Fieldpiece ARH5 User Manual

Fieldpiece
2
2000
00
2
2000
00
E Exit TExEx
e
Target
arget
arget
Targe
ator
ator
ator
Ta Evapor at
emp
E Exit TExEx
e
Target
arget
arget
Targe
ator
ator
ator
Ta Evapor at
emp
In-Duct Psychrometer Head
OPERATOR'S MANUAL
Model ARH5
1%RH/mVDC
1°F/mVDC 1°C/mVDC
TEMP
%RH
ARH5
AUTO OFF
ON
LO BATT
°F
°CONOFF
In-Duct Psychrometer Head
WET BULB
DEW POINT
Quick Start
1. Connect ARH5 to Fieldpiece meter.
2. Select mVDC range on meter.
3. Remove vinyl slip cover from the probe tip.
4. Select desired switch position on ARH5 for temperature, wet bulb, dew point, or %RH.
Certications
80
C-Tick (N22675)
CE
RoHS compliant
WARNING
Do not retract the sensor probe by pulling on the cord.
Doing so may sever the cord from the sensors.
Description
With your purchase of the ARH5 you now have the ability to take supply/ return temperature, %RH, wet bulb and dew point measurements from inside the duct or plenum.
Use the telescopic probe to take measurements in hard to reach places.
Your ARH5 measures both relative humidity and ambient air temperature. It also calculates dew point and wet bulb temperatures automatically.
The ARH5 snaps directly onto Fieldpiece HS series DMMs, Fieldpiece Datalogger or HVAC Guide® System Analyzer. For other meters, use Fieldpiece ADLS2 test leads or the AHDL1 handle adapter.
Use your ARH5 in combination with the HVAC Guide and easily perform Target Evaporator Exit Temperature tests and get more reliable and convenient Target Superheat calculations.
Go wireless with your ARH5 by using Fieldpiece wireless transmitters (ET2W/EH4W) to send measurements over-the-air to Fieldpiece wireless receivers (HG3, LT17AW, EH4W) anywhere on the jobsite.
Use the RCONE1 for hands-free
in-duct measurements.
In-Duct
ON
Psychrometer Head
LO BATT
ON
°F
1%RH/mVDC
1°F/mVDC 1°C/mVDC
OFF
°C
TEMP
WET BULB
DEW POINT
%RH
INPUT FORM SH Table: Standard
Refrigerant: R-22 OD Dry Bulb: 85.4°F
Return WB: 63.0°F
SL Pressure: 52.4psig SL Temp: 45.4°F CustomerID: __JONES123
Output
Sync
Input
Enter
SETUP
CFM
Target
CheckMe! Evaporator Exit Temp
Display
Data
Logger
Superheat Service Light
SubcoolingCombustion
Clear
Save
Recall
HVAC Guide
HG3
Fieldpiece
ARH5 w/ ET2W
transmitting wirelessly to HG3
AUTO OFF
ARH5
ET2W
AC DC
SEND
ON
Wireless
SYNC
Transmitter
RECEIVE
LO BATT
Specications
Telescoping Probe Length: Up to 38 inches (97cm) Probe Tip Diameter: 0.35 inch (9mm) Storage temperature: -4°F to 140°F (-20°C to 60°C), 0
to 80% RH (with battery removed)
Temperature Coecient: 0.1 x (specied accuracy)/°C
(<18°C or >28°C)
Power: Single standard 9-volt battery, NEDA 1604, JIS
006P, IEC 6F22 Auto Power O: Approx. 15 minutes Battery life: 150 hours typical (alkaline) Low Battery Indication: Red LO BATT LED will light to
indicate low battery. Output Impedance: 500Ω approx. Dimensions: 144mm(H) x 67mm(W) x 32mm(D) Weight: Approx. 240g, including battery
Temperature:
Sensor type: Precision thermistor Operating environment: -4°F to 140°F (-20°C to 60°C) Range: -4°F to 140°F (-20°C to 60°C) Resolution: 0.1°F / 0.1°C Accuracy: ±(1°F) 32°F to 113°F ±(2°F) -4°F to 32°F, 113°F to 140°F ±(0.5°C) 0°C to 45°C ±(1°C) -20°C to 0°C, 45°C to 60°C Output: 1mV to 1°F/°C
Relative Humidity:
Sensor Type: Capacitance polymer lm Operating environment: 32°F to 131°F (0°C to 55°C) Range: 0% to 100%RH Accuracy: ±(2.5%) 10% to 90%RH ±(5%) <10%RH and >90%RH Note: Above accuracies stated at 73.4°F (23°C). Output: 1mV to %RH Sensor Response Time: 60 seconds typical for 90% of
total range.
