A Warning identifies conditions and procedures
that are dangerous to the user. A Caution identies
conditions and procedures that can cause damage to
the Product or the equipment under test.
WARNING
To avoid possible electric shock, personal injury or
death, follow these guidelines:
•Use the meter only as specied in this manual;
otherwise, the protection provided by the meter
may be impaired.
•Do not use if meter appears damaged. Visually
inspect the meter to ensure case is not cracked
and back case is securely in place.
•Inspect and replace leads if insulation is damaged,
metal is exposed, or probes are cracked. Pay
particular attention to the insulation surrounding
the connectors.
•Do not use meter if it operates abnormally as
protection maybe impaired.
•Use only correct measurement category (CAT),
voltage, and amperage rated probes, test leads,
and adapters for the measurement.
•Do not use this meter to verify the presence of
hazardous voltages on circuits that may have
voltages generated from frequencies above
1000Hz as the low pass filter limits voltage
measurements to below 1000Hz.
•Do not use during electrical storms or in wet
weather.
•Do not use around explosive gas, dust, or vapor.
•Do not apply more than the rated voltage to,
as marked on the meter, between terminals or
between any terminal and earth ground.
•Do not use without the battery and the back case
properly installed.
•Replace battery as soon as battery indicator
appears to avoid false readings.
•Remove the test leads from the circuit prior to
removing battery cover.
•Do not attempt to repair this unit as it has no
user-serviceable parts.
•Temperature switch prevents leaving
thermocouple plugged in while measuring
voltage.
•Do not measure current while the test leads are
in the input jacks.
•When measuring high frequency AC current,
do not exceed the rated 600AAC of the clamp.
Failure to adhere may cause the clamp to heat
up dangerously.
•Do not use the HOLD function to measure
unknown potentials. When HOLD is turned on,
the display does not change when a dierent
potential is measured.
•Do not use in CAT III or CAT IV environments
without the protective cap of test probe. The
protective cap decreases the exposed probe
metal <4mm. This decreases the possibility of arc
32
Page 3
ash from short circuits.
!
!
!
•Do not place magnet inside Category IV panel.
Place it outside the panel instead.
•Always work with a partner.
•Keep ngers behind the nger guards on the
probes.
CAUTION
To protect yourself, think “Safety First”:
•Voltages exceeding 30VAC or 60VDC pose a shock
hazard so use caution.
•Use appropriate personal protective equipment
such as safety glasses, face shields, insulating
gloves, insulating boots, and/or insulating mats.
•Disconnect circuit power and discharge all highvoltage capacitors before testing resistance,
continuity, diodes, or capacitance.
Before each use:
•Perform a continuity test by touching the test
leads together to verify the functionality of the
battery and test leads.
•Use the 3 Point Safety Method. (1) Verify meter
operation by measuring a known voltage. (2)
Apply meter to circuit under test. (3) Return to
the known live voltage again to ensure proper
operation.
•Use the proper terminals, functions and range for
your measurements.
•Never ground yourself when taking electrical
measurements.
•Connect the black common lead to ground
or neutral before applying the red test lead to
potential voltage. Disconnect the red test lead
from the voltage rst.
All voltage tests: All voltage ranges will
withstand up to 1000VDC/750VAC rms. Do not
apply more than 1000VDC or 750VAC rms.
Symbols used:
Caution, risk of electric shock
Caution, refer to manual.
Ground
Double insulation
WARNINGS
DISCONNECT AND UNPLUG TEST LEADS before opening case.
TEST NCV FUNCTION ON KNOWN LIVE WIRE before using.
DO NOT APPLY VOLTAGE greater than 30VAC/VDC to the
thermocouple or the jacks when the rotary dial is on °F°C. (Use
only Type K thermocouples)
DO NOT APPLY VOLTAGE TO THE JACKS when the rotary dial is on
microamps. Even low voltages can cause a current overload and
potentially harm the meter.
