Fire-Lite ACM-8RF User Manual

G
PN 50362:C0 ECN 01-155
Control Relay Module
ACM-8RF
Instruction Manual
Document 50362 03/21/2001 Rev:
C
Fire Alarm System Limitations
An automatic fire alarm system–typically made up
of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommenda­tions, State and local codes, and the recommenda­tions contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guaran­tee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a develop­ing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detec­tors are located.
• Smoke particles may be blown away from detec­tors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelec­tronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing
fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representa­tive. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Installation Precautions
WARNING - Several different sources of power can
be connected to the fire alarm control panel.
Disconnect all sources of power before servicing. Control unit and associated equipment may be dam­aged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Soft­ware Changes. To ensure proper system operation,
this product must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific software. Reacceptance test­ing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or soft­ware functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49° C/32-120° F 85% RH (non-condensing) at 30° the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. There­fore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
and at a relative humidity of
C/86° F. However,
Adherence to the following will aid in problem-free
installation with long-term reliability:
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce sus­ceptibility. Overhead or outside aerial wiring is not
recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system com­ponents can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not installed and used in accordance with the instruc­tion manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing de­vice pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operat­ed in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be re­quired to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
This page intentionally left blank
4
ACM-8RF PN 50362:C 03/21/01
Table of Contents
Table of Contents
1. Introduction
General...................................................................................................7
Mounting ............................................................................................... 7
Features .................................................................................................8
Relays .................................................................................................8
24 VDC Power and Earth Ground......................................................8
EIA-485 Communications..................................................................9
Address Switches ...............................................................................9
Relay Function Selection....................................................................9
Mode Selection...................................................................................9
Related Documentation........................................................................9
2. Installation
Mounting the Enclosure. ....................................................................11
Wiring the Power Terminal Blocks...................................................11
Wiring the Relay Terminal Blocks....................................................12
Wiring the EIA-485 Terminal Blocks...............................................13
Wiring Specifications....................................................................... 13
EIA-485 Shield in Conduit ..........................................................13
EIA-485 Shield Not in Conduit ...................................................14
EIA-485 - TB2 Terminals ................................................................14
Configuring the ACM-8RF................................................................15
Address Switches - SW1 and SW2 ..................................................15
Relay Assignment DIP Switch - SW3..............................................15
Mode Select Switch - SW4 ..............................................................16
Mounting in the ABS-8RF Enclosure ...............................................16
UL Power-limited Wiring Requirements .........................................17
3. Electrical Ratings
24 VDC.................................................................................................19
Relay Contacts ....................................................................................19
Data Communications Port ...............................................................19
Power Requirements ..........................................................................19
Appendix A: MS-5210UD
Capabilities..........................................................................................21
FACP Activations ............................................................................... 22
Alarm Only Activation.....................................................................22
Alarm and Trouble Activation .........................................................23
Application Example #1 .....................................................................24
Application Example #2 .....................................................................25
Application Example #3 .....................................................................26
Application Example #4 .....................................................................28
Table of Contents
Appendix B: MS-9200
Capabilities ..........................................................................................31
Testing..................................................................................................31
Wiring ..................................................................................................31
FACP Activations ...............................................................................32
Alarm Only Activation .....................................................................32
Alarm and Trouble Activation..........................................................33
Appendix C: MS-9600
Capabilities ..........................................................................................37
Testing..................................................................................................37
Wiring ..................................................................................................37
Configuration ......................................................................................38
Setting Rotary Switches ...................................................................38
Mode Select ......................................................................................39
Alarm Only or Alarm/Trouble Mode...........................................39
Receive Only or Receive/Transmit Mode....................................39
Setting the DIP Switches ..................................................................40
Alarm Only Activation.................................................................40
Alarm and Trouble Activation .....................................................41
Multiple ACM-8RFs ....................................................................42

1. Introduction

General

The ACM-8RF Relay Control Module contains eight high current (5 amps) Form-C relays. The module interfaces to host Fire•Lite control panels which employ an EIA-485 communications bus and may be connected to the bus up to 6,000 feet away from the host control panel.
Typically, each relay is assigned to a zone on the host fire alarm control panel. The relays may be triggered by either a zone alarm (activation) or zone trouble. The relays may also take on special functions depending upon the host panel. Refer to the Appendices for additional information.
The ACM-8RF Relay Control Module may be used in combination with the following products on the same EIA-485 bus circuit:
• AFM/ACM Series LED annunciators
• LDM Series graphic annunciators
• UDACT-F (Universal Digital Alarm Communicator/Transmitter)
• LED-10 Annunciator
EIA-485 bus compatible accessories are designed to provide maximum flexibility to system configurations. Examples include multiple remote LED annunciators with customized labels per corresponding area or function, multiple remote graphic annunciators that illustrate building layout and floor plans, remote DACTs for strategic mounting location near telephone equipment plus remote high current switching relays for such purposes as fan and damper control, elevator recall and door releasing.
OFF
12345678
O
12
F F
ACM-8RF.cdr

