GARAGE
S
UGGESTED AREAS FOR INSTALLING ADDITIONAL CO ALARMS
BEDROOM
BEDROOM
HALL
LIVING ROOM
KITCHEN
B
ASEMENT
BEDROOM
REQUIRED TO MEET NFPA RECOMMENDATIONS
EGULAR MAINTENANCE
R
This unit has been designed to be as maintenance-free as possible, but there
re a few simple things you must do to keep it working properly.
a
se only the replacement batteries listed below. The unit may not
U
operate properly with other batteries. Never use rechargeable batteries
since they may not provide a constant charge.
Test it at least once a week.
•
• Clean the CO Alarm at least once a month; gently vacuum the outside
f the CO Alarm using your household vacuum’s soft brush attachment.
o
can of clean compressed air (sold at computer or office supply stores)
A
may also be used. Follow manufacturer instructions for use. Test the CO
larm. Never use water, cleaners or solvents since they may damage the
A
nit.
u
If the CO Alarm becomes contaminated by excessive dirt, dust and/or
•
rime, and cannot be cleaned to avoid unwanted alarms, replace the unit
g
immediately.
Relocate the unit if it sounds frequent unwanted alarms. See “Where CO
•
larms Should Not Be Installed” for details.
A
hoosing a replacement battery:
C
our CO Alarm requires two standard AA batteries. The following batteries are
Y
acceptable as replacements: Energizer E91.
any local retail stores.
m
ctual battery service life depends on the CO Alarm and the environment in
A
which it is installed. All the batteries specified above are acceptable replace-
ent batteries for this unit. Regardless of the manufacturer’s suggested
m
attery life, you MUST replace the battery immediately once the unit starts
b
“chirping” (the “low battery warning”).
To replace the batteries (without removing Alarm from the ceiling or wall):
. Open the battery compartment.
1
2. Press tabs A and B as shown in the
diagram and remove each battery.
. Insert the new batteries, making sure
3
hey snap completely into the battery
t
compartment. Match the terminals on
he ends of the batteries with the
t
erminals on the unit.
t
4. Close the battery compartment, and
hen test the unit by pressing the
t
st/Silence button.
e
T
These batteries are available at
WHAT YOU NEED TO KNOW ABOUT CO
WHAT IS CO?
O is an invisible, odorless, tasteless gas produced when fossil fuels do not
C
burn completely, or are exposed to heat (usually fire). Electrical appliances
typically do not produce CO.
These fuels include: Wood, coal, charcoal, oil, natural gas, gasoline,
erosene, and propane.
k
ommon appliances are often sources of CO. If they are not properly main-
C
ained, are improperly ventilated, or malfunction, CO levels can rise quickly.
t
O is a real danger now that homes are more energy efficient. “Air-tight”
C
omes with added insulation, sealed windows, and other weatherproofing
h
an “trap” CO inside.
c
SYMPTOMS OF CO POISONING
These symptoms are related to CO POISONING and should be discussed
ith ALL household members.
w
ild Exposure:Slight headache, nausea, vomiting, fatigue (“flu-like”
M
ymptoms).
s
edium Exposure:Throbbing headache, drowsiness, confusion, fast heart
M
ate.
r
me Exposure:
xtre
E
Exposure to Carbon Monoxide can cause brain damage, death.
ome individuals are more sensitive to CO than others, including people
S
ith cardiac or respiratory problems, infants, unborn babies, pregnant
w
others, or elderly people can be more
m
O. Members of sensitive populations should consult their doctors for
C
dvice on taking additional precautions.
a
onvulsions, unconsciousness, heart and lung failure
C
quickly and severe
ly affected by
FINDING THE SOURCE OF CO AFTER AN ALARM
Carbon monoxide is an odorless, invisible gas, which often makes it difficult
o locate the sourc
t
can make it difficult to locate sources of CO:
• House well ventilated before the investigator arrives.
Pro
•
ansient CO pro
Tr
•
ecause CO may dissipate by the time an investigator arrives, it may be
B
ifficult to locate the source of CO.
d
to pay for any carbon monoxide investigation or ser
e of CO after an alarm. These are
blem caused by “backdrafting.”
blem caused by special circ
RK Brands, Inc. shall not be obligated
B
a few of the factors that
umstances.
vice call.
POTENTIAL SOURCES OF CO IN THE HOME
d to r
n
ecr
ning appliances like:
Fuel-bur
gas kitchen range or cooktop, gas clothes dryer.
Damaged or insufficient venting: corroded or disconnected water heater
vent pipe, leaking chimney pipe or flue, or cracked heat exchanger, blocked
or clogged chimney opening.
Improper use of appliance/ device: operating a barbecue grill or vehicle in
an enclosed area (like a garage or screened por
Transient CO Problems: “transient” or on-again-off-again CO problems can
be caused by outdoor conditions and other special circumstances.
The following conditions can result in transient CO situations:
1. Excessive spillage or reverse venting of fuel appliances caused by outdoor
conditions such as:
Wind direction and/or velocity, including high, gusty winds. Heavy air in
•
the vent pipes (cold/humid air with extended periods between cycles).
• Negative pressure differential resulting from the use of exhaust fans.
Several appliances running at the same time competing for limited
•
fresh air.
ent pipe connections vibrating loose from clothes dryers, furnaces,
V
•
or water heaters.
• Obstructions in or unconventional vent pipe designs which can amplify
the above situations.
2. Extended operation of unvented fuel burning devices (range, oven,
fireplace).
3. Temperature inversions, which can trap exhaust close to the ground.
Car idling in an open or closed attached garage, or near a home.