54
Page 4
Description
Your SC480 is the essential clamp meter with
wireless functionality for the HVACR professional.
Send your electrical measurements directly to the
Job Link® System mobile app. Leave the meter
behind a closed blower door and view the current
measurement on your mobile device.
Help determine system eciency by directly
measuring power consumption (W) of the system.
Use this value to inform your customer of energy
saving measures you can take to help them save
money on their energy bills.
The SC480 is great for troubleshooting minisplit systems. Reach those cramped mini-split
connectors with the included RCT2 probe tips
for voltage and resistance measurements. Plus,
measure frequency (Hz) directly with clamp jaw.
Hang your SC480 clamp meter to any metallic
surface with the heavy-duty magnet. See both
voltage and amperage readings at the same time
on the big dual display.
Verify the order of 3-phase voltage lines with
just two leads. Capture L1L2 and L1L3 to check
that motor lines are correctly installed with Phase
Rotation test.
Take more accurate VAC and AAC readings on
variable frequency drives with True RMS sensing
technology. Measure the starting amp draw of a
compressor with Inrush current mode.
Illuminate the way with a powerful LED built into
the clamp jaw. Easily see your measurements with
the bright blue backlight on the display.
Take measurements more safely with one hand
using the single test lead holder. Test leads come
with removable gold plated tips to reliably connect
Fieldpiece accessory heads.
What’s Included
• SC480 Job Link® System Clamp Meter
• ADLS2 Deluxe Test Leads Kit
• ASA2 Alligator Clips
• RCT2 Molex Probe Tips
• ATB1 Type K Thermocouple
• 1 Velcro Strap
• 9V Alkaline Battery (Not installed)
• ANC12 Protective Padded Case
• Operator’s Manual
Quick Start
1. For electrical testing, connect test leads to black "COM"
and red "+" jacks.
2. Rotate the dial to your desired measurement.
3. Connect to test points and read measurement.
4. For temperature testing, remove test leads, slide TEMP
switch to the right and connect a Type K thermocouple.
76
Page 5
Measurements Dial
ZEROA
DC
INRUSH
H/M/m
DC
INRUSH
OFF
Select
H/M/m
ZEROA
DC
°F°C
INRUSH
Sync
OFF
Range
Select
H/M/m
ZEROA
DC
°F°C
INRUSH
Buttons
Illuminate backlight
INRUSH
Activate Inrush AAC capture mode
Activate wireless to connect to Job Link®
System mobile app
Activate and cycle through Hold, Maximum,
minimum, and real-time measurements
(Press for 1 second to clear and exit)
The SC480 is loaded with the measurement
parameters essential for HVACR professionals.
Select the parameter on the dial you want to
measure with the rotating selector switch.
Deactivate autoranging and select the
range manually
Cycle through displayed values on
applicable switch positions
98
Page 6
Display Icons
Battery Life Monitor
Auto Power O Enabled
High Voltage Warning (>30VAC/VDC)
Manual Ranging
Data Hold
Maximum
Minimum
Inrush AAC
Wireless ON to Job Link® mobile app
Watts (Active Power)
Power Factor
Reactive Power
Apparent Power
Fahrenheit
Celsius
Continuity Test
Diode Test
Frequency (Hertz)
Resistance Test (Ohms)
Capacitance Test (farads)
Microamps DC
Nano Unit (10−9, one billionth)
Micro Unit (10−6, one millionth)
Milli Unit (10−3, one thousandth)
Kilo Unit (103, one thousand)
Mega Unit (106, one million)
Alternating Current
Direct Current
Easy to Read Display
Easily see your measurements on the big dual
display. You’ll never miss a reading no matter the
lighting with the bright blue backlight to illuminate
the way.
1110
Page 7
Measurement Dial
Volts AC (VAC) True RMS (50-400Hz)
Test power lines (120 to 480VAC), test 24VAC going to controls and test
Use NCV to check 24VAC from a thermostat or live voltage up to 600VAC.