Sensor Hystersis: ±1%RH typical (Excursion of 10% to
90% to 10%RH)
ON
In-Duct Psychrometer
ON
In-Duct Psychrometer Head
WET BULB DEW POINT
In-Duct Psychrometer Head
1%RH/mVDC
1°F/mVDC
ON
In-Duct
ON
Psychrometer Head
LO BATT
LO BATT
1%RH/mVDC
1°F/mVDC 1°C/mVDC
TEMP
%RH
AUTO OFF
ARH5
°F
1%RH/mVDC
°F
1°F/mVDC 1°C/mVDC
°CONOFF
°CONOFF
TEMP WET BULB DEW POINT
%RH
AUTO OFF
ARH5
MAX 30VDC
24VAC
CONNECT ONLY TO ACCESSORY HEAD!
AUTO-OFF
MAX/MIN
SYNCHOLD
ET2W
500
50
5000m
AC
500m
DC
RECV
500µ 50m
200m
2
K
200
20
SEND
ON
20
Wireless
SYNC
Transmitter
LO BATT
RECEIVE
FUSED
1°C/mVDC
TEMP WET BULB DEW POINT
%RH
WIRELESS ENABLED
600600
500
50 5000m
500m
500µ 50m
200m 500 750
500 1400
M
2
K
200
200
K
500mV
15 SEC FOR
RANGE CAT.III MAX 600V
FUSED
200mA
MAX
30V MAX
Head
LO BATT
°F
°CONOFF
AUTO OFF
ARH5
OFF
2000
LO BATT
°F
1%RH/mVDC
1°F/mVDC 1°C/mVDC
°CONOFF
TEMP WET BULB DEW POINT
%RH
AUTO OFF
ARH5
Figure 1
01
Fieldpiece
In-Duct Psychrometer Head
OPERATOR'S MANUAL
Model ARH5
1%RH/mVDC
1°F/mVDC 1°C/mVDC
TEMP
%RH
ARH5
AUTO OFF
ON
LO BATT
°F
°CONOFF
In-Duct Psychrometer Head
WET BULB
DEW POINT
02
Quick Start
1. Connect ARH5 to Fieldpiece meter.
2. Select mVDC range on meter.
3. Remove vinyl slip cover from the probe tip.
4. Select desired switch position on ARH5 for temperature, wet bulb, dew point, or %RH.
Certications
80
C-Tick (N22675)
CE
RoHS compliant
WARNING
Do not retract the sensor probe by pulling on the cord.
Doing so may sever the cord from the sensors.
03
Description
With your purchase of the ARH5 you now have the ability to take supply/ return temperature, %RH, wet bulb and dew point measurements from inside the duct or plenum.
Use the telescopic probe to take measurements in hard to reach places.
Your ARH5 measures both relative humidity and ambient air temperature. It also calculates dew point and wet bulb temperatures automatically.
The ARH5 snaps directly onto Fieldpiece HS series DMMs, Fieldpiece Datalogger or HVAC Guide® System Analyzer. For other meters, use Fieldpiece ADLS2 test leads or the AHDL1 handle adapter.
Use your ARH5 in combination with the HVAC Guide and easily perform Target Evaporator Exit Temperature tests and get more reliable and convenient Target Superheat calculations.
04
Go wireless with your ARH5 by using Fieldpiece wireless transmitters (ET2W/EH4W) to send measurements over-the-air to Fieldpiece wireless receivers (HG3, LT17AW, EH4W) anywhere on the jobsite.
Use the RCONE1 for hands-free
in-duct measurements.
