Models: ATC1 and ATC1R Pipe Clamp K-type Thermocouple Max: 257ºF (125°C)
OPERATOR’S MANUAL
Description
The ATC1 and ATC1R, K-type, pipe clamp ther­mocouples, can be used to take temperatures of pipes or any other cylindrical surface within their jaw range. Using a pipe clamp thermocouple greatly facilitates taking superheat or subcooling measure­ments. Use the ATC1 for most A/C units and the ATC1R for most residential and commercial refrig­eration appliances. Both models can be used with any thermometer accepting a K-type thermocouple.
Advantages
The sensor is virtually isolated from ambient con­ditions, allowing the thermocouple to read the true pipe temperature for as long as it is attached.
The sensor’s large surface area and increased clamping force help the sensor reach the correct temperature within 30 seconds.
Because the jaw is designed for HVAC/R, its clamping ability lets you measure temperatures of pipes that are fixed, at any angle, to walls or other surfaces.
Operation
Plug the ATC1 or ATC1R into any thermometer accepting a K-type thermocouple and adjust the thermometer to the appropriate settings. Simply clamp the thermocouple to a pipe and take the measurement when the reading stabilizes.
Field calibration
Due to variances in the thermocouple wire and other parts of the system, a field calibration should be conducted before use. Field calibration typically gives +/- 1ºF (0.5°C) overall accuracy. Refer to the thermometer’s operating manual for calibration instructions.
Specifications
ATC1 jaw range: 3/8” to 1 3/8” pipe diameter (OD) ATC1R jaw range: 1/8” to 3/4” pipe diameter (OD) Accuracy: +/- 4ºF (2°C) ; ±1°F (0.5°C) after field
calibration, 32 to 176ºF (0 to 80°C)
Temperature range: -50 to 257ºF (-46 to 125°C) Thermocouple conductors: K-type nickel
chromium/nickel aluminum.
Probe insulation and clamp material: While cal-
ibration and atmosphere will affect maximum useful temperature in applications, the wire insu­lation and clamp material are designed to with­stand a maximum continuous use at 257°F (125°C).
Plug: K-type thermocouple male mini plug. Typical stabilization time: less than 30 seconds.
Warranty
The ATC1 and ATC1R, K-type, clamp-on thermo­couples are warranted against manufacturer’s defects for one year. This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the instrument. Any implied warranty arising out of the sale of Fieldpiece's products including but not limited to implied warranties of merchantability, and fitness for purpose, are limited to the above. Fieldpiece shall not be liable for incidental or conse­quential damages.
Service
Return any defective ATC1 or ATC1R to Fieldpiece for warranty service along with proof of purchase. Contact Fieldpiece for out of warranty repair charges.
www.fieldpiece.com
WARNINGS
The thermocouple and metal band may
become hot when testing hot pipes or cylinders.
Do not handle the thermocouple or the metal
band when hot.
!
!
v24