4.
These conditions are dangerous because they can trap exhaust in your home.
Since these conditions can come and go, they ar
a CO investigation.
portable heater
, gas or wood bur
ch).
e also har
5 6 7
place,
ing fire
eate during
.
EGULATORY INFORMATION FOR CO ALARMS, Continued
OW CAN I PROTECT MY FAMILY FROM
H
O POISONING?
C
CO Alarm is an excellent means of protection. It monitors the air and sounds
A
loud alarm before Carbon Monoxide levels become threatening for average,
a
healthy adults.
CO Alarm is not a substitute for proper maintenance of home
A
ppliances.
a
To help prevent CO problems and reduce the risk of CO poisoning:
• Clean chimneys and flues yearly. Keep them free of debris, leaves, and
ests for proper air flow. Also, have a professional check for rust and
n
orrosion, cracks, or separations. These conditions can prevent proper
c
air movement and cause backdrafting. Never “cap” or cover a chimney
n any way that would block air flow.
i
Test and maintain all fuel-burning equipment annually. Many local gas
•
or oil companies and HVAC companies offer appliance inspections for
nominal fee.
a
Make regular visual inspections of all fuel-burning appliances. Check
•
appliances for excessive rust and scaling. Also check the flame on the
urner and pilot lights. The flame should be blue. A yellow flame means
b
uel is not being burned completely and CO may be present. Keep the
f
blower door on the furnace closed. Use vents or fans when they are
vailable on all fuel-burning appliances. Make sure appliances are
a
ented to the outside. Do not grill or barbecue indoors, or in garages
v
or on screen porches.
Check for exhaust backflow from CO sources. Check the draft hood on
•
an operating furnace for a backdraft. Look for cracks on furnace heat
exchangers.
Check the house or garage on the other side of shared wall.
•
• Keep windows and doors open slightly. If you suspect that CO is
scaping into your home, open a window or a door. Opening windows
e
nd doors can significantly decrease CO levels.
a
In addition, familiarize yourself with all enclosed materials. Read this
anual in its entirety, and make sure you understand what to do if your
m
CO Alarm sounds.
EGULATORY INFORMATION FOR CO ALARMS
R
UNDERWRITERS LABORATORIES INC. UL2034
HAT LEVELS OF CO CAUSE AN ALARM?
W
Underwriters Laboratories Inc. Standard UL2034 requires residential CO
larms to sound when exposed to levels of CO and exposure times as
A
described below. They are measured in parts per million (ppm) of CO over
ime (in minutes).
t
L2034 Required Alarm Points*:
U
• If the alarm is exposed to 400 ppm of CO, IT MUST ALARM BETWEEN
4 and 15 MINUTES.
• If the alarm is exposed to 150 ppm of CO, IT MUST ALARM BETWEEN
10 and 50 MINUTES.
If the alarm is exposed to 70 ppm of CO, IT MUST ALARM BETWEEN
•
60 and 240 MINUTES.
pproximately 10% COHb exposure at levels of 10% to 95% Relative
* A
umidity (RH).
H
he unit is designed not to alarm when exposed to a constant level of
T
30 ppm for 30 days.
CO Alarms are designed to alarm before there is an immediate life threat.
ince you cannot see or smell CO, never assume it’s
S
An exposure to 100 ppm of CO for 20 minutes may not affect average,
•
ealthy adults, but after 4 hours the same level may cause headaches.
h
An exposure to 400 ppm of CO may cause headaches in average, healthy
•
dults after 35 minutes, but can cause death after 2 hours.
a
This CO Alarm measures exposure to CO over time. It alarms if CO levels
re extremely high in a short period of time, or if CO levels reach a certain
a
inimum over a long period of time. The CO Alarm generally sounds an
m
alarm before the onset of symptoms in average, healthy adults.
Why is this important? Because you need to be war
roblem while you can still react in time. In many reported cases of CO
p
, victims may be aware
xposure
e
disoriented and can no longer react well enough to exit the building or get
elp. Also, young children and pets may be the first affected. The average
h
ealthy adult might not feel any symptoms when the CO Alarm sounds.
h
However, people with cardiac or respiratory problems, infants, unborn babies,
regnant mothers, or elderly people can be more quickly and severely affected
p
y CO. If you experience even mild symptoms of CO poisoning, consult your
b
doctor immediately!
f the Alarm... Problem... You should...
I
n "chirps" about once per minute.
Hor
orn sounds three "chirps" every minute;
H
LED has 3 flashes with "chirps".
The light flashes (RED) and the horn sounds 5
chirps” every minute;
“
oice:"Detector error in [Location, example
V
"Basement"], please see manual" r
ours.
h
The Alarms are linked but do not communicate with
ach other.
e
O Alarm goes back into alarm 4 minutes after you
C
Silence it.
CO Alarm sounds fr
evels of CO are
l
or a list of acceptable replacement batteries, see “Regular Maintenance.”
*F
f you have questions that cannot be answere
I
equently even though no high
vealed in an investigation.
re
that they are not feeling well, but become
epeated every 5
not present.
ed of a potential CO
n
ROUBLESHOOTING GUIDE
T
ing. Install two new AA batteries
Low battery war
ALFUNCTION SIGNAL. Device is not working
M
operly
pr
END OF LIFE SIGNAL. CO Alarm needs to be
eplaced.
r
Possible interference. Reference the Wireless
peration section of this manual.
O
O levels indicate a potentially dangerous
C
situation.
