FieldServer FS-8700-24 User Manual

Driver Manual
(Supplement to the FieldServer Instruction Manual)
FS-8700-24 ControlNet
Effective for all systems manufactured after May 1, 2001
Driver Version: 1.06 Document Revision: 7
FS-8700-24 ControlNet Driver Manual Table of Contents
TABLE OF CONTENTS
1. ControlNet Description...................................................................................................3
2. Driver Scope of Supply...................................................................................................4
2.1. Supplied by FieldServer Technologies for this driver ...................................................4
2.2. Provided by the Supplier of 3rd Party Equipment..........................................................4
3. Hardware Connections...................................................................................................5
3.1. Connection Notes.........................................................................................................6
4. Configuring the FieldServer for Unscheduled ControlNet Access with PCCC
messaging .......................................................................................................................7
4.1. Server Side Connection Descriptors.............................................................................7
4.2. ControlNet Node Descriptors........................................................................................8
4.3. Unscheduled Map Descriptors using PCCC messaging ..............................................8
4.3.1. FieldServer Specific Map Descriptor Parameters .....................................................8
4.3.2. Driver Specific Map Descriptor Parameters..............................................................9
4.3.3. Timing Parameters....................................................................................................9
4.3.4. Unscheduled Map Descriptor Example...................................................................10
Appendix A. Advanced Topics............................................................................................11
Appendix A.1. Write-throughs...............................................................................................11
Appendix A.2. Map Descriptor functions...............................................................................11
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 3 of 12

1. ControlNet Description

The ControlNet driver allows the FieldServer to transfer data to and from devices using ControlNet protocol. The SST 5136-CN-ISA Communications Adapter card is included with the FieldServer. The FieldServer can communicate using un-scheduled transfers with PCCC messages embedded in the ControlNet messages.
When the FieldServer originates PCCC messages to communicate with PLC5 controllers, it uses connected messages. This provides fast reliable communication to the other node. When another device originates PCCC messaging, the FieldServer will emulate a PLC5 controller supporting connected or unconnected messages to files N7 through to N32..
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 4 of 12

2. Driver Scope of Supply

2.1. Supplied by FieldServer Technologies for this driver

FieldServer Technologies PART #
SST 5136-CN-ISA
Description
Communication Adapter - complete with BNC Tee
Connector ControlNet Tools CD ControlNet Module User’s Guide (Version 1.00) CNF2BSS.EXE utility FS-8700-24 Driver Manual.

2.2. Provided by the Supplier of 3rd Party Equipment

PART # DESCRIPTION
ControlNet Network with cables and terminators
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 5 of 12

3. Hardware Connections

The FieldServer is connected to the ControlNet Network with 75 ohm coaxial cable. If the ControlNet is not wired in redundant mode, ensure that all connectors are connected to the COM A port. A 75 ohm terminator must be placed at either end of the ControlNet Bus.
SST-5136-CN-ISA
FS-x40
75 O T-pieces
AB
To ControlNet Network
75 O network terminators
(408)-262-2299
FIELDSERVER CONTROLNET
CONNECTION DIAGRAM
BASE NAME: FILE NAME: FS8700-24
DATE: 11/4/05 BY: MC
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 6 of 12

3.1. Connection Notes

Before connecting the FieldServer to the network, the FieldServer MacId should be set. The MacId is the term used for a ControlNet station address. The ControlNet MacId of the FieldServer is set to the System_Station_Address specified in the FieldServer configuration file.
Section Title
Bridge
Column Title Function Legal Values
System_Station_Address Provide MacId for the FieldServer 1-99
Example
// .Bridge Information Bridge
System_Station_Address 5
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 7 of 12

4. Configuring the FieldServer for Unscheduled ControlNet Access with PCCC messaging

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with ControlNet devices using PCCC messaging. This transfer mechanism would be used to communicate between the FieldServer and PLC-5 controllers.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for ControlNet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Nodes” section, and the data to be transferred needs to be mapped in the “Unscheduled Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

4.1. Server Side Connection Descriptors

Section Title
Connections
Column Title Function Legal Values
Adapter Adapter Name ControlNet Protocol Specify protocol used ControlNet
Example
// Connections Connections
Adapter, Protocol ControlNet, ControlNet
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 8 of 12

4.2. ControlNet Node Descriptors

This section of the configuration file defines the different MacIds of the ControlNet devices on the network. If you want to transfer the data on the local ControlNet card to the data­arrays on your FieldServer, typically used when acting as a Server, define a Node_ID with the same value as the System_Station_Address.
Section Title
Nodes
Column Title Function Legal Values
Node_Name Provide name for node Node_ID
Protocol Specify protocol used ControlNet
Example
// ControlNet Nodes Nodes
Node_Name, Node_ID, Protocol PLC_1, 1, ControlNet Local, 5, ControlNet
ControlNet MacId of the node to communicate with
Up to 32 alphanumeric characters
1-99

4.3. Unscheduled Map Descriptors using PCCC messaging

Maintained on the SST 5136-CN-ISA card are 32 integer files (N7-N39) that can be read or written to by other devices on the ControlNet network using PCCC messaging. Client style Map Descriptors are used to transfer data to or from the file buffers on the card to the Data Arrays on the FieldServer.

