Fieldpiece ASX14 User Manual

AUTO-
OFF
T/C Cal
STABLE
Pressure
Temp
ON
LOBATT
Air Conditioner Superheat and Subcooling
ENGLISH
METRIC
R22
R410A
Set ATM
ASX14
SH
SC
Superheat and Subcooling Head for R22 and R410A
with pipe clamp thermocouple
Model: ASX14
OPERATOR’S MANUAL
Description
The model ASX14 superheat and subcooling accessory head measures refrigerant pressure and temperature simultaneously. It then calculates and displays superheat or subcooling. It has a 1/4” industry standard fitting for actual pressure. A pipe clamp thermocouple is included for temperature. Select R22 or R410A. Select superheat or subcool­ing.Select english or metric units.
Use it your way
EHDL1 AHDL1 w/ Meter DL3 HS30
How to use
1. Connect to COM and Volts jack. Slide ASX14 superheat head onto Fieldpiece "stick" meter, data logger, electronic handle or connect to most other meters using Fieldpiece ADLS2 deluxe test leads or AHDL1 handle.
2. Set meter to mVDC range.
3. Calibrate if needed (see Field calibration)
4. Hand tighten 1/4” flare to suction line or liquid line as close to the evaporator or condenser as possible using an EPA approved service hose (not included).
5. Select superheat or subcooling, refrigerant (R22 or R410A) and units (English or metric).
6. Connect the pipe clamp to the suction (super­heat) or liquid (subcooling) line at least six inch­es from the condenser and slide it under the insulation for best accuracy isolating the pipe clamp from the ambient air (pg. 2).
7. Select parameter to display (superheat, sub­cooling, pressure, or temperature).
8. You must wait until the system you are testing has stabilized. The STABLE LED lights when the reading is stable.
9. Disable Auto-off to data log any of the above parameters with the DL3 data logger.
10. Once you have the superheat or subcooling reading follow the manufacturer of the air condi­tioner’s specifications to properly charge or diagnose the system.
Field calibration
Temperature: To calibrate the system (ASX14, pipe clamp thermocouple, meter), adjust the cali­bration pot underneath the rubber covering while measuring a known temperature. Ice water is 32°F (0°C) and is readily available.
1. Stabilize (by repeated stirring) a large cup of ice
water.
2. Select temperature on ASX14, plug in the pipe
clamp thermocouple and then immerse entire
clamp into the ice water (keep stirring).
3. Adjust the calibration pot to read 32.0 (0.0 if
using °C) on the DMM for optimum accuracy at
room temp.
Pressure: The pressure/vacuum reading prior to connecting to an A/C system should always be zero. If you see that you’re getting pressure read­ings of something other than zero without your serv­ice hose attached, you need to set atmospheric pressure before connecting the ASX14 to the sys­tem. To set atmospheric pressure, press the button underneath the rubber covering entitled “Set ATM”. You usually have to set atmospheric pressure each time you dramatically change elevations. For exam­ple, if you “Set ATM” in Denver and take a pressure reading of an A/C system in Los Angeles, the pres­sure reading in Los Angeles will be lower than it actually is.
OFF
2000
AUTO­OFF
T/C Cal
STABLE
Pressure
Temp
SHor SC
ON
LOBATT
Air Conditioner Superheat andSubcooling
ENGLISH
METRIC
R22
R410A
Set ATM
ASX14
SH
SC
AUTO­OFF
T/C Cal
STABLE
Pressure
Temp
SHor SC
ON
LOBATT
Air Conditioner Superheat andSubcooling
ENGLISH
METRIC
R22
R410A
Set ATM
ASX14
SH
SC
AUTO­OFF
T/C Cal
STABLE
Pressure
Temp
SHor SC
ON
LOBATT
Air Conditioner Superheat andSubcooling
ENGLISH
METRIC
R22
R410A
Set ATM
ASX14
SH
SC
AUTO­OFF
T/C Cal
STABLE
Pressure
Temp
SHor SC
ON
LOBATT
Air Conditioner Superheat andSubcooling
ENGLISH
METRIC
R22
R410A
Set ATM
ASX14
SH
SC
SPECIFICATIONS
Operating environment: 32ºF to 122ºF; 0ºC to
50ºC at <75%RH
Allow ~5 min. for ASX14 to come to ambient temp.
Storage environment: -4ºF to 140ºF; -20ºC to
60ºC at <80%RH with battery removed.
Battery life: 25 hours typical. No measurable
current draw when in "off" position.
Low battery indication: Red LED lights Battery: 9V Auto off: Approx. 15 minutes Overloads: The ASX14 outputs 3.4V when tem-
perature or pressure is outside of their working range (overloaded). For ranges below 3400mVDC, the normal overload symbol will be displayed on the meter (“OL”). For ranges above 3400mVDC, reading displayed will be approximately 3.4VDC.
Stated Accuracy: at 73°F ± 9°F (23°C ±5°C) ,
<90% R.H.
Temperature
Range (temperature): -40ºF to 400ºF;
-40ºC to 204ºC
Resolutions: 0.1º Sensor type: k-type thermocouple Pipe clamp thermocouple accuracy: ±4ºF
(±2°C) or ±0.75%, whichever is greater, -30ºF to 200ºF (-34°C to 93°C)
System accuracy: ±1ºF;±0.06ºC @ 73ºF ± 5ºF
after ice water calibration (see Field calibration).
Pressure and vacuum
Working range (pressure):
0 to 500 psi; 0 to 4000 kPa
Max displayed pressure: 800psi (5500 kPa) Working range (vacuum):
29”Hg vac. to 0; 74cmHg vac. to 0
Vacuum will show up as negative value on meter.
