Operating Range: 40° to 130°F (-17.8° to 54.4°C); 10 to 90% relative humidity, non-condensing
Digital Outputs: Five digital outputs relay contacts rated at 1A resistive @ 24VAC; configured as dry contact,
normally open.
Universal Inputs: 8 inputs. Inputs 1 and 2 are configurable for 0-5VDC, 10K ohm thermistor,
or dry contact; inputs 3 and 4 support thermistor or dry contact only; inputs 5 and 6 support
thermistor, dry contact, or LogiStat. Inputs 7 and 8 are used for 1-10K adjustment pots or dry
contacts.
Standard Comm Port: 3-pin port configurable for ARC156 (BACnet-over- ARC156) or
Communication EIA-485communications (BACnet MS/TP, Modbus RTU, orN2).
Ports: Rnet Port: 4-pin port for interface with remote mounted BACview6 or RS sensors
Local Access Port: For local communication with a laptop computer running WebCTRL or
for communication with a BACview6.
Status Indication: Visual (LED) status of network communication, running, errors, power, and
all digital outputs
Battery: Lithium 3V coin cell battery, CR2032, provides a minimum of 10,000 hours of
Data retention during power outages
Protection: Surge and transient protection circuitry for power and communications.
Listed by: FCC Part 15 - Subpart B - Class A. Pending listings at the time of publishing
this document: UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), CE (1997).
Weight: 0.6 lbs. (0.27 Kg).
Overall
Dimensions: 5-1/16” (width) by 5-11/16” (height) by 1-1/2” (recommended panel depth).
129mm (width) by 144mm (height) by 38mm (recommended panel depth).
Mounting Hole
Dimensions: Two mounting holes center line as at left with 5-9/16” (141mm)
Spacing (height)
5
Page 6
Controller ComponentsController Components
LED Indicators LED Indicators
DDC controller is equipped with three
The DDC controller is equipped with three
The
bank sets of LED that help the user
bank sets of LED that help the user
diagnose problems and or identify normal
diagnose problems and or identify normal
operation.
operation.
The first bank is located in the upper left
The first bank is located in the upper left
hand corner as shown in the figure 2. They
hand corner as shown in the figure 2. They
flash repeatedly when the controller is
flash repeatedly when the controller is
communicating with the network and usually
communicating with the network and usually
service support refers to them as Rx and Tx.
service support refers to them as Rx and Tx.
The second bank is located on the upper
The second bank is located on the upper
right hand corner of the controller as shown
right hand corner of the controller as shown
in figure 3. The first one from top to bottom
in figure 3. The first one from top to bottom
is normally lit (on) while the controller is
is normally lit (on) while the controller is
powered the second is the heart beat and
powered the second is the heart beat and
will flash during normal operation, the third
will flash during normal operation, the third
LED will remain off and will lit red in case
LED will remain off and will lit red in case
Figure 2 - Network LEDs Figure 2 - Network LEDs
Figure 3 - Power LEDs
there is an error in the controller.
there is an error in the controller.
In addition, when downloading new or
In addition, when downloading new or
modified versions of software these LEDs
modified versions of software these LEDs
will flash on and off indicating new files are
will flash on and off indicating new files are
being written to its non-volatile memory.
being written to its non-volatile memory.
6
Page 7
Figure 4 – Digital Output LEDs
The Third Bank of LEDs are located on the
bottom right corner of the controller as
shown on figure 4 (right) and their purpose
is to show the status of individual Digital
Outputs (DO) as they are energized
DIP and Rotary Switches
Two sets of switches can be found on the
controllers, they must be set properly to
allow correct operation of the unit.
The first set are rotary switches, as shown in
figure 5, is located on the left hand corner
near the top and their function is to provide
the controller address it always convenient
to identify the rotary for the tens and the
rotary for the ones as shown in figure 6.
The second set is located on the top left
hand corner of the controller and it is used
Figure 5 – Controller Address Rotary DIP switch
IMPORTANT:
Controllers must be
addressed correctly
for multiple units to
work on a network.
Figure 6 – Rotary switches
for two purposes:
(1) SW1 and SW2 set the baud rate of the
communications port on the controller:
BAUD RATE SW1 SW2
9600 Off Off
19.2K Off On
38.4K On Off
76.8K On On
Figure 7 – DIP Switches
(2) SW3 and SW4 enable different
supported protocols on the controller
additional hardware is needed for LonTalk®.