Always test a known live source before using. A segment graph and RED
LED will display the presence of voltage. An audible beep increases from
intermittent to continuous as intensity of eld (EF) increases.
AC Voltage Detection Range: 24VAC to 600VAC (50-60Hz)
1312
Page 8
Amps AC (AAC) True RMS (50-60Hz)
!
Test isolated power lines. Press SELECT once on VAC/AAC/Hz position.
Read AAC in upper display and VAC on the lower display at the same time.
Measure Hz on variable frequency drive motors. Turn dial to VAC/AAC/
Hz and press SELECT twice. Hz will show in upper display and VAC on the
lower display at the same time.
Range: 10Hz to 400Hz Resolution: 0.1Hz
Accuracy: ±(0.1% + 5)
Minimum current range: >7AAC (10 to 100Hz); >20AAC (100 to
400Hz) on 100AAC range; >25AAC (10 to 400Hz) on 600AAC range.
Overload Protection: 600AAC
Inrush AAC Current
Inrush mode captures the starting amp draw of a motor. Starting amp
draw can assist in diagnosing a motor before it fails.
Activate Inrush mode
1 Rotate selector switch to VAC/AAC/Hz.
2 Press SELECT once to show AAC on upper display. Press INRUSH on the
right side of meter to activate Inrush Mode.
3 Clamp jaw around the motor’s start wire.
4 Turn motor on. The starting amp draw will hold on the upper display.
5 Press INRUSH to clear captured reading. Press INRUSH for 2 seconds to
exit.
Inrush measurement period: 100-milliseconds
Minimum input: >2A on 100A range; >20A on 600A range
Note: AAC or Hz through the clamp and VAC through the test leads
can be measured simultaneously. However, if only AAC, Frequency
(Hz), or Inrush AAC is measured through the clamp, test leads and
thermocouples must be unplugged from the meter.
Amps AC (AAC), Frequency (Hz) through the clamp and Inrush AAC
current is measured in the VAC/AAC/Hz switch position shown above.
1514
Page 9
MicroAmps DC (µADC)
Test ame rectier diodes on a heater control. Connect leads between
ame sensor probe and control module. Turn heating unit on. When the
ame is on, there should be a measurable µADC signal, typically under
10µADC. Compare measurement to manufacturer’s specication to
determine if replacement is necessary.
Test motor start and run capacitors. Capacitors are one of the most
failure prone components in a HVACR system. Disconnect from power and
any resistors found between terminals. Discharge capacitor before testing.
If dIS.C is displayed, the capacitor needs to be fully discharged to test.
Press SELECT three times to enter Capacitance mode.
Used for “ohming out” a compressor. A 0.01Ω resolution is useful to
test the resistance between the terminal poles because the values are
typically very low. Resistance is default test in this switch position. For
best practice, use a megger (Fieldpiece SMG5) to measure motor winding
insultion to ground.
Open circuit volts: -1.1VDC typical, -3.2VDC (100Ω range)
Overload Protection: 600VDC or 600VAC rms
Continuity (
Perfect for checking isolated fuses, use the continuity function to test
whether a circuit is open (no beep, no green LED) or closed (beep and
green LED). Press SELECT once to enter Continuity mode.
Range: 100Ω Resolution: 0.01Ω Response time: 100ms
Audible beep: <30Ω
Visual Indicator: Green LED
Overload Protection: 600VDC or 600VAC rms
)
Diode Test (
Test diodes for proper forward and reversed-biased functions. A
voltage will display in forward-bias and “OL” in reversed-bias. Press SELECT
twice to enter Diode mode.
Test current: 0.8mA (Approx.) Accuracy: ±(1.5% + 5)
Open circuit volts: 3.2VDC typical Audible beep: <0.05V
Visual Indicator: Green LED
Overload Protection: 600VDC or 600VAC rms
)
1918
Page 11
Temperature
Plug any Type K thermocouple directly into the meter to measure
temperature. Measure outdoor dry bulb temperature for target superheat
while at the condensor with the Type K thermocouple input.
