Fire-Lite ACM-32AF User Manual

Annunciator Control Modules
ACM-16ATF
ACM-32AF
Instruction Manual
Document 51480 02/02/2001 Rev:
A
Fire Alarm System Limitations
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke detectors may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detec­tor is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist.
detectors are designed to protect property, not life.
IMPORTANT!
the same room as the control panel and in rooms used by the system for the connection of alarm transmission
Smoke detectors must be installed in
wiring, communications, signaling, and/or power.
detectors are not so located, a developing fire may dam­age the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A mainte­nance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Heat
If
LimWarSm.p65 01/10/2000
Installation Precautions
WARNING -
connected to the fire alarm control panel.
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION -
Changes.
product must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system compo­nents, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49° C/32-120° F RH (non-condensing) at 30° useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Several different sources of power can be
Disconnect all
System Reacceptance Test after Software
To ensure proper system operation, this
and at a relative humidity of 85%
C/86° F. However, the
Adherence to the following will aid in problem-free installation with long-term reliability:
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and inter­ferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning
Consult with the Technical Services Department
strikes.
if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system compo­nents can fail at any time. This system contains static­sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static­suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and
can radiate radio frequency energy and if not in­stalled and used in accordance with the instruction manual, may cause interference to radio commu­nications. It has been tested and found to comply with the limits for class A computing device pursu­ant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.
LimWarSm.p65 01/10/2000
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interfer­ence Regulations of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
This page intentionally left blank
4
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
Table of Contents
Table of Contents
1. Product Overview
General................................................................................................... 9
Canadian Information........................................................................10
Related Documentation......................................................................10
2. Inventory
ACM-16ATF Series ............................................................................11
Control Modules...............................................................................11
ACM-16ATF ...............................................................................11
ACM-16ATCS4F (for use in Canada).........................................11
ACM-16ATYF.............................................................................11
Expander Modules............................................................................12
AEM-16ATF................................................................................12
ACM-32AF Series...............................................................................13
Control Modules...............................................................................13
ACM-32AF .................................................................................13
Expander Modules............................................................................13
AEM-32AF ..................................................................................13
Cabinet & Panel Hardware ...............................................................14
Surface-Mount Backboxes ............................................................... 14
ABS-1F ............................................................................................14
ABS-2F ........................................................................................14
ABS-1TF......................................................................................14
Flush-mount Backboxes................................................................... 15
ABF-1F .......................................................................................15
ABF-2F ........................................................................................15
ABF-4F ........................................................................................15
Semi Flush-mount Backboxes..........................................................16
ABF-1DF ...................................................................................16
ABF-2DF .....................................................................................16
Additional Hardware ........................................................................17
ABM-1 .........................................................................................17
AKS-1F ........................................................................................17
3. Design Considerations
Limits ...................................................................................................19
Wire Runs............................................................................................19
Wiring Specifications.......................................................................... 19
Receive Only and Transmit/Receive .................................................20
Electrical Ratings................................................................................21
Annunciator Power Requirements.................................................... 21
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
5
Table of Contents
4. Installation
Mounting the Backbox or Cabinet ................................................... 23
Wiring and Connecting...................................................................... 23
Connect Wiring to Backbox or Cabinet........................................... 24
When the EIA-485 shield is not in conduit: ................................ 24
When the EIA-485 shield is in conduit: ...................................... 24
EIA-485 Circuit ............................................................................... 25
24 VDC Circuit................................................................................ 26
Installing Labels ................................................................................. 27
Setting Rotary and DIP Switches...................................................... 28
DIP Switch Settings ......................................................................... 28
Mounting Annunciators and Expanders.......................................... 29
Surface Mount Backbox (ABS Series) ............................................ 29
Flush Mount Backbox (ABF Series)................................................ 29
ABF-1F Backbox Only................................................................ 29
ABF-2F and ABF-4F Backboxes Only. ...................................... 30
Semi-Flush Mount Backbox (ABF-1DF/-2DF)............................... 31
Dress Panel (ADP-4F) ..................................................................... 31
Wiring the Expander Connections ................................................... 31
Two Position Backbox (-2 Series) ................................................... 31
Four Position Backbox (-4 Series) or Cabinet ................................. 32
ACM-16 Series/AEM-16ATF ..................................................... 32
ACM-32AF/AEM-32AF ............................................................. 32
Supervising Devices............................................................................ 33
Main Power Supply Connections...................................................... 33
Programming and Testing the Annunciators .................................. 33
5. LED and Switch Functions
ACM-16ATF ....................................................................................... 37
AEM-16ATF ....................................................................................... 39
ACM-32AF.......................................................................................... 40
AEM-32AF.......................................................................................... 41
UDACT-F and Annunciators ............................................................ 41
Appendix A: Sensiscan 200
Capabilities ......................................................................................... 43
Circuits:............................................................................................ 43
System Controls:.............................................................................. 43
Connecting EIA-485 Circuit.............................................................. 43
Providing Power to Annunciators .................................................... 44
Program Mapping .............................................................................. 45
6
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
Table of Contents
Appendix B: Sensiscan 2000
Capabilities..........................................................................................47
Circuits: ............................................................................................47
System Controls: ..............................................................................47
Configuring for the Sensiscan 2000...................................................47
Connecting the EIA-485 Circuit........................................................ 48
Providing Power to Annunciators.....................................................49
Installing Modules in the System.......................................................50
Program Mapping ..............................................................................51
Appendix C: MS-9200
Capabilities..........................................................................................53
Connecting the EIA-485 Circuit........................................................ 53
Providing Power to Annunciators.....................................................54
Program Mapping ..............................................................................55
Appendix D: MS-9600
Capabilities..........................................................................................57
Connecting the EIA-485 Circuit........................................................ 57
Providing Power to Annunciators.....................................................58
Program Mapping ..............................................................................59
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
7
This Page Intentionally Left Blank
8
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