7
Page 8
PROTOCOLS SW3 SW4
BACnet® MS/TP
N2 On Off
Modbus Off On
Option Card On On
Off Off
Typical DIP switch for LonTalk® (Option
Card) is shown in figure 8.
Jumpers and settings
Controllers come equipped with a series of
jumpers which allow different types of inputs
to be terminated in a particular point.
Most inputs allow thermistor or dry contact
input devices to be terminated in them,
however IN1 and IN2 can be used as analog
or digital input points and their available
IMPORTANT:
The LonTalk® card
must be installed.
Jumpers set up will be
cover under the jumper
section.
ON
Figure 8 - LonTalk® DIP Settings
1234
EIA-485
BACnet
over ARC156
Figure 9 - Jumper setting for LonTalk® only.
options are as follows:
0-5 VDC Analog Input
Thermistor
Dry Contact
FHP sets most switches in the factory,
however there are certain cases where a
particular sensor is required by the
customer, therefore it is important for the
installer to understand jumper settings and
their relationship with unit configuration and
operation. Figure 9 shows the location of the
jumpers on the controller.
Figure 10 - Jumper Settings
8
Page 9
LonWorks® card option
LonWorks® is a network platform that allows any facility or to integrate sub-systems using a
common system architecture and infrastructure.
This platform provides fully open operability of the components within a system or sub-system,
this enables the facility owner to utilize different vendors and still have the capability of
integrating their system into one single server or front end.
The LON card option is available for both controllers 641-224 and 641-242.
The Lon card connects to the option card port as shown in figure 11.
Figure 11 - LonTalk® Card – 641-237
9
Page 10
Water to Air Operation
General Description
The Heat Pump Factory mounted I/O Zone 560 or 583 DDC Controllers are factory configured
with the Water to Air application program and factory installed in the unit to be job site
configureable to run.
The unit will operate in a 100% stand-alone control mode or connect to a Building Automation
System (BAS) using open protocols BACnet® (ARCNET and MS/TP), Modbus RTU, N2 or
LonWorks® (additional network interface board required for LonWorks® option).
The point mapping to all of these protocols is available in www.fhp-mfg.com and can be pre-set,
so that the protocol and baud rates desired can be easily field-selected and commissioned
without the need for any additional downloads or technical assistance.
The DDC Controller also supports communications to intelligent RS Room sensors and
BACview keypad/display panels.
Key Features and Benefits
I/O point count: 5 Digital outputs and 6 Universal inputs
Powerful high speed microprocessor with 1MB Flash memory and 1MB of battery-backed
RAM
Built-in protocol support: BACnet® (ARCNET and MS/TP), Modbus, N2 and LonWorks®
(additional network interface board required for LonWorks® option)
Built-in local access support: BACview6 keyboard/display and Intelligent RS Room
sensors
On-board lithium battery holds Controller time clock settings
Program archived in non-volatile memory allows unit to be ready after long periods of
power outages.