The CO Alarm may be impr
Where
“
d by reading this manual, call Consumer Affairs at 1-800-323-9005, M-F 7:30 a.m. to 5:00 p.m. (CST)
n
, and needs to be r
to Install CO Alarms” for details.
R
Standards: Underwriters Laboratories Inc. Single and Multiple Station carbon
onoxide alarms UL2034.
m
According to Underwriters Laboratories Inc. UL2034, Section 1-1.2: “Carbon
onoxide alarms covered by these requirements are intended to respond to
m
he presence of carbon monoxide from sources such as, but not limited to,
t
exhaust from internal-combustion engines, abnormal operation of fuel-fired
ppliances, and fireplaces. CO Alarms are intended to alarm at carbon
a
onoxide levels below those that could cause a loss of ability to react to the
m
dangers of Carbon Monoxide exposure.” This CO Alarm monitors the air at
he Alarm, and is designed to alarm before CO levels become life threatening.
t
his allows you precious time to leave the house and correct the problem.
T
This is only possible if Alarms are located, installed, and maintained as
escribed in this manual.
d
Gas Detection at Typical Temperature and Humidity Ranges: The CO
larm is not formulated to detect CO levels below 30 ppm typically. UL tested
A
or false alarm resistance to Methane (500 ppm), Butane (300 ppm), Heptane
f
(500 ppm), Ethyl Acetate (200 ppm), Isopropyl Alcohol (200 ppm) and Carbon
Dioxide (5000 ppm). Values measure gas and vapor concentrations in parts
er million.
p
udible Alarm:85 dB minimum at 10 feet (3 meters).
A
GENERAL LIMITATIONS OF CO ALARMS
his CO Alarm is intended for residential use. It is not intended for use
T
in industrial applications where Occupational Safety and Health
Administration (OSHA) requirements for carbon monoxide detectors
ust be met.
m
CO alarms may not waken all individuals.
aken to the sound of the CO alarm, or if there are infants or family members
w
ith mobility limitations, make sure that someone is assigned to assist them
w
in the event of an emergency.
O Alarms will not work without power.This alarm requires a two (2) AA
C
batteries to operate.
O Alarms for Solar or Wind Energy users and battery backup power
C
ystems:
s
sine wave inverters. Operating this Alarm with most battery-powered UPS
uninterruptible power supply) products or square wave or “quasi sine wave”
(
nverters
i
UPS type, please consult with the manufacturer to verify.
his CO Alarm will not sense carbon monoxide that does not reach the
T
sensor.
in other areas. Doors or other obstructions may affect the rate at which CO
eaches the CO Alarm. For this reason, if bedroom doors are usually closed
r
at night, we recommend you install a CO Alarm in each bedroom and in the
hallway between them.
CO Alarms may not sense CO on another level of the home. For example,
CO Alarm on the second level, near the bedrooms, may not sense CO in the
a
asement. For this reason, one CO Alarm may not give adequate warning.
b
Complete coverage is recommended. Place CO Alarms on each level of the
ome.
h
O Alarms may not be heard.The alarm horn loudness meets or exceeds
C
urrent UL standards of 85 dB at 10 feet (3 meters). However, if the CO Alarm
c
s installed outside the bedroom, it may not wake up a sound sleeper or one
i
ho has recently used drugs or has been drinking alcoholic beverages. This
w
s especially true if the door is closed or only partly open. Even persons who
i
re awake may not hear the alarm horn if the sound is blocked by distance or
a
losed doors. Noise from traffic, stereo, radio, television, air conditioner, or
c
ther appliances may also prevent alert persons fr
o
his CO Alarm is not intended for people who are hearing impaired.
T
O Alarm
C
ourc
s
O Alarm senses CO that may be escaping unnoticed from malfunctioning
C
urnaces, appliances, or other sources. Early warning of fire requires the
f
installation of smoke alarms.
O Alarms are not a substitute for life insurance.Though these CO Alarms
C
arn against increasing CO levels, BRK Brands, Inc. does not warrant or
w
mply in any way that they will protect lives from CO poisoning. Homeowners
i
nd re
a
CO Alarms have a limited life. Although the CO Alarm and all of its parts
have passed many stringent tests and ar
ossible, any of these parts could fail at any time. Therefore, you must test
p
your CO Alarm weekly.
O Alarms are not foolproof.Like all other electronic devices, CO Alarms
C
ave limitations. They can only detect CO that r
h
ay not give early warn
m
emote part of the home, away from the CO Alarm.
r
placed.
e
operly located. Refer to
C powered CO Alarms should only be operated with true or pure
A
ill damage the Alarm.If you are not sure about your inverter or
w
This CO Alarm will only sense CO at the sensor. CO may be present
not a substitute for a smoke alarm.
s are
e of carbon monoxide, this CO Alarm does not sense smoke or fire. This
nters must still insure their lives.
ing to rising CO levels if the CO is coming fro
nits under warranty should be returned to
U
manufactur
rranty” for details.
a
W
Immediately replace the CO Alarm.
Move Alarms to different locations. Add an additional
larm between the unresponsive Alarms to route the
A
ignal aro
s
F YOU ARE FEELING SYMPTOMS OF CO
I
POISONING, EVACUATE your home and call 911
r the Fire Department. Refer to "If The CO Alarm
o
ounds" for details.
S
Relocate your Alarm. If fr
ave home re
h
You may be experiencing an intermittent CO problem.
LIMITED WARRANTY
BRK Brands, Inc., ("BRK") the maker of First Alert®brand products warrants
that for a period of seven years from the date of purchase, this pr
be free from defects in material and workmanship. BRK, at its option, will
repair or replace this product or any component of the product found to be
defective during the warranty period. Replacement will be made with a new or
emanufactur
r
replacement may be made with a similar product of equal or greater value.