Insulated cold junction is located inside the meter and allows for
accurate measurements even in rapidly changing ambient temperatures
(going from rooftop to freezer). No adapter is required.
By default, °F will show on top display and °C on bottom display.
Range: -58°F to 2372°F, (-50°C to 1300°C) Resolution: 0.1°
Accuracy: ±(1°F)* 32°F to 120°F, ±(1°C) 0°C to 49°C
±(1%+2°F) 32°F to 932°F, ±(1%+1°C) 0°C to 500°C
±(2%+6°F) -58°F to 32°F, ±(2%+3°C) -50°C to 0°C
±(2%+6°F) 932°F to 2372°F, ±(2%+3°C) 500°C to 1300°C
Sensor type: Type K thermocouple
Overload protection: 30 VDC or 30VAC rms
*After eld calibration
Unplug Leads and Slide
TEMP Switch to the Right
Temperature Calibration
Thermocouples (T/C) are not calibrated directly. Instead, each T/C jack
(T1 and T2) must be calibrated to the particular T/C that is plugged into it.
Though it’s possible for a calibration to hold for years, it’s best practice to
calibrate regularly if only to verify accuracy. Labelling your T/C, T1 or T2,
will help ensure using the same T/C for T1 and T2 ports.
Calibration is quick and easy, requiring just a known temperature to
calibrate to. Ice water is probably the most accurate and readily available
known temperature (32.0°F, 0.0°C) in the eld.
1. Rotate dial to the °F °C position.
2. Plug one thermocouple to be
calibrated into the Type K input.
3. Unscrew A and B and remove the
battery cover.
4. Stabilize a large cup of ice water.
Stir the ice with the water until
temperature stays at a stable value.
5. Immerse the thermocouple probe
and let it stabilize. Keep stirring
water to prevent thermocouple from
direct contact with ice.
6. Use a small screwdriver to adjust
calibration Temp Cal pot below the
battery as close to 32°F(0°C) as you
would like.
Note: J1-J2 switch is for factory
calibration purposes only. Do not
switch from J2.
A
DO NOT SWITCH
FROM J2
C
TEMP CAL
B
2120
Page 12
Power (Watts, VAr, VA, PF)
!
Help determine system eciency by measuring the power exerted
by the system. The actual power consumed by the system is called Active
Power and is measured in watts (W or kW). Reactive loads, inductors
and capacitors, dissipate zero power, but they drop voltage and draw
current giving the deceptive impression they do dissipate power. This is
called Reactive Power and is measured in Volt-Amps-Reactive (VAr). The
combination of reactive and real power is called Apparent Power and
is the product of a system’s voltage and current, without phase angle
consideration. Apparent Power is measured in Volt-Amps (VA).
Power Factor (PF) is the ratio of the power the system draws from
the main power supply and the power the system actually consumes. An
ideal PF is 1, meaning the system consumes all the power it draws. Due to
inductive and capacitive loads of the system however, this is not possible.
To take the power reading you need to measure both voltage and
amperage simultaneously. Connect test leads to main power supply
terminals and secure amp clamp around the same line that the positive
(red) test lead is connected to.
See Power Factor in top display and Power in bottom display. Press
SELECT to toggle Active Power (W), Reactive Power (VAr), Apparent Power
(VA ).
CAUTION! DO NOT MEASURE VOLTAGE LINES OR EXPOSE THE METER TO
LIVE POWER LINES EXCEEDING 750VAC/1000VDC NOMINAL VOLTAGE.