Mounting

The ACM-8RF module will mount to an ABS-8RF backbox. A blank faceplate is provided with the backbox.
The CAB-3F Series cabinets, with CHS-4L or CHS-4F chassis, may also be used to house several ACM-8RFs.
ACM-8RF PN 50362:C 03/21/01
ABS-8RF
abs8rf.cdr
7
1. Introduction Features

Features

SW3 - Relay Assignment
DIP Switches

Relays

TB2 - EIA-485
Terminal Block
TB1 - 24 VDC
Terminal Block
Relays
K4
K3
K2
K1
OFF
12345678
O
12
F F
Figure 1 ACM-8RF Features
K5
Relays
K6
K7
K8
ACM-8RF.cdr
SW4 - Mode Select Switch
SW1-SW2 Address Select Rotary Switches
The Relay Control Module provides eight Form-C relays with 5 amp contacts @ 125 VAC (resistive) or 30 VDC (resistive) and 2 amps at 125 VAC inductive). The relay contacts are gold plated silver alloy for medium duty switching and are not intended for motor control or pilot duty. Wiring to the relays is via sturdy removable terminal blocks.

24 VDC Power and Earth Ground

Wiring to removable terminal block TB1 is for 24 VDC power-limited, regulated, nonresettable power from the host FACP or a compatible UL listed battery backed power supply such as the Fire•Lite FCPS-24F. This terminal block may be used to daisy chain the 24 VDC to other ACM-8RFs or EIA-485 Fire•Lite compatible devices.
8
ACM-8RF PN 50362:C 03/21/01
Related Documentation 1. Introduction

EIA-485 Communications

Wiring to removable terminal block TB2 is for communications over the EIA­485 bus. The bus carries commands and data sent between the host FACP and ACM-8RFs. The EIA-485 circuit is power-limited. The host FACP supervises devices wired to the EIA-485 bus. A maximum of 32 ACM-8RFs may be connected to the FACPs EIA-485 bus, but if other types of devices are also connected to the bus, the maximum number of ACM-8RFs must be reduced by the total of such devices.

Address Switches

Two rotary BCD (Binary Coded Decimal) switches, located on the lower right of the module, are used to set the ACM-8RF system address. SW1 represents the 'tens' position and SW2 represents the 'ones' position of the address setting.

Relay Function Selection

DIP switch SW3 is used to program the assignment of each ACM-8RF relay to either a zone function (such as zone alarm or zone trouble triggering) or to a system function (such as system alarm, system trouble, system supervisory, signal silence, pre-alarm or AC fail). Be certain to review the Appendices for information on SW3 switch settings for specific FACPs and the operation and options available to each host FACP.

Mode Selection

DIP switch SW4 is used to set the mode of operation for the ACM-8RF as follows:
• #1 sets Alarm activation or Alarm/Trouble activation mode.
• #2 sets Receive or Receive/Transmit mode.

Related Documentation

Further details about products referenced in this document can be found in the manuals for the particular fire alarm control panel and components.
Product
MS-5210UD Fire Alarm Control Panel Instruction Manual 50193
MS-9200 Fire Alarm Control Panel Instruction Manual 51003
MS-9600 Fire Control Panel Instruction Manual 51335
LED-10 Remote Fire Annunciator 50400
FCPS-24F Instruction Manual 50079
UDACT-F Instruction Manual 50049
CAB-3F Series Cabinets 15391
Table 1 Related Documentation
ACM-8RF PN 50362:C 03/21/01
Part Number
9
1. Introduction Related Documentation
NOTES
10
ACM-8RF PN 50362:C 03/21/01

2. Installation

Mounting the Enclosure.

Select and remove the appropriate knockout(s) on the ABS-8RF enclosure.
Securely mount the enclosure.
Ground the enclosure to a solid electrical ground per NEC Article 250.
Pull all wiring into the enclosure (refer to "UL Power-limited Wiring Requirements" on page 17).

Wiring the Power Terminal Blocks

24 VDC power supplied by the host control panel or external power supply must be regulated and power-limited. Th is power is inherently supervised (loss of power also results in a communication failure at the control panel).
• Limit the total wire resistance to 10 ohms.
• Connect 24 VDC power from FACP or Power Supply to TB1-3 (+) and TB1-4 (–).
• Connect earth ground (TB1-1 backbox or cabinet.
24 VDC Power
Figure 2 24 VDC Power & Earth Ground Terminals - TB1
Wiring of multiple modules.
Host FACP or Remote Power Supply
– 24 VDC
+ 24 VDC
Figure 3 Multiple Module Wiring
) to a mounting screw on the
EARTH
TB1
5
SYS COM (–)
4
SYS COM (–)
3
24 V (+)
2
24 V (+)
1
EARTH
ACM8RF-TB1.cdr
First ACM-8RF -- -- -- -- -- -- Last ACM-8RF
TB1
5
4
3
2
1
TB1
5
4
3
2
1
ACM8RF-power.cdr
ACM-8RF PN 50362:C 03/21/01
11
2. Installation Wiring the Relay Terminal Blocks