1. Product Overview

This manual provides instructions for connecting an ACM-16ATF series and ACM-32AF series annunciators to various Fire Alarm Control Panels. Each appendix contains instructions that are unique to a particular FACP.

General

This series provides Fire•Lite FACPs with up to 32 remote serially connected annunciators, each with a capacity of 64 points, for a total capacity of 2048 points. Expander modules are provided for each series.
The series provides an array of LEDs to indicate, at a remote location, the status of circuits within the system. Individual fire alarm control panels offer different methods of identifying annunciator points:
Sensiscan 200 and Sensiscan 2000 - Annunciator points directly
follow the circuit arrangement of modules installed in the cabinet.
MS-9200 and MS-9600 - Annunciator points are programmable by
group.
Common system functions such as signal silence, system reset, and local annunciation controls (local acknowledge and lamp test) are controlled through the annunciator's integral membrane push switches.
Communication between the control panel and the modules is accomplished over a power-limited, two-wire serial interface employing an EIA-485 communication standard. Power for the modules is provided via a separate power-limited power loop from the control panel which is inherently supervised by the annunciator module (loss of power results in an communication failure at the control panel). The module can also be powered from a power-limited and regulated remote power supply listed for fire­protective signaling use.
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
9
1. Product Overview Canadian Information

Canadian Information

The National Standard of Canada (CAN/ULC-S527) requires that a dedicated display employ yellow visual indicators to indicate the status of supervisory inputs. The Fire•Lite annunciators listed in this manual are intended to be used for Canadian Supervisory Service in conjunction with Fire•Lite Sensiscan 200, Sensicsan 2000, MS-9200 and MS-9600 control units. The ACM-16ATF/AEM-16ATF and ACM-32AF/AEM-32AF annunciators can not be employed for ULC Supervisory Service. See Canadian Requirements for Supervisory Signal in Fire•Lite Document
50057.
Annunciator control and expander modules in the “Y” series have been designed with yellow LEDs.