Resolutions: 0.1psi or kPa, 0.1”Hg or cmHg vac. Accuracy:
0 to 200 psig, ±1 psi, 0 to 1378 kPa ±6.9 kPa; 200 to 500 psig, 0.3% ±1 psi, 1378 to 3447 kPa
0.3% ±6.9kPa
Sensor breakdown pressure: 800psi (5500 kPa)
Superheat
Range (temperature): 0ºF to 80ºF; 0ºC to 27ºC Resolutions: 0.1º System Accuracy: ±1ºF @ 73ºF ± 5ºF (±0.06ºC
@ 23°C ±3°C) after calibration (see Field cali­bration).
Subcooling
Range (temperature): 0ºF to 80ºF; 0ºC to 27ºC Resolutions: 0.1º System Accuracy: ±1ºF @ 73ºF ± 5ºF (±0.06ºC
@ 23°C ±3°C) after calibration (see Field cali­bration).
Warranty
The ASX14, Superheat and Subcooling accesso­ry head is warranted against manufacturer’s defects for one year. This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the instrument. Any implied warranty arising out of the sale of Fieldpiece's products including but not limited to implied warranties of merchantability, and fitness for purpose, are limited to the above. Fieldpiece shall not be liable for incidental or con­sequential damages.
Service
Return any defective ASX14 to Fieldpiece for warranty service along with proof of purchase. Contact Fieldpiece for out of warranty repair charges.
.
v07
*These charts are an example of a generic
superheat charts for a typical fixed orifice, split res­idential system. These charts should not be used for charging. A typical manufacturer’s recommend­ed subcooling is 12°F (7°C). These are only exam­ples of what the manufacturer’s may recommend. Heed all manufacturer’s indications, instructions and warnings above those in this manual.
The indoor wet bulb measurement can be accomplished by a Fieldpiece ARH4 or ATWB1 and should be taken as close to the evaporator coil inlet as possible. The outdoor dry bulb reading can be taken with an ARH4, ATB1, ATA1 or any other Fieldpiece air thermocouple and should be taken as close to the condenser air inlet as possible.
Measuring actual superheat and subcooling
Superheat is the difference between the actual temperature of the refrigerant (gas) as it leaves the evaporator and the boiling point temperature of the refrigerant in the evaporator coil. After boiling, the refrigerant continues to warm up. The number of degrees it “warmed up” after boiling is called the superheat. Under worst case conditions (low load for fixed orifice systems), the refrigerant in the evap­orator boils off near the end of the evaporator coil. To make sure liquid doesn’t enter the compressor under the worst case condition (low load), the AC manufacturers publish charts indicating what the superheat should be at a given indoor wet bulb measurement and outdoor air temperature.
Measuring superheat is your best indication on a fixed orifice system of the proper refrigerant charge and operating conditions. If everything else is work­ing properly and the actual superheat is too high, add refrigerant. If it’s too low, remove refrigerant.
Subcooling is the difference between the boiling point of the refrigerant in the condenser and the actual temperature of the refrigerant as it leaves the condenser. The degrees that the refrigerant “cools down” below the boiling point is the sub­cooling. Under worst case scenario (low load for TXV) the subcooling will continue to rise. If the subcooling rises to high, liquid may be backed into
the compressor causing damage and catastrophic failure.
On TXV systems, subcooling is the best indica­tion of the state of charge in the refrigerant system since these systems are designed to maintain con­stant superheat.
Properly charging a system ensures maximum
efficiency and longer equipment life.
The hose must have a schraeder valve depress­er on one end to release the refrigerant from the suction or liquid line. This is the same type of hose available with most pressure gauge sets. We sug­gest EPA sanctioned “no leak” hoses.
Exercise caution whenever working with any electricity and high pressure liquid or gas. Follow all instructions provided with equipment being serviced or installed.
Target superheat and subcooling
Heed all equipment manufacturer’s specifica­tions, warnings and suggestions above anything found in this manual.
To determine the target superheat (fixed orifice system) or subcooling (charts vary dramatically from one system to another), you will typically need three things. Outdoor dry bulb (outdoor air temper­ature), indoor wet bulb, and the manufacturers tar­get superheat chart or subcooling chart.
You can use the ARH4 Fieldpiece accessory
head for both indoor wet bulb and outdoor dry bulb. Or you can use any Fieldpiece meter that has a temperature function along with a ATWB1 wet bulb thermocouple. Below is a diagram of the ASX14 on a split-system residential A/C unit.
Condenser
Evaporator
Compressor
Throttle Valve (TXV, Cap tube, Fixed Oriffice)
Outside
Indoor
Liquid
Vapor and Liquid
Vapor
Liquid
Vapor
Vapor and Liquid
Liquid
Vapor
Outside
Indoor
AUTO­OFF
T/C Cal
STABLE
Pressure
Temp
SHorSC
ON
LOBATT
Air Conditioner Superheat andSubcooling
ENGLISH
METRIC
R22
R410A
Set ATM
ASX14
SH
SC
AUTO­OFF
T/C Cal
STABLE
Pressure
Temp
SHorSC
ON
LOBATT
Air Conditioner Superheat andSubcooling
ENGLISH
METRIC
R22
R410A
Set ATM
ASX14
SH
SC
Checking Subcooling Using the ASX14
Checking Superheat Using the ASX14
R
e
f
r
i
g
e
r a
n
t
F
l
o
w
R
e
f
r
i
g
e
r
a
n
t
F
l
o
w
Generic Target Superheat Charts*
Loading...