4.3.1. FieldServer Specific Map Descriptor Parameters

Column Title Function Legal Values
Map_Descriptor_Name
Data_Array_Name Name of Data Array
Data_Array_Offset Starting offset in Data Array Function
Name of this Map Descriptor
Function of Client Map Descriptor
Up to 32 alphanumeric characters One of the Data Array names from “Data Array” section above 0 to maximum specified in “Data Array” section above
RDBC, WRBC, WRBX
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 9 of 12

4.3.2. Driver Specific Map Descriptor Parameters

Column Title Function Legal Values
Node_Name
Block_Number PLC File Number
PCCC_Type
Address Starting address within file
Length Length of Map Descriptor
Note the number of bytes per PCCC_Type: SINT, INT = 2 bytes, REAL, FLOAT = 4 bytes, BOOL, BIT, FLAG = 8 bits per byte
Each PLC file is 2000 bytes long and therefore the address values will range from zero to a maximum value as indicated. The start address is specified in increments of the basic data type specified under PCCC_Type.
The message buffers in the ControlNet card are each 498 bytes long and only one message buffer can be allocated to a Map Descriptor. The Map Descriptor lengths are therefore limited to maximum values as indicated when taking the data type byte lengths into account.
Name of Node to communicate with
Type of PCCC data to be transferred over ControlNet
One of the node names specified in “Node Descriptor” above For local node 7-39
For remote node 1-999 UINT, (SINT, INT) (REAL,
FLOAT) (BOOL, BIT, FLAG) Equal types are shown in brackets. 0 – 999 ( INT, SINT ) 0 – 499 ( REAL, FLOAT ) 0 – 15999 ( BOOL, BIT, FLAG ) 1 – 249 ( INT, SINT ) 1 – 124 ( REAL, FLOAT ) 1 – 3984 ( BOOL, BIT, FLAG )

4.3.3. Timing Parameters

Column Title Function Legal Values
Scan_Interval Rate at which data is polled >0.1s
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
(
)
(
)
FS-8700-24 ControlNet
Driver Manual Page 10 of 12

4.3.4. Unscheduled Map Descriptor Example

The following Map Descriptor will read data from a PLC5.
// Server Side Map Descriptors Map Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Block_Number, PCCC_Type, Address, Length A1, DA_AI3, 0, RDBC, PLC5, 7, SINT, 33, 5
Active Map Descriptor polls the PLC regularly (change to WRBC to write)
Remote Node name of the PLC to poll
PLC 5 file number to
N7:33
read
The following Map Descriptor will send data to the card to allow other nodes to read the data contained in the FieldServer’s Data Array.
// Server Side Map Descriptors Map Descriptors
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name, Block_Number, PCCC_Type, Length Address, A1, DA_AI3, 0, WRBC, Local, 7, SINT, 5 125,
Offset into the file
N7:33
Active Map Descriptor transfers the data to or from the card (change to RDBC to read data written by other nodes)
Node name whose MacId matches the System_Station_Address
PLC 5 emulated file number (7-39)
Offset into the file (N7:125)
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 11 of 12
Appendix A. Advanced Topics
Appendix A.1. Write-throughs
Some FieldServer drivers support “write-throughs”. This is the ability of a Read Map Descriptor to automatically create a temporary write Map Descriptor to update the value of an external R/W (Read or Write) memory location. Since the ControlNet card contains separate Read-Only (Output) and Write-Only (Input) Buffers, write-throughs are not supported on ControlNet messaging, but are supported for PCCC messaging. This is because PCCC messages are embedded within ControlNet messages allowing for the receiving device to process the embedded write message.
Appendix A.2. Map Descriptor functions
The diagram below explains the difference between the use of WRBC (Write Block Continuous) and RDBC (Read Block Continuous) Map Descriptors. Note that WRBC Map Descriptors write data from the FieldServer’s Data Arrays into the output data memory area of the card whereas RDBC Map Descriptors place data from the card’s input data memory area into the FieldServer’s Data Arrays. The IO data memory areas are kept in RAM on the card and are defined by Connection Control Blocks on the card.
FieldServer
Data Array
WRBC Mapdesc
Connection
Block 01
Connection
Control
Block 128
SST 5136-CN Card
Control
Data Array
RDBC Mapdesc
Input data memory
area
Output data memory
area
. . .
Input data memory
area
Output data memory
area
ControlNet
Network
ControlNet Device
Output data memory
area
Input data memory
area
Note:
1. For ControlNet messagi ng the target connection is specified by Node_Name & CN_Instance.
2. For PCCC messaging the target c on ne c tion is specified by Node_Name & Block_Number.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com
FS-8700-24 ControlNet Driver Manual Page 12 of 12
THIS PAGE INTENTIONALLY LEFT BLANK