Eective Current Range: 2AAC/ADC to 600AAC/ADC
Eective Voltage Range: 80VAC to 750VAC
Eective Frequency Response: 50Hz to 60Hz
Power accuracies unspecied for non-sinusoidal current waveforms
Active Power (W)
Ranges: 1000W, 10kW, 100kW, 450kW
Resolution: 0.1W
Accuracy: ±(5.0% + 5) >10A
±(10.0% + 5) 2A to 10A on 450kW range
Reactive Power (VAr)
Ranges: 1000VAr, 10kVAr, 100kVAr, 450kVAr
Resolution: 0.1VAr
Accuracy: ±(5.0% + 5) >10A on 1000VAr range
Power Factor (PF)
Ranges: -1.00 to +1.00
Resolution: 0.01 PF
Accuracy: ±(5.0% + 5) >10A, ±(10.0% + 5) 2A to 10A
PF readings will be displayed on upper display
2322
Page 13
Phase Rotation Test (L1L2, L1L3)
Connect 3-phase power lines in the correct order to the terminals of
a motor to ensure the motor turns in the intended direction. Incorrect
wiring can damage some equipment. The terminals on the motor are
usually marked L1, L2, and L3; however, the wires supplying power
usually are not. Perform a simple phase rotation test with two test leads
to quickly identify the order of 3-phase power lines.
Range: 80±5 VAC to 600VAC (50Hz to 80Hz) Resolution: 0.1V
Accuracy: ±(1.5% rdg + 10 dgts)
Overload Protection: 600VDC or AC rms
Step 2: Connect Leads
Connect both black and red
test leads to any two of the three
phase voltage lines in question.
The line voltage will hold on the
bottom display. Blinking L1 and
L2 disappear. L3 will blink on top
display to indicate test is ready for
Step 2.
How to Perform a Phase Rotation Test
Set 1: Select Function
Switch to . Plug black test lead
into the COM (L1) port and red test lead
to the VΩ (L2 L3) port on the SC480.
You will see “L1L2” blinking
to indicate phase rotation test
is ready to begin.
Important: Step 2 must
be performed within
5 seconds of completing Step 1 or “Err” will
show and Step 1 must
be repeated.
Step 3: Move Red Lead
With the black lead still on
“L1”, move the red test lead to the
third 3-phase voltage line. The line
voltage will hold on the bottom
display. The top display will show
L123 indicating forward or L321
indicating reversed.
Simply swap any two lines to
change the direction. You can verify
this by performing the test again.
2524
Page 14
Phase Rotation Testing Tips
1 The measured voltage during phase rotation test
must be >80.0±5VAC. If not, the phase rotation
test can not be performed and “Err” will show on
the top display.
2 After phase rotation test is complete, press SELECT
button to begin a new phase rotation test.
3 Be sure to connect test leads to 3-phase voltage
lines for at least 2 seconds until voltage reading
holds on the bottom display
4 Phase rotation test cannot be performed on Hi-
frequency voltage signals. Be sure voltage lines
are within 50-80Hz to perform the phase rotation
test.
Modular
Expandability
Your SC480 is compatible with all Fieldpiece
Accessory Heads. With Fieldpiece Accessory Heads,
you can measure any available parameter, and read
the measurement on your new meter’s display in
real-time, Hold, Max, and min.
Rotate the selector to VDC and stay in mV range.
Remove the probe tips of your test leads, and
connect your accessory head (model AAV3 shown).
LCDX
100
ON
READLOBATT
AirVelocity
&Temperature
Average
English
(16sec)
Head
Real
Metric
time
English Metric
Ft/min M/s
KM/hrMPH
ºF ºC
OFF
AUTOOFF
AAV3
2726
Page 15
Works with Job Link® System
Do More with the Job Link® System
Directly document critical electrical
measurements at the job site, and add them to
professional PDF reports. No separate transmitter
required.
Combine your new clamp meter with other Job
Link System tools to create seamless reports. Show
customers what needs to be done (Pre-work) and
prove how that work helped (Post-work).
