Fire Fighting Enterprises FIRERAY 5000 User Manual

Motorised Infrared
Optical Beam Smoke Detector
User Guide
EN
50cm
8-100m
50cm
1. General Information
50cm
50cm
8-100m
Ensure clear line of
Mount on solid surfaces (structural wall or girder) sight from Detector to Reflector
50—100m = 4
18—50m = 1
8—18m = 1
Use Short Range Mask
• All installations should comply with local regulations
• For detectors approved to UL268 refer to NFPA72 for installation guidance. In such installations, it is advised that the maximum distance of Detector and Reflector from the ceiling must be 10% of the distance between floor and ceiling
• Position beam as high as possible, but with a minimum distance of 0.5m from Detector and Reflector to ceiling.
• Mount Detector and Reflector directly opposite each other
• Do NOT position Detector where personnel or objects can enter the beam path
• Do NOT position 2 Detectors facing each other
• Detector LED indicator must face downward
• Do NOT install the Detector or Reflector in environments where condensation or icing are likely to occur
2
2. Fitting the Product
LED indicator must face downward
Clip PCB into base
Insert Detector cable
3
3. Wiring Diagrams
Wiring two Detectors onto two Zones:
To Detector 1 To Detector 2
DET 1 DET 2
Fire
Con A
1 2 3 1 2 3
N/O COM N/C N/O COM N/C
EOL
see
note 1
N/O COM N/C N/O COM N/C
1 2 3
Con C
Fire
Fault
Con B
1 2 3
Con D
Fault
14V - 36V DC
Ext
Reset
see
note 1
Zone 1 ­Zone 1 +
Ext Reset
Supply + Supply -
Zone 2 + Zone 2 -
EOL
• Note 1: This component is the fire resistor. Its value is specified by the Fire Control Panel manufacturer. For U.S. installations it is typically a short circuit
• ALWAYS use a separate 2-core cable for each Detector head
• CAUTION: For system monitoring - Do not use looped wire under any terminals. Break wire run to provide monitoring of connections
• Components not supplied:
• End Of Line ('EOL') component - supplied by Fire Control Panel manufacturer
• Fire Resistor
• After installation, check operation of Fire and Fault connection on Fire Panel
• Apply a voltage of 5V to 40V to ‘Ext Reset’ contact for at least 2 seconds to clear a latched fire condition
4
3. Wiring Diagrams (continued)
Relay connections for wiring the two Detectors of one Controller onto one Zone:
EOL
N/O COM N/C N/O COM N/C
1 2 3
Con D
Fault
Zone 1 ­Zone 1 +
1 2 3
Fire
Con A
1 2 3 1 2 3
N/O COM N/C N/O COM N/C
see
note 1
Fault
Con B
Con C
Fire
For wiring to other types of Fire Control Panel, or to wire multiple Controllers onto one Zone, refer to additional installation instructions supplied with the product
5
Loading...
+ 11 hidden pages