Wiring the Relay Terminal Blocks

The ACM-8RF provides eight relays with Form-C contacts rated for 5 amps.
Note: Wiring from these relays is not supervised.
The terminal assignments are illustrated below. For information on wiring limitations, refer to "UL Power-limited Wiring Requirements" on page 17.
Relay 4
Normally Open
Common
Normally Closed
Relay 3
Relay 2
Relay 1
OFF
12345678
O
12
F F
Note: All Relays have the same terminal
assignment position as those on relay #4 & #5
Figure 4 Relay Terminal Assignments
Relay 5
Normally Open Common Normally Closed
Relay 6
Relay 7
Relay 8
ACM8RF-relay.cdr
12
ACM-8RF PN 50362:C 03/21/01
Wiring the EIA-485 Terminal Blocks 2. Installation

Wiring the EIA-485 Terminal Blocks

Communications between the Fire Alarm Control Panel and the ACM-8RF is accomplished over a two-wire EIA-485 serial communications bus which must be power-limited. Communications between the host FACP and ACM-8RFs is supervised by the fire alarm control panel.

Wiring Specifications

• The EIA-485 circuit cannot be T-tapped; it must be wired in a continuous fashion from the control panel to the ACM-8RFs.
• The maximum wiring distance between the panel and ACM-8RFs is 6,000 feet.
• The wiring must be a 18 AWG to 14 AWG twisted shielded pair cable having a characteristic impedance of 120 ohms, +/- 20%.
• Limit the total wire resistance to 100 ohms.
• Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, noisy electrical circuits that are powering mechanical bells or horns, audio circuits above 25 V power circuits.
Note: Never use the EIA-485 shield for grounding purposes. Terminate the EIA-485 shield at the Fire Alarm Control Panel only.
, motor control circuits, or SCR
RMS
Standard Annealed Copper Wire
Wire Size
A.W.G
14 64 4110 0.00323 2.85 2.97 12.4
16 51 2580 0.00203 4.09 4.73 7.82
18 40 1620 0.00128 6.51 7.51 4.92
Diameter
in Mils
Cross Section Ohms per 1000 feet
Circ. Mils Sq. Inch @ 77°F. @ 149°F.
Table 2 Wire Specifications
EIA-485 Shield in Conduit
When the EIA-485 wiring is in conduit, connect the shield to system common. The shield can enter the cabinet, but must be insulated from the cabinet (no electrical contact). Between ACM-8RFs, wire-nut multiple shields together (which can be inside of the respective ACM-8RF enclosure but ensure that the shield does not contact earth ground).
TB2
4
IN (–)
3
OUT (–)
2
OUT (+)
1
IN (+)
Figure 5 Terminating the Shield in Conduit
ACM-8RF PN 50362:C 03/21/01
Pounds per
1000 feet
ACM8RF-term1.cdr
13
2. Installation Wiring the EIA-485 Terminal Blocks
EIA-485 Shield Not in Conduit
When the EIA-485 wiring is not in conduit, terminate the shield at the outside of the FACP cabinet. Do not allow the shield to enter or even touch the cabinet housing the ACM-8RFs. Between ACM-8RFs, wire-nut multiple shields together outside of the respective enclosures. Ensure that the shield does not touch earth ground at any junction points.
TB2
4
IN (– )
3
OUT (–)
2
OUT (+)
1
IN (+ )
ACM8RF-term2.cdr
Figure 6 Terminating the Shield with No Conduit

EIA-485 - TB2 Terminals

Wire as shown below:
Note: Leave a 120 ohm ELR installed across the EIA-485 Out terminals at the last ACM-8RF on the circuit (see below). All other ACM-8RFs should not have a resistor installed.
TB2
4
IN (–)
OUT (–)
3
OUT (+)
2
IN (+)
1
ACM8RF-TB2.cdr
Figure 7 EIA-485 Terminal Block - TB2
Multiple wiring of EIA-485 circuits
Host FACP
EIA-485 (–)
EIA-485 (+)
Figure 8 Wiring Multiple ACM-8RFs - EIA-485
14
First ACM-8RF -- -- -- -- -- -- Last ACM-8RF
TB2
4
3
2
1
TB2
4
3
2
1
ACM-8RF PN 50362:C 03/21/01
ACM8RF-mult.cdr
Configuring the ACM-8RF 2. Installation

Configuring the ACM-8RF

Address Switches - SW1 and SW2

It is critical to the operation of the relays that the address switches be set correctly.
To set the relay module for address ‘01’, position the arrow on SW1 (tens) so it points to 0 and position the arrow on SW2 (ones) so it points to 1.
TENS
SW1
Figure 9 Address Switches SW1 & SW2
SW2
ONES
ACM8RF-SW1-2.cdr

Relay Assignment DIP Switch - SW3

Check the Appendices for information on SW3 switch settings for specific FACPs and the operation and options available to each host FACP. The following illustration provides details on DIP switch placement in the On and OFF position.
Side View of Switch Shown in the OFF Position
OFF
2
1
O
F F
Figure 10 Relay Assignment Switch
345
678
ACM8RF-S W3.cdr
ACM-8RF PN 50362:C 03/21/01
15
Loading...
+ 33 hidden pages