Send electrical measurements wirelessly from
SC480 directly to the Job Link® mobile app. No JL2
transmitter required.
Sending Wireless Measurements
1 Select any switch position other than L1L2 and NCV
on SC480.
2 Press WIRELESS ON/OFF button on meter.
3 Favorite your SC480 by going to the measurement
screen in the Job Link app.
4 Tap on Electrical tab in the Job Link measurement
screen.
Note: By default, wireless is OFF when powering on
the SC480. Press WIRELESS ON/OFF buton to turn
wireless ON.
Wireless Specications
Wireless range: Up to 115 feet (35m) line of sight. Distance decreases
through obstructions.
Wireless frequency: 2.4 GHz
Wireless Compatibility
Minimum Device Requirement:
BLE 4.0 devices running iOS® 7.0 or Android™ 5.0
2928
Page 16
Functions
Sync
OFF
Range
Select
H/M/m
ZEROA
DC
°F°C
INRUSH
Sync
OFF
Range
Select
H/M/m
ZEROA
DC
°F°C
INRUSH
H/M/m
DC
INRUSH
H/M/m
DC
INRUSH
H/M/m
DC
INRUSH
ZEROA
DC
INRUSH
ZEROA
DC
INRUSH
Sync
OFF
Range
Select
H/M/m
ZEROA
DC
°F°C
INRUSH
Auto Power O
Auto power o or APO will automatically turn o
your meter after 30 minutes of inactivty. By default
it is activated and APO will show on the display. To
disable, turn meter o. Hold
the meter by turning the selector dial to any range.
Release
after the beep. APO will no longer
display over the battery icon.
and power on
Battery Replacement
When your meter’s battery is low, the battery icon
will appear empty and blink for 30 seconds. “bAtt”
will display and meter will power o.
Turn dial to OFF position, disconnect test leads
and remove the battery cover with magnet strap
on the back of your meter. Remove old battery and
replace with a standard 9V battery only. Be sure to
re-insert the magnet strap before re-installing the
battery cover.
Hold/Max/min
Press
minimum, or real-time measurements. When
MAXMIN is displayed, you are seeing the real-time
measurement, but Max and min values are still
being recorded. Press
and exit. Press
in Job Link mobile app. See Wireless Section for Job
Link compatibility details.
High Voltage Warning
The symbol will display when measuring
>30VAC/VDC. An audible beep will be heard and
red LED will be shown.
to cycle through Hold, Maximum,
for 1 second to clear
to log an SC480 measurement
Backlight Illumination
See your measurements in dark environments.
Press
to illuminate the display. Illumination
will stay on for 5 minutes before turning off
automatically. Illumination can be turned o at any
time by pressing
.
Manual Ranging
Press
clamp meter to a specic range. Manual ranging
applies to VAC, VDC, MFD, W and resistance (Ω).
Press for 1 second to exit manual ranging and return
to auto-ranging.
IC: Industry CanadaIFETEL: Federal Telecom Institute
22518-BT005 RCPFI2A19-0287
CATIV 600V, CATIII 1000V or above. Included test leads are gold-plated and
have removable safety caps.
CATIII 1000V, CATIV 600 class II and pollution degree 2 indoor use comply
with CE, RoHS compliant.
CATIII is designated for measurements performed in the building
installation.
CATIV is for measurements performed at the source of the low-voltage
installation.
