned
automatic if zone no. 17-24 entered as AW type or relay assigned
automatic if zone no. 25-32 entered as AW type or relay assigned
automatic if zone no. 33-40 entered as AW type or relay assigned
automatic if zone no. 41-48 entered as AW type or relay assigned
entered at device address prompt
entered at device address prompt
entered at device address prompt
entered at device address prompt
always enabled, all sounds enabled.
data field *190
data field *191
data field *192
data field *193
data field *194
data field *195
data field *196
– 15 –
EOL
POWER
SUPERVISION
RELAY MODULE
RED
+
N.O.
_
BLK
4-WIRE SMOKE DETECTOR CONNECTIONS
N.C.
RELAY
5
4
AS ZONE TYPE 54
PROGRAM RELAY
_
+
4219
8-PIN CONNECTOR
USED FOR 4300/1321X10
BATTERY FUSE
CONTACT OPENS MOMENTARILY
(FIRE ZONE RESET)
OR
OUTPUT
AUX PWR
TERMINALS
SET UNIT’S
DIP SWITCH
FOR DEVICE
ADDRESSES
7 - 15
SEE
-OR-
4229
OUTPUT RELAYS)
WIRED EXPANSION MODULE
(8 ADD'L EOLR WIRED ZONES)
WIRED EXPANSION/RELAY MODULE
(8 ADD'L EOLR WIRED ZONES PLUS 2
BLK
RED
CABLE)
(USE SA4120XM-1
78
TRANSFORMER
SEE INSTRUCTIONS.
ON-BOARD TRIGGERS
CONNECTIONS AND FOR
1234 5 6
FOR REPLACEMENT,
USE SAME VALUE
(e.g. ADEMCO No. 90-12)
3A
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
VIOLET
2000
OHMS
EOLR
_
+
DETECTOR
4-WIRE SMOKE
OR COMBUSTION
TO OUTPUT 17
UPON FIRE ALARM RESET
(UP TO 16 DETECTORS
MAX. CURRENT = 100 mA
"OUT NORM LOW" = YES IN
PROGRAM OUTPUT 17 FOR
TYPE 54 IN 80 MENU MODE
79 MENU MODE AND AS ZONE
INSTRUCTIONS.
SET
RECEIVER’S
DIP SWITCH
FOR DEVICE
-OR-
AND/OR
5881* Type
RF RECEIVER
WIRELESS ZONES
(4 OUTPUT RELAYS)
4204 RELAY MODULE
GRN
YEL
BLK
OPTIONAL
TO
TRANS.
COM
DATA
SYNC
TO TERM 4
(TRIG. 2)
GND
+12 AUX
(TRIG. 1)
FLYING LEADS
FOR BATTERY
CONNECTION
+
BLACK
RED
+
HEAT
DETECTOR
+
_
PLUS EOL MODULE)
TO ZONE TERM. ( )
TO ZONE TERM. ( )
ADDRESS
OF “0”.
SEE
INSTRUCTIONS.
*5882 IN CANADA
5881L: UP TO 8
5881H: UP TO 64
5881M: UP TO 16
RED
GRN
YEL
( FROM EITHER OR BOTH GROUPS)
FOR UP TO 40 ADDITIONAL ZONES
BLK
YEL
RED
GRN
TO TERM 5
TO TERM 6
TO TERM 7
OUTPUT 18
OUTPUT 17
RED JUMPER
CUT FOR BELL SUPERVISION.
ALSO, CONNECT 2000 OHM
RESISTOR DIRECTLY ACROSS
SOUNDER.
EARTH
GROUND
SEE
INSTRUCTIONS
FOR PROPER
GROUNDING
RING
(RED)
}
INCOMING
TIP
PHONE LINE
(GREEN)
RING
(GRAY)
TIP
(BROWN)
HI
20
LO
19
LO
HI
18
HI
17
LO
16
LO
HI
15
HI
14
LO
13
LO
HI
12
HI
11
LO
}
HANDSET
CONNECT CORD)
*CA38A IN CANADA
TELEPHONE WIRING
(VIA RJ31X* JACK AND DIRECT
10
LO
89
HI
▲
▲
654
+
}
AUX. POWER
OUTPUT
+
)
-
) RETURN
FOR UL
600mA MAX.
(500mA MAX.
10.5-13.8VDC
INSTALLATIONS)
TO PREVENT RISK OF SHOCK,
DOC LOAD NO.: 3
WARNING:
DISCONNECT TELEPHONE LINE AT TELCO
FOR CONNECTION OF OPTIONAL FA4285 OR FA4286 VIP
MODULES TO PHONE TERMINALS, SEE INSTRUCTIONS.
FA168CPS ONLY
ZONE 8
2000
EOLR
OHMS
ZONE 7
2000
EOLR
OHMS
ZONE 6
2000
EOLR
OHMS
ZONE 5
2000
EOLR
OHMS
ZONE 4
2000
EOLR
OHMS
ZONE 3
2000
EOLR
OHMS
ZONE 2
2000
EOLR
OHMS
ZONE 1
2000
EOLR
OHMS
YELLOW: KEYPAD DATA OUT
GREEN: DATA IN FROM KEYPAD
RED: KEYPAD PWR (
BLACK: KEYPAD GROUND (
ALL OUTPUTS
ARE POWER
LIMITED.
NOTE:
KEYPAD (S)
CURRENT (IN
COMPLIES WITH FCC RULES, PART 68.
FCC REGISTRATION NO. 5GBUSA-44003-AL-E
RINGER EQUIVALENCE: 0.1B.
THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES.
OPERATION IS SUBJECT TO THE FOLLOWING TWO
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY
INTERFERENCE RECEIVED, INCLUDING INTERFERENCE
POWER SHUTDOWN NOTE:
ZONE
PAIRS
2k
TAMPER
CONTACTS
2k
DEVICES
(e.g. 5800TM,
4285/4286, LRR,
POWER FROM
TERMS 4 & 5
SYSTEM SHUTS DOWN SENSOR
DETECTION PROCESSING IF
CONTROL'S VOLTAGE DROPS
2 / 10
3 / 11
4 / 12
5 / 13
ZONE 2
1011
TAMPER
4219, 4229,
4204, 5881)
MUST BE
INCLUDED IN
AUX CURRENT
THAT MAY CAUSE UNDESIRED OPERATION.
BELOW 9.6V.
6 / 14
3k
2k
CONTACTS
2k
REMOTE KEYPADS
DRAIN
7 / 15
CAN USE FA215KP, FA260KP,
CALCULATIONS.
WEEKLY TESTING IS REQUIRED TO ENSURE PROPER OPERATION OF THIS
8 / 16
FA260RF, OR FA560KP
JACK BEFORE SERVICING THIS UNIT.
MAXIMUM LOOP RESISTANCE: (EACH ZONE) 300 OHMS (PLUS EOLR)
RESPONSE, ZONES 1-8: 10, 350, OR 700 MSEC (PROGRAMMABLE)
MAXIMUM NUMBER OF 2-WIRE SMOKE DETECTORS ON ZONE 1 IS 16;
DETECTORS MUST HAVE COMPATIBILITY IDENTIFIER AS "A".
•
•
•
131214
CAN BE USED FOR 2-WIRE SMOKE DETECTORS
REMOTE
KEYPADS
AND OTHER
ADDRESSABLE
BOTH
PARTITIONS)
AND ALL
OTHER DEVICES
DRAWING
SYSTEM. IN ADDITION, THIS SYSTEM MUST BE CHECKED BY A QUALIFIED