10
Page 11
Inputs
RS Room temperature sensor (Rnet)
RS Room temperature sensor Set point adjust (Rnet)
RS Room temperature sensor Occupancy override (Rnet)
Discharge air temperature sensor
Leaving water temperature sensor
Unit Protection module (UPM) Alarm codes (7 safety shutdown alarms)
Unit Filter status (optional)
Unit Enable manual control (optional DI Enable)
Outputs
Unit blower control
Reversing Valve
Cooling Stage 1
Cooling Stage 2 (Comp 2 Circuit or Comp1 Stage 2)
Humidity control output (optional Hot gas re-heat)
Auxiliary/Emergency Heating Stage (optional Electric Heat)
Control & Status Parameters and Alarms
Control
BACview occupancy schedule
System control: Schedule, Manual ON, BAS command or DI Enable
Room temperature occupied cooling/heating set point
Room temperature unoccupied cooling/heating set point
Unit blower control
Reversing valve control
Compressor 1 control
Compressor 2 control (Comp 2 Circuit)
Unit Enable manual control (optional)
Humidity Control ( hot gas re-heat optional)
Auxiliary/Emergency Electric heat output control (optional)
11
Page 12
Status
Cooling/Heating control status
Cooling/Heating percentage (0-100%)
Room temperature
Discharge air temperature
Leaving water temperature
Changeover temperature
Unit filter status (optional)
Fan-Hours runtime counter (filter replacement indicator)
Fan starts counter
Comp 1 starts counter
Comp 2 starts counter (Comp 2 Circuit)
Alarms
Room temperature high/low differential
Leaving water temperature high/low trip
Discharge air temperature high/low trip
Sensor failure alarm
Unit filter Runtime trip (optional)
Comp 1 Runtime trip
Comp 2 Runtime trip (Comp 2 Circuit)
Freeze Stat sensor UPM alarm (optional)
Low pressure sensor UPM alarm
High pressure sensor UPM alarm
Low pressure sensor UPM alarm (Comp 2 Circuit)
High pressure sensor UPM alarm (Comp 2 Circuit)
Condensate overflow UPM alarm
High/low voltage UPM alarm
12
Page 13
Sequence of Operation
Run Conditions:
The unit will run according to a user definable time schedule, dry contact (physical digital input
number 1), manual ON command from BACview control interface, timed local override from
Zone temperature sensor or via third party front end start command (software point). When
commanded to run the unit will operate in the following modes:
Occupied Mode: The unit will maintain
A 74°F (adj.) Cooling setpoint
A 70°F (adj.) Heating setpoint
Unoccupied Mode (night setback): The unit will maintain
A 90°F (adj.) Cooling setpoint.
A 55°F (adj.) Heating setpoint.
The unit will operate and adjust the setpoints according to the heating and cooling limits which
can be changed by the technical agent during the commissioning process if needed. The factory
default limits are the following:
Occupied Limits:
75 °F Heating High
60 °F heating Low
85 °F Cooling High
65 °F Cooling Low
Unoccupied Limits:
70 °F Heating High
50 °F Heating Low
95 °F Cooling High
80 °F Cooling Low
IMPORTANT: It is important not to overlap these limits on their respective modes (occupied and
unoccupied), overlapping may result in unit cycling between heating and cooling.
13
Page 14
Zone Temperature
The occupant will be able to see the zone temperature on the sensor LCD display in addition the
user will be able to see other parameters that have been configured in the controller such as
alarm status, alarm codes, Inputs and outputs status among others.
NOTE: These codes and values vary from version to version for additional information on what
is available on the RS-Pro sensor please check its commissioning BACview manual in our web
site www.fhp-mfg.com.
Alarms will be provided as follows:
High Zone Temp: If the zone temperature is greater than the cooling setpoint plus a user
definable amount (adj.), the factory default for this amount is 10.
Low Zone Temp: If the zone temperature is less than the heating setpoint minus a user
definable amount (adj.) the factory default for this amount is 10.
Zone Sensor Failure: If Zone sensor outside of normal operating limits, typically produced by a
wire failure between the sensor and the controller.
Zone Setpoint Adjust:
The occupant will be able to adjust the zone temperature heating and cooling setpoints at the
zone sensor (when RS Plus or RS Pro sensors are used). Zone sensor adjustment will allow for
+/-5°F of adjustment. If RS Standard sensor is used, then setpoint adjustments must be done at
the BACview keyboard/display or through BAS third party control.
Zone Unoccupied Override:
A timed local override control will allow an occupant to override the schedule and place the unit
into an occupied mode for an adjustable period of time (presets at 1-2-4 or 6 hours). At the
expiration of this time, control of the unit will automatically return to the software schedule or
third party control.
14
Page 15
Freeze Protection:
The unit shall shut down and generate an alarm upon receiving a freezestat status.
Fan:
Constant Volume
In the occupied mode, the fan shall run continuously or cycle with the compressor(s) depending
on fan mode settings. In the unoccupied mode, fan cycles as required for unoccupied heating
and cooling setpoints while in night setback.
Variable Frequency Drive
On units equipped with a factory or field installed Variable Frequency Drive (VFD) the controller
will command the VFD signal to maintain a particular ( User Definable) value of Static pressure,
this is typical on VAV applications with discharge air control requirements.
Zone Humidity:
If specified the controller has the capability to monitor and control the zone humidity via the hot
gas re-heat option.