Specifications
Display: 10000 count dual display
Backlight: 5 minute duration with auto-o, blue color
Overrange: “OL” or “-OL” is displayed
Measurement rate: 3.3 times per second, nominal
Zero: Automatic
Operating environment: 32°F to 122°F (0°C to 50°C) at <70%RH
Storage temperature: -4°F to 140°F (-20°C to 60°C), 0 to 80%RH (with
battery removed)
Accuracy: Stated accuracy @ 73°F±9°F (23°C±5°C), <75%RH
Temperature coecient: 0.1 x (specied accuracy) per °C [0°C to 19°C
(32°F to 66°F), 28°C to 50° C (82°F to 122°F)]
APO (Auto Power O): Approx. 30 minutes
Power: Single standard 9-volt battery, NEDA 1604, JIS 006P, IEC 6F22
Battery life: 100 hours typical alkaline (No wireless, no backlight)
Low battery indication: Battery icon blinks and "batt" is displayed
when the battery voltage drops below the operating level
Dimensions: 247mm(H) x 79mm(W) x 48mm(D)
Weight: Approx. 345g including battery
Altitude: Up to 6562 ft (2000m)
Overload protection: 1000VDC or 750VAC rms unless otherwise stated
Test leads: Use UL listed test leads that comply to UL61010-031 rated
CATIV 600V, CATIII 1000V or above. Included test leads are gold-plated
and have removable safety caps.
Please operate the instrument following all instructions of
the operator's manual to avoid impairing the safety of
the product.
3332
Page 18
FCC Statement
This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will
not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment o and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
1. Reorient the receiving antenna.
2. Increase the separation between the equipment and receiver.
3. Connect the equipment into an outlet on a circuit dierent from that
to which the receiver is connected.
4. Consult the dealer or an experienced radio/TV technician for help.
FCC Caution:
Any changes or modications not expressly approved by the party
responsible for compliance could void the user’s authority to operate this
equipment.
This device complies with Part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
This device and its antenna(s) must not be co-located or operating in
conjunction with any other antenna or transmitter.
IMPORTANT NOTE:FCC Radiation Exposure Statement:
This equipment complies with FCC radiation exposure limits set forth
for an uncontrolled environment. This equipment should be installed and
operated with minimum distance 20cm between the radiator & your body.
IC Statement
This device contains licence-exempt transmitter(s)/receiver(s) that
comply with Innovation, Science and Economic Development Canada’s
licence-exempt RSS(s). Operation is subject to the following two
conditions:
1.This device may not cause interference.
2.This device must accept any interference, including interference
that may cause undesired operation of the device.
L’émetteur/récepteur exempt de licence contenu dans le présent
appareil est conforme aux CNR d’Innovation, Sciences et Développement
économique Canada applicables aux appareils radio exempts de licence.
L’exploitation est autorisée aux deux conditions suivantes :
1.L’appareil ne doit pas produire de brouillage;
2.L’appareil doit accepter tout brouillage radioélectrique subi,
même si le brouillage est susceptible d’en compromettre le
fonctionnement.
IMPORTANT NOTE: IC Radiation Exposure Statement:
This equipment complies with IC RSS-102 radiation exposure limits set
forth for an uncontrolled environment. This equipment should be installed
and operated with minimum distance 20cm between the radiator & your
body.
Cet équipement est conforme aux limites d’exposition aux
rayonnements IC établies pour un environnement non contrôlé. Cet
équipement doit être installé et utilisé avec un minimum de 20cm de
distance entre la source de rayonnement et votre corps
3534
Page 19
IFETEL Statement
Limited Warranty
The operation of this equipment is subject to the following two
conditions: (1) this device or device may not cause harmful interference,
and (2) this device or device must accept any interference, including
interference that may cause undesired operation.
This product is warranted against defects in material or workmanship
for one year from date of purchase from an authorized Fieldpiece dealer.
Fieldpiece will replace or repair the defective unit, at its option, subject to
verication of the defect.
This warranty does not apply to defects resulting from abuse, neglect,
accident, unauthorized repair, alteration, or unreasonable use of the
machine.
Any implied warranties arising from the sale of a Fieldpiece product,
including but not limited to implied warranties of merchantability and
tness for a particular purpose, are limited to the above. Fieldpiece
shall not be liable for loss of use of the machine or other incidental or
consequential damages, expenses, or economic loss, or for any claim of
such damage, expenses, or economic loss.
State laws vary. The above limitations or exclusions may not apply to
you.