Fire Fighting Enterprises FIRERAY 2000 User Manual

FIRERAY
FEATURES
2000
Range 10 – 100 Metres
Optical Beam Smoke Detector
11.5Vdc to 28 Vdc operating voltage
Selectable alarm thresholds
Low current consumption
Ground level electronics
Manual or automatic reset
Automatic contamination compensation
Fire Fighting Enterprises Ltd.
Approved by VdS No. : G 297058 to EN54 Part 12
Fireray 2000 Installation Guide 22318.00.R 25.08.05
System Description
The Fireray 2000 is a linear beam smoke detection system capable of protecting an open indoor area of up to 1500 square metres.
The System comprises a Transmitter which projects a modulated infrared beam over an area to a Receiver, which then for wards a signal to a Control Unit f or analysis. T he System ca n detect smok e particles obsc uring the beam path. When obscured for a predefined length of time the Control Unit will generate an alarm.
Smoke Detection
When smoke i s presen t in th e beam pat h the s ignal rec eived by the Recei ver is re duced rela tive to the densit y of the smoke. If the density of the smoke reduces the signal below a preset threshold for a period of 10 seconds an alarm relay is activated.
There are 3 selectable threshold levels available, 25%, 35%, and 50%. (25% being the most sensitive).
Auto Reset
The alarm relay is configurable and can be either latching or non-latching. If non-latching is selected the alarm relay will reset 5 seconds after the smoke has cleared. If latching is selected the alarm relay will remain set until either a power down reset is performed, or the
Controller Unit receives an external reset.
Automatic Gain Control
The Control Unit supports an Automatic Gain Control (AGC) circuit. Long term degradation of signal strength by the build up of dirt on optical surfaces will not generate an alarm because of compensation provided by the AGC circuit. This operates by comparing the received signal against a standard over a predefined time interval which is nominally 1.5 hours, if the signal strength deviates by more than 7% over this time span the Receiver gain is automatically adjusted to compensate.
Fault Detection
The Control Unit is capable of detecting failures within the System. In the event of a System failure being detected the fault relay is activated.
System failures will be caused by:
The TEST/RESET switch in the Control Unit set to the ON position
Total loss of power or a supply reduction below the specified minimum to the Control Unit.
The System is unable to settle during the power on AGC stabilisation period.
The System AGC circuits have reached the limit of compensation.
The signal has been reduced by more than 93% for approximately 10 seconds.
The beam path is completely blocked.
A Transmitter failure.
Loss of power to the Transmitter.
A Receiver failure.
Misalignmen t of the Transmitter and Receiver resulting in a signal loss of greater than 93%
Fireray 2000 Installation Guide 22318.00.R 25.08.05
2
Detector Positioning
Φ
Υ
It is important that the Fireray 2000 Detector is positioned correctly to minimise the detection time. Experiments have shown that smoke from a fire does not rise directly upwards, but fans out or mushrooms due
to air currents and heat layering effects. The time to signal a fire condition depends on the location of the Detector within the premises, the volume of smoke produced, construction of the roof, and ventilation arrangements.
The maximum distance either side of the beam axis is found to be typically 7.5 metres for satisfactory detection under flat ceilings.
Single Beam
Multiple Beams
0.3m ↔ 0.6m
15 m
MAX
(0.5m 7.5m)
MAX
15 m MAX
(0.5m 7.5m)
MAX
Smoke layerin g, where smoke does not reach the ceiling l evel due to layers of static hot air is over come by mounting the Detector at the recommended height below the ceiling of between 0.3 and 0.6 metres, bringing the infrared beam below the heat layer and into the smoke layer.
However in all i nstallations the national fi re standards for that particu lar country mus t be consulted. If there is any doubt on the correct mounting height, positioning may be determined by smoke tests.
Detector Positioning In Apex Of Sloping Ceiling
A ceiling is defined as sloping if the distance from the top of the apex to the intersection of the ceiling and adjacent wall is greater than 0.6 metres (See fig. 1).
Υ
Χ
Slope if Χ 0.6 Metres
= Pitch angle
=
+
Fig 1 Fig 2
When a Detect or is posit ioned in the apex of a ceiling (See f ig. 2). The lat eral beam dist ance covered (Υ) can be increased in relation to the angle of pitch (Φ).
For Example: If the pitch angle is 20 degrees the lateral coverage can be increased from 7.5 metres either side of the beam
(Υ) to:
Υ = 7.5 + (7.5 x 20/100) metres Υ = 9 metres
Therefore with a roof pitch of 20 degrees the lateral coverage can be increased from 7.5 metres either side of the beam to 9 metres either side of the beam, but only for the beam positioned in the apex. All other calculations remain the same.
This formula can be applied to pitch angles up to and including 25 degrees. Therefore the maximum increase in lateral coverage can be:
Υ = 7.5 + (7.5 x 25/100) metres Υ = 9.375 metres
Pitch angles over 25 degrees must use the maximum lateral figure of 9.375 metres either side of the beam.
Fireray 2000 Installation Guide 22318.00.R 25.08.05
3
Loading...
+ 5 hidden pages