Fire Fighting Enterprises FireRay 100R, FireRay 50 User Manual

®
FIRERAY50/100R
OPTICAL BEAM SMOKE DETECTOR
Doc. No: 32-0008-01
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
OPTICAL BEAM SMOKE DETECTORS
This training material provides information to assist the Fire System
Designer and Installer in achieving a successful Optical Beam Smoke
Detector installation. The appropriate local installation standards and legislation in effect
at the time of installation must be adhered to and take precedence
over any statements made or implied by this training material.
Fire Fighting Enterprises cannot take responsibility for the
installation (beam positioning and mounting), commissioning or
maintenance of products.
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
AGENDA
AGENDA
•WHAT IS FIRERAY50/100R?
INSTALLING FIRERAY50/100R
COMMISSIONING FIRERAY50/100R
•USING FIRERAY50/100R
MAINTAINING FIRERAY50/100R
TECHNICAL SPECIFICATIONS OF FIRERAY50/100R
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
OVERVIEW
Optical Beam Smoke Detector (Reflective)
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Fireray 50/100R is a reflective type beam detector comprising a transmitter and receiver contained within one enclosure. It transmits an Infrared beam that is reflected from a retro reflector on the opposite wall, back to the internal receiver for analysis. Fireray50/100R reports its status back to the alarm/fire panel or monitoring device.
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
VERSIONS OF FIRERAY50/100R
There are three different types Fireray50/100R:
•Conventional
• Analogue Addressable
• Zone Powered
All of these types are available in either:
• (5 to 50m) or (50 to 100m) versions
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
The FIRERAY50/100 comes in two ranges - 5m to 50m and 50m to 100m.
There are a number of variants available in these two ranges.
Conventional:
50RV / 100RV – Standard conventional beam with EN54-12 and CPD approval. Typically used in Europe. 50RU / 100RU – Standard conventional beam with UL and ULC approval. Typically used in United States and other countries requiring UL approval.
We also do Analogue Addressable and Zone Powered versions for various customers.
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
WHY USE THE FIRERAY50/100R?
3 year warranty
Designed, fully assembled and tested at FFE factory
International Approvals including EN54:12 and UL
Minimal reflective prisms versus range
Note: If more flexibility is required consider the FIRERAY5000
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Any FIRERAY50/100 returned under warranty is replaced with new product without question, provided the fault is due to a manufacturing fault. We conduct full tests to establish and resolve causes of failures, improving product quality. FFE have full control over product quality and minimising customer lead times. Fully approved by all the internationally recognised authorities including LPCB, UL, VdS, VNIIPO (Russia) Needs only 1 reflective prism for 5 to 50m and only 4 prisms for 50 to 100m. Adjustable brackets, brackets to hold reflective prisms (surface mount or adjustable).
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
OUT OF THE BOX
BREAKDOWN OF PARTS
Detector
Reflector
(Fly lead
connected to
Test Filter
detector)
User Guide
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
The FIRERAY50/100 can be broken down into 2 key elements.
The Detector
Transmits and receives the infrared and then communicates the status to the alarm/fire panel or device monitor.
The Reflector
Reflects the infrared from the transmitter lens along the same path back onto the receiver lens. The number of Reflectors required depends on the operating distance. 5 to 50m = 1 Reflector 50 to 100m = 4 Reflectors. Note the additional 3 reflectors required for 50 to 100m operation must be purchased separately as the Long Range Kit.
Additional components
In the box one will also find the User Guide, test filter and the fly lead for the detector. No End-Of-Line components or Fire resistors are provided as these components are fire panel specific and as such are normally provided by the fire panel manufacture.
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
INSTALLATION & WIRING
FOR 50/100RV & RU
FIRERAY50/100R to the Fire System
•Cables
Typical Single Zone Wiring
Multiple Detectors On Single Zone Wiring
Mounting of the Detector
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
INSTALLING THE FIRERAY50/100R TO
THE FIRE SYSTEM
Detector mounted at high level
Reflector
Fly Lead
Junction Box for fly lead to fire proof
Protected Area
cable connection
Dedicated fireproof
Fire Panel
screened cable (1 to 100m)
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
The Detector and Reflector must to be mounted to a secure structure. The fly lead that is supplied with the detector should not be extended, but rather wired into a termination box where it is interfaced to the fire proof cable that goes back to the fire panel.
