Fire Fighting Enterprises FIRERAY 5000 User Manual

Motorised Infrared
Optical Beam Smoke Detector
User Guide
EN
50cm
8-100m
50cm
1. General Information
50cm
50cm
8-100m
Ensure clear line of
Mount on solid surfaces (structural wall or girder) sight from Detector to Reflector
50—100m = 4
18—50m = 1
8—18m = 1
Use Short Range Mask
• All installations should comply with local regulations
• For detectors approved to UL268 refer to NFPA72 for installation guidance. In such installations, it is advised that the maximum distance of Detector and Reflector from the ceiling must be 10% of the distance between floor and ceiling
• Position beam as high as possible, but with a minimum distance of 0.5m from Detector and Reflector to ceiling.
• Mount Detector and Reflector directly opposite each other
• Do NOT position Detector where personnel or objects can enter the beam path
• Do NOT position 2 Detectors facing each other
• Detector LED indicator must face downward
• Do NOT install the Detector or Reflector in environments where condensation or icing are likely to occur
2
2. Fitting the Product
LED indicator must face downward
Clip PCB into base
Insert Detector cable
3
3. Wiring Diagrams
Wiring two Detectors onto two Zones:
To Detector 1 To Detector 2
DET 1 DET 2
Fire
Con A
1 2 3 1 2 3
N/O COM N/C N/O COM N/C
EOL
see
note 1
N/O COM N/C N/O COM N/C
1 2 3
Con C
Fire
Fault
Con B
1 2 3
Con D
Fault
14V - 36V DC
Ext
Reset
see
note 1
Zone 1 ­Zone 1 +
Ext Reset
Supply + Supply -
Zone 2 + Zone 2 -
EOL
• Note 1: This component is the fire resistor. Its value is specified by the Fire Control Panel manufacturer. For U.S. installations it is typically a short circuit
• ALWAYS use a separate 2-core cable for each Detector head
• CAUTION: For system monitoring - Do not use looped wire under any terminals. Break wire run to provide monitoring of connections
• Components not supplied:
• End Of Line ('EOL') component - supplied by Fire Control Panel manufacturer
• Fire Resistor
• After installation, check operation of Fire and Fault connection on Fire Panel
• Apply a voltage of 5V to 40V to ‘Ext Reset’ contact for at least 2 seconds to clear a latched fire condition
4
3. Wiring Diagrams (continued)
Relay connections for wiring the two Detectors of one Controller onto one Zone:
EOL
N/O COM N/C N/O COM N/C
1 2 3
Con D
Fault
Zone 1 ­Zone 1 +
1 2 3
Fire
Con A
1 2 3 1 2 3
N/O COM N/C N/O COM N/C
see
note 1
Fault
Con B
Con C
Fire
For wiring to other types of Fire Control Panel, or to wire multiple Controllers onto one Zone, refer to additional installation instructions supplied with the product
5
4. Apply power
NOTE: One System Controller can be used to control and monitor up to two Detector heads. The ‘#’ symbol in this guide is used to represent the number of the Detector currently selected (1 or 2).
5 seconds
5 seconds
5 seconds
• Commissioned system:
• Detectors have been found but the selected Detector is not aligned:
• Detector is connected but not ‘Found’ (normal on uncommissioned system):
• Communications fault, or no Detector connected:
6
5. Enter Pass Code to Access Engineering Menu
Press for Pass Code screen:
Default Pass Code: 1 2 3 4
Change digit
Move between digits
Accept
An incorrect Pass Code will return the display
to the Pass Code entry screen
Three incorrect attempts will lock access for three minutes
6. Find Detectors
‘Find’ is automatically displayed the first time this process is run. ‘Find’ can also be accessed
in the System Controller settings menu. Find must be performed when adding or removing a detector to an already ‘Found’ system.
60 seconds
This will be the number of Detectors found
Press to enable ‘Found’ Detectors at any point during 60s countdown
Any unused Detector channels are switched off
Press to re-scan if number is incorrect
7
7. Select Power Mode
In ‘Hi A’ mode (default), during
normal operation the system will take 5.5mA if one Detector is connected or 8mA if two Detectors are connected. During Laser targeting, Auto, Hand and Home functions, the system will take 36mA.
In ‘Lo A’ mode (selected via the System Controller settings menu), the system will take
5.5mA or 8mA in ALL modes of operation. The Detector will move more slowly during Align, Laser targeting and Home, so it is recommended to leave the system set to ‘Hi A’ if the current is available.