Related Documentation

Further details about products referenced in this document can be found in the manuals for the particular fire alarm control panels and components.
Product
Sensiscan 200 Fire Alarm Control Panel Instruction Manual 15032
Sensiscan 2000 Fire Alarm Control Panel Instruction Manual 15017
MS-9200 Fire Alarm Control Panel Instruction Manual 51003
MS-9600 Fire Alarm Control Panel Instruction Manual 51335
UDACT-F Instruction Manual 50049
APS-6RF Auxiliary Power Supply Instruction Manual 50893
FCPS-24F Field Charger/Power Supply Instruction Manual 50079
Canadian Requirements for Supervisory Signal 50057
Fire•Lite Device Compatibility Document 15384
Table 1 Related Documentation
Part Number
10
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

2. Inventory

ACM-16ATF Series

Control Modules

ACM-16ATF
Incorporates 16 red “point active” and 16 yellow “trouble” LEDs, 16 momentary touch-pad switches for controlling each point, a system trouble LED, an On-line/Power LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator.
Height = 8-3/8" (21.27 cm) Width = 4-3/8" (11.11 cm).
Note: In Canada this module must be used to annunciate the fire alarm input points/zones only.
ACM-16ATCS4F (for use in Canada)
The ACM-16ATCS4 contains 12 red “point active”, four yellow “point active”, and 16 yellow “trouble” LEDs, 16 momentary touch-pad switches for controlling each point, a system trouble LED, an On-line/Power LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator.
Note: In Canada this module must be used to annunciate supervisory and burglary signals from associated points/zones.
ACM-16AT.cdr
ACM-16ATYF
Same as the ACM-16ATF, except that all LEDs are yellow (yellow On/Alarm and yellow Trouble).
Note: In Canada this module must be used to annunciate supervisory and burglary signals from associated points/zones.
Note: In Canada the color red may only be used to indicate active alarm inputs. The color yellow may be used to indicate supervisory, burglary and trouble signals, and the color green may be used to indicate the presence of power, or an activated output.
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
11
2. Inventory ACM-16ATF Series

Expander Modules

AEM-16ATF
Expands the ACM-16ATF Series by 16 system points. The unit is identical in size and in frontal appearance to the control module. One to three of these expander modules can be supported by a control module to a maximum of 64 system points.
Note: The AEM-16ATF Series cannot be used to expand the ACM-32AF. Expander LED colors need not match the control module LED colors for the expander to operate.
12
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
ACM-32AF Series 2. Inventory

ACM-32AF Series

Control Modules

ACM-32AF
This control module contains 32 red “point active” LEDs, a system “trouble” LED, an On-line/Power LED, and a local piezo sounder with a silence/acknowledge switch for audible indication of alarm and trouble conditions at each annunciator.
Height = 8-3/8" (21.27 cm) Width = 4-3/8" (11.11 cm).
Note: In Canada this module must be used to annunciate the fire alarm input points/zones only.

Expander Modules

AEM-32AF
Expands the ACM-32AF Series by 32 system points. This unit is identical in size and frontal appearance to the control module. One expander module can be supported by a control module providing a maximum of 64 points.
Note: The AEM-32AF cannot be used to expand the ACM-16ATF Series control modules.
ACM-32A.cdr
Note: In Canada the color red may only be used to indicate active alarm inputs. The color yellow may be used to indicate supervisory, burglary and trouble signals, and the color green may be used to indicate the presence of power, or an activated output.
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
13
2. Inventory Cabinet & Panel Hardware

Cabinet & Panel Hardware

Surface-Mount Backboxes

ABS-1F

This surface mounted backbox provides for the remote mounting of a single ACM-16ATF Series or ACM­32AF Series annunciator in a surface-mount enclosure. Knockouts are provided for use with 1/2" conduit. The annunciator mounts directly to the box without a dress plate.
Height = 8-1/2" (21.59 cm) Width = 4-1/2" (11.43 cm) Depth = 1-3/8" (3.49 cm).
ABS-2F
This surface mounted backbox provides for the surface mounting of an annunciator-expander combination. Knockouts are provided for use with 1/2" conduit. The annunciator module mounts directly to the box without a dress plate.
Height = 8-1/2" (21.59 cm) Width = 8-15/16" (22.7 cm) Depth = 1-3/8" (3.49 cm).
Note: The ABS-1F and ABS-2F will not support the installation of the AKS-1 Annunciator Key Switch.
50439d2.tif
ABS-1TF
The ABS-1TF is a surface mounted backbox for mounting one ACS Series annunciator. This backbox has an increased depth that allows mounting of the AKS-1 Annunciator Key Switch.
Height = 9-15/16" (25.24 cm) Width = 4-5/8" (11.75 cm) Depth = 2-1/2" (6.35 cm).
14
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
Cabinet & Panel Hardware 2. Inventory