There are two hardware options for humidity control:
Hot Gas Re-Heat Valve On/Off: This valve is controlled based on a 60% relative humidity
setpoint (User Definable) and will only be energized once the temperature set points are
satisfied, this valve is a two position valve and therefore is an on/off operation.
Alarms will be provided as follows:
High Zone Humidity: If the zone humidity is greater than 75% (adj.).
Low Zone Humidity: If the zone humidity is less than 35% (adj.).
The controller prioritizes the sensible load and therefore if temperature rises or decreases
during the re-heat operation the controller will switch to heating or cooling operation.
15
Page 16
Modulating Re-Heat Valve:
This valve is an analog device and has the capability to modulate the amount of hot gas that is
allowed through the re-heat coil, thus allowing control of the discharge air temperature to a user
defined setpoint.
The operation is similar to the on/off control except once the space temperature is satisfied the
controller will monitor the space humidity if the value is greater than the setpoint the controller
will modulate the valve to meet a particular a desired discharge air temperature on zone
applications only.
A typical application of modulating re heat valves can be seen on Discharge Air Control systems
where the unit is required to maintain a particular value of supply air temperature (neutral air).
For this particular type of units the unit will only discharge air to meet the specific setpoint, this
operation is done via a reverse acting PID closed loop, and its sequence of operation is
described in detail under the Discharge air section of this document.
Filter:
Based on fan runtime, a filter alarm message is generated after a user definable amount (adj.
factory default 2000 hours) or can be enabled by an optional differential pressure switch.
Heating and Cooling – (1 and 2 Compressor Stages):
The controller will measure the zone temperature and stage the compressor(s) to maintain its
setpoint. To prevent short cycling, there will be a 5 minute delay between compressor stages (if
equipped with 2 compressors). Additionally, there will be a 1 minute delay when transitioning
between heat and cool modes. The compressor will run subject to internal safeties and controls
provided by UPM board.
16
Page 17
The heating will be enabled whenever:
The fan output is on.
AND the reversing valve is in heat mode (de-energized).
The cooling will be enabled whenever:
The fan output is on.
AND the reversing valve is in cool mode (energized).
Reversing valve:
The reversing valve is energized on a call for cooling and will remain energized until a call for
heating. Upon a call for heating, the reversing valve is de-energized and remains de-energized
until a call for cooling or a call for re-heat on units with humidity (on/off) control option. The
compressor will be disabled and remain off for 10sec after the reversing valve has changed
position.
Alarms will be provided as follows:
Compressor 1 Runtime Exceeded: Compressor 1 runtime exceeds a user definable limit (adj.).
Compressor 2 Runtime Exceeded: Compressor 2 runtime exceeds a user definable limit (adj.).
Supplemental Electric Heating Stage:
The controller will measure the zone temperature and stage the heating to maintain its heating
setpoint should the compressors not meet the heating demand. To prevent short cycling, the
stage will have a 5 minute delay allowing compressor stages to meet the needs of the space.
The heating will be enabled whenever:
The heat pump is in heating mode.
AND the zone temperature is below heating setpoint.
AND the fan is on.
17
Page 18
The controller will only allow supplemental heating if the unit is configured to allow this
operation, units equipped with hot gas re heat valves or damper control enable will not have
supplemental electric heat functionality.
Discharge Air Temperature:
The controller will monitor the discharge air temperature to be located at discharge side of coil. If
the supplemental heating is installed then sensor will be in the discharge side of heating coil.
Alarms will be provided as follows:
High Discharge Air Temp: If unit running in cool mode and the discharge air temperature is
greater than 70°F (adj.).
Low Discharge Air Temp: If unit running in heat mode and the discharge air temperature is
less than 75°F (adj.).
Discharge Air Sensor Failure: If discharge air sensor outside of normal operating limits.
Discharge Air Control
On units with factory mounted modulating re-heat valves the controller will operate the unit to
maintain a particular discharge temperature setpoint. The discharge air temperature sensor
(DATS) will be located at discharge side of coil preferable 3/4 downstream of the total length of
the duct work.
The controller can operate on single or Multiple Outside Air Temperature Reset, the controller
will monitor the value of the Outside Air temperature via a BACnet point or via a physical point
terminated in one of the controllers available inputs. The controller will stage the unit’s
compressors and modulate the re-heat valve mode to maintain the Discharge Air Setpoint (User
adjustable).