8. Select Detector
Select Detector to be accessed
All Detectors need to be aligned separately
Steps 9 to12 explain how to align individual Detectors
2
1
9. Select Distance between Detector and Reflector
Select 8- 50m (default) or 100m
(Set for each Detector)
8
10. LASER Targeting
The system will signal Fault while in this mode
The LASER is used to align the Detector with the Reflector. It is an approximate alignment tool only. After Auto-Align the LASER will not necessarily be pointing on the Reflector
• Use to move the LASER as close to the Reflector as possible
• One press of an arrow key results in one movement of the Detector head
• Press or to turn off the LASER and return to the Settings menu
• Refer to Additional Detector Information for troubleshooting if LASER is not visible
DANGER
LASER RADIATION - AVOID DIRECT EYE EXPOSURE
POWER OUTPUT < 5mW
CLASS IIIa LASER
Wavelength 630 - 680 nm
11. ‘Auto’ Alignment
• Select ‘Auto’ to automatically align the infrared beam
• Signal Strength will be shown during Alignment
• If the LASER is turned on it will not necessarily be pointing on the Reflector after ‘Auto’ is run - this is normal
• If ‘Auto’ ends with an error code ‘E- ’, refer to troubleshooting
HiA: 2 minutes
LoA: 25 minutes
9
12. ‘Set’ 0/100 (Calibrate)
When ‘Set’ is displayed press whilst the Reflector is still uncovered
When ‘S-00’ is displayed, cover the Reflector with a non- reflective material and leave
covered, then press
When ‘S-01’ is displayed, uncover the Reflector and leave uncovered, then press
Repeat Steps 8 to 12 for any other Detectors found during the ‘Find’ process
13. System is Aligned
Green LED on Detector will flash every 10 seconds, and Signal Strength should be between
99% and 101%
Default values: 35% Fire Threshold, 10 second delay to Fire and Fault, Non-Latching mode
10
14. Manual Fire and Fault Tests
After installation or cleaning, it is recommended that a manual Fire and Fault test is performed:
Fire Test: Cover the Reflector slowly so that it takes longer than 5 seconds to cover. The System Controller will signal Fire to the Fire Control Panel after the delay to fire has expired (10s default)
Fault Test: Cover the Reflector completely within 2 seconds. The System Controller will signal Fault back to the Fire Control Panel after the delay to fault has expired (10s default)
15. Remote Fire Test
It is possible to perform a Fire Test from the System Controller, to test the wiring to the Fire Control Panel
NOTE: The Remote Fire Test is acceptable for Fire Authority Acceptance and Routine Maintenance per UL268-5
Detector Fire LED Test
Detector will signal Fire, System Controller will stay Normal. Press to exit without performing the test
Relay/Controller Wiring Test
System Controller signals ‘Fire’ to Fire Control Panel Press or to exit
11
16. Fire Threshold
This setting is the threshold at which the Detector will detect a fire Default factory setting=35%
(Set for each Detector)
Sensitivity can be adjusted in 1% steps by pressing up or down keys
Press to accept setting
UL268 Fire Threshold Ranges:
Distance between Detector and Reflector
8—10m (26.2—32.8ft) 10—18%
10—15m (32.8—49.2ft) 15—25%
15—22m (49.2—72.2ft) 15—35%
22—40m (72.2—131.2ft) 25—50%
40—60m (131.2—196.8ft) 35—50%
60—100m (196.8—328.1ft) 50%
EN Approved Sensitivity Ranges:
Complies with EN54-12 for sensitivity levels between 25% and 35% with a maximum delay to fire of 20 seconds
Fire Threshold Range
12
17. Fire/Fault Delay
These settings are the delays that the System Controller uses before signalling a FIRE or FAULT condition respectively to the Fire Control Panel. Default factory setting=10 seconds
(Set for each Detector)
elay 2 (Fault)
Delay 1 (Fire)
D
18. Latching/Non-Latching Mode
In Latching Mode the system will stay in Fire condition after the fire clears. In Non-Latching Mode the system will automatically return to normal condition after the fire clears
(Set for each Detector)
Non-Latching
Latching
Use to move between icons in the
Detector Menu, until the graph and bell icons
are shown
To clear a latched fire, apply 5-40V to the External Reset terminal, enter the passcode, or power cycle for 20s
13
19. Cleaning the System
The system will automatically compensate for dust build-up by changing the Compensation Level.
However, it is recommended that the Detector lenses and the Reflector are cleaned periodically with a soft lint-free cloth.
If the Compensation Level for a particular Detector remains above 130 for several days, this indicates that cleaning should take place on that Detector.
The system should be isolated from the Fire Control Panel before cleaning takes place.