This is your exclusive warranty.
This warranty is valid for the original retail pur
etail purchase and is not transferable. Keep the original sales receipt. Proof
r
of purchase is required to obtain warranty performance. BRK dealers, service
centers, or retail stores selling BRK products do not have the right to alter,
modify or any way change the terms and conditions of this warranty.
This warranty does not cover normal wear of parts or damage r
any of the following: negligent use or misuse of the pr
voltage or current, use contrary to the operating instructions, disassembly,
epair or alteration by anyone other than BRK or an authorized service center.
r
Further
hurricanes and tornadoes or any batteries that are included with this unit.
For your records, please record:
Date Purchased: _______________________________
Where Purchased: ____________________________________________
Date Installed: ____________/____________Month/Year
Replace alarm 7 years after installation. Please write the date in the
space provided:
The alarm will also provide an audible End-of-Life Signal approximately
7 years after installation to r
The End-of-Life Signal can be silenced for up to 2 days. Do not unplug
the alarm or remove the batteries until you get replacement.
First Alert®is a registered trademark of the First Alert Trust used under license.
ONELINK
ed product or component. If the product is no longer available,
chaser from the date of initial
oduct, use on impr
, the warranty does not cover Acts of God, such as fir
_____________/____________Month/Year
emind you to r
®
is a trademark of BRK Brands, Inc.
eplace the unit.
oduct will
esulting from
e, flood,
oper
BRK shall not be liable for any incidental or consequential damages caused
by the breach of any express or implied warranty
prohibited by applicable law, any implied warranty of merchantability or fitness
for a particular purpose is limited in duration to the duration of the above
warranty. Some states, provinces or jurisdictions do not allow the exclusion or
limitation of incidental or consequential damages or limitations on how long
an implied warranty lasts, so the above limitations or exclusion may not apply
to you. This warranty gives you specific legal rights, and you may also have
other rights that vary fr
How to Obtain W
Service:
If service is required, do not return the product to your retailer.
In order to obtain warranty service, contact the Consumer Affairs Division at
1-800-323-9005, 7:30 AM - 5:00 PM Central Standard Time, Monday through
Friday. To assist us in serving you, please have the model number and date of
purchase available when calling.
BRK Brands, Inc., 25 Spur Drive, El Paso, TX 79906
Battery: BRK Brands, Inc. make no warranty, express or implied, written or
oral, including that of merchantability or fitness for any particular purpose
with respect to battery.
om state to state or province to province.
arranty Service
TABLE OF CONTENTS
oduction
Intr
Wireless Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Step By Step Guide to Programming This Alarm . . . . . . . . . . . . . . . . . .2-3
Weekly Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Optional Locking Featur
If Your CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Regular Maintenance
What Y
How Can I Pr
Regulatory Information For CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
General Limitations Of CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
Limited W
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Basic Safety Information
Where to Install CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Where CO Alarms Should NOT Be Installed . . . . . . . . . . . . . . . . . . . . .2
How to Install This Alarm
Adding and Linking Additional ONELINK®Alarms
What You Will See and Hear With This Alarm . . . . . . . . . . . . . . . . . . . .3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
es
Using the Silence Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Latching Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
ou Need T
What is CO? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Symptoms of CO Poisoning
Finding the Source of CO after an Alarm . . . . . . . . . . . . . . . . . . . . . . . .5
Potential Sour
Underwriters Laboratories Inc. UL 2034
ranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7
ar
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
o Know About CO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
ces of CO in the Home
otect My Family Fr
If children or others do not readily
om hearing the alarm hor
lthough fire
A
e designed to be as reliable as
aches their sensors. They
e
*.
eplacement. See “Limited
er for r
und obstructions.
checked for potential CO pro
For Warranty Service return to:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
om CO Poisoning?
Printed in Mexico M08-0195-002 Q 09/10
equent alarms continue,
. Except to the extent
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .5
. . . . . . . . . . . . . . . . .6
. . . . . . . . . . . . . . . . . . . . . . .
is a
m a
blems.
3-4
6-7
INSTALLATION
USER’S MANUAL
ONELINK®BATTERY OPERATED
CARBON MONOXIDE ALARM
Features:
O
Voice with Programmable Location
T
T
®
NELINK
wo Latching Features
wo Silence Features
nabled
E
LISTED TO
UL 2034
STANDARD
Model CO511
Printed in Mexico
08-0195-002
M
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.
This user’s manual contains important information about your Carbon
onoxide Alarm’s operation. If you are installing this Alarm for use by others,
M
ou must leave this manual—or a copy of it—with the end user.
y
NTRODUCTION
I
hank you for choosing First Alert
T
ou have purchased a state-of-the-art Alarm designed to provide you with
Y
early warning of a carbon monoxide danger.
ONELINK
enabled alarms when installed.
E
location of the initiating unit and danger detected. Programmable up to 11
locations (ex. "basement"). When alarms sounds, if programmed for basement
t will say "Warning, evacuate, carbon monoxide in basement" along with all
i
other installed ONELINK
S
e
t
R
b
frequency hopping.
n.
S
t
t
t
T
h
m
Two Latching Features. Alarm Latch: Easily identifies initiating alarm even
a
s in low battery condition.
i
P
a mounting bracket that keeps the alarm secure over a wide rotation range
t
E
r
© 2010 BRK Brands, Inc. All rights reserved.