Two modes are selectable for Discharge Air Control (DAC) Applications are as follows:
Single Outside Air Temperature Reset point
Multiple Outside Air Temperature Reset points
18
Page 19
Single Outside Air Temperature (OAT) Reset:
OAT> OAT Reset °F (adj.):
Controller will initiate cooling call to run compressors and modulate Re-heat Valve only when
the outside air temperature is greater than 55°F (Factory Default)
OAT< OAT Reset °F (adj.):
Controller will initiate a call for heating. Straight cool units will run their fan continuously or if the
unit is equipped with a Variable Frequency Drive (VFD) it will command the drive to maintain its
static pressure setpoint.
Multiple Outside Air Temperature (OAT) Reset:
OAT Reset °F < OAT< OAT Reset 2 °F (adj.):
Controller will command the unit to run free-cooling operation the fan will run continuously or if
the unit is equipped with a Variable Frequency Drive (VFD) it will command the drive to maintain
its static pressure setpoint.
OAT Reset 2 °F < OAT< OAT Reset 3 °F (adj.):
Controller will command the unit to run single stage of cooling operation, the valve will be set for
cooling operation and the first compressor will be commanded on, the fan will run continuously
or if the unit is equipped with a Variable Frequency Drive (VFD) it will command the drive to
maintain its static pressure setpoint and the re-heat valve will be modulated to maintain a 65°F
(Factory Default (adj.)) discharge air temperature setpoint .
OAT > OAT Reset 3 °F (adj.):
19
Page 20
Controller will command the unit to run full mechanical cooling operation (on units with more
than two compressors please check with factory), the valve will be set for cooling operation and
both first and second compressors will be commanded on, the fan will run continuously or if the
unit is equipped with a Variable Frequency Drive (VFD) it will command the drive to maintain its
static pressure setpoint and the re-heat valve will be modulated to maintain a 65°F (Factory
Default (adj.)) discharge air temperature setpoint .
Leaving Water Temperature:
The controller will monitor the leaving water temperature.
Alarms will be provided as follows:
High Leaving Water Temp: If compressor(s) is running and the leaving water temperature is
greater than 135°F (adj.).
Low Leaving Water Temp: If compressor(s) is running and the leaving water temperature is
less than 35°F (adj.).
Leaving Water Sensor Failure: If leaving water sensor outside of normal operating limits.
Should a High or Low Leaving Water Temperature Alarm occur, the call for heat or cool will be
removed.
UPM Fault Monitor:
The controller will monitor the Unit protection Module (UPM) fault input.
Upon hard lock out alarm, compressors are disabled by FHP UPM board.
Alarms will be provided as follows:
HP1: High Pressure Alarm (circuit 1)
HP2: High Pressure Alarm (circuit 2)
LP1: Low Pressure Alarm (circuit 1)
LP2: Low Pressure Alarm (circuit 2)
FRE: Freeze Alarm
CON: Condensate Alarm
BRN: Brownout Alarm
20
Page 21
Figure 12 - Typical water to air applications – Water to Air Standard
21
Page 22
Figure 13 -Typical water to air applications – Water to Air with Hot Gas Re-Heat
22
Page 23
Figure 14 - Typical water to air applications – Water to Air with CO2 and OA Damper
23
Page 24
Figure 15 – Typical water to air application – Discharge Air Control with Modulating Reheat Valves
24
Page 25
25
Page 26
Figure 16 - Typical water to air integration points list
26
Page 27
Water to Water Operation
General Description
The Heat Pump Factory mounted I/O Zone 560 or 583 DDC Controllers are factory configured
with the Water to Water application program and factory installed in the unit to be job site
configurable to run.
The Unit will operate in a 100% stand-alone control mode or connect to a Building Automation
System (BAS) using open protocols BACnet® (ARCNET and MS/TP), Modbus RTU, N2 or
LonWorks® (additional network interface board required for LonWorks® option).
The point mapping to these protocols can be pre-set, so that the protocol and baud rates
desired can be easily field-selected and commissioned without the need for any additional
downloads or technical assistance. The Controller also supports communications to intelligent
RS Room sensors and BACview keypad/display panels.