After cleaning, verify that the system is operating normally:
If the Signal Strength is between 92% and 108%
- leave the system to compensate back to 100% (this should take no more than 12 hours)
If the Signal Strength is above 108%
- reduce Compensation Level until Signal Strength is 92—108%, and wait for system to compensate back to 100%
If the Signal Strength is below 92%
- perform LASER Targeting, Auto-Align, and Set.
How to change Compensation Level:
14
20. Troubleshooting
E-00
E-01
E-02
E-03
AIM not recognised
Detector Communications Error
Detector is connected but not ‘Found’
Compensation limit reached
• Refer to manufacturer for technical assistance
• Check wiring between System Controller and Detector (Voltage to Detector should be 11—13V)
• Follow ‘Find’ process and align if necessary
• Clean and realign system
Compensation
E-08
Level Not Zero during ‘SET’
Signal Strength Out of Range
E-09
when ‘SET’ selected
Reflector Not
E-10
Found during Auto-Align
Auto-Align
E-11
Failed
• Re-align Detector using Auto­Align
• Ensure Reflector uncovered when ‘SET’ selected
• Ensure clear line of sight from Detector to Reflector for a radius of 0.5m
• Ensure correct distance has been selected
• Ensure correct Reflectors have been used
• Realign Detector
• Ensure clear line of sight from Detector to Reflector for a radius of 0.5m
• Ensure correct distance has been selected
• Ensure correct Reflectors have been used
• Realign Detector
• Ensure clear line of sight from Detector to Reflector for a radius of 0.5m
• Ensure correct distance has been selected
• Ensure correct Reflectors have been used
• Realign Detector
E-04
E-05
E-06
E-07
Detector missed too many readings
Detector is not aligned
Rapid Obscuration Fault
Signal Too High Fault
• Check voltage to Controller.
• Check voltage to Detector is >11V
• Follow alignment procedure
• Ensure clear line of sight from Detector to Reflector
• Ensure clear line of sight from Detector to Reflector
• Ensure there is no strong light on Detector
Cannot Zero During ‘S-00’ in ‘Set’
E-12
Signal did not decrease when ‘S-00’ selected
No Signal During ‘S-01’ in ‘Set’
E-13
Signal did not increase when ‘S-01’ selected
‘Centre’ Stage of Alignment Failed
Detector has
E-14
aligned on something other than the Reflector
Power too low
E-21
fault
• Ensure Reflector was completely covered with a non­reflective material
• Re-align Detector using Auto­Align
• Ensure Reflector was uncovered when ‘S-01’ was selected
• Ensure clear line of sight from Detector to Reflector for a radius of 0.5m
• Check power supply to Controller
15
21. Technical Specifications
Parameter Value
Operating Voltage 14—36V DC
Operating Current – Normal Operation
(including fire or fault activated)
Operating Current – Alignment modes - HiA
Alignment modes - LoA
Fire Threshold Range
Delay to Fire 2—30 s
Delay to Fault 2—30 s
Operating Distance between Detector and Reflector 8—100 m
Maximum angular misalignment of Detector ± 0.3 Deg
Maximum angular misalignment of Reflector ± 5 Deg
Maximum angular movement of Detector head ± 3.5 Deg
Optical wavelength 850 nm
Rapid Obscuration Fault threshold 87%
Operating Temperature (UL Approved) 0—+37.8 Deg C
5.5mA - 1 Detector 8mA - 2 Detectors
36mA
5.5mA / 8mA
0.45—3.98 dB 10—60%
Operating Temperature (EN54-12 Approved) -10—+55 Deg C
Operating Temperature (FM Approved) -20—+55 Deg C
Storage temperature -40—+85 Deg C
Relative Humidity (non condensing) 93%
IP Rating IP54
Relay Contact Rating
Maximum Cable Length (Controller to Detector) 100 m
Cable Gauge
Housing Flammability rating UL94 V0
UL File S3417
CPD Certificate Number 0832-CPD-0565
Dimensions
System Controller, including base 202 (8.0) 230 (9.1) 81 (3.2) 1.0 (2.2)
Width, mm (in)
Height, mm (in)
VFCO, 2A@30VDC Resistive
24—14 AWG
0.5—1.6 mm
Depth, mm (in)
Weight, kg (lb)
Detector, including 'easy fit' base 135 (5.3) 135 (5.3) 135 (5.3) 0.5 (1.1)
Reflector (Single) 100 (3.9) 100 (3.9) 10 (0.4) 0.1 (0.2)
Document Number: 0044-033-04-EN
16
Loading...