Flush-mount Backboxes

ABF-1F
This flush mounted backbox provides for the remote mounting of a single annunciator module in a flush-mount enclosure. Knockouts are provided for use with 1/2" conduit. Includes a trim plate, mounting hardware, and an adhesive-backed annunciator label for the dress plate (15824).
Height = 9-15/16" (25.24 cm) Width = 4-5/8" (11.75 cm) Depth = 2-1/2" (6.35 cm).
Trim Plate dimensions ­11" (27.94 cm) x 6-1/4" (15.875 cm)
ABF-2F
This flush mounted backbox provides for flush mounting of one annunciator­expander combination. Includes a trim plate and an adhesive-backed annunciator label for the dress plate (15824).
50439d3.tif
Height = 8-1/2" (21.59 cm), Width = 8-15/16" (22.7 cm) Depth = 1-3/8" (3.49 cm)
Trim Plate dimensions - 11" (27.94 cm) x 10-5/8" (26.99 cm)]
ABF-4F
This flush mounted backbox provides for the remote mounting of one to four annunciator modules. Knockouts are provided for use with 1/2" conduit. Includes a trim plate and an annunciator label.
Height = 9-15/16" (25.24 cm) Width = 17-3/8" (44.13 cm) Depth = 2-1/2" (6.35 cm).
Trim Plate dimensions ­11" (27.94 cm) x 19-3/8" (49.21 cm)
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
50439d1.tif
15
2. Inventory Cabinet & Panel Hardware

Semi Flush-mount Backboxes

ABF-1DF
This backbox mounts one Annunciator module and includes an attractive smoked glass door with keylock.
Box dimensions ­Height = 9-15/16" (25.24 cm) Width = 4-5/8" (11.75 cm) depth = 2-1/2" (6.35 cm).
Door dimensions ­Height = 10.713" (27.21 cm) Width = 6" (15.24 cm) Depth = 0.75" (1.9 cm).
ABF-2DF
Same as ABF-1DF except that two modules can be mounted.
Box dimensions ­Height = 9-15/16" (25.24 cm) Width = 9-3/16" (23.37 cm) Depth = 2-1/2" (6.35 cm)
Door dimensions ­Height = 10.713" (27.21 cm) Width = 10.375" (26.35 cm) Depth = 0.75" (1.9 cm).
ABF-1DF.cdr
16
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
Cabinet & Panel Hardware 2. Inventory

Additional Hardware

ABM-1
The Annunciator Blank Module is a two-sided dress plate identical in appearance to the front panel of the ACM-16ATF module on one side, and the front panel of the ACM-32AF module on the other side. The blank module covers unused module positions in the annunciator backbox or dress panel.
Height = 8-3/8" (21.27 cm), Width = 4-3/8" (11.11 cm).
AKS-1F
The Annunciator Key Switch provides access security for the control switches on the ACM-16ATF Series. The key switch kit includes a key and hardware for mounting to the trim plate of a flush-mount type annunciator enclosure. Also included is an adhesive-backed Annunciator Label for use with the key switch/dress plate assembly.
Note: The AKS-1F can only be employed with a flush-mount type backbox.
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
17
2. Inventory Cabinet & Panel Hardware
NOTES
18
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01

3. Design Considerations

Limits

The standard Fire•Lite EIA-485 circuit can drive up to 32 annunciators or expanders. The number of annunciators that can engage in two-way communication is dependent on the number of addresses available with a given fire alarm control panel. The actual number of annunciator/expander modules that can be powered in a particular system depends on the current available from the control panel’s power supply.
Note: Refer to the instruction manual of the particular Fire Alarm Control Panel for more details.