In-Duct
ON
Psychrometer Head
LO BATT
ON
°F
1%RH/mVDC
1°F/mVDC 1°C/mVDC
OFF
°C
TEMP WET BULB DEW POINT
%RH
INPUT FORM SH Table: Standard Refrigerant: R-22 OD Dry Bulb: 85.4°F
Return WB: 63.0°F
SL Pressure: 52.4psig SL Temp: 45.4°F CustomerID: __JONES123
Output
Sync
Input
Enter
SETUP
CFM
Target
CheckMe! Evaporator Exit Temp
Display
Data
Logger
Superheat Service Light
SubcoolingCombustion
Clear
Save
Recall
HVAC Guide
HG3
Fieldpiece
ARH5 w/ ET2W
transmitting wirelessly to HG3
AUTO OFF
ARH5
ET2W
AC DC
SEND
ON
Wireless
SYNC
Transmitter
RECEIVE
LO BATT
05
Specications
Telescoping Probe Length: Up to 38 inches (97cm) Probe Tip Diameter: 0.35 inch (9mm) Storage temperature: -4°F to 140°F (-20°C to 60°C), 0
to 80% RH (with battery removed)
Temperature Coecient: 0.1 x (specied accuracy)/°C
(<18°C or >28°C)
Power: Single standard 9-volt battery, NEDA 1604, JIS
006P, IEC 6F22 Auto Power O: Approx. 15 minutes Battery life: 150 hours typical (alkaline) Low Battery Indication: Red LO BATT LED will light to
indicate low battery. Output Impedance: 500Ω approx. Dimensions: 144mm(H) x 67mm(W) x 32mm(D) Weight: Approx. 240g, including battery
Temperature:
Sensor type: Precision thermistor Operating environment: -4°F to 140°F (-20°C to 60°C) Range: -4°F to 140°F (-20°C to 60°C) Resolution: 0.1°F / 0.1°C Accuracy: ±(1°F) 32°F to 113°F ±(2°F) -4°F to 32°F, 113°F to 140°F ±(0.5°C) 0°C to 45°C ±(1°C) -20°C to 0°C, 45°C to 60°C Output: 1mV to 1°F/°C
06
Relative Humidity:
Sensor Type: Capacitance polymer lm Operating environment: 32°F to 131°F (0°C to 55°C) Range: 0% to 100%RH Accuracy: ±(2.5%) 10% to 90%RH ±(5%) <10%RH and >90%RH Note: Above accuracies stated at 73.4°F (23°C). Output: 1mV to %RH Sensor Response Time: 60 seconds typical for 90% of
total range.
Sensor Hystersis: ±1%RH typical (Excursion of 10% to
90% to 10%RH)
In-Duct Psychrometer
ON
In-Duct Psychrometer Head
WET BULB DEW POINT
In-Duct Psychrometer Head
1%RH/mVDC
1°F/mVDC
ON
In-Duct
ON
Psychrometer Head
LO BATT
LO BATT
1%RH/mVDC
1°F/mVDC 1°C/mVDC
TEMP
%RH
AUTO OFF
ARH5
°F
1%RH/mVDC
°F
1°F/mVDC 1°C/mVDC
°CONOFF
°CONOFF
TEMP WET BULB DEW POINT
%RH
AUTO OFF
ARH5
MAX 30VDC
24VAC
CONNECT ONLY TO ACCESSORY HEAD!
AUTO-OFF
MAX/MIN
SYNCHOLD
ET2W
500
50
5000m
AC
500m
DC
RECV
500µ 50m
200m
2
K
200
20
SEND
ON
20
Wireless
SYNC
Transmitter
LO BATT
RECEIVE
FUSED
1°C/mVDC
TEMP WET BULB DEW POINT
%RH
WIRELESS ENABLED
600600
500
50 5000m
500m
500µ 50m
200m 500 750
500 1400
M
2
K
200
200
K
15 SEC FOR
500mV
RANGE CAT.III MAX 600V
FUSED
200mA
MAX
30V MAX
Head
LO BATT
1%RH/mVDC
°F
1°F/mVDC 1°C/mVDC
°CONOFF
TEMP WET BULB DEW POINT
AUTO OFF
ARH5
OFF
2000
ON
LO BATT
°F
°CONOFF
%RH
AUTO OFF
ARH5
Figure 1
01
02
03
04
05
06
How to Use
General Instructions
1. Remove vinyl slip cover from the telescopic probe tip.
2. Connect directly onto any Fieldpiece HS multimeter. For most Fieldpiece SC and LT meters, use Fieldpiece ADLS2 test leads plugged into the COM and VΩ jacks.