Inputs
Load (entering) water temperature sensor
Leaving (source) water temperature sensor
Changeover temperature sensor
Cooling/Heating mode select (DI Mode)
UPM Alarm codes (7 safety shutdown alarms)
Unit Occupancy Enable (DI Enable)
Outputs
Pump control
Reversing Valve
Compressor Stage 1
Compressor Stage 2
Aux Output
27
Page 28
Control & Status Parameters and Alarms
Status and Control
BACview occupancy schedule
System control: Schedule, Manual ON, BAS or DI Enable
Load (entering) water temperature
Leaving (source) water temperature
Changeover temperature (optional)
Cooling/Heating control status
Cooling/Heating percentage (0-100%)
Heating/Cooling mode manual control (optional)
Reversing valve control
Pump control (optional)
Comp 1 control
Comp 2 control (Comp 2 Circuit)
Alarms
Load (entering) water temperature high/low limits
Leaving (source) water temperature high/low limits
Sensors failure alarm
Comp 1 Runtime trip
Comp 2 Runtime trip (Comp 2 Circuit)
Freeze Stat sensor UPM alarm (optional)
Low pressure sensor UPM alarm
High pressure sensor UPM alarm
Low pressure sensor UPM alarm (Comp 2 Circuit)
High pressure sensor UPM alarm (Comp 2 Circuit)
Condensate overflow UPM alarm
High/low voltage UPM alarm
28
Page 29
Sequence of Operation
Run Conditions:
The unit will run according to a user definable time schedule, dry contact (physical digital input
number 1), manual ON command from BACview control interface or via third party front end
start command (BV software point). When commanded to run the unit will operate in the
following modes:
Occupied Mode: The unit will maintain
A 54°F (12°C) adj. Cooling setpoint
A 105°F (40 °C) adj. Heating setpoint
Unoccupied Mode (night setback): The unit will maintain
A 74°F (12°C) adj. Cooling setpoint.
A 85°F (30°C) adj. Heating setpoint.
The values above can be changed by the commissioning agent by using the BACview or via the
BAS.
Auto Changeover Mode
When operating on Changeover mode the unit will automatically change from heat to cool and
vice versa, by using the
Changeover Setpoint
and the
Changeover Deadband
.
These points can be changed by the commissioning agent, the factory defaults are 65°F and
3°F (18°C and 2°C) respectively, the units will enter in cooling or heating mode according to the
following:
29
Page 30
Auto Cool:
Chageover Temperature > Changeover Setpoint + Change over dead Band
Auto Heat:
Chageover Temperature < Changeover Setpoint - Change over dead Band
When using the changeover feature the system will require an air temperature sensor (10KΩ @
77°F (25°C) Thermistor) typically located in the controlled zone.
Digital Input Mode
When operating on Digital Input mode the unit will change from heat to cool and by using the
state of the digital input (IN6) on controller as follows:
Off = Heat
On = Cool
This feature is typically used when a remote switch is needed but no BAS is available, if a BAS
is available FHP recommends operating the unit by using the integration points as they will
provide additional and valuable information the end user.
BAS Mode
When operating on BAS mode the unit will change from heat to cool and by writing to the
Control Mode
integration point.
Please refer to the integration points list for additional information on how to make the unit part
of the BAS.
30
Page 31
Lead - Lag Compressor operation
NOTE: This feature is only available on two stage systems.
The unit will alternate the compressors by using Lead Lag control algorithm; the rotation method
is user definable and can be set during the commissioning process as follows:
Monthly
Daily
Time of Day
By default the unit will change its lead compressor if the one acting as lead fails.
The unit will provide the following compressor alarms:
Compressor 1 Runtime: If the compressor runtime hours are greater than 8760.
Compressor 2 Runtime: If the compressor runtime hours are greater than 8760.
Pump Control (optional)
The unit can control a pump by using Digital Output 1 (DO1) on controller; this feature can be
enable or disabled, set to run with compressors or continuously during the commissioning
process.
If commissioned to run continuously the pump will run when the unit is in occupied mode.
If commissioned to cycle with compressors the pump will be commanded on only when
the compressors are running.
The factory default is enabled to cycle with compressors.
The unit will provide the following compressor alarms:
Pump Runtime Alarm: If the pump runtime hours are greater than 8760.
31
Page 32
Load Water (Entering) Temperature:
The controller will monitor the entering load water temperature which is located at entering side
of coil.