Wire Runs

Communication between the control panel and the annunciator occurs over a power-limited 2-wire EIA-485 serial interface. This communication is supervised by the fire alarm control panel. Each annunciator/expander module also requires a filtered 24 VDC power connection. This power circuit is inherently supervised; loss of power registers as a communication failure at the control panel.
Fire Alarm Control Panel
ACS Power
Filtered & Power-limited
Annunciator
EIA-485 Circuit
(two-wire)
Power-limited & Supervised
Figure 1 Wire Run Diagram

Wiring Specifications

The EIA-485 circuit cannot be T-Tapped; it must be wired in a continuous fashion. The maximum wiring distance is 6,000 feet at 16 AWG. The wiring size must be a 12 AWG to 18 AWG twisted shielded pair cable having a characteristic impedance of 120 ohms, +/- 20%. Limit the total wire resistance to 100 ohms on the EIA-485 circuit, and 10 ohms on the annunciator power circuit. Do not run cable adjacent to, or in the same conduit as, 120 volts AC service, “noisy” electrical circuits that are powering mechanical bells or horns, audio circuits above 25 volts RMS, motor control circuits, or SCR power circuits.
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
ACSf-wirerun.cdr
19
3. Design Considerations Receive Only and Transmit/Receive

Receive Only and Transmit/Receive

For redundant annunciation of system points, annunciators can be configured as “Receive Only” annunciators. Receive Only annunciators must be set to the same address as the annunciators they duplicate. Receive Only annunciators intercept information being transmitted to a “Receive/Transmit” annunciator for duplication at an intermediate display location. When configured for Receive Only operation, they cannot be used to send information to the system, and as a result are not supervised by the control panel. They cannot perform remote functions such as Acknowledge, Silence, or Reset. Control switches on Receive Only annunciators can be used only for local functions, such as Lamp Test. Wiring to Receive Only annunciators may be supervised by installing the modules “upstream” of fully supervised, Receive/Transmit annunciators along the EIA-485 line.
Annunciators that are configured to serve as full function annunciators can both receive status information as well as transmit commands to the control panel. This allows the annunciator to remotely execute functions of the control panel in addition to displaying the status of the system.
Fire Alarm
Control Panel
“Receive Only” Annunciator set to address “X” and installed upstream.
Full Function “Receive/Transmit” Annunciator set to address “X”.
Figure 2 Receive/Transmit Annunciator Diagram
Two-wire
EIA-485
Circuit
Annunciator
Annunciator
Expander
ACSf-RTannun.cdr
Expander
20
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
Electrical Ratings 3. Design Considerations

Electrical Ratings

Input Voltage: 24 VDC (must be filtered and power-limited).
Current Draw from 24 VDC Input: Standby Alarm
ACM-16ATF & ACM-32AF Series 0.040 amps 0.056 amps
AEM-16ATF & AEM-32AF Series 0.002 amps 0.018 amps
Data Communications Port: EIA-485 operating at 20 Kbps (must be power­limited).

Annunciator Power Requirements

Annunciators draw their power from the control panel and must be considered when calculating the primary and secondary power supply requirements for the system. Each annunciator module is accounted for in the power calculations outlined in the respective installation manual. However, if the current draw dedicated to the annunciators must be calculated as a separate figure, use the equations below:
Number of ACM modules [ ] X 0.040 = [ ] amps
Note: The 0.040 amps can be reduced to 0.030 for modules with Piezo Disable or Flash Inhibit modes selected.
Number of AEM modules [ ] X 0.002 = [ ] amps
Total Annunciator Standby Current = [ ] amps
Number of ACM and AEM modules assumed to be in alarm simultaneously
Note: This entry assumes that all LEDs are lit simultaneously. When the alarm system specification permits, calculations can be based on a 10% alarm loading capacity. For 10% capacity, enter 10% of the total number of ACM and AEM modules multiplied by the number of remote annunciator locations, but do not enter less than one.
Total Annunciator Alarm Current = [ ] amps
Table 2 Calculation of Power Requirements
ACM-16ATF/ACM-32AF Manual PN 51480:A0 02/02/01
[ ] X 0.016 = [ ] amps
21
Loading...
+ 47 hidden pages