3. Select mVDC range on multimeter.
4. Set switch position of ARH5 to TEMP, WET BULB, DEW POINT, or %RH.
5. Read the measurement directly on the multimeter display.
Protecting the Sensor
The ARH5 uses a precision
thermistor sensor. When not in use it is best to protect this sensor with the vinyl slip cover included with the ARH5.
RCONE1 Probe Lock
For hands-free use, RCONE1 locks
your sensor probe in place inside the duct. See Figure 1 on other side.
07
Diagnostic Tests
Wireless Return Wet Bulb for Target Superheat
The ARH5 with a wireless transmitter (ET2W, EH4W, or LT17AW) allows you to monitor the return wet bulb while you are at the condensor. Send this real-time WB measurement wirelessly to the INPUT FORM of the HG3 HVAC Guide® System Analyzer to calculate a real-time target superheat.
1. Sync your transmitter with ARH5 to
the Return WB INPUT line in Super-
heat Test of the HG3 HVAC Guide.
2. Punch or drill a small 3/8" hole in the
return plenum to insert ARH5 probe.
Press ENTER to lock in reading.
3. Input an outdoor dry bulb tempera-
ture manually with the ATH4 at the
condensor into the OD Dry Bulb
INPUT line in the Superheat Test of
the HVAC Guide.
4. Press OUTPUT on HVAC Guide to see
your target superheat calculations.
08
Target Evaporator Exit Temp with the HVAC Guide
The ARH5 with Fieldpiece HVAC Guide allows you to easily perform a Target Evaporator Exit Temperature (TEET) test to determine if the evaporator is getting the optimum airow.
1. Slide ARH5 onto the top of the HVAC
Guide. Select TEET switch position.
2. In the INPUT FORM, highlight Return
DB. Press ENTER to measure air tem-
perature going into the evaporator.
Drill a small 3/8" hole in the return
plenum and insert the ARH5 probe.
Set ARH5 switch position to TEMP.
Press ENTER to lock in reading. Take
measurements as close to the air
handler as possible. Seal any holes
before leaving the jobsite.
3. In the INPUT FORM, highlight Return
WB. Press ENTER to measure wet
bulb temperature going into the
evaporator by inserting ARH5 probe
through the same hole at the return.
Set ARH5 switch position to WET
09
BULB. Press ENTER to lock reading.
4. In the INPUT FORM, highlight Sup­ply DB. Press ENTER to measure air temperature coming out of the evaporator. Punch or drill a small 3/8" hole in the supply plenum and insert ARH5 probe in the center of the plenum to take measurement. Press ENTER to lock reading.
5. Press OUTPUT to view results.
Maintenance
Clean the exterior with a dry cloth.
Do not use liquid.
Battery Replacement
The batteries on the ARH5 must be
replaced when the LO BATT LED turns red. Replace with one 9V battery.
Auto Power O
Your ARH5 powers o automatically
after approximately 15 minutes to lengthen battery life. To disable "Auto O," remove the grey rubber cover on the front of ARH5 and slide the Auto O switch to the left.
10
Limited Warranty
In the USA, this meter is warranted against defects in material or workmanship for one year from date of purchase. Fieldpiece will replace or repair the defective unit, at its option, subject to verication of the defect.
This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the instrument.
Any implied warranties arising from the sale of a Fieldpiece product, including but not limited to implied warranties of merchantability and tness for a particular purpose, are limited to the above. Fieldpiece shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim of such damage, expenses, or economic loss.
State laws vary. The above limitations or exclusions may not apply to you.
11
For Service
In the USA, call Fieldpiece Instruments for one-price-x-all out of warranty service pricing. Send check or money order for the amount quoted. Send the meter freight prepaid to Fieldpiece Instruments. Send proof of date and location of purchase for in-warranty service. The meter will be repaired or replaced, at the option of Fieldpiece, and returned via least cost transportation. Outside of the USA, please visit www.eldpiece.com for service contact information.
www.fieldpiece.com
© Fieldpiece Instruments, Inc 2011; v07
12
How to Use
General Instructions
1. Remove vinyl slip cover from the telescopic probe tip.
2. Connect directly onto any Fieldpiece HS multimeter. For most Fieldpiece SC and LT meters, use Fieldpiece ADLS2 test leads plugged into the COM and VΩ jacks.