Alarms will be provided as follows:
Load High Temp: If the water temperature at the entering load side is greater than the cooling
setpoint plus a user definable amount (adj.), the factory default for this amount is 10°F.
Load Low Temp: If the water temperature at the entering load side is less than the heating
setpoint minus a user definable amount (adj.) the factory default for this amount is 10°F.
Load Sensor Failure: If the load water sensor is outside of normal operating limits, typically
produced by a wiring failure between the sensor and the controller.
Source Water (Leaving) Temperature:
The controller will monitor the leaving water temperature on the source which is located on the
source leaving side of coil.
Alarms will be provided as follows:
Leaving High Temp: If the leaving water temperature is greater than 135°F
Leaving Low Temp: If the leaving water is less than 35°F.
Leaving Sensor Failure: If leaving water sensor is outside of normal operating limits, typically
produced by a wiring failure between the sensor and the controller
32
Page 33
Figure 17 - Typical water to water applications – Water to Water Standard
33
Page 34
34
Page 35
Figure 18 - Typical water to water integration points list
35
Page 36
BACview Termination Detail
36
Page 37
RS-Sensor Termination Detail
The RS Sensor is remotely mounted and installed (up to 500ft) in the zone it is recommended to
use shielded cable (20AWG conductors) if installing RS-sensor only.
If BACview is installed remotely using the same cable is recommended to use shielded cable
(18AWG conductors).
DDC - Unit
Room
Sensor
Rnet port termination:
Black = Ground
White = R-net +
Blue = R-net Red =12VDC
Field installed wiring
four conductor shielded
cable
37
Page 38
The RS-Pro Sensor interface
The RS-Pro sensor factory part number 641-230 is a combination keypad/display unit that
attaches to a control module to let you view and change temperature and set points values and
the controller’s components status, the following features only apply to the software version
covered on this manual.
ICONS
Alarm Bell Indicates Alarm Condition (see INFO button for more information)
Cooling Indicates unit enabled in cooling mode
Heating Indicates unit enabled in heating mode
Occupied Indicates unit in occupied mode
Unoccupied Indicates unit in unoccupied mode
Fan Indicates fan output energized
BUTTONS
ANUAL ON Places unit into occupied mode. Allows for incremental increase in override
time ( 60min, 120min, 180 min , 4hrs, 5hrs, 6hrs, 0 min) each time button is
pressed
WARMER Allows for increase in zone temperature setpoint (+1° to per push to a
maximum of +5° or as configured at DDC through BAC view6) from default
setpoint value
COOLER Allows for decrease in zone temperature setpoint (-1° to per push to a
maximum of -5° or as configured at DDC through BAC view6) from default
setpoint value.
38
Page 39
IMPORTANT: By Pressing the Info button on the sensor the user can see the following
typical data:
INFO PRESS 1 – Displays occupancy override time (in minutes)
PRESS 2 – Displays actual heating setpoint (in degrees F)
PRESS 3 – Displays actual cooling setpoint (in degrees F)
PRESS 4 – [ 1 ] - Displays discharge air temperature (in degrees F)
PRESS 5 – [ 2 ] - Displays leaving water temperature (in degrees F)
PRESS 6 – [ 3 ] - Displays active alarm code
0 Indicates NO ALARM
1 Indicates active HP alarm comp 1
2 Indicates active LP alarm comp 1
3 Indicates active HP alarm comp 2
4 Indicates active LP alarm comp 2
5 Indicates active freezestat alarm
6 Indicates active condensate alarm
7 Indicates brownout condition
20 Indicates input/out in MANUAL lock position. It is not in
AUTO
30 Indicates RS zone, discharge or leaving water
temperature sensor failure
40 Indicates high or low RS zone temperature condition
50 Indicates high or low discharge air temperature condition
60 Indicates filter or compressor service alarm
70 Indicates high or low leaving water temperature condition
PRESS 7 – [ 1 ] – Displays status of compressor 1 output (ON/OF)
PRESS 8 – [ 2 ] – Displays status of compressor 2 output (ON/OF)
PRESS 9 – [ 3 ] – Displays status of auxiliary heat output (ON/OF)
PRESS 10 – Displays fan status (fan icon=fan ON), unit condition
(AU=auto)
PRESS 11 – Displays unit mode (AU=auto)
PRESS 12 – Goes back to default screen display