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
CABLES
It is always advisable to have a dedicated, screened (shielded), fireproof cable for both power and signal lines
Don’t leave the shield of the cable unconnected, always connect it to the earth of the system
Always mount power and signal cables away from any switching machinery or HV (High Voltage) lines
Ensure that any connections are made properly. Intermittent connections are very difficult to trace and cause problems that are not easy to diagnose.
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Wiring up other equipment with the same cable that is used to monitor or power the detector can lead to unexpected behavior. It is always best to have a dedicated, screened cable for the power and the zone wiring. Also avoid the temptation to place the wiring in the same conduit that may be carrying cables that are used for large switching machinery or high voltage cables. These can sometimes cause problems due to mutual induction. Although it is possible to have a long power cable or zone cable, it is always worth remembering that that shorter the cable the less the risk of there being any interference on the cable.
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
TYPICAL SINGLE ZONE WIRING
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
The diagram can be found in the installation guide for the FIRERAY50/100. Zone wiring – sometimes called a ‘Conventional’ system. Note: External PSU, end-of-line device (EOL device), and fire resistor are not supplied by Fire Fighting Enterprises. The EOL and fire resistor are specified by the fire panel manufacturer. The power supply should be able to supply a minimal current of 20mA (between
10.2 to 30v DC to power 1 FIRERAY50/100). Power should not be applied until all wiring has been completed. EOL Device and fire resistor are either supplied or specified by the switch monitor manufacturer. A complete fire and fault test of the FIRERAY50/100 should be conducted to ensure correct wiring to the fire panel.
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
MULTIPLE DETECTORS ON SINGLE ZONE
WIRING
TECHMAINTAIN
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
In the event that more than one detector is connected to a “Zone” it is important to ensure that the fire panel or device monitor is capable of checking for “Detector out faults”. It is also crucial that the schottky diode is inserted, failing to do so will not allow a detector further down the zone wiring to report a fire condition if a detector preceding it goes into a fault condition, as it will break the line to remove the EOL component from the zone.
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
MOUNTING OF THE DETECTOR
Do
Do… Mount onto a secure
structure.
Do… Fasten all mounting
points before aligning.
Do… Mount where both
thumb screws and mode switch are accessible.
Do… Use the correct number
of reflectors for the required distance.
Don’t… Mount onto the skin
of a building.
Don’t… Remove the detector
from the mounting to switch the mode switch.
Don’t… Use a single piece of
uni-strut to mount the detector from the main structure.
Don’t… Mount anywhere near
open louvres that could allow condensation to build up.
Don’t… Mount where there
will be direct sunlight on the detector, consider the path of the sun all year round.
Do Not
USECOMMISSIONINSTALLWHAT
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
TECHMAINTAIN
It is not always obvious to installers but one of the crucial elements of a beam type detector is its mounting! The detector is designed to compensate for a certain amount of building movement, it is not designed for poor installation. One of the most useful pieces of kit a installer can have on his possession is a laser pointer. By mounting this onto the mounting where the beam is going to go will give you a great deal of information about the sturdiness of the mounting setup.
If one considers that the beam has a angle of misalignment of 0.8 Degrees then there is not much required to move the beam off alignment. This is why it is crucial that the beam in not mounted on plaster board, single pieces of hanging uni-strut… etc...
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
BEAM SETTINGS PRIOR TO ALIGNMENT
Mode Switch
DIP SWITCH
SETTINGS
ON
1234
1
X2X XX X
X
X
X
X
XXX XXXX X
ON
4321
3X4
X
X
DIP Switches
ON
321
4
Shows defaults
INSTALL
USECOMMISSIONINSTALLWHAT
TECHMAINTAIN
Prior to alignment, the user should select the alarm threshold to suit the environment using the switches shown. See next slide. Alarm thresholds of 12, 25,35 and 50% can be selected. The Default setting is 35%.
The alarm relay can be set in one of two modes – Auto reset or alarm latching using switch 1. Auto reset is the factory default setting. Auto reset mode will reset the alarm relay and alarm LED 5 seconds after received signal has recovered to a level above the alarm threshold.
Latching mode holds the alarm relay and alarm LED active indefinitely, until cleared by either: placing the beam into prism targeting or alignment mode and then going back to run mode, or Removing the power to the beam for 10 seconds before powering back up
Copyright © 2008-2010 Fire Fighting Enterprises Ltd.
Loading...
+ 32 hidden pages