3. Select mVDC range on multimeter.
4. Set switch position of ARH5 to TEMP, WET BULB, DEW POINT, or %RH.
5. Read the measurement directly on the multimeter display.
Protecting the Sensor
The ARH5 uses a precision
thermistor sensor. When not in use it is best to protect this sensor with the vinyl slip cover included with the ARH5.
RCONE1 Probe Lock
For hands-free use, RCONE1 locks
your sensor probe in place inside the duct. See Figure 1 on other side.
07
Diagnostic Tests
Wireless Return Wet Bulb for Target Superheat
The ARH5 with a wireless transmitter (ET2W, EH4W, or LT17AW) allows you to monitor the return wet bulb while you are at the condensor. Send this real-time WB measurement wirelessly to the INPUT FORM of the HG3 HVAC Guide® System Analyzer to calculate a real-time target superheat.
1. Sync your transmitter with ARH5 to
the Return WB INPUT line in Super-
heat Test of the HG3 HVAC Guide.
2. Punch or drill a small 3/8" hole in the
return plenum to insert ARH5 probe.
Press ENTER to lock in reading.
3. Input an outdoor dry bulb tempera-
ture manually with the ATH4 at the
condensor into the OD Dry Bulb
INPUT line in the Superheat Test of
the HVAC Guide.
4. Press OUTPUT on HVAC Guide to see
your target superheat calculations.
08
Target Evaporator Exit Temp with the HVAC Guide
The ARH5 with Fieldpiece HVAC Guide allows you to easily perform a Target Evaporator Exit Temperature (TEET) test to determine if the evaporator is getting the optimum airow.
1. Slide ARH5 onto the top of the HVAC
Guide. Select TEET switch position.
2. In the INPUT FORM, highlight Return
DB. Press ENTER to measure air tem-
perature going into the evaporator.
Drill a small 3/8" hole in the return
plenum and insert the ARH5 probe.
Set ARH5 switch position to TEMP.
Press ENTER to lock in reading. Take
measurements as close to the air
handler as possible. Seal any holes
before leaving the jobsite.
3. In the INPUT FORM, highlight Return
WB. Press ENTER to measure wet
bulb temperature going into the
evaporator by inserting ARH5 probe
through the same hole at the return.
Set ARH5 switch position to WET
09
BULB. Press ENTER to lock reading.
4. In the INPUT FORM, highlight Sup­ply DB. Press ENTER to measure air temperature coming out of the evaporator. Punch or drill a small 3/8" hole in the supply plenum and insert ARH5 probe in the center of the plenum to take measurement. Press ENTER to lock reading.
5. Press OUTPUT to view results.
Maintenance
Clean the exterior with a dry cloth.
Do not use liquid.
Battery Replacement
The batteries on the ARH5 must be
replaced when the LO BATT LED turns red. Replace with one 9V battery.
Auto Power O
Your ARH5 powers o automatically
after approximately 15 minutes to lengthen battery life. To disable "Auto O," remove the grey rubber cover on the front of ARH5 and slide the Auto O switch to the left.
10
Limited Warranty
In the USA, this meter is warranted against defects in material or workmanship for one year from date of purchase. Fieldpiece will replace or repair the defective unit, at its option, subject to verication of the defect.
This warranty does not apply to defects resulting from abuse, neglect, accident, unauthorized repair, alteration, or unreasonable use of the instrument.
Any implied warranties arising from the sale of a Fieldpiece product, including but not limited to implied warranties of merchantability and tness for a particular purpose, are limited to the above. Fieldpiece shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim of such damage, expenses, or economic loss.
State laws vary. The above limitations or exclusions may not apply to you.
11
For Service
In the USA, call Fieldpiece Instruments for one-price-x-all out of warranty service pricing. Send check or money order for the amount quoted. Send the meter freight prepaid to Fieldpiece Instruments. Send proof of date and location of purchase for in-warranty service. The meter will be repaired or replaced, at the option of Fieldpiece, and returned via least cost transportation. Outside of the USA, please visit www.eldpiece.com for service contact information.
www.fieldpiece.com
© Fieldpiece Instruments, Inc 2011; v07
12