D
3
Consumer Affairs: (800) 323-9005 • www.firstalert.com
B
®
Enabled. Alarm automatically communicates with other ONELINK
xclusive Voice Warning with Locationwill tell you the preprogrammed
pread Spectrum Horn Tone.Lower and varying horn frequency makes it
asier for elderly with normal age related hearing loss to hear horn. Sweeps
hrough the 2200 – 3400 Hz range.
F Interconnect.Reliable and secure radio frequency communication
etween alarms. 915MHz frequency with 65,000 security codes and 3 channel
ingle Button Test/Silenceeliminates confusion. Depending on what mode
he alarm is in, pushing the button provides different functions such as testing
he alarm, silencing the alarm, re-testing the alarm when in silence and clearing
he Latching features.
wo Silence Features. Temporarily silence low battery chirp for up to eight
ours before replacing low battery or silence an unwanted alarm for several
inutes.
fter alarm condition has subsided. Low Battery Latch: Identifies which unit
ect Mount System
erf
o allow for perfect alignment.
nd of Life Signal.Provides audible confirmation alarm needs to be
eplaced.
istributed by BRK Brands, Inc.
901 Liberty Street Road, Aurora, IL 60504-8122
ASIC SAFETY INFORMA
• Dangers, Warnings, and Cautions alert you to important operating
nstructions or to potentially hazardous situations. Pay special
i
ttention to these items.
a
This CO Alar
•
•
he CO Alarm is not designed to detect fire or any other gas. It will
T
nly indicate the presence of carbon monoxide gas at the sensor.
o
Carbon monoxide gas may be present in other areas.
This CO Alar
•
emoving the batteries for any reason, or failing to replace the
R
batteries at the end of their ser
NEVER ignore any alarm. See “If Your CO Alarm Sounds” for more
•
ation on how to re
nform
i
result in injury or death.
The Silence Features are for your convenience only and will not
•
ct a pro
e
r
cor
Always check your home for a potential problem after any alarm.
to do so can result in injury or death.
ailure
F
• Test this CO Alarm once a week. If the Alarm ever fails to test
• This product is intended for use in ordinary indoor locations of
, have it r
ectly
orr
c
properly, it cannot alert you to a problem.
amily living units. It is not designed to measure CO levels in
f
compliance with Occupational Safety and Health Administration
(OSHA) commer
edical conditions that may make them more sensitive to carbon
m
monoxide may consider using warning devices which provide
audible and visual signals for carbon monoxide concentrations
under 30 ppm. For additional information on carbon monoxide
and your medical condition contact your physician.
9/10
Q 0
®
or your Carbon Monoxide Alarm needs.
f
Key features include:
®
Voice alarms.
ncludes a gasketless base for easy installation and
i
TION
sidences.
m is appr
m cannot operate without working batteries.
oved for use in single-family r
ice life, re
v
spond to an alarm
blem. See "Using the Silence Features" for details.
eplaced immediately! If the Alar
cial or industrial standards. Individuals with
moves your pro
. Failure to r
e
tection.
espond can
m is not working
®
WIRELESS OPERATION
First Alert®ONELINK®Technology is the easy, cost-effective way to provide
your family with whole-home safety. All ONELINK
each other without wires or connectors. When one Alarm sounds, they all
sound. This pr
and gives you mor
The communication distance (range) between any two ONELINK
typically 50 feet (15 meters) inside of a home. Some features of a home, such
as the number of floors, number/size of r
materials used may r
suspended ceilings, ductwork, large metallic appliances (refrigerators) and
metal studs. A featur
network. All Alarms will repeat any alarm signal that is received to all other
ONELINK®Alarms. Interference from structural conditions can be overcome
by adding additional Alarms to r
ovides your family with an earlier warning of potential danger,
e time to react.
educe the range of the Alarms. Examples include:
®
e of ONELINK
Alarms is that they operate as a mesh
oute the wireless signal around obstructions.
ooms, fur
®
Alarms communicate with
®
Alarms is
e and types of building
nitur
WHERE TO INSTALL CO ALARMS
The National Fire Protection Association (NFPA) recommends that a CO Alarm
hould be centrally located outside of each separate sleeping area in the
s
immediate vicinity of the bedrooms. For added protection, install additional
CO Alarms in each separate bedroom, and on every level of your home.
f your bedroom hallway is longer than 40 feet (12 meters), install a CO Alarm
I
at BOTH ends of the hallway.
efer to state and local building codes for additional requirements.
R
In a Single-level Home:
Install at least one CO Alarm near or within each separate sleeping area.
•
• For added protection, install an additional CO Alarm at least 20 feet
6 meters) away from the furnace or fuel burning heat source.
(
n a Multi-level Home:
I
• Install at least one CO Alarm near or within each separate sleeping area.
For added protection, install at least one CO Alarm on each level of the
•
ome. If you have a basement, install that CO Alarm at the top of the
h
basement stairs.
For added protection, install an additional CO Alarm at least 20 feet
•
(6 meters) away from the furnace or fuel burning heat source.
In Mobile Homes:
Install CO Alarms on inside walls ONLY. Uninsulated outside walls and
•
oofs of mobile homes often transfer heat and cold from outdoors.
r
WHERE CO ALARMS SHOULD NOT BE INSTALLED
Do NOT locate this CO Alarm:
In garages, kitchens, furnace rooms, or in any extremely dusty, dirty or
•
greasy areas.
Closer than 15 feet (4.6 meters) from a furnace or other fuel burning heat
•
ource, or fuel burning appliances like a water heater.
s
Within 5 feet (1.5 meters) of any cooking appliance.
•
In areas where temperature is colder than 40˚ F (4˚ C) or hotter than 100˚ F
•
38˚ C). These areas include unconditioned crawl spaces, unfinished attics,
(
uninsulated or poorly insulated ceilings, porches, and garages.
In turbulent air, like near ceiling fans, heat vents, air conditioners, fresh air
•
turns, or open windows. Blowing air may prevent CO from reaching the
e
r
ensors.
s
In direct sunlight.
•
• This CO Alarm is designed for use inside a single-family home or
partment. It is not meant to be used in common lobbies, hallways,
a
r basements of multi-family buildings unless working CO Alarm
o
are also installed in each family living unit. CO Alarms in common
reas may not be heard from inside individual family living units.
a
This CO Alarm alone is not a suitable substitute for complete
•
etection systems in places which house many people, like hotels
d
mitories, unless a CO Alar
or dor
DO NOT use this CO Alar
•
uildings, special-purpose non-residential buildings, RVs, boats,
b
r airplanes. This CO Alarm is specifically designed for residential
o
use, and may not pr
pplications.
a
ovide adequate pr
m is also placed in each unit.
houses, industrial or commerc
in ware
m
otection in non-r
sidential
e
HOW TO INSTALL THIS ALARM
or quick installation instructions see the “Quick Installation Instructions”
F
included.
his CO Alarm was designed to be mounted on the ceiling or wall. It is
T
ot a tabletop device.You must install this device on the ceiling or wall as
n
outlined below
Tools you will need: pencil, drill with 3/16” (5mm) drill bit,
Phillips screwdriver, hammer.
. Hold the mounting bracket against the ceiling (or wall) so the vertical
1
mounting slot is aligned in the 12 o’clock position and trace ar
inside of the mounting slots (vertical and horizontal mounting).
Put the unit wher
2.
m
. Using a 3/16” (5 mm) drill bit, drill a hole through the center of the oval
3
outlines you traced.
4. Insert the plastic screw anchors (in the plastic bag with screws) into the
holes. Tap the screw anchors gently with a hammer, if necessary, until
they are flush with the ceiling or wall.
5. Line the mounting bracket up over the plastic scr
6. Screw the mounting bracket to the ceiling or wall through the mounting
slots using the two scr
7. Attach the CO Alarm to the mounting
bracket. Line up the guides on the alarm’s
base with the guides on the mounting
bracket. When guides ar
the base clockwise (right) until it snaps
into place.
NOTE: Once the Alarm is snapped onto
the mounting bracket, you can rotate
the Alarm to adjust the alignment.
8. Test the CO Alarm. See “Weekly Testing”
for details.
. Read “Wher
ounting holes.
e it won’
Install CO Alarms” before
o
e T
TS OF THIS CO ALARM
AR
P
1 Test/Silence Button
2Battery Compartment
3Power LED
4CO Alarm LED
t get covered with dust when you drill the
ews provided.
e lined up, turn
starting.
ound the
ew anchors.
he optional locking features are designed to prevent unauthorized removal of the battery or alarm. It is not necessary to activate the locks in
T
ingle-family households where unauthorized battery or alarm removal is not a concern.
s
These CO Alarms have two separate locking features: one to lock the battery compartment, and the other to lock the CO Alarm
o the mounting bracket. You can choose to use either feature independently, or use them both.
t
Tools you will need: • Needle-nose pliers • Standard flathead screwdriver.
oth locking features use locking pins, which are molded into the mounting bracket. Depending on which locking features you
B
use, remove one or both pins from the mounting bracket using needle-nose pliers.
To permanently remove either locking pin, insert a flathead screwdriver between the locking pin and the lock, and pry
he pin out of the lock.
t
T
O LOCK THE BATTERY COMPARTMENT
Do not lock the battery compartment until you install the batteries and
est the CO Alarm.
t
If the unit does not alarm during testing,
DO NOT lock the battery compartment!
nstall new batteries and test again.
I
If the CO Alarm still does not alarm, replace
it immediately.
1. Using needle-nose pliers, detach one
ocking pin from the mounting bracket.
l
. After batteries are inserted, then push
2
he locking pin through the hole near the
t
battery door latch on the back of the CO
larm.
A
TO LOCK THE MOUNTING BRACKET
. Using needle-nose pliers, detach one
1
locking pin from the mounting bracket.
. Insert the locking pin through the hole on
2
he back of the CO Alarm as shown in the
t
iagram.
d
. When you attach the CO Alarm to the
3
ounting bracket, the locking pin’s head
m
will fit into a notch on the bracket.
A
DDING AND LINKING ADDITIONAL ONELINK
OTE: Steps 1 through 3 need to be completed within two minutes.
N
than two minutes pass, the Green power LED will stop blinking.
f more
I
Simply open the battery drawer of the second Alarm and repeat steps 1
hrough 3.
t
. Insert the batteries into the battery
1
drawer of the next Alarm.
O NOT CLOSE THE DRAW
D
. Press and hold the test button
2
nd then close the battery drawer.
a
. Once you hear the unit chirp,
s
ial
3
release the test button.
he Green power LED will start
T
o blink indicating the ONELINK
t
Alarm is waiting for program data
m one of the other setup ONELINK
ro
f
4. Press and hold the test button on the first Alarm, until the second Alarm
hirps and its Green power LED stops blinking. Then release the test button.
c
f you have purc
. I
5
you can now connect the hardwired Alarm by installing the three-wire
onnector on the ceiling to the Alarm.
c
Repeat steps 1-5 for additional ONELINK
6.
ou have now successfully linked your new ONELINK
Y
To add additional Alarms at a later time, follow steps 1 through 5.
hased the hard
ER.
®
®
larms.
A
d battery back-up ONELINK
wire
®
Alarms.
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM
nder Normal Operations
U
oice:
V
Silent
orn:Silent
H
Power LED: Flashes Green once/minute
u Test the Alar
hen Yo
W
Voice:
“
Testing.”
ice:
o
V
CO LED: Flashes Red in sync with the horn pattern
f Battery Becomes Low or is Missing
I
Voice: “Replace battery in [Location, example “Basement”].”
Horn: chirps once a minute
ower LED:Flashes Green On for 2 seconds/Off for 2 seconds.
P
If Alarm is Not Operating Properly (MALFUNCTION SIGNAL)
o
V
H
CO LED: 3 Flashes approximately once a minute
m
Alar
o
V
Horn: 5 chirps every minute
CO LED: 5 Flashes approximately once a minute
Alarm Levels of CO are Detected
Horn: 4 fast beeps, pause, 4 fast beeps, pause*
oice:
V
Horn: 4 beeps, pause, 4 beeps, pause repeating 2 times followed by
CO LED: During Alarm: Flashes Red in sync with the horn pattern.
*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause cycle will
repeat for fifteen minutes. After fifteen minutes, the pause will increase to one
minute.
CO Alar
Horn:
CO LED: Flashes Red
rn
Wa
“
“Basement”]. Evacuate.” Pause. “Highest carbon monoxide level
as [CO level example: _0_
w
epeated every 5 hours
R
ow Battery Latch is now engaged.
L
ice:
Detector erro
“
manual.” Repeated every 5 hours
orn:3chirps every minute
ached its End of Life
has re
ice:
Detector erro
“
manual.” Repeated every 5 hours
arning, evacuate carbon monoxide in [Location, example:
“W
“Basement”]. Evacuate.” Pause. “Highest carbon monoxide level
was [CO level example: ___ ppm]”.
Voice Warning above.
After Alarm: Flashes Red On for 2 seconds/Off for 2 seconds.
CO Alarm Latch is now engaged.
m is Silenced
Off
m
Horn: 4 fast beeps, pause, 4 fast beeps;
ing, evacuate carbon monoxide in [Location, example:
ppm]”.
r in [Location, example “Basement”], please see
r in [Location, example “Basement”], please see
OPTIONAL LOCKING FEATURES
T
O UNLOCK THE BATTERY COMPARTMENT
. Remove the CO Alarm from the
1
mounting bracket. If the unit is locked
o the bracket, see the section
t
To Unlock the Mounting Bracket.”
“
2. Insert a flathead screwdriver under the
head of the locking pin, and gently pry
t out of the battery compartment lock.
i
(If you plan to relock the battery
compartment, save the locking pin.)
. To relock the battery compartment,
3
lose the battery door and reinsert
c
locking pin in lock.
. Reattach the CO Alarm to the mounting
4
racket.
b
hen replacing the batteries, always test
W
the Alarm before relocking the battery
compartment.
TO UNLOCK THE MOUNTING BRACKET
. Insert a flathead screwdriver into the
1
rectangular cut-out on the mounting
bracket nearest to the locking pin.
2. Pry the CO Alarm away from the
racket by pushing up on the screw-
b
driver and turning the CO Alarm
counterclockwise (left) at the same
ime.
t
®
A
®
larms.
A
LARMS
®
larm,
A
F YOUR CO ALARM SOUNDS
I
What You See and Hear
efer to section “What You Will See and Hear With This Alarm”.
R
Actuation of your CO Alarm indicates the presence of carbon monoxide
CO) which can kill you. In other words, when your CO Alarm sounds,
(
ou must not ignore it!
y
IF THE ALARM SIGNAL SOUNDS
1. Operate the Test/Silence button.
all your emergency services, fire department or 911. Write down the
. C
2
umber of your local emergency service here:
n
_______________________________________________________________
_
. Immediately move to fresh air—outdoors or by an open door or window.
3
Do a head count to check that all persons ar
nter the premises, or move away from the open door or window until
e
he emerg
t
aired out, and your CO Alarm remains in its normal condition.
4. After following steps 1-3, if your CO Alarm reactivates within a 24-hour
p
igate for sourc
t
inspect for proper operation of this equipment. If problems are identified
d
a
the manufactur
or more information about CO safety and this equipment. Make sure
f
hat motor vehicles are
t
garage or adjacent to the residence. Write down the number of a qualified
a
_
Alarms have various limitations. See "General Limitations of CO Alarms"
for details.
ency services responder has arrived, the premises have been
eriod, repeat steps 1-3 and call a qualified appliance technician to inves-
uring this inspection have the equipment serviced immediately. Note
ny combustion equipment not inspected by the technician, and consult
ppliance technician here:
_______________________________________________________________
If you hear the CO alar
USING THE SILENCE FEATURES
emove the batteries to quiet an unwanted alar
Never r
atteries disables the alarm and removes your protection.
b
The Silence Featur
dentify and correct the problem. Do not use the Silence Feature in emergency
i
situations. It will not correct a CO problem.
The Silence Feature can temporarily quiet an unwanted alarm for several
minutes. You can silence this Alarm by pressing the Test/Silence button on
the alarm cover for at least 3-5 seconds.
After the Test/Silence button is released, the Red LED blinks during the silence
mode.
When the CO Alarm is Silenced the CO Alarm will remain silent for up to
4 minutes. After 4 minutes, if CO levels remain potentially dangerous the hor
will start sounding again.
SILENCING THE LOW BA
This silence featur
up to 8 hours. Y
the Test/Silence button on the alarm cover.
Once the low battery warning “chirp” silence feature is activated, the unit
continues to flash the Green light twice a minute for 8 hours. After 8 hours, the
low battery “chirp” will r
this unit will not operate without batter
o deactivate this featur
T
go into Test Mode and the low battery warning will resume (LED flashes and
unit sounds “chirp” once a minute).
accounted for.
e
es of CO fro
rs’ instructions, or contact the manufacture
e
“ALARM—MOVE TO FRESH AIR”
ove everyone to a source of fresh air.
m
e is intended to temporarily silence the hor
m fuel-burn
not, and have not, been operating in an attached
m horn and the CO red light is flashing,
DO NOT remove the batteries!
ing equipment and appliances, and
Do not re-
rs dire
m. Removing the
n while you
TTERY WARNING
e can temporarily quiet the low battery warning “chirp” for
ou can silence the low battery war
Replace the batteries as soon as possible;
esume.
e:
Pr
est/Silence button again. The unit will
ess the T
ning “chirp” by pr
y power!
essing
ctly,
n
STEP BY STEP GUIDE TO PROGRAMMING
• The range and proper operation of any wireless device will vary
depending on its surroundings. It is very important that each
m is tested individually befor
Alar
1
2
3
5
sure that all Alarms respond properly.
• The ONELINK
between buildings. The Alar
under these conditions.
Metal objects and metallic wallpaper may interfere with signals
•
from wireless Alarms. Alarms should be tested after changes to
your home such as remodeling, moving furniture, and with metal
doors opened and closed.
Your First Alert®ONELINK®CO Alarm will automatically communicate both
potential fires and carbon monoxide presence with all other First Alert
ONELINK®Smoke/CO Alarms.
FCC NOTICE: This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may not
cause harmful interfer
received, including interference that may cause undesired operation.
FCC ID: M7U5001L
Changes or modifications not expr
could void the user
®
Alarms are not to be used outdoors or to transmit
ence, and (2) this device must accept any interfer
s authority to operate the equipment.
’
e and after installation to make
ms will not communicate pr
essly appr
oved by BRK Brands, Inc.
1 2 3
operly
®
ence
THIS ALARM
FOR FIRST TIME AND WHEN CHANGING BATTERIES
Action:
1. Insert batteries (2, AA batteries).
2. Press & Hold Test Button if you
would like to pr
or change the location of the
Alarm. Release button after Alarm
responds.
3. After you hear the location of
where you are placing the Alarm,
ess & Hold the T
Pr
our Alarm has now been pr
Y
vailable locations:
A
Basement Kitchen Child’s Bedroom
Living Room
Family Room
Office Hallway Utility Room
ogram the location
est Button.
ogrammed for the location of your choice.
Dining Room Master Bedroom
No Location
Alarm Will Say:
elcome, First Alert Carbon
“W
Monoxide Alarm.”
“No location pr
time
“Basement”] location programmed”
when changing batteries.
“To select location, press and hold
test button now.”
“To save location, press and hold
test button after location is hear
Alarm will speak list of locations
(see below).
“[Location, example: “Basement”]
location saved.”
If no location is chosen:
“No location saved.”
ogrammed” if
or “[Location, example:
Guest Bedr
oom
first
d.”
WEEKL
It is important to test this unit every week to make sure it is working
operly. Using the test button is the recommended way to test this CO
pr
Alarm.
ou can test this CO Alar
Y
on the Alarm cover (typically 3-5 seconds).
During testing, you will see and hear the following sequence:
If the unit does not alarm, make sure the batteries are correctly installed, and
test again. If the unit still does not alarm, replace it immediately.
Y TESTING
•
T
est the CO Alar
properly, have it replaced immediately! If the CO Alarm is not
working pr
DO NOT stand close to the Alar
•
Exposure at close range may be harmful to your hearing.
When testing, step away when horn starts sounding.
Horn will sound 4 beeps, pause, 4 beeps. The Power LED will be
• The
Off and the
m once a week. If the CO Alarm ever fails to test
, it cannot aler
operly
m by
CO LED flashes Red.
t you to a problem.
m when the hor
essing and holding the T
pr
n is sounding.
est/Silence button
SILENCING THE END OF LIFE SIGNAL
This silence feature can temporarily quiet the End of Life warning “chirp” for
up to 2 days. You can silence the End of Life warning “chirp” by pressing the
Test/Silence button. The horn will chirp, acknowledging that the End of Life
silence feature has been activated.
After approximately 2 days, the End of Life “chirp” will resume.
After approximately 2-3 weeks the End of Life warning cannot be silenced.
TCHING FEA
LA
Alarm Latch is activated after an Alarm is exposed to alarm levels of carbon
monoxide. After CO levels drop below alarm levels, the
begin to flash On for 2 seconds/Of
“latch” for about 15 minutes, to give you time to determine which unit initiated
the alarm.
Low Batter
condition". When this occurs, the
Off for 2 seconds for about 15 minutes. This feature is designed to help you
identify which Alarm needs to have the battery replaced. Although, the Alarm
will sound the low battery chirp approximately once every minute, sometimes
during the initial stages of "low battery", the Alarm will chirp in greater intervals
than one minute, sometimes up to several hours, until the battery r
steady low battery level. This innovative feature eliminates the frustration of
waiting for and/or identifying which unit is chirping.
TURES
f for 2 seconds. It will continue to flash or
y Latch
is activated when the Alarm is in the "low battery
Power LED flashes Green On for 2 seconds/
4
“CO